OxyReduct®

FirExting® SILENT
Reference solution
Fire prevention and
soft flooding in
a data centre

Ta i l o r - m a d e f i r e
protection for
maximum-security
data centres
THE CUSTOMER

In a former vault building, DARZ GmbH operates a data


centre with what is likely to be the highest level of building
security in Germany.

Founded in 2010, DARZ GmbH


is a full service provider that
offers colocation/housing, man-
aged services and data centre
solutions in an extraordinary
environment at its data centre
in Darmstadt. This is located
in the former vault building of
the Hessian State Bank and has
what is likely to be the highest
level of building security of any
data centre in Germany.
DARZ founder and Managing Director Sergey Mirochnik
with the German Data Centre Award 2015
Erected in the late 1980s, the
centrally located building with its
striking white facade housed the
Hessian State Bank’s gold and a suitable, high-security infrastruc- intersection-free fibreglass con-
cash reserves from 1988 to 2005. ture”, explains DARZ founder nection to Frankfurt furthermore
The building’s physical security and Managing Director Sergey enables the realisation of dual
is evident in its structure with Mirochnik, clarifying: “Our concept data centre solutions in accord-
metre-thick walls and bullet- aims at avoiding risks before they ance with the highest protective
proof tank windows as well as arise. This also involves huge category for banks and insurance
the design of the vault area as costs. However, in these danger- companies (Basel III, Luxembourg
a ‘building in a building’ able to ous times, especially for data, we regulation). DARZ GmbH sought
withstand explosions and earth- believe that our customers value to round out this IT landscape by
quakes. This provides optimum our efforts and investments.” constructing a high-grade data
basic structural protection. Follo- centre infrastructure (TÜV Level
wing extension renovations, in The site’s suitability as a colocation III+/Tier 3+), true to its motto:
particular the installation of new, data centre was also based on its “Data is worth more than gold!”.
redundant building technology location: Darmstadt is only about From a green IT perspective, the
for use as a data centre, the new 30 kilometres from the world’s overall concept, with its indirect
data centre with a total output of largest internet exchange DE-CIX free cooling, has already been
5.2 MW was put into operation by in Frankfurt am Main and, with its awarded the 2015 German Data
DARZ GmbH in July 2014. technical university, three Fraun- Centre Award in the “Overall En-
hofer Institutes, several localIT ergy Efficiency in Data Centres”
Award-winning green IT data associations and a city IT cluster category.
centre with high availability facility, an important place for the
We supplemented the building ITC sector. The short distance
protection that we inherited with with a both fully redundant and
Fire prevention concept customised

T H E R I S K A N A LY S I S

In today’s world, constant data availability and the


prevention of as much downtime as possible are vital
for companies.

If a company acts as a service ware. A fire prevention concept


provider that offers data centre was therefore required for the
capacities, as in the case with high-security building in order to
DARZ GmbH, maintaining 24/7 minimise the internal risks. The
availability is essential to survival. technical fire prevention solution
The company is not only respon- should detect any outbreak of fire
sible for its own data but also, at the earliest possible moment in
and in particular, for that of its order to enable a rapid response.
customers. Accordingly, the Optimum fire suppression methods
associated liability risks can be should also prevent consequential
high. A full-service provider such damages caused by the extin-
as DARZ GmbH which stores guishing process itself.
customer-owned hardware in its
data centre is also responsible for
the physical safety of this hard-

THE PROTECTION OBJECTIVE

Certified maximum safety

All areas of the building had to and the avoidance of conse-


be equipped with fire prevention quential damage in the form
solutions, which take the various of downtime and hardware
structural conditions into ac- defects that could lead to
count. data losses are of the utmost
importance.
■ The safety level needed to be
approved by an expert from ■ A suitable solution was
the Property Insurers Organi- also required for the special
zation VdS in order to sup- structure of the vault room
port DARZ’s sales team with not usually found in normal
a credible guarantee promise. buildings as it was not pos-
sible to create pressure relief
■ Instant effectiveness of the surfaces for a gas extinguish-
extinguishing equipment ing solution.
Great demands on fire prevention

THE SOLUTION

The energetically-optimised choice of cooling tech-


nology posed special challenges with regard to fire
prevention.

Gaseous extinguishing agents was selected for the Darmstadt


which fight fires effectively without data centre. In combination with
leaving residue are ideally suited air sampling smoke detectors for
to the IT sector. When fed into the highly sensitive fire detection and
extinguishing zone, the inert gas supplementary point-type detectors,
nitrogen displaces oxygen until fires can be detected and combat-
there is no longer enough of it to ted at the earliest possible stage.
sustain a fire.
WAGNER’s protection concepts
As a natural component of the air goes one step further
we breathe (78% vol.), nitrogen is in order to effectively and reliably
non-toxic and has a density similar extinguish a fire within the short-
to that of air. It is also simple and est time possible, gas extinguish-
compact to store in extinguishing ing systems have to flood the area
cylinders and can be distributed to be protected with extinguishing
quickly and homogenously around gas under high pressure. As a
the room without residues when result, conventional nitrogen ex-
used for extinguishing purposes. tinguishing systems used to cre-
ate sound pressure levels of over
In view of all of these reasons, a 130 db(A) when the gas rapidly
nitrogen-based FirExting® gas ex- rushed through the extinguishing
tinguishing system from WAGNER nozzles, causing vibrations and

G 310025

Air sampling smoke detector Special sound absorbers are attached to the extinguishing nozzles
therefore serious damage to hard flooding is a further special feature. DARZ’s high requirements in
disks. The indirect damage from Flow regulators were attached to terms of IT security as the design
this is often much worse than the the extinguishing agent cylinders enables the high-security building
fire damage itself – not only in the in order to minimise pressure envelope to remain as intact as
form of temporary server failures, spikes at the start of the extin- possible.
but also due to data damage or guishing process.
even loss. Special protection in the
The soft flooding device also con- vault room
Silent extinguishing system siderably reduces the size of the What distinguishes DARZ from
protects sensitive IT equipment pressure-release vents needed. all other data centre buildings
WAGNER solved this problem This means that a single on-site in Germany is the vault room.
in the server areas of the DARZ F90 conduit system can provide In line with its original purpose,
data centre by developing special pressure relief for all extinguishing the room is hermetically sealed
sound absorbers (FirExting® SILENT zones on the first basement floor from the outside. The pressure
with VdS device approval) which of the DARZ. Only one opening to relief holes required to use a gas
are attached to the extinguishing the outdoors is therefore needed extinguishing system would be
nozzles and reduce the sound for all the pressure relief on the associated with a huge amount
pressure to approx. 98 dB(A). Soft first basement floor. This meets of cost and effort. Instead, active

The nitrogen required for extinguishing


purposes is stored in a cylinder bank and
fed into the data centre at a low pressure
using a soft flooding device if necessary.
S 303006
S 315002
fire prevention through oxygen “What is good for one is not
reduction is used. permissible for another.”
Receiving the VdS certificate as
WAGNER’s OxyReduct® system quickly as possible was an impor-
generates nitrogen from the air tant goal for DARZ GmbH, and
in the room and the ventilation one which was easily achieved
system feeds it into the protected thanks to WAGNER’s solution.
area, where it continuously According to the client Miroch-
reduces the amount of oxygen nik, WAGNER’s expertise played
in the vault to create a heavily a major part in this as: “The
fire-retardant atmosphere. The main challenge is meeting all
O2 level of 15.9% vol. is below the requirements of the different
the ignition threshold of typical IT committees such as the VdS but
materials, so a fire can no longer also the fire brigade, construction
develop or spread. authorities and TÜV.”
Flow regulators were attached to the extinguishing agent
cylinders in order to minimise pressure spikes at the start of
the extinguishing process.

E X A M P L E S Y S T E M I N T H E D ATA C E N T R E

2 4

3 4
6

1 5

1 Air sampling smoke detector 4 Alarm indicator

2 Point-type detector 5 Extinguishing cylinder bank (nitrogen) as a soft flooding option

3 Extinguishing nozzles with silent sound 6 Extinguishing control panel


absorbers
Innovative engineering solutions

To protect the former vault room, the OxyReduct® fire prevention system feeds in nitrogen via the ventilation system to reduce the oxygen level
and create a fire-retardant atmosphere.

Summary centre infrastructure as well as


The unique construction material the energy-efficient management
used for the data centre made of the facility as a whole. By
DARZ special, even for WAGNER’s working with strong partners, we
project manager. Frankfurt branch were able to build one of Europe’s
manager Michael Leibner recalls: most environmentally friendly data
“We had never before worked centres.
with special bulletproof concrete.
The holes we had to make in this
extremely hard material were a
real stress test for all the equip-
ment we used. We also had to
proceed with extreme caution.
Remaining on schedule under
these conditions was definitely a
challenge.”

Managing Director Sergey


Mirochnik stressed the impor-
tance of the interaction between
all the trades in the data centre:
“We placed great value on the
efficiency of all individual com-
ponents throughout the data
PREVENTIO
RE N
FI
Y F I RE DE
RL T
A

EC
E

WAGNER sets standards for innovative and comprehensive solutions in fire protection:
Y
HAZARD MA

T IO
VER

ASPIRATING with very early fire detection systems, TITANUS® for aspirating smoke detection,

SSION
N
SMOKE
DETECTION FirExting® for fire-extinguishing, OxyReduct® to actively prevent fires from breaking
out and VisuLAN® for hazard management. www.wagner.eu

RE
PP
N

U
A

EM
G

S
EN RE
T FI

Headquarters Subsidiaries Worldwide Russia

© WAGNER Group GmbH. Subject to technical changes without notice. Art. no. 68-30-1295. Last revised 10/2016.
Sales International WAGNER RU GmbH
Austria Businesscentre SMART PARK
WAGNER Group GmbH WAGNER Austria GmbH 117246, Moscow
Schleswigstraße 1–5 Am Hafen 6/1/12 Nauchnij Projezd
D-30853 Langenhagen A-2100 Korneuburg 14 A, Building 1, Office 4.12.
Germany Phone +43 2262 64262 0 Phone +7 495 96767 69
Phone +49 511 97383 0 office@wagner-austria.com info@wagner-russia.com
info@wagner.eu
Benelux Singapore
WAGNER Nederland B.V. WAGNER Asia
Computerweg 10 No. 61 Tai Seng Avenue
NL-3542 DR Utrecht #B1-01 Crescendas Print Media Hub
Phone +31 346 5580 10 Singapore 534167
info@wagner-nl.com Phone +65 6296 7828
info@wagner-asia.com
Great Britain
WAGNER UK Limited Switzerland
Unit H WAGNER SCHWEIZ AG
Suites 3&4 Peek Business Centre Industriestrasse 44
Woodside, Dunmow Road CH-8304 Wallisellen
Bishop’s Stortford Phone +41 44 832540 0
Hertfordshire CM23 5RG info@wagner-schweiz.ch
Phone +44 870 333 6116
info@wagner-uk.com USA
WAGNER Fire Safety, Inc.
Poland 135 Beaver Street #402
WAGNER Poland Sp. z o.o. Waltham, MA 02452
ul. Puławska 38 Phone +1 781 899 9100
PL 05-500 Piaseczno info@wagner-us.com
Phone +48 22 185530 0
info@wagnerpoland.pl

You might also like