You are on page 1of 1

001 03 X AA-036069 990 NOTES:

REV. NO. SHT. NO. DRAWING NUMBER INDEX PLANT NO.


1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
OTHERWISE NOTED.

A
2. ANODES MAY BE INSTALLED VERTICALLY OR
HORIZONTALLY.
MATERIAL LIST 3. THERMITE WELDING OF CABLES SHALL BE IN
ACCORDANCE WITH SAUDI ARAMCO STD. DWG. AB-036381.
CODE SAMS NO. DESCRIPTION
| CARRIER PIPE 4. INSTALLATION OF CATHODIC PROTECTION AT THRUST
1 17-851-611 ANODE: MAGNESIUM; 60 LB; PREPACKAGED
ANCHOR SHALL BE IN ACCORDANCE WITH SAES-X-400.
2 17-851-681 ANODE: MAGNESIUM; 100 LB; BARE 5. ALL GALVANIC ANODES TO BE THOROUGHLY SOAKED
3 15-111-101 CABLE: NO. 8 AWG WITH WATER PRIOR TO AND DURING BACKFILLING.
4 14-112-366 CONNECTOR: SPLIT BOLT 6. AFTER SECURING ANODE LEAD WIRE TO HEADER
CABLE WITH SPLIT BOLT CONNECTOR, AND SOLDERING
5 18-080-020 TAPE: RUBBER
WIRES, WRAP CONNECTION WITH 3 ONE HALF LAP
6 18-079-940 TAPE, VINYL LAYERS RUBBER TAPE, THEN 3 ONE HALF LAP
LAYERS OF PLASTIC VINYL TAPE.
7. F. B . E. COATING REPAIRS AT THERMITE WELDS
1000 TO BE PER APCS-113.
C.P. TEST STATION
(TYP.) 8. DIMENSIONS OF ANODES FROM PIPELINE & THRUST
SEE DETAIL 1 ANCHOR ARE FOR ALL THRUST ANCHOR TYPES.
ANODE #2
9. IN SUBKHA AREAS, ONLY BARE 100 LB. ANODE IS
ANODE #1 MARKER PLATE TO BE USED.
1/C #8 AWG
HEADER CABLE SEE DWG. AB-036351

3
(TYP.)

1/C #8 AWG
600

SPLICE MOUNTING SUPPORT


NEGATIVE CABLE
THRUST ANCHOR SEE DWG. AB-036540
(TYPICAL)

1220
SEE NOTE 8

CURRENT RETURN
PIPE
CABLE BERM
BERM
EXISTING GRADE

1/C #8 AWG
TEST LEAD CABLE 3

THERMITE WELD
CABLE ONTO SLEEVE
SPLICE
(TYP. FOR 2) 3 3
SEE DETAIL 2
SEE NOTE 3 & 7
FOR CONNECTION (TYP.)
THERMITE WELD
SEE NOTES 3 & 7

3 SPLICE
MAGNESIUM ANODE
(TYP. FOR-4)
ANODE #3 ANODE #4

1/C #8 AWG

300
HEADER CABLE REFERENCE DRAWINGS
THERMITE WELDING OF CABLES AB-036381
3 CATHODIC PROTECTION MARKER
AB-036351
PLATE DETAIL
CATHODIC PROTECTION MOUNTING
SPLICE AB-036540
SUPPORT DETAIL FOR JUNCTION BOX
MAGNESIUM ANODE
CLOSE TO EDGE

(TOE)OF BERM
1 DETAILS OF INST’N OF GALVANIC ANODES
600 AA-036352
(TYP. FOR 4) ROADS CAMEL PIPELINE CROSSING.
CLOSE TO EDGE
OR SEE NOTE 9 (TYP.)
(TOE)OF BERM GALVANIC ANODE 3-PIN TEST STATION AA-036157
2 SECTION "A-A"

THRUST ANCHOR ANODE INSTALLATION


A

C.P. TEST STATION


PLAN SEE DETAIL 1

GALVANIC ANODE
3-PIN TEST STATION
SEE AA-036352 DETAIL 3 & 4 MANDATORY DRAWING
WRAP CONNECTIONS
5 6
WITH TAPE (SEE NOTE 6) EDSD
REVISED TO SHOW 3-PIN TEST
03 MAY98 DMC STATION; ADDED MAT’L. LIST ITEM #2.
SOLDER
ESSD REVISED NOTE-3 AND
02 AUG95
RLO REFERENCE DRAWINGS
ANODE LEAD WIRES ANODE HEADER CABLE
3 ESSD CORRECTED REFERENCE DWG. NO
TO JUNCTION BOX 01 NOV92
MAQ & ADDED DETAIL REFERENCE.

REV. DATE BY JO/EWO DESCRIPTION CHKD. CERT. APPD.


NO.

SOLDER SAUDI ARABIAN OIL COMPANY


SPLIT BOLT CONNECTOR 4
DRAWN BY EPE (ESSD) CHECKED BY SCALE: NONE

03-31-92 03-31-92
DETAIL-2 DATE STARTED DATE COMPLETED

OPR’G. DEPT. ENG. DEPT.


CONNECTION OF ANODE CABLES
APP’D. FOR CONST.

THIS DRAWING IS NOT TO BE USED FOR CERTIFIED


CONSTRUCTION OR FOR ORDERING
MATERIAL UNTIL CERTIFIED AND DATED BY DATE

CATHODIC PROTECTION
INSTALLATION DETAILS
GALVANIC ANODES AT THRUST ANCHOR
STD. DWG. METRIC
DETAIL-1 PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

990 X AA-036069 001 03


Saudi Aramco 2615 ENG. (3/91)

Copyright©Saudi Aramco 2009. All rights reserved. CADD-02