User manual LED (W) is on. The “k” and “M” measurement units are associated with two LEDs which come on automatically
Mod. EV3M TRMS ELECTRONIC DIGITAL MULTIMETERS Example depending on the value of the measurement taken.
Read all instructions carefully field 1 100 L1
Example (with TA 5000/5A)
Vemer S.p.A. I1=160A; I2=1000A; I3=2500A, the information displayed will be as follows:
field 2 170 L2
I - 32032 Feltre (BL) • Via Camp Lonc, 16 The measurement instruments in the EV3M series are TRMS electronic digital multimeters to view the
Tel +39 0439 80638 • Fax +39 0439 80619 main electric measurements of 3 or 4 wire three-phase systems field 3 120 L1 0.16
e-mail: info@vemer.it - web site: www.vemer.it The electric measurements: voltage, current, power, power factor, frequency and neutral current
L3 L1
are shown on three LED displays with three digits Press the “OK” key to view the system power as follows: L2 1.00
L2
EV3M-D During the installation and operation of the instrument, comply with the following instructions: field 1 P L1 LEDs “A” and “k” are on.
1) The product must be installed by a qualified expert.
2) Do not power or connect the instrument if it is damaged. field 2 SYS L2 PARAMETER SETTING: TA AND 3 OR 4 WIRE SYSTEM
2) The appliance must be installed and operated in compliance with current electric systems
standards. field 3 390 (calculated value) L3 • TA setting
3) After installation, inaccessibility to the connection terminals without appropriate tools must The value of the TA secondary is 5A and cannot be modified.
be guaranteed. Press “OK” again to go back to the phase measurement. To set the capacity of the primary, proceed as follows.
5) Before accessing the connection terminals, verify that the leads are not live. With the instrument turned off, hold down the “PRG” key, then power the instrument. After
6) The instrument is destined for use in environments with overvoltage category III and pollution Page 5: PHASE APPARENT POWER
approximately 3 seconds, the following information is displayed:
level 2, according to the CEI EN 61010-1 standard. LED (VA) is on.
7) There must be a bipolar cut-off in the power supply network. Example field 1 Pr
8) A device to protect against overloads must be installed in the electrical system upstream from L1
To modify field 3 use the c key (increase) or d key (decrease). The value can be modified in steps
Press the “OK” key to view the system power as follows: of 5 up to 1000A (5, 10, 15, 20, etc.) and in steps of 50 from 1000 to 10000A (1050, 1100, 1150,
TECHNICAL CHARACTERISTICS
etc.)
• Power supply: 230 V AC (-15%/+10%), 50/60Hz Example Once you have selected your chosen capacity, press “OK” to confirm.
• Input voltage: Vmax = 300V (phase-neutral)
• The instrument must be installed exactly as shown in the figure. • Incorrect TA connection
field 3 78.0 (calculated value) L3
• Connection for the voltage inputs is always direct, whereas an external amperometric transformer (TA) is In case of incorrect connection of one or more TA, the display relating to the phase concerned by the
L1 L1 Press “OK” again to go back to the phase measurement.
L2 L2 used for the current inputs. incorrect connection flashes on the active powers page [LED (W) on].
L3 L3
N N Attention! The current transformer secondary circuits CANNOT be earthed. Page 7: POWER FACTOR (cosφ)
No LEDs on and the displays show the value of cosφ measured on each phase. ERROR MESSAGES
S2 S1 P1 P2 Example
I
OPERATION • Error messages
I
P1 P2 S1 S2
• Once the instrument has been installed, the pages of the various electric measurements monitored can field 1 L.86 L = inductive phase shift L1
field 1 PF L1
field 2 230 L2 HHH (flashing)
k V(L-N)
field 2 SYS L2
Means the current and/or voltage values are beyond the full scale value.
L1
field 3 230
M V(L-L) L3
PRG
field 3 0.80 (calculated value) L3
Voltage overload V>Vmax + 6%
k V(L-N) A
Page 2: CHAINED VOLTAGES (L-L) Current overload I>In + 20% for connection via 5/5A TA (for different TAs, multiply by the
L2
M L1 V(L-L)
W LED V(L-L) is on. Press “OK” again to go back to the phase measurement. transformation ratio).
A
VA Example
L2 W
L3
VA
EV3M-R
var Page 8: FREQUENCY If the page displayed is not related to the measurement in overload (out of scale), phase or chained
field 1 300 L1
L3
var OK No LEDs on and information displayed as follows: voltage or phase current, the message is nonetheless shown by flashing the value of the overall
EV3M-D Prg OK
field 2 300 L2
Example measurement (if the page displayed concerns the system) or the measurements related to the
phases in overload (if the page displays the phase measurements).
field 3 300 field 1 F L1
L3
field 2 50.0 Note. If at least one of the phase currents is out of scale, three dashes are displayed on the neutral
L2
Page 3: PHASE CURRENTS current page:
LED (A) is on. field 3 (empty)
PRG — Parameter programming — Field 1 Example L3
- - - (flashing)
L1 Page 9: NEUTRAL CURRENT
field 1 10.8 L1
— Increase LED (A) is on. REFERENCE STANDARDS
— Field 2 Example
L2
field 2 0.53 L2
Compliance with Community Directives:
— Decrease field 1 In
field 3 3.00 L1
2006/95/EC (Low Voltage)
L3
— Field 3 2004/108/EC (Electromagnetic Compatibility)
L3 field 2 1.4 is declared with reference to the following harmonized standards:
OK — Display / confirm data L2