TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 05F - Zone 1 - Office '' IN ZONE '' 5F- Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 320 m² 49804 - 320 m² - -
Wall Transmission 303 m² 7114 - 303 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 320 m² 5470 - 320 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1873 m² 6095 - 1873 m² 0 -
Partitions 303 m² 4929 - 303 m² 0 -
Ceiling 1873 m² 21022 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10344 0 0% 0 0
>> Total Zone Loads - 113786 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 05F - Zone 1 - Office '' IN ZONE '' 5F- Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 21 2.575 - 522 - 0
WINDOW 1 239 2.270 0.510 3779 42338 0
WINDOW 2 43 3.014 0.435 893 6426 0
ESE EXPOSURE
WALL 87 2.575 - 2133 - 0
SSW EXPOSURE
WALL 108 2.575 - 2318 - 0
WINDOW 1 21 3.014 0.435 446 582 0
WINDOW 2 17 3.016 0.435 352 459 0
WNW EXPOSURE
WALL 87 2.575 - 2141 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 06F - Zone 1 - Office '' IN ZONE '' 6F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 303 m² 46714 - 303 m² - -
Wall Transmission 320 m² 7556 - 320 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 303 m² 5126 - 303 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1873 m² 6106 - 1873 m² 0 -
Partitions 303 m² 4939 - 303 m² 0 -
Ceiling 1873 m² 21082 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10053 0 0% 0 0
>> Total Zone Loads - 110583 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 06F - Zone 1 - Office '' IN ZONE '' 6F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 42 2.575 - 1052 - 0
WINDOW 1 239 2.270 0.510 3785 42338 0
WINDOW 2 21 3.014 0.435 447 3213 0
ESE EXPOSURE
WALL 87 2.575 - 2135 - 0
SSW EXPOSURE
WALL 104 2.575 - 2225 - 0
WINDOW 2 43 3.014 0.435 894 1164 0
WNW EXPOSURE
WALL 87 2.575 - 2143 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 06F - Zone 2 - Con. Room '' IN ZONE '' 6F-Meeting/Con. Room ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32.9 °C / 31.5 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 82 m² 603 - 82 m² - -
Wall Transmission 525 m² 11835 - 525 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 82 m² 2075 - 82 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 7 m² 508 - 7 m² 0 -
Floor Transmission 1672 m² 6208 - 1672 m² 0 -
Partitions 251 m² 4665 - 251 m² 0 -
Ceiling 1672 m² 25443 - 1672 m² 0 -
Overhead Lighting 8360 W 6821 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 418 23111 25122 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 8127 2512 0% 0 0
>> Total Zone Loads - 89396 27634 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 06F - Zone 2 - Con. Room '' IN ZONE '' 6F-Meeting/Con. Room ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 104 2.575 - 2288 - 0
WINDOW 2 43 3.014 0.435 1073 358 0
ESE EXPOSURE
WALL 77 2.575 - 1736 - 0
SSW EXPOSURE
WALL 257 2.575 - 5521 - 0
WINDOW 1 21 3.014 0.435 537 122 0
WINDOW 2 17 3.016 0.435 424 96 0
DOOR GLASS 7 5.000 0.880 301 207 0
WNW EXPOSURE
WALL 88 2.575 - 2289 - 0
WINDOW 1 2 3.065 0.435 42 27 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 07F - Zone 1 - Office '' IN ZONE '' 7F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 341 m² 50386 - 341 m² - -
Wall Transmission 282 m² 6665 - 282 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 341 m² 5926 - 341 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1873 m² 6106 - 1873 m² 0 -
Partitions 303 m² 4939 - 303 m² 0 -
Ceiling 1873 m² 21082 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10411 0 0% 0 0
>> Total Zone Loads - 114523 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 07F - Zone 1 - Office '' IN ZONE '' 7F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 21 2.575 - 522 - 0
WINDOW 1 239 2.270 0.510 3785 42338 0
WINDOW 2 43 3.014 0.435 894 6426 0
ESE EXPOSURE
WALL 87 2.575 - 2135 - 0
SSW EXPOSURE
WALL 87 2.575 - 1864 - 0
WINDOW 1 17 3.016 0.435 353 459 0
WINDOW 2 43 3.014 0.435 894 1164 0
WNW EXPOSURE
WALL 87 2.575 - 2143 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 07F - Zone 2 -Restaurent '' IN ZONE '' 7F - Restaurent ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 82 m² 7525 - 82 m² - -
Wall Transmission 513 m² 11844 - 513 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 82 m² 1729 - 82 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 19 m² 2595 - 19 m² 0 -
Floor Transmission 1340 m² 4369 - 1340 m² 0 -
Partitions 251 m² 4096 - 251 m² 0 -
Ceiling 1340 m² 15082 - 1340 m² 0 -
Overhead Lighting 6700 W 6002 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5000 W 4767 - 0 0 -
People 536 38278 42398 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9629 4240 0% 0 0
>> Total Zone Loads - 105916 46637 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 07F - Zone 2 -Restaurent '' IN ZONE '' 7F - Restaurent ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 92 2.575 - 2291 - 0
WINDOW 2 43 3.014 0.435 894 6426 0
DOOR GLASS 12 5.000 0.880 404 1696 0
ESE EXPOSURE
WALL 77 2.575 - 1887 - 0
SSW EXPOSURE
WALL 257 2.575 - 5505 - 0
WINDOW 1 21 3.014 0.435 447 582 0
WINDOW 2 17 3.016 0.435 353 459 0
DOOR GLASS 7 5.000 0.880 251 244 0
WNW EXPOSURE
WALL 88 2.575 - 2160 - 0
WINDOW 1 2 3.065 0.435 35 59 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 8F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 325 m² 49927 - 325 m² - -
Wall Transmission 299 m² 7026 - 299 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 325 m² 5573 - 325 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1873 m² 6106 - 1873 m² 0 -
Partitions 303 m² 4939 - 303 m² 0 -
Ceiling 1873 m² 21082 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10366 0 0% 0 0
>> Total Zone Loads - 114026 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 8F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 21 2.575 - 522 - 0
WINDOW 1 239 2.270 0.510 3785 42338 0
WINDOW 2 43 3.014 0.435 894 6426 0
ESE EXPOSURE
WALL 87 2.575 - 2135 - 0
SSW EXPOSURE
WALL 104 2.575 - 2225 - 0
WINDOW 2 43 3.014 0.435 894 1164 0
WNW EXPOSURE
WALL 87 2.575 - 2143 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 8F - Office 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 0400 HEATING DATA AT DES HTG
COOLING OA DB / WB 24.0 °C / 23.8 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 326 m² 75201 - 326 m² - -
Wall Transmission 288 m² 4529 - 288 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 326 m² 538 - 326 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1672 m² 3903 - 1672 m² 0 -
Partitions 251 m² 2933 - 251 m² 0 -
Ceiling 1672 m² 5274 - 1672 m² 0 -
Overhead Lighting 0W 1810 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 288 - 0 0 -
People 0 2898 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9737 0 0% 0 0
>> Total Zone Loads - 107112 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 8F - Office 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 104 2.575 - 924 - 0
WINDOW 2 43 3.014 0.435 86 1092 0
ESE EXPOSURE
WALL 77 2.575 - 2019 - 0
SSW EXPOSURE
WALL 20 2.575 - 563 - 0
WINDOW 1 239 2.270 0.510 363 64145 0
WINDOW 2 43 3.014 0.435 86 9736 0
WNW EXPOSURE
WALL 88 2.575 - 1023 - 0
WINDOW 1 2 3.065 0.435 3 229 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 9F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 325 m² 49927 - 325 m² - -
Wall Transmission 299 m² 7026 - 299 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 325 m² 5573 - 325 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1873 m² 6106 - 1873 m² 0 -
Partitions 303 m² 4939 - 303 m² 0 -
Ceiling 1873 m² 21082 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10366 0 0% 0 0
>> Total Zone Loads - 114026 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 9F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 21 2.575 - 522 - 0
WINDOW 1 239 2.270 0.510 3785 42338 0
WINDOW 2 43 3.014 0.435 894 6426 0
ESE EXPOSURE
WALL 87 2.575 - 2135 - 0
SSW EXPOSURE
WALL 104 2.575 - 2225 - 0
WINDOW 2 43 3.014 0.435 894 1164 0
WNW EXPOSURE
WALL 87 2.575 - 2143 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 9F - Office 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 0400 HEATING DATA AT DES HTG
COOLING OA DB / WB 24.0 °C / 23.8 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 326 m² 75201 - 326 m² - -
Wall Transmission 288 m² 4529 - 288 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 326 m² 538 - 326 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1672 m² 3903 - 1672 m² 0 -
Partitions 251 m² 2933 - 251 m² 0 -
Ceiling 1672 m² 5274 - 1672 m² 0 -
Overhead Lighting 0W 1810 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 288 - 0 0 -
People 0 2898 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9737 0 0% 0 0
>> Total Zone Loads - 107112 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 9F - Office 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 104 2.575 - 924 - 0
WINDOW 2 43 3.014 0.435 86 1092 0
ESE EXPOSURE
WALL 77 2.575 - 2019 - 0
SSW EXPOSURE
WALL 20 2.575 - 563 - 0
WINDOW 1 239 2.270 0.510 363 64145 0
WINDOW 2 43 3.014 0.435 86 9736 0
WNW EXPOSURE
WALL 88 2.575 - 1023 - 0
WINDOW 1 2 3.065 0.435 3 229 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 10F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 325 m² 49927 - 325 m² - -
Wall Transmission 299 m² 7026 - 299 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 325 m² 5573 - 325 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1873 m² 6106 - 1873 m² 0 -
Partitions 303 m² 4939 - 303 m² 0 -
Ceiling 1873 m² 21082 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10366 0 0% 0 0
>> Total Zone Loads - 114026 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 10F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 21 2.575 - 522 - 0
WINDOW 1 239 2.270 0.510 3785 42338 0
WINDOW 2 43 3.014 0.435 894 6426 0
ESE EXPOSURE
WALL 87 2.575 - 2135 - 0
SSW EXPOSURE
WALL 104 2.575 - 2225 - 0
WINDOW 2 43 3.014 0.435 894 1164 0
WNW EXPOSURE
WALL 87 2.575 - 2143 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 10F - Office 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 0400 HEATING DATA AT DES HTG
COOLING OA DB / WB 24.0 °C / 23.8 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 326 m² 75201 - 326 m² - -
Wall Transmission 288 m² 4529 - 288 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 326 m² 538 - 326 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1672 m² 3903 - 1672 m² 0 -
Partitions 251 m² 2933 - 251 m² 0 -
Ceiling 1672 m² 5274 - 1672 m² 0 -
Overhead Lighting 0W 1810 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 288 - 0 0 -
People 0 2898 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9737 0 0% 0 0
>> Total Zone Loads - 107112 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 10F - Office 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 104 2.575 - 924 - 0
WINDOW 2 43 3.014 0.435 86 1092 0
ESE EXPOSURE
WALL 77 2.575 - 2019 - 0
SSW EXPOSURE
WALL 20 2.575 - 563 - 0
WINDOW 1 239 2.270 0.510 363 64145 0
WINDOW 2 43 3.014 0.435 86 9736 0
WNW EXPOSURE
WALL 88 2.575 - 1023 - 0
WINDOW 1 2 3.065 0.435 3 229 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 11F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 325 m² 49927 - 325 m² - -
Wall Transmission 299 m² 7026 - 299 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 325 m² 5573 - 325 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1873 m² 6106 - 1873 m² 0 -
Partitions 303 m² 4939 - 303 m² 0 -
Ceiling 1873 m² 21082 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10366 0 0% 0 0
>> Total Zone Loads - 114026 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 11F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 21 2.575 - 522 - 0
WINDOW 1 239 2.270 0.510 3785 42338 0
WINDOW 2 43 3.014 0.435 894 6426 0
ESE EXPOSURE
WALL 87 2.575 - 2135 - 0
SSW EXPOSURE
WALL 104 2.575 - 2225 - 0
WINDOW 2 43 3.014 0.435 894 1164 0
WNW EXPOSURE
WALL 87 2.575 - 2143 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 11F - Office 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 0400 HEATING DATA AT DES HTG
COOLING OA DB / WB 24.0 °C / 23.8 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 326 m² 75201 - 326 m² - -
Wall Transmission 288 m² 4529 - 288 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 326 m² 538 - 326 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1672 m² 3903 - 1672 m² 0 -
Partitions 251 m² 2933 - 251 m² 0 -
Ceiling 1672 m² 5274 - 1672 m² 0 -
Overhead Lighting 0W 1810 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 288 - 0 0 -
People 0 2898 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9737 0 0% 0 0
>> Total Zone Loads - 107112 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 11F - Office 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 104 2.575 - 924 - 0
WINDOW 2 43 3.014 0.435 86 1092 0
ESE EXPOSURE
WALL 77 2.575 - 2019 - 0
SSW EXPOSURE
WALL 20 2.575 - 563 - 0
WINDOW 1 239 2.270 0.510 363 64145 0
WINDOW 2 43 3.014 0.435 86 9736 0
WNW EXPOSURE
WALL 88 2.575 - 1023 - 0
WINDOW 1 2 3.065 0.435 3 229 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 12F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 325 m² 49927 - 325 m² - -
Wall Transmission 299 m² 7026 - 299 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 325 m² 5573 - 325 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1873 m² 6106 - 1873 m² 0 -
Partitions 303 m² 4939 - 303 m² 0 -
Ceiling 1873 m² 21082 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10366 0 0% 0 0
>> Total Zone Loads - 114026 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 12F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 21 2.575 - 522 - 0
WINDOW 1 239 2.270 0.510 3785 42338 0
WINDOW 2 43 3.014 0.435 894 6426 0
ESE EXPOSURE
WALL 87 2.575 - 2135 - 0
SSW EXPOSURE
WALL 104 2.575 - 2225 - 0
WINDOW 2 43 3.014 0.435 894 1164 0
WNW EXPOSURE
WALL 87 2.575 - 2143 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 12F - Office 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 0400 HEATING DATA AT DES HTG
COOLING OA DB / WB 24.0 °C / 23.8 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 326 m² 75201 - 326 m² - -
Wall Transmission 288 m² 4529 - 288 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 326 m² 538 - 326 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1672 m² 3903 - 1672 m² 0 -
Partitions 251 m² 2933 - 251 m² 0 -
Ceiling 1672 m² 5274 - 1672 m² 0 -
Overhead Lighting 0W 1810 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 288 - 0 0 -
People 0 2898 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9737 0 0% 0 0
>> Total Zone Loads - 107112 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 12F - Office 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 104 2.575 - 924 - 0
WINDOW 2 43 3.014 0.435 86 1092 0
ESE EXPOSURE
WALL 77 2.575 - 2019 - 0
SSW EXPOSURE
WALL 20 2.575 - 563 - 0
WINDOW 1 239 2.270 0.510 363 64145 0
WINDOW 2 43 3.014 0.435 86 9736 0
WNW EXPOSURE
WALL 88 2.575 - 1023 - 0
WINDOW 1 2 3.065 0.435 3 229 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 13F - Zone 1 - Office '' IN ZONE '' 13F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.1 °C / 29.9 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 278 m² 49325 - 278 m² - -
Wall Transmission 197 m² 4281 - 197 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 278 m² 4219 - 278 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1309 m² 4032 - 1309 m² 0 -
Partitions 256 m² 3939 - 256 m² 0 -
Ceiling 1309 m² 12669 - 1309 m² 0 -
Overhead Lighting 0W 2280 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 363 - 0 0 -
People 0 3652 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 8476 0 0% 0 0
>> Total Zone Loads - 93235 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 13F - Zone 1 - Office '' IN ZONE '' 13F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 12 2.575 - 279 - 0
WINDOW 1 239 2.270 0.510 3483 45415 0
WINDOW 2 21 3.014 0.435 411 3446 0
ESE EXPOSURE
WALL 87 2.575 - 2032 - 0
SSW EXPOSURE
WALL 99 2.575 - 1970 - 0
WINDOW 2 17 3.016 0.435 325 463 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 13F - Zone 2 - Office '' IN ZONE '' 13F - Office 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32.9 °C / 31.5 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 43 m² 301 - 43 m² - -
Wall Transmission 385 m² 8751 - 385 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 43 m² 1073 - 43 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1295 m² 4808 - 1295 m² 0 -
Partitions 251 m² 4665 - 251 m² 0 -
Ceiling 1672 m² 25443 - 1672 m² 0 -
Overhead Lighting 9065 W 7396 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3238 W 2971 - 0 0 -
People 162 8950 9729 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 6436 973 0% 0 0
>> Total Zone Loads - 70795 10702 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 13F - Zone 2 - Office '' IN ZONE '' 13F - Office 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 104 2.575 - 2295 - 0
WINDOW 2 21 3.014 0.435 537 179 0
SSW EXPOSURE
WALL 192 2.575 - 4125 - 0
WINDOW 2 21 3.014 0.435 537 122 0
WNW EXPOSURE
WALL 89 2.575 - 2332 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 14F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 325 m² 49927 - 325 m² - -
Wall Transmission 299 m² 7026 - 299 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 325 m² 5573 - 325 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1873 m² 6106 - 1873 m² 0 -
Partitions 303 m² 4939 - 303 m² 0 -
Ceiling 1873 m² 21082 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10366 0 0% 0 0
>> Total Zone Loads - 114026 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 14F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 21 2.575 - 522 - 0
WINDOW 1 239 2.270 0.510 3785 42338 0
WINDOW 2 43 3.014 0.435 894 6426 0
ESE EXPOSURE
WALL 87 2.575 - 2135 - 0
SSW EXPOSURE
WALL 104 2.575 - 2225 - 0
WINDOW 2 43 3.014 0.435 894 1164 0
WNW EXPOSURE
WALL 87 2.575 - 2143 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 14F - Office 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 0400 HEATING DATA AT DES HTG
COOLING OA DB / WB 24.0 °C / 23.8 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 326 m² 75201 - 326 m² - -
Wall Transmission 288 m² 4529 - 288 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 326 m² 538 - 326 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1672 m² 3903 - 1672 m² 0 -
Partitions 251 m² 2933 - 251 m² 0 -
Ceiling 1672 m² 5274 - 1672 m² 0 -
Overhead Lighting 0W 1810 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 288 - 0 0 -
People 0 2898 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9737 0 0% 0 0
>> Total Zone Loads - 107112 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 14F - Office 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 104 2.575 - 924 - 0
WINDOW 2 43 3.014 0.435 86 1092 0
ESE EXPOSURE
WALL 77 2.575 - 2019 - 0
SSW EXPOSURE
WALL 20 2.575 - 563 - 0
WINDOW 1 239 2.270 0.510 363 64145 0
WINDOW 2 43 3.014 0.435 86 9736 0
WNW EXPOSURE
WALL 88 2.575 - 1023 - 0
WINDOW 1 2 3.065 0.435 3 229 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 15F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 325 m² 49927 - 325 m² - -
Wall Transmission 299 m² 7026 - 299 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 325 m² 5573 - 325 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1873 m² 6106 - 1873 m² 0 -
Partitions 303 m² 4939 - 303 m² 0 -
Ceiling 1873 m² 21082 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10366 0 0% 0 0
>> Total Zone Loads - 114026 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 15F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 21 2.575 - 522 - 0
WINDOW 1 239 2.270 0.510 3785 42338 0
WINDOW 2 43 3.014 0.435 894 6426 0
ESE EXPOSURE
WALL 87 2.575 - 2135 - 0
SSW EXPOSURE
WALL 104 2.575 - 2225 - 0
WINDOW 2 43 3.014 0.435 894 1164 0
WNW EXPOSURE
WALL 87 2.575 - 2143 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 15F - Office 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 0400 HEATING DATA AT DES HTG
COOLING OA DB / WB 24.0 °C / 23.8 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 326 m² 75201 - 326 m² - -
Wall Transmission 288 m² 4529 - 288 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 326 m² 538 - 326 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1672 m² 3903 - 1672 m² 0 -
Partitions 251 m² 2933 - 251 m² 0 -
Ceiling 1672 m² 5274 - 1672 m² 0 -
Overhead Lighting 0W 1810 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 288 - 0 0 -
People 0 2898 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9737 0 0% 0 0
>> Total Zone Loads - 107112 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 15F - Office 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 104 2.575 - 924 - 0
WINDOW 2 43 3.014 0.435 86 1092 0
ESE EXPOSURE
WALL 77 2.575 - 2019 - 0
SSW EXPOSURE
WALL 20 2.575 - 563 - 0
WINDOW 1 239 2.270 0.510 363 64145 0
WINDOW 2 43 3.014 0.435 86 9736 0
WNW EXPOSURE
WALL 88 2.575 - 1023 - 0
WINDOW 1 2 3.065 0.435 3 229 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 16F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 325 m² 49927 - 325 m² - -
Wall Transmission 299 m² 7026 - 299 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 325 m² 5573 - 325 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1873 m² 6106 - 1873 m² 0 -
Partitions 303 m² 4939 - 303 m² 0 -
Ceiling 1873 m² 21082 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10366 0 0% 0 0
>> Total Zone Loads - 114026 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 16F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 21 2.575 - 522 - 0
WINDOW 1 239 2.270 0.510 3785 42338 0
WINDOW 2 43 3.014 0.435 894 6426 0
ESE EXPOSURE
WALL 87 2.575 - 2135 - 0
SSW EXPOSURE
WALL 104 2.575 - 2225 - 0
WINDOW 2 43 3.014 0.435 894 1164 0
WNW EXPOSURE
WALL 87 2.575 - 2143 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 16F - Office 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 0400 HEATING DATA AT DES HTG
COOLING OA DB / WB 24.0 °C / 23.8 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 326 m² 75201 - 326 m² - -
Wall Transmission 288 m² 4529 - 288 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 326 m² 538 - 326 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1672 m² 3903 - 1672 m² 0 -
Partitions 251 m² 2933 - 251 m² 0 -
Ceiling 1672 m² 5274 - 1672 m² 0 -
Overhead Lighting 0W 1810 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 288 - 0 0 -
People 0 2898 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9737 0 0% 0 0
>> Total Zone Loads - 107112 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 16F - Office 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 104 2.575 - 924 - 0
WINDOW 2 43 3.014 0.435 86 1092 0
ESE EXPOSURE
WALL 77 2.575 - 2019 - 0
SSW EXPOSURE
WALL 20 2.575 - 563 - 0
WINDOW 1 239 2.270 0.510 363 64145 0
WINDOW 2 43 3.014 0.435 86 9736 0
WNW EXPOSURE
WALL 88 2.575 - 1023 - 0
WINDOW 1 2 3.065 0.435 3 229 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 17F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 325 m² 49927 - 325 m² - -
Wall Transmission 299 m² 7026 - 299 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 325 m² 5573 - 325 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1873 m² 6106 - 1873 m² 0 -
Partitions 303 m² 4939 - 303 m² 0 -
Ceiling 1873 m² 21082 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10366 0 0% 0 0
>> Total Zone Loads - 114026 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 17F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 21 2.575 - 522 - 0
WINDOW 1 239 2.270 0.510 3785 42338 0
WINDOW 2 43 3.014 0.435 894 6426 0
ESE EXPOSURE
WALL 87 2.575 - 2135 - 0
SSW EXPOSURE
WALL 104 2.575 - 2225 - 0
WINDOW 2 43 3.014 0.435 894 1164 0
WNW EXPOSURE
WALL 87 2.575 - 2143 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 17F - Office 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 0400 HEATING DATA AT DES HTG
COOLING OA DB / WB 24.0 °C / 23.8 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 326 m² 75201 - 326 m² - -
Wall Transmission 288 m² 4529 - 288 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 326 m² 538 - 326 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1672 m² 3903 - 1672 m² 0 -
Partitions 251 m² 2933 - 251 m² 0 -
Ceiling 1672 m² 5274 - 1672 m² 0 -
Overhead Lighting 0W 1810 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 288 - 0 0 -
People 0 2898 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9737 0 0% 0 0
>> Total Zone Loads - 107112 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 17F - Office 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 104 2.575 - 924 - 0
WINDOW 2 43 3.014 0.435 86 1092 0
ESE EXPOSURE
WALL 77 2.575 - 2019 - 0
SSW EXPOSURE
WALL 20 2.575 - 563 - 0
WINDOW 1 239 2.270 0.510 363 64145 0
WINDOW 2 43 3.014 0.435 86 9736 0
WNW EXPOSURE
WALL 88 2.575 - 1023 - 0
WINDOW 1 2 3.065 0.435 3 229 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 18F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 325 m² 49927 - 325 m² - -
Wall Transmission 299 m² 7026 - 299 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 325 m² 5573 - 325 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1873 m² 6106 - 1873 m² 0 -
Partitions 303 m² 4939 - 303 m² 0 -
Ceiling 1873 m² 21082 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10366 0 0% 0 0
>> Total Zone Loads - 114026 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 18F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 21 2.575 - 522 - 0
WINDOW 1 239 2.270 0.510 3785 42338 0
WINDOW 2 43 3.014 0.435 894 6426 0
ESE EXPOSURE
WALL 87 2.575 - 2135 - 0
SSW EXPOSURE
WALL 104 2.575 - 2225 - 0
WINDOW 2 43 3.014 0.435 894 1164 0
WNW EXPOSURE
WALL 87 2.575 - 2143 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 18F - Office 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 0400 HEATING DATA AT DES HTG
COOLING OA DB / WB 24.0 °C / 23.8 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 326 m² 75201 - 326 m² - -
Wall Transmission 288 m² 4529 - 288 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 326 m² 538 - 326 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1672 m² 3903 - 1672 m² 0 -
Partitions 251 m² 2933 - 251 m² 0 -
Ceiling 1672 m² 5274 - 1672 m² 0 -
Overhead Lighting 0W 1810 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 288 - 0 0 -
People 0 2898 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9737 0 0% 0 0
>> Total Zone Loads - 107112 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 18F - Office 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 104 2.575 - 924 - 0
WINDOW 2 43 3.014 0.435 86 1092 0
ESE EXPOSURE
WALL 77 2.575 - 2019 - 0
SSW EXPOSURE
WALL 20 2.575 - 563 - 0
WINDOW 1 239 2.270 0.510 363 64145 0
WINDOW 2 43 3.014 0.435 86 9736 0
WNW EXPOSURE
WALL 88 2.575 - 1023 - 0
WINDOW 1 2 3.065 0.435 3 229 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 19F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 325 m² 49927 - 325 m² - -
Wall Transmission 299 m² 7026 - 299 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 325 m² 5573 - 325 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1873 m² 6106 - 1873 m² 0 -
Partitions 303 m² 4939 - 303 m² 0 -
Ceiling 1873 m² 21082 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10366 0 0% 0 0
>> Total Zone Loads - 114026 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 19F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 21 2.575 - 522 - 0
WINDOW 1 239 2.270 0.510 3785 42338 0
WINDOW 2 43 3.014 0.435 894 6426 0
ESE EXPOSURE
WALL 87 2.575 - 2135 - 0
SSW EXPOSURE
WALL 104 2.575 - 2225 - 0
WINDOW 2 43 3.014 0.435 894 1164 0
WNW EXPOSURE
WALL 87 2.575 - 2143 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 19F - Office 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 0400 HEATING DATA AT DES HTG
COOLING OA DB / WB 24.0 °C / 23.8 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 326 m² 75201 - 326 m² - -
Wall Transmission 288 m² 4529 - 288 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 326 m² 538 - 326 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1672 m² 3903 - 1672 m² 0 -
Partitions 251 m² 2933 - 251 m² 0 -
Ceiling 1672 m² 5274 - 1672 m² 0 -
Overhead Lighting 0W 1810 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 288 - 0 0 -
People 0 2898 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9737 0 0% 0 0
>> Total Zone Loads - 107112 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 19F - Office 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 104 2.575 - 924 - 0
WINDOW 2 43 3.014 0.435 86 1092 0
ESE EXPOSURE
WALL 77 2.575 - 2019 - 0
SSW EXPOSURE
WALL 20 2.575 - 563 - 0
WINDOW 1 239 2.270 0.510 363 64145 0
WINDOW 2 43 3.014 0.435 86 9736 0
WNW EXPOSURE
WALL 88 2.575 - 1023 - 0
WINDOW 1 2 3.065 0.435 3 229 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 20F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 325 m² 49927 - 325 m² - -
Wall Transmission 299 m² 7026 - 299 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 325 m² 5573 - 325 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1873 m² 6106 - 1873 m² 0 -
Partitions 303 m² 4939 - 303 m² 0 -
Ceiling 1873 m² 21082 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10366 0 0% 0 0
>> Total Zone Loads - 114026 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 20F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 21 2.575 - 522 - 0
WINDOW 1 239 2.270 0.510 3785 42338 0
WINDOW 2 43 3.014 0.435 894 6426 0
ESE EXPOSURE
WALL 87 2.575 - 2135 - 0
SSW EXPOSURE
WALL 104 2.575 - 2225 - 0
WINDOW 2 43 3.014 0.435 894 1164 0
WNW EXPOSURE
WALL 87 2.575 - 2143 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 20F - Office 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 0400 HEATING DATA AT DES HTG
COOLING OA DB / WB 24.0 °C / 23.8 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 326 m² 75201 - 326 m² - -
Wall Transmission 288 m² 4529 - 288 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 326 m² 538 - 326 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1672 m² 3903 - 1672 m² 0 -
Partitions 251 m² 2933 - 251 m² 0 -
Ceiling 1672 m² 5274 - 1672 m² 0 -
Overhead Lighting 0W 1810 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 288 - 0 0 -
People 0 2898 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9737 0 0% 0 0
>> Total Zone Loads - 107112 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 20F - Office 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 104 2.575 - 924 - 0
WINDOW 2 43 3.014 0.435 86 1092 0
ESE EXPOSURE
WALL 77 2.575 - 2019 - 0
SSW EXPOSURE
WALL 20 2.575 - 563 - 0
WINDOW 1 239 2.270 0.510 363 64145 0
WINDOW 2 43 3.014 0.435 86 9736 0
WNW EXPOSURE
WALL 88 2.575 - 1023 - 0
WINDOW 1 2 3.065 0.435 3 229 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 21F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 325 m² 49927 - 325 m² - -
Wall Transmission 299 m² 7026 - 299 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 325 m² 5573 - 325 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1873 m² 6106 - 1873 m² 0 -
Partitions 303 m² 4939 - 303 m² 0 -
Ceiling 1873 m² 21082 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10366 0 0% 0 0
>> Total Zone Loads - 114026 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F -Zone 1- Office '' IN ZONE '' 21F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 21 2.575 - 522 - 0
WINDOW 1 239 2.270 0.510 3785 42338 0
WINDOW 2 43 3.014 0.435 894 6426 0
ESE EXPOSURE
WALL 87 2.575 - 2135 - 0
SSW EXPOSURE
WALL 104 2.575 - 2225 - 0
WINDOW 2 43 3.014 0.435 894 1164 0
WNW EXPOSURE
WALL 87 2.575 - 2143 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 21F - Office 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 0400 HEATING DATA AT DES HTG
COOLING OA DB / WB 24.0 °C / 23.8 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 326 m² 75201 - 326 m² - -
Wall Transmission 288 m² 4529 - 288 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 326 m² 538 - 326 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1672 m² 3903 - 1672 m² 0 -
Partitions 251 m² 2933 - 251 m² 0 -
Ceiling 1672 m² 5274 - 1672 m² 0 -
Overhead Lighting 0W 1810 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 288 - 0 0 -
People 0 2898 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9737 0 0% 0 0
>> Total Zone Loads - 107112 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 08F- 21F- Zone 2- Office '' IN ZONE '' 21F - Office 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 104 2.575 - 924 - 0
WINDOW 2 43 3.014 0.435 86 1092 0
ESE EXPOSURE
WALL 77 2.575 - 2019 - 0
SSW EXPOSURE
WALL 20 2.575 - 563 - 0
WINDOW 1 239 2.270 0.510 363 64145 0
WINDOW 2 43 3.014 0.435 86 9736 0
WNW EXPOSURE
WALL 88 2.575 - 1023 - 0
WINDOW 1 2 3.065 0.435 3 229 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 22F - Zone 1 - Office '' IN ZONE '' 22F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 303 m² 46714 - 303 m² - -
Wall Transmission 320 m² 7556 - 320 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 303 m² 5126 - 303 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 1873 m² 6106 - 1873 m² 0 -
Partitions 303 m² 4939 - 303 m² 0 -
Ceiling 1873 m² 21082 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10053 0 0% 0 0
>> Total Zone Loads - 110583 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 22F - Zone 1 - Office '' IN ZONE '' 22F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 42 2.575 - 1052 - 0
WINDOW 1 239 2.270 0.510 3785 42338 0
WINDOW 2 21 3.014 0.435 447 3213 0
ESE EXPOSURE
WALL 87 2.575 - 2135 - 0
SSW EXPOSURE
WALL 104 2.575 - 2225 - 0
WINDOW 2 43 3.014 0.435 894 1164 0
WNW EXPOSURE
WALL 87 2.575 - 2143 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 22F- Zone 2 - Mfun. Hall '' IN ZONE '' 22F - Multi Function Hal ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32.9 °C / 31.5 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 350 m² 7297 - 350 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 12 m² 165 - 12 m² 0 -
Floor Transmission 802 m² 2978 - 802 m² 0 -
Partitions 603 m² 11202 - 603 m² 0 -
Ceiling 802 m² 12204 - 802 m² 0 -
Overhead Lighting 4010 W 3699 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 5000 W 4827 - 0 0 -
People 321 19527 11292 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 6190 1129 0% 0 0
>> Total Zone Loads - 68089 12421 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 22F- Zone 2 - Mfun. Hall '' IN ZONE '' 22F - Multi Function Hal ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SSE EXPOSURE
WALL 350 2.575 - 7297 - 0
DOOR 12 1.703 - 165 - 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 22F - Zone 2 - Corridoor '' IN ZONE '' 22F - Multi Function Hal ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 32.9 °C / 31.5 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 86 m² 1994 - 86 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 179 m² 665 - 179 m² 0 -
Partitions 127 m² 2358 - 127 m² 0 -
Ceiling 179 m² 2724 - 179 m² 0 -
Overhead Lighting 895 W 826 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 18 1161 1076 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 973 108 0% 0 0
>> Total Zone Loads - 10699 1183 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 22F - Zone 2 - Corridoor '' IN ZONE '' 22F - Multi Function Hal ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 86 2.575 - 1994 - 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 22F - Zone 2 - Hall 2 '' IN ZONE '' 22F - Hall 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 44 m² 3853 - 44 m² - -
Wall Transmission 128 m² 3049 - 128 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 44 m² 929 - 44 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 6 m² 69 - 6 m² 0 -
Floor Transmission 332 m² 1082 - 332 m² 0 -
Partitions 119 m² 1945 - 119 m² 0 -
Ceiling 332 m² 3737 - 332 m² 0 -
Overhead Lighting 1660 W 1568 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3000 W 2926 - 0 0 -
People 133 8333 4675 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2749 467 0% 0 0
>> Total Zone Loads - 30240 5142 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 22F - Zone 2 - Hall 2 '' IN ZONE '' 22F - Hall 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 9 2.575 - 216 - 0
WINDOW 1 21 3.014 0.435 447 3213 0
SSW EXPOSURE
WALL 31 2.575 - 667 - 0
WINDOW 1 21 3.014 0.435 447 582 0
DOOR 6 1.703 - 69 - 0
WNW EXPOSURE
WALL 88 2.575 - 2165 - 0
WINDOW 2 2 3.065 0.435 35 59 0
TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' 22F - Zone 2 - Hall 2 '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 44 m² 3853 - 44 m² - -
Wall Transmission 128 m² 3049 - 128 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 44 m² 929 - 44 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 6 m² 69 - 6 m² 0 -
Floor Transmission 332 m² 1082 - 332 m² 0 -
Partitions 119 m² 1945 - 119 m² 0 -
Ceiling 332 m² 3737 - 332 m² 0 -
Overhead Lighting 1660 W 1568 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3000 W 2926 - 0 0 -
People 133 8333 4675 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2749 467 0% 0 0
>> Total Zone Loads - 30240 5142 - 0 0
TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' 22F - Zone 2 - Hall 2 '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 9 2.575 - 216 - 0
WINDOW 1 21 3.014 0.435 447 3213 0
SSW EXPOSURE
WALL 31 2.575 - 667 - 0
WINDOW 1 21 3.014 0.435 447 582 0
DOOR 6 1.703 - 69 - 0
WNW EXPOSURE
WALL 88 2.575 - 2165 - 0
WINDOW 2 2 3.065 0.435 35 59 0
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 23F - Zone 1 - Office '' IN ZONE '' 23F - Office 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 30.4 °C HEATING OA DB / WB 27.0 °C / 24.3 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 282 m² 43501 - 282 m² - -
Wall Transmission 318 m² 7512 - 318 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 282 m² 4679 - 282 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 23 m² 3832 - 23 m² 0 -
Floor Transmission 1873 m² 6106 - 1873 m² 0 -
Partitions 303 m² 4939 - 303 m² 0 -
Ceiling 1873 m² 21082 - 1873 m² 0 -
Overhead Lighting 0W 3262 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 520 - 0 0 -
People 0 5225 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 10066 0 0% 0 0
>> Total Zone Loads - 110725 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 23F - Zone 1 - Office '' IN ZONE '' 23F - Office 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NNE EXPOSURE
WALL 52 2.575 - 1294 - 0
WINDOW 1 239 2.270 0.510 3785 42338 0
DOOR GLASS 12 5.000 0.880 404 1696 0
ESE EXPOSURE
WALL 81 2.575 - 1993 - 0
DOOR GLASS 6 5.000 0.880 202 870 0
SSW EXPOSURE
WALL 104 2.575 - 2225 - 0
WINDOW 2 43 3.014 0.435 894 1164 0
WNW EXPOSURE
WALL 81 2.575 - 2001 - 0
DOOR GLASS 6 5.000 0.880 202 459 0