DC1000 Manual en PDF
DC1000 Manual en PDF
SERIES
PRODUCT MANUAL
Symbol Definition
This CAUTION symbol on the equipment refers the user to the Product
Manual for additional information. This symbol appears next to required
information in the manual.
WARNING
PERSONAL INJURY: Risk of electrical shock. This symbol warns the user
of the potential shock hazard where HAZARDOUS LIVE voltages greater
than 30 Vrms, 42.4 Vpeak, or 60 Vdc may be accessible. Failure to
comply with these instructions could result in death or serious injury.
CAUTION
Installation should be performed only by personnel who are technically competent to do
so. Local Regulations regarding electrical & safety must be observed.
DC10 0 - - -
Size
Table III
1 48*48
Manual
2 48*96
E English
3 72*72
C Chinese
4 96*96
K Korean
Program Input
C None R RTD
P Program T TC
L Linear
Table I Table II
Output 1 Output 2 Alarm Aux. Input 2 Comm.
d e c
Side View
CAUTION
Applying 85-264Vac to a controller rated for 15-50Vdc will severely damage the controller
and is a fire and smoke hazard.
Noise
POWER Filter
1 6
11
AC 85 ~ 265V 2 7
(50 / 60Hz) 12
DC 15 ~ 50V 3 8
13
(option)
4 9
14
5 10
OUTPUT PV
OUT2 Relay Volt Linear OUT1=5 Linear RTD TC
1 2 3
7 7 7
2 11 G1
B
8 8 8
3 12 K1
A,B,C,D
9 B 9 9
13 G2
OUT1 Linear
Relay Volt
10 A 10 10
14 K2
1 2 3
4
ALARM
5
A,B,C,D
AL1 AL1 AL2
2 11 13
OUT1=7
3 12 14
SG
13 13
1 11
Noise
POWER
Filter 2 12
AC 85 ~ 265V 3 13
(50 / 60Hz)
DC 15 ~ 50V 4 14
(option) 5 15
6 16
7 17
8 18
9 19
10 20
OUTPUT PV
OUT2 Relay Volt Linear L inear R TD TC
1 2 3
17 17 17
6
B
18 18 18
7
A,B,C,D
19 B 19 19
OUT1 Relay Volt Linear
NO 1 2 3
20 A 20 20
8
NC
9
ALARM AUX. OUT
AL1 AL2 AL3
10 COM NC NC
A,B,C,D 3 11 6 11
TRS
NO NO
OUT1=7 4 12 7 12
6
5 COM 13 13
COM
7 CLOSE
INPUT2 COMM.
8 OPEN
COMM COMM
RS232 RS485
9 RD
14 14 D-
14
10 COM SD
15 15 15
D+
SG
16 16 16
1 15 8
Noise
POWER
Filter 2 16 9
AC 85 ~ 265V 3 17 10
(50 / 60Hz)
4 18 11
DC 15 ~ 50V
(option) 5 19 12
6 20 13
7 21 14
OUTPUT PV
12 12 12
4 17 G2
A,B,C,D
13 B 13 13
OUT1 Relay Volt Linear
19
PROT
NO 1 2 3
14 A 14 14
5 20
NC
6
ALARM AUX. OUT
AL1 AL2 TRS
7 COM COM
A,B,C,D 3 11 18
NO
OUT1=7 OUT1=8 4 12 19
3 15 G1
NC 13
4 CLOSE 16 K1
INPUT2 COMM.
5 OPEN 17 G2
Remote SP COMM COMM
RS232 RS485
6 18 K2 RD
14 14 14
D-
7 COM 20 SD
15 15 15
D+
PROT
21 SG
16 16 16
1 31 11 COMM.
Noise
POWER COMM COMM
Filter
2 32 12 RS232 RS485
RD
AC 85 ~ 265V 3 33 13
31
D-
31
(50 / 60Hz)
4 34 14 SD
DC 15 ~ 50V 32
D+
32
(option)
5 35 15
SG
33 33
6 36 16
7 37 17
AUX. OUT
8 38 18 TRS
39
9 39 19
10 40 20 40
OUTPUT PV
OUT2 Relay Volt Linear OUT1=6 OUT1=5 Linear RTD TC
1 2 3
6 31 RG 31 G1
17 17 17
B
7 33 RG 33 G2
18 18 18
A,B,C,D
19 B 19 19
OUT1 Relay Volt Linear
35 TG1 39
PROT
NO 1 2 3 20 A 20 20
8 37 TG2 40
NC
9 39 OUT1=9
ALARM
PROT AL1 AL2 AL3
31 G1
10 COM NC NC
A,B,C,D 40 3 11 6
32 K1
NO NO
OUT1=7 OUT1=8 4 12 7
6 31 G1 33 G2
5 COM 13
COM
7 CLOSE 32 K1 34 K2
INPUT2 COMM.
8 OPEN 33 G2 35 G3
Remote SP COMM COMM
RS232 RS485
9 34 K2 36 K3 RD
14 14 14
D-
10 COM 35 39 SD
15 15 15
D+
PROT PROT
36 40 SG
16 16 16
Upper Display
Lower Display
LEDs
Bar Graph SHIFT key
% %
(2)
(3) (2)
Program Configuration 2
(3)
Set Up
CAUTION
DO NOT access to ‘Set Up’ mode without instruction from techical assistant.
Parameter Description
PV Display
SP Display
SET
Output Limit To limit the Maximum of Control Ouput
Percentage (%)
SET
Auto Tuning
SET
Alarm 1 Enter deviation value or absolute value
SET
Alarm 2
SET
Alarm 3
Parameter Description
Main Control (OUT1) Range: 0~200%
P value (Proportional Band) P1=0, ON/OFF Control
SET
Main Control (OUT1) Range: 0~3600 seconds
I value (Integral Time) I=0, Integral off
SET
Main Control (OUT1) Range: 0~900 seconds
D value (Derivative Time) D=0, Derivative off
SET
Main Control * DO NOT CHANGE THE VALUE
Dead-Band Time
SET
Main Control (OUT1) Range: 0~ Upper limit value (USPL)
‘Auto Tuning’ offset Prevent from ‘Overshoot’ during auto tuning
SET
Main Control (OUT1) Output type (SSR Æ 1, 4~20mAÆ0, relayÆ10)
Cycle of Control Output Range: 0~150 seconds
SET
Main Control (OUT1) Just in case of ON/OFF control (P1=0) (Range: 0~1000)
Actuation of Hystersis ON : PV<=(SP-HYS1)
SET OFF : PV > (SP+HYS1)
Sub Control (OUT2) The same with the method of CYT1 configuration
Cycle of Control Output
SET
Sub Control (OUT2) The same with the method of HYS1 configuration
Hysteresis
SET
Main Control (OUT 1) Control ouput is turned off before getting to SP
Gap Turning Point = SP-GAP1; OFF (OUT1=Heat)
SET
SET
* The parameters are only for ‘Output’ 2 function, so it will appear only in the model which has the “OUT2” option.
Parameter Description
Input 1 (INP1) To define input type & input range
* Refer to
SET
Input 1 (INP1) To be used during the calibration for linear input
Lower limit of linear Input * DO NOT change this value without techincal assistant
SET
Input 1 (INP1) To be used during the calibration for linear input
Upper limit of linear Input * DO NOT change this value without technical assistant
SET
Decimal Point Available in linear input only
SET
Lower limit of Input range i.e) Linear input = 4~20mA,
when 4mA (0%), set the indication value for lower limit
SET
Upper limit of Input range when 20mA (100%), set the indication value for upper limit
SET
Input 2 (INP2) To be used during the calibration for linear input
Lower limit of linear input * DO NOT change this value without techincal assistant
SET
Input 2 (INP2) To be used during the calibration for linear input
Upper limit of linear input * DO NOT change this value without technical assistant
SET
Alarm Code of ‘Alarm 1’ * Refer to
SET
SET
Time Set for ‘Alarm 2’ The same configuration method with ALT1
SET
Alarm Code of ‘Alarm 3’
SET
Time Set for ‘Alarm 3’ The same configuration method with ALT1
SET
Hysteresis of alarms To set the hysteresis of alarm actuation (Range: 0 – 1000)
ON : PV<=(SP-HYS1)
OFF : PV > (SP+HYS1)
SET
Main Control (OUT1) To adjust the linear control output during the calibration
Lower limit of linear output * DO NOT change the value without technical assistant
SET
Main Control (OUT1) To adjust the linear control output during calibration
Upper limit of linear output * DO NOT change the value without techincal assistant
SET
Sub Control (OUT2) The same configuration method with ‘CL01’
Lower limit of linear output
SET
Sub Control (OUT2) The same configuration method with ‘CH01’
Upper limit of linear output
SET
Aux. Output The same configuration method with ‘CL01’
Lower limit of linear output
SET
Aux. Output The same configuration method with ‘CH01’
Upper limit of linear output
SET
Timer for Motor Control Full actuation time of TPSC
Range: 5 – 200 sec
SET
WAIT function To set ‘wait’ for program operation
0= No wait, others = Wait volume
SET
SET
SET
Baud Rate DO NOT change the value of this parameter
SET
SP compensation Range: -1000~1000
SET
PV compensation Range: LSPL~USPL
SET
SET
Soft Filter To adjust PV response time (Range: 0.05 – 1.00)
* The bigger value meanse the faster response.
SET
* Those 2 parameters are only for adjusting the linear signal of control output, not for the limitation of the control output
or any other purpose. Pls, DO NOT change the values without techincal assistant.
SET
SET
Control Process PID or Fuzzy
SET
Frequency 50 or 60Hz
* Please, check whether the proper frequency is selected
SET
2.4 Alarms
2.4.1 Deviation Alarm
The Alarm SP (Set Point) is to be changed as the SP moves. In this case, the Alarm SP preserves a
certain deviation value with the SP. When an alarm is set, a certain deviation value with the preset SP
should be defined.
Alarm SP moves along SP change
Deviation
(Lower limit)
2.4.1.1 Upper Limit Deviation Alarm (Alarm Code 01, Alarm release in the first alarming situation)
: Set Point
2.4.1.2 Upper Limit Deviation Alarm (Alarm Code 11, No alarm release in the first alarming situation)
2.4.1.4 Lower Limit Deviation Alarm (Alarm Code 12, No alarm release in the first alarming situation)
2.4.1.5 Dev. Band Breakaway Alarm(Alarm Code 03, Alarm release in the first alarming situation)
2.4.1.6 Dev. Band Breakaway Alarm(Alarm Code 13, No alarm release in the first alarming situation)
2.4.1.7 Deviation Band Alarm (Alarm Code 04, Alarm release in the first alarming situation)
2.4.1.8 Deviation Band Alarm (Alarm Code 14, No alarm release in the first alarming situation)
2.4.2.2 Absolute Upper Limit Alarm (Alarm Code 15, No alarm release in the first alarming situation)
2.4.2.4 Absolute Lower Limit Alarm (Alarm Code 16, No alarm release in the first alarming situation)
CAUTION
Configuration should be performed only by personnel who are technically competent to
do so. Local Regulations regarding electrical & safety must be observed.
0.0~400.0°C 0.0~752.0°F
0~600°C 0~1112°F
K
0~800°C 0~1472°F
0~1000°C 0~1832°F
0~1200°C 0~2192°F
0.0~200.0°C 0.0~392.0°F
0.0~400.0°C 0.0~752.0°F
0~600°C 0~1112°F
J
0~800°C 0~1472°F
0~1000°C 0~1832°F
0~1200°C 0~2192°F
0~1600°C 0~2912°F
R
0~1796°C 0~3216°F
0~1600°C 0~2912°F
S
0~1796°C 0~3216°F
B 0~1820°C 0~3308°F
0~800°C 0~1472°F
E
0~1000°C 0~1832°F
0~1200°C 0~2192°F
N
0~1300°C 0~2372°F
-199.9~400.0°C -199.9~752.0°F
T -199.9~200.0°C -199.9~392.0°F
0.0~350.0°C 0.0~662.0°F
0~2000°C 0~3632°F
W
0~2320°C 0~2372°F
0~1300°C 0~2372°F
PLII
0~1390°C 0~2534°F
-199.9~600.0°C -199.9~999.9°F
U -199.9~200.0°C -199.9~392.0°F
0.0~400.0°C 0.0~752.0°F
L 0~400°C 0~752°F
0~800°C 0~1472°F
* The default of Input Code is ‘K2’ for the model of themocouple input type. (DC10X0XT-XXX-XXX-X)
-199.9~400.0°C -199.9~752.0°F
JIS -199.9~200.0°C -199.9~392.0°F
Pt100 0~200°C 0~392°F
0~400°C 0~752°F
0~600°C 0~1112°F
-199.9~600.0°C -199.9~999.9°F
-199.9~400.0°C -199.9~752.0°F
DIN -199.9~200.0°C -199.9~392.0°F
Pt100 0~200°C 0~392°F
0~400°C 0~752°F
0~600°C 0~1112°F
-199.9~600.0°C -199.9~999.9°F
-199.9~400.0°C -199.9~752.0°F
0~400°C 0~752°F
0~600°C 0~1112°F
* The default of Input Code is ‘DP3’ for the model of RTD input type. (DC10X0XR-XXX-XXX-X)
0 - 10mV -1999~9999
0 - 20mV -1999~9999
0 - 50mV 0-20mA, 0-1V, 0-5V, 0-10V -1999~9999
* The default of Input Code is ‘AN4’ (4-20mA) for the model of linear input type.
(DC10X0XL-XXX-XXX-X)
* DO NOT change the input type without technical assistant because it requires some hardware
changes on the input board in order to select a certain linear input type.