KALTIM 2 (2x100MW) CFSPP

GPK Weekly Report (06 July- 12 July 2020) No. : GPK-WR-MB-2020-07-06

Prepared by : Roland Mahendra Wahid


Job Title : Electrical operator
Department : Main Block
Area Picture Remarks
CCR Date : 07/07/2020

Decrease Reactive Power in Excitation


Generator for decrease Reactive power
in G-T1 and G-T2 Transformer until
Voltage Outgoing 150 kV system 153
kV

Relay GT Date : 06/07/2020 - 12/07/2020


protection,
SST, HSDT

Inspection and check in local 1#GT


protection A,B,C #1HSDT and 2#GT
protection A,B,C, #2HSDT and SST
protection (Not indication fault and
Not alarm )(condition normal)

489729493.docxwahid Page 1 of 43
489729493.docxwahid Page 2 of 43
400 V Date : 06/07/2020 - 12/07/2020

Inspection in local Panel MCC 380


Volt unit PC 1A,1B and 2A,2B ,
station PC, emergency PCunit1 and 2,
standby, emergeny lightning MCC,
Lightning MCC in Main Building,
Maintenance MCC in Main Building
unit PC section 1A (winding Transformer temperature
normal, Fan normal Function, room
temperature normal, voltage, current,
CB, load for MCC, normal condition
and not indication alarm )

Unit PC section 1B

489729493.docxwahid Page 3 of 43
Station PC A

Station PC 1B

Emergency PC unit 1B

489729493.docxwahid Page 4 of 43
Emergency PC unit 1A

Emergency
lightning MCC

lightning MCC in main building

489729493.docxwahid Page 5 of 43
Maintenance MCC in main building

MCC central control Build

Emergency PC unit 2B

Emergency PC unit 2A

489729493.docxwahid Page 6 of 43
unit PC section 2A

Unit PC section 2B
6 kV Date : 06/07/2020 - 12/07/2020

Inspection and check in local


switchgear panel 6kV section 1A,1B
and 2A,2B (Normal power from UAT
Normal condition, stanby power from
SST normal, Voltage, current, ES open
position, PT normal, Room
temperature Normal, Fuse Normal, No
Metal enclosed swichgear 6 kV section 1B from Normal indication Fault alarm )
Power Unit Auxiliary Transformer (normal condition)

489729493.docxwahid Page 7 of 43
Metal enclosed swichgear 6 kV section 1B

Metal enclosed swichgear 6 kV section 1A from Normal


Power Unit Auxiliary Transformer

Metal enclosed swichgear 6 kV section 1A

489729493.docxwahid Page 8 of 43
Metal enclosed swichgear 6 kV section 2A from
Normal Power Unit Auxiliary Transformer

Metal enclosed swichgear 6 kV section 2A

Metal enclosed swichgear 6 kV section 2B from Normal


Power Unit Auxiliary Transformer

489729493.docxwahid Page 9 of 43
Metal enclosed swichgear 6 kV section 2B

Batery Room Date : 06/07/2020 - 12/07/2020

Inspection condition 104 Battery cell


DC unit1 and unit 2 in local (cable
connection, batery DC voltage,liquid
level batery, temperature batery room
normal)

489729493.docxwahid Page 10 of 43
Emergency Date : 06/07/2020 - 12/07/2020
Diesel
Generator

Inspection and check local Emergency


Diesel generator(Fuel level, Oil Level,
accu batery DC, Temperature,)
(normal condition)

#1 DC 220 V Date : 06/07/2020 - 12/07/2020


and UPS

Inspection Condition in local Cabinet


DC 220 system and UPS system

Rectifier Voltage, Batery Voltage,


Batery Current, Control Voltage,
current, distribution cabinet normal
and Not indication fault alarm,
condition Normal, UPS mode: input
Aux, UPS bypass normal, distribution
load UPS normal, Fan for UPS Normal

489729493.docxwahid Page 11 of 43
489729493.docxwahid Page 12 of 43
#2 DC 220 V Date : 06/07/2020 - 12/07/2020
and UPS

Inspection Condition in local Cabinet


DC 220 system and UPS system

Rectifier Voltage, Batery Voltage,


Batery Current, Control Voltage,
current, distribution cabinet normal
and Not indication fault alarm,
condition Normal, UPS mode: input
Aux, UPS bypass normal, distribution
load UPS normal, Fan for UPS Normal

489729493.docxwahid Page 13 of 43
489729493.docxwahid Page 14 of 43
MCC for Date : 06/07/2020 - 12/07/2020
Turbine unit
#1

Inspection and check condition in local


MCC for Turbine (power incoming
From Unit PC section 1A and unit PC
1B, ATS for power incoming Normal,
Voltage, current, load 10BJA and
10BJB (Not indication alarm, normal
condition )

MCC For Turbine 10BJA

MCC for Turbine 10BJB

489729493.docxwahid Page 15 of 43
MCC for Date : 06/07/2020 - 12/07/2020
Turbine unit
#2

Inspection and check condition in local


MCC for Turbine (power incoming
From Unit PC section 2A and unit PC
2B, ATS for power incoming Normal,
Voltage, current, load 20BJA and
20BJB (Not indication alarm, normal
condition )

MCC For Turbine 20BJA

MCC for Turbine 10BJB

489729493.docxwahid Page 16 of 43
#1 excitation Date : 06/07/2020 - 12/07/2020
Transformer

Inspection and checking in local


temperature excitation Transformer
(temperature winding normal, Not
indication fault and not alarm, fan
normal function)

#2 excitation Date : 06/07/2020 - 12/07/2020


Transformer

Inspection and checking in local


temperature excitation Transformer
(temperature winding normal, Not
indication fault and not alarm, fan
normal function)

#1 Potential Date : 06/07/2020 - 12/07/2020


Transformer
and surge
arrrester
cabinet,

Inspection and check in local Potential


Transfromer and surge Arrester
cabinet, Generator NGR (Potential
Transformer rack in position,

489729493.docxwahid Page 17 of 43
Temperature Normal, Fuse normal, PT
condition normal NGR switch close
position )

Potential Transformer

Surge Arrester

Generator Neutral Grounding Resistors Cabinet

#2 Potential Date : 06/07/2020 - 12/07/2020


Transformer
and surge
arrrester
cabinet,

Inspection and check in local Potential


Transfromer and surge Arrester cabinet
(Potential Transformer rack in
position, Fuse normal, PT condition
normal )

489729493.docxwahid Page 18 of 43
Potential Transformer

Surge Arrester

Generator Neutral Grounding Resistors Cabinet

489729493.docxwahid Page 19 of 43
380 MCC Date : 11/07/2020

Measure Resistance Insulated in


Busbar MCC 380 V Emergency PC
Section 2B (Phase to Ground and
Phase to Phase) for power EH Device
Main Oil Pump B
Condition Normal

SST.GT.UAT Date : 06/07/2020 - 12/07/2020


Transformer

Inspection and check condition in


Local Starting Stanby Transformer
(OLTC, Oil Level, oil and winding
temperature,silica Gel, bushing
Transformer, Fan, normal condition )
Oil and winding oil Level SST
Temperature SST Relay bulcolz SST near conservator oil
Tank leakage indication

OLTC SST trafo local control cooling Fan


Fan SST

Silica Gel SST

489729493.docxwahid Page 20 of 43
Bulcolz Relay in SST Transformer leakage
indication

Inspection and Checking in local


silica gel, oil tank Transformator,
GT relay bulcolz, Tap changer GT:
9 temperature winding, oil
temperature, Fan Normal, bushing
normal, silica Gel, normal and
nothing indication Fault )

Oil and winding conservator tank Oil


Temperature GT1 level GT1

OLTC GT 1 local control cooling Fan


GT1

489729493.docxwahid Page 21 of 43
Silica Gel GT 1 Temperature line R,S,T
Gen to GT1

Inspection and Checking in local


silica gel, oil tank Transformator,
UAT relay bulcolz, temperature
winding, oil temperature, Fan
Normal, bushing normal, silica Gel,
normal and nothing indication Fault
)

Oil and winding conservator tank oil level


Temperature UAT

Silica gel UAT 1 local control cooling


Fan

489729493.docxwahid Page 22 of 43
Oil and winding conservator tank Oil
Temperature GT2 level GT2 Inspection and Checking in local
silica gel, oil tank Transformator,
GT relay bulcolz, Tap changer GT:
9 temperature winding, oil
temperature, Fan Normal, bushing
normal, silica Gel, normal and
nothing indication Fault )

Temperature line R,S,T


Gen to GT2 local control Air cooling
Fan GT 2

489729493.docxwahid Page 23 of 43
Silica Gel GT 2

Oil and winding conservator tank oil level


Temperature UAT2

Silica gel UAT2 local control cooling Fan

489729493.docxwahid Page 24 of 43
1# excitation Date : 06/07/2020 - 12/07/2020

Inspection and check local excitation


panel (SCR(silicon control rectifier,
generator Voltage, Field voltage, Field
current, Reactive power, Active
Power, power factor, normal
condition)

2 # excitation Date : 06/07/2020 - 12/07/2020

Inspection and check local excitation


panel (SCR(silicon control rectifier,
generator Voltage, Field voltage, Field
current, Reactive power, Active
Power, power factor, normal
condition)

489729493.docxwahid Page 25 of 43
GIS 150 kV Date : 06/07/2020 - 12/07/2020

Inspection and checking condition in


local Gas Insulated Switchgear 150
kV(CB,DS,close position SF6 Gas
pressure Normal, oxygen, density No
indication fault alarm)
(Condition Normal and Nothing
indication leakage) remote position
and all ES open

489729493.docxwahid Page 26 of 43
SF6 in line 02DS3 and 02ES3
Relay room Date : 06/07/2020 - 12/07/2020
150 kv M
protection inspection Check in local area Relay
Room 150kv CubicleJ0APS01
SCMCS #1 (TELECONTROL &
COMMON COMMUNICATION)
And Cubicle J0APS02 SCMS #2
(COMMOM DIVICE) BUSBAR
(Nothing indication alarm)

Inspection Check local area Relay


Room 150KV, Cubicle J0APS06
SCMCS #6 (150KV BUSBAR
TIE AND VOLTAGE PARALLEL)
And Cubicle J0APS07 150KV
BUSCOUPLE PROTECTION

489729493.docxwahid Page 27 of 43
Inspection Check local area Relay
Room 150kv Cubicle J0APS03
SCMCS #3 (CB OF GT ) and Cubicle
J0APS05 SCMCS #5 CUBICLE
(150KV OUTGOING )
(Nothing indication alarm)

Inspection check in local area relay


room 150 kV cubicle 1 150KV LINE
PROTECTION PANEL CB A1
CLOSE , CB B1 CLOSE, CB C1
CLOSE
(Nothing indication alarm)

Inspection check in local area relay


room 150 kV cubicle 1 150KV
BUSBAR ROTECTION PANEL
(Nothing indication alarm)

489729493.docxwahid Page 28 of 43
Inspection and check MCC for relay
room 150 kV J0BLB (load at MCC
normal, ATS normal, voltage normal,
power incoming

Inspection and check in local DC 110


V cabinet (rectifier voltage, AC
voltage, Batery Voltage, batery
Current, charging cabinet,distribution
cabinet 1 and distributon cabinet 2,
batery voltage, batery current, DC bus
Voltage normal)

489729493.docxwahid Page 29 of 43
Water Date : 06/07/2020 - 12/07/2020
treatment

Inspection and check in local MCC for


Water treatment (Transformer winding
Temperature normal, Fan Function
water Treatment PC Normal, room temperature Normla,
Section A Not indication fault alarm in MCC,
power incoming working, CB close
position, Voltage and current normal
condition)

489729493.docxwahid Page 30 of 43
Water Treatment PC section B

Coal handling Date : 06/07/2020 - 12/07/2020

Inspection and check in local MCC for


Coal handling (Transformer winding
Temperature normal, Fan Function
Normal, room temperature Normal,
Not indication fault alarm in MCC,
power incoming working, CB close
position, Voltage and current normal
condition)

489729493.docxwahid Page 31 of 43
Service water Date : 06/07/2020 - 12/07/2020
pump

Inspection and check in local MCC for


service water pump (power incoming,
voltage, current, ATS, No indication
fault alarm, Normal condition)

489729493.docxwahid Page 32 of 43
Note :Found a puddle of water on the
MCC 380 V service water pump cable
track

1# ESP Date : 06/07/2020 - 12/07/2020

Inspection and check in local MCC for


ESP 1B, (Transformer winding
Temperature normal, Fan Function
Normal, room temperature Normla,
Not indication fault alarm in MCC,
power incoming working, CB close
position, Voltage and current normal
condition)

489729493.docxwahid Page 33 of 43
ESP and Ash Handling PC Section 1B

Inspection and check in Local ESP


controler Building MCC (Voltage,
current, load distribution,
ATS(automatic transfer switch)normal

Inspection and check HV Control


Cabinet of Chamber unit 1(Voltage,
Current Normal condition, not
indication Alarm)

489729493.docxwahid Page 34 of 43
Inspection and check in local MCC for
ESP 2B, (Transformer winding
Temperature normal, Fan Function
Normal, room temperature Normla,
Not indication fault alarm in MCC,
power incoming working, CB close
position, Voltage and current normal
condition)

ESP and Ash Handling PC Section 2B

489729493.docxwahid Page 35 of 43
FGD MCC Date : 06/07/2020 - 12/07/2020

Inspection and check in local MCC for


FGD (Transformer winding
Temperature normal, Not indication
fault alarm in MCC, power incoming
working, CB close position, Voltage
and current normal condition)

489729493.docxwahid Page 36 of 43
Circulating Date : 06/07/2020 - 12/07/2020
Water Pump
house MCC

Inspection and check in local MCC for


Circulating water pump house (power
incoming, voltage, current, ATS, load
at MCC Not indication fault alarm,
Normal condition)

Note :Found a puddle of water in the


cable track MCC 380 V Circulating
water pump

489729493.docxwahid Page 37 of 43
1# Generator Date : 06/07/2020 - 12/07/2020
House

Inspection and check in local bearing


temperature, bearing outlet oil,
Lubricating oil temperature inlet and
oulet generator(nothing indication
leakage), slip ring and carbon brush
generator temperature normal, frame
temperature, electric heater off,
(condition normal)

Temperature Carbon Brush and


collector Generator #1 (37°C-46°C)

489729493.docxwahid Page 38 of 43
2 #Generator Date : 06/07/2020 - 12/07/2020
House

Inspection and check in local bearing


temperature, bearing outlet oil,
Lubricating oil temperature inlet and
oulet generator(nothing indication
leakage), slip ring and carbon brush
generator temperature normal, frame
temperature, electric heater off,
(condition normal)
Temperature Carbon Brush and
collector Generator #2 (37°C-46°C)

489729493.docxwahid Page 39 of 43
CCR Date : 06/07/2020 - 12/07/2020

Monitoring and record ECS(HV GT,


voltage generator, reactive power and
powe factor in Generator and
GT,Generator Temeperature syste,
temperature winding and oil
Transformer GT, SST, UAT, winding
temperature and oil temperature,
Transformer Excitation voltage and
excitation current, winding transformer
excitation, 6 kv work position, DC
system, UPS system, 400 V)
(Nothing indication fault alarm)

ECS unit 1

Monitoring and record ECS(HV GT,


voltage generator, reactive power and
powe factor in Generator and
GT,Generator Temeperature syste,
temperature winding and oil
Transformer GT2, UAT2, winding
temperature and oil temperature,
Transformer Excitation voltage and
excitation current, winding transformer
excitation, 6 kv work position, DC
system, UPS system, 400 V)
(Nothing indication fault alarm)

489729493.docxwahid Page 40 of 43
DCS unit 2

ECS unit 2

Monitoring record SCADA 150 kV


substation, (Generator Transformer,
outgoing Line 1, Bus 1 PT and Bus 2
PT, SST, ,Buscouple, arrester, nothing
alarm ) all condition normal

380 V MCC Date : 08/07/2020

Change Relay Undervoltage in MCC


Station PC Busbar PT
- Side incoming power Station
PC A gateway ATS input/exit
open and gateway
autorecovery input exit open
- All gateway interlock tripping
in the MCC station PC A open
- open CB busbar PT
- and change Relay
undervoltage

489729493.docxwahid Page 41 of 43
Side incoming power Station PC A gateway ATS
input/exit open and gateway autorecovery input exit
open

All gateway interlock tripping in the MCC station PC A


open

Open CB Busbar PT and change undervoltage Relay

489729493.docxwahid Page 42 of 43
489729493.docxwahid Page 43 of 43