Professional Documents
Culture Documents
net/publication/320410426
Dissolved gas analysis and its interpretation techniques for power transformers
CITATIONS READS
4 2,526
3 authors, including:
Adam Junid
University of Michigan
23 PUBLICATIONS 9 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
Efficiency of Brushed and Brushless Electronic Speed Control Systems and Lithium Batteries View project
All content following this page was uploaded by Adam Junid on 15 October 2017.
Abstract
This report is an investigation on Dissolved Gas Analysis and its interpre-
1
Acknowledgements:
We thank:
Dr Toan Phung for his help and explanations on ELEC9712 (High Voltage
System) topics
Zulkarnain Muhamad and Ahmad Zarir Makhtar from Petronas Gas Berhad
(CUF-Kerteh) for sharing practical DGA data and photos with us
Yee Yen Fu and Nor Azhar Saad from Asean Bintulu Fertilizer for sharing
DGA reports with us
2
Acronyms and Abbreviations
ANSI
AS
ASTM
BS
British Standards
H2
Hydrogen
C 2 H2
Acetylene
C 2 H4
Ethylene
CH4
Methane
C 2 H6
Ethane
CM
Condition Monitoring
DG
Dissolved Gas
DGA
3
HPLC
LTC
OLTC
PD
Partial Discharge
ppm
TCG
TDCG
4
Glossary
Condition Monitoring
Fault Gases
Fuller's Earth
A nonplastic clay or claylike earthy material used to purify mineral oil [Wikipedia, 2008d]
Furan
A colorless, ammable, highly volatile liquid with a boiling point of about 31.4
o
C; produced by thermal decomposition of cellulose [Wikipedia, 2008g]
A Tap Changer that can be adjusted either manually or automatically while the
transformer is supplying power to loads
Pyrolysis
5
(Beta) Scission
The initial step in the chemistry of thermal cracking of hydrocarbons and the
formation of free radicals [Wikipedia, 2008i]
Tap Changer
X-Wax
6
Contents
1 Introduction 12
1.1 Concepts . . . . . . . . . . . . . . . . . . . . . . 12
1.2 Applications . . . . . . . . . . . . . . . . . . . . 16
1.3 History . . . . . . . . . . . . . . . . . . . . . . . 17
2 Sampling 18
2.1 Guidelines . . . . . . . . . . . . . . . . . . . . . 18
4 Interpretation techniques 23
4.1 Guidelines . . . . . . . . . . . . . . . . . . . . . 23
7
4.5 Predicting fault locations within the trans-
former based on DGA results . . . . . . . . . 34
5 Case Study 35
5.1 Pre-trip DG . . . . . . . . . . . . . . . . . . . 35
5.2 Post-trip DG . . . . . . . . . . . . . . . . . . . 35
7 Conclusion 42
8
List of Figures
1. Figure 1: A chemcal bond diagram showing how (naphtenic) mineral oil,
under heat or arcing, breaks down to form hydrocarbon gases
6. Figure 6: Tables of dissolved Fault Gas ratios which indicate pyrolysis due
to overheating, partial discharge and arcing
9. Figure 10: Table of key gases used for particular DGA interpretations
14. Figure 14: Simplied diagnostics table for IEC 60599 interpretation
16. Figure 16: IEEE denitions for transformer condition based on TDCG
17. Figure 17: IEEE recommendations for transformer operation and mainte-
nance action, based on TDCG
21. Figure 21: Table showing variations in laboratory reading errors for medium
and low DG concentrations
22. Figure 22: DG concentration limits for transformers and separate OLTC
tanks requiring attention
9
23. Figure 23: Cinergy Monthly Watch Criteria for DG in LTCs
24. Figure 24: Youngblood (Cinergy) 90th percentile Fault Gas Ratios
29. Figure 29: CUF-K 11kV transformer incident ratios (2008) compared to
Youngblood (Cinergy) 90th percentile Fault Gas Ratios
C2 H4
31. Figure 30: Proposed graphical interpretation of IEC 60599
C2 H6 ratio
applied to biodegradeable oil
10
Standards and Recommended Practice
1. ANSI C57.104-1978: Guide for the detection and determination of gener-
ated gases in oil-immersed transformers and their relation to the service-
ability of the equipment
2. IEEE Std C57.104-1991: IEEE Guide for the Interpretation of Gases Gen-
erated in Oil-Immersed Transformers
11
1 Introduction
Dissolved Gas Analysis (DGA) is a method of diagnosing faults
1 in electrical
equipment having oil as a conductor insulator [Wikipedia, 2008a]. It may also be
a good indicator of the likelihood [IEC 60599, 2007, 8.1.1] of transformer failure
[Duval, 1989, Figures 8 and 9]. DGA interpretation techniques have become so
sensitive and accurate that it has now become standard practice in transformer
acceptance [Waukesha Electric, 2004], maintenance programs involving online
CM [Wong, 2000, Osztermayer at al, 2003], and post-mortem equipment failure
studies [Schroeder, 2000].
1.1 Concepts
Transformer insulating oil, whether paranic, naphthenic or aromatic contain
dissolved gases.
1 It is also used in transformer factory acceptance tests, both before, during and after a
heat run [IEC 60567, 2006, "Introduction"]
2 Analysis of Furans, although not part of this report because they are considered uids
[Wikipedia, 2008g] at standard temperature and pressure, are useful in predicting buildup of
X-Wax at paper insulation that could possibly lead a future fault [IEC 60599, 2007, 5.8]. Oil
additives such as oxidation inhibitors, and the eect of copper sludge has on oil conductivity
and tan δ are also not covered here.
3 Winding and tap-changer oil should ideally be contained separately to ease troubleshoot-
ing and fault location [Kramer, 2008, Reinhausen Grp, 2006].
4 See Figure 17
12
Figure 1: A chemcal bond diagram showing how (naphtenic) mineral oil,
under heat or arcing, breaks down to form hydrocarbon gases (Taken from
[Jakob, 2008, Slide 12])
The decomposition
5 (Figure 1) of transformer oil6 under heat or arcing result in
7 8 9
more Fault Gases produced and dissolved in the oil than were there originally
10
[Blackburn, 2008] . Both the amount and types of Fault Gases produced are
13
Bond type Scission energy required
C −H 338 kJ/mole
C −C 607 kJ/mole
C=C 720 kJ/mole
14
Figure 4: Relative gas production with respect to oil temperature (Taken from
[Blackburn, 2008, Slide 13])
11 This may include headspace Fault Gas results (see Section 4.6), should the suspect fault
be large enough to produce large enough Fault Gas volume
12 The degree of hydrogen unsaturation of the molecule correlates to the amount of energy
released by the fault [Duval, 1989]
13 Gas ratios are used because Fault Gas solubility with respect to oil temperature relative
to one another appears reasonably constant (see Figure 5). Thus DGA samples may be taken
even when the transformer has cooled and their relative ratios would remain similar.
15
Figure 5: Relative gas solubility with respect to temperature (Taken from
[Blackburn, 2008, Slide 6])
1.2 Applications
DGA concepts are applied to assess oil which insulates conductors, such as
transformer cores and windings, and oil-insulated cables. By using DGA tech-
niques, information about the equipment from which the oil sample was taken
from can be deduced, e.g. has there been overheating (see Figure 4
14 ), has there
been internal arcing within the oil (see Figure 6), has there been atmospheric
ingress. Such DGA interpretations would then be applied to estimate:
2. How much derating (or uprating) it should (or could) be safely operated
at in its remaining condition, and
3. How soon the next transformer oil change, ltering, Fuller's Earth treat-
ment or inspection should be.
14 There are also other sources of gas production, such as from newly facbricated steel and
via reaction of steel with water in the oil [IEC 60599, 2007, 4.3]
16
Pyrolysis Ratios PD Ratios
EthyleneC 2 H4 60% Hydrogen H2 85%
Ethane C2 H6 20% Methane CH4 5%
Methane CH4 20% Ethane C2 H6 5%
Arcing Ratios
Acetylene C2 H2 30%
Hydrogen H2 60%
Methane CH4 5%
Ethylene C2 H4 5%
Figure 6: Tables of dissolved Fault Gas ratios which indicate pyrolysis due to
overheating, partial discharge and arcing (Taken from [Blackburn, 2008, Slide
16])
1.3 History
DGA has been used for transformer routine monitoring since the late 1960s
[Duval, 1989]. In 2003, it was estimated that about a million DGA tests were
done annually at laboratories worldwide [Duval et al, 2003]
15 .
15 This averages to more than 10 DGAs per minute, or > 1 DGA every 6 seconds
17
2 Sampling
2.1 Guidelines
Transformer operators may obtain gas samples from the gas relays (or Buchholz
relays), but for more accurate and early diagnosis [Wikipedia, 2008a, "Usage"],
DGA by careful oil sampling, gas extraction
16 [Duval et al, 2003] and chro-
matography is recommended. In all cases, sampling should not endanger the
operation of the equipment [IEC 60567, 2006, 4.1].
To minimise air ingress, it is important that the syringe not be pulled forcefully,
i.e. the transformer oil's natural gravity ow should be allowed to work the oil
into the syringe [NTT, 2001a].
16 Internationally recognized standards for gas extraction from oil samples are IEC 60567
(see Section 3.1) and ASTM D3612.
18
2.3 Online sampling
2.3.1 Manual sampling while the transformer is on
Some oil-sampling contractors can obtain oil-samples from live transformers for
DGA [IET, 2008], subject to transformer owner clearance of such practice.
There are also manufacturers oering automated online sampling equipment for
undissolved gases [Kelman, 2005-8]. However the gases such equipment detect
from the headspace or Buchholz (gas) relay and are not dissolved, limiting the
rapidity of this CM diagnostic.
Operator Periodicity
NGC UK (1998) Annually [Esp et al, 1998]
Petronas CUF-K (2008) Annually [Makhtar et al, 2008]
Petronas MCOT (2004) Pending oil dielectric test per 2 years [Makhtar et al, 2008]
Shell (2000) Pending dielectric test per 4 yrs; nonsealed units [Shell, 2000]
Syprotec (1995) Annually [Gibeault et al, 1995]
Transgrid (2008) Annually [Transgrid, 2007]
19
2. Not allowing some oil to ow to clean the drain valve piping before taking
a sample [NTT, 2001a]
17
Figure 9: Sampling syringe and 3-way valve set (Taken from [NTT, 2008b])
17 Oil at the bottom of the tank may also be more susceptible to contaminants & dierent
DG levels [Ward, 2003]
20
3 Gas extraction and measurement
3.1 Extraction methods
Gas extraction methods specied in IEC 60567 include [IEC 60567, 2006, "Scope"]:
Extraction by vacuum
for the sample oil sample, each DGA lab report should include the accuracy
margins of the lab equipment used [Duval et al, 2005].
1. Method of DGA
5. Special incidents just before the sampling, e.g. tripping, alarm, repair,
degassing, outage
21
(a) Revised oil sampling frequency
CO2
(b) Furanic compound analysis if
CO < 3
(c) Other tests, inspections or maintenance
22
4 Interpretation techniques
4.1 Guidelines
DGA interpretation techniques take into account the amounts of Key Gases
[Blackburn, 2008, "Analysis"] (see Figure 10) found in oil samples (in ppm) and
their relative ratios to each other to arrive at conclusions about the transformer
condition. These techniques include empirical approaches such as Roger's Ra-
tios (IEEE - 1978)
18 , IEC 60599 Ratios [Blackburn, 2008], IEEE 57.104 Ratios
19
[Jakob, 2008] , and graphical methods such as the Duval Triangle.
Figure 10: Table of key gases used for particular DGA interpretations (Taken
from [Blackburn, 2008, "Analysis"])
The following gas ratio methods work best with diaphragm or hermetically
sealed transformers. Kan et al has also noted its applicability to nitrogen sealed
transformers with N2 replenishment, because release of fault gases are infrequent
enough to treat the gas mixtures as being in equilibrium within the transformer
[Kan et al, 1995, "CO2/CO value for transformers with gas space above oil",]
20 .
It would be less accurate
21 for transformers with open type conservators because:
1. The diusion rate of H2 would be faster than the heavier Fault Gases
To obtain data related to the transformer's most recent fault, the most recent
DGA results should have gas concentrations from previous DGA results sub-
tracted from it [IEC 60599, 2007, 6.1].
18 Roger's Ratios originated from the Doernenburg method [Serveron, 2007, p8]
19 Also known as the Key Gas Method [Serveron, 2007, Table 3, p4]
20 Although it has been argued that the headspace gases are aected by headspace purging
[Woolley et al, 2994]
21 IEC60599 mentions there is no agreement yet on adjustment techniques to account for
gases esacping to the atmophere for ventilated transformers [IEC 60599, 2007, 6.1]
23
4.1.1 Roger's Ratio method
C2 H6 C2 H4 C2 H2
CH4 C2 H6 C2 H4 Diagnosis
R < 10 R < 1 R < 0 Normal deterioration
R < 1 R < 1 R < 0.5 PD activity
o
R < 1 R < 1 R < 0.5 Heating to 150 C
o
R > 1 R < 1 R < 0.5 Heating 150 - 300 C
R < 1 1 < R < 3 R < 0.5 Winding circulating current and overheating
R < 1 R > 3 R < 0.5 Overheated contacts
R < 1 R < 1 0.5 < R < 3 Transient arcing
R < 1 R > 1 R > 0.5 Transient arcing at power frequency
R < 1 R > 3 R > 3.0 Continuous sparking
R < 1 R < 1 R > 0.5 PD and tracking
Figure 11: Diagnostics using the Roger's Ratio approach (Taken from
[Blackburn, 2008, Slide 20])
A manually faster approach to Roger's Ratio diagnostics may be done using the
following Roger's Ratio owchart [Jakob, 2008, Slide 26]:
24
Figure 12: A owchart approach to Roger's Ratio diagnostics (Taken from
[Jakob, 2008, Slide 26])
IEC 60599 has a similar diagnostic approach, using dissolved gas ratios [IEC 60599, 2007,
5.3 (Table 2), 9, Figure 1]
24 :
The IEC 60599 ratios in Figure 13 above should only apply if one of the gas
concentrations exceeds typical values [IEC 60599, 2007, 5.3, Table 2 and 6.1c].
The ratios may also be reproduced in a twin square, graphical format (Figure
31, Appendix). In some cases, no diagnosis may be forthcoming from the above
24 IEC 60599 [Duval et al, 2001] also species that: (a) Faults are considered active if DG
rates continue to rise at 10% per month for hermetically sealed transformers [IEC 60599, 2007,
8.4]; and (b) Higher DG rates of increase such as 50% per week are considered very serious.
25
Figure 13: IEC 60599 Dissolved Gas Ratio Diagnostics (Taken from
[Miranda et al, 2005, Table II])
C2 H2 CH4 C2 H4
Case C2 H4 H2 C2 H6
Partial Discharge < 0.2
Discharge (Arcing) > 0.2
Thermal fault < 0.2
For TDCG baseline acceptance criteria, IEC 60599 allows transformer opera-
tors to set their own thresholds, based on forensic evidence [IEC 60599, 2007,
8.2]. IEC 60599 also presents an overall owchart for its DGA interpretation,
reproduced in Figure 32, Appendix.
IEEE 57.104 also has a set of ratios for DG and headspace gas
25 diagnostics
26
that borrows from the Dornenburg method :
25 Fault Gases from may help asses the size of a recent large fault [IEC 60567, 2006, "In-
troduction"]. Headspace Fault Gas analysis is addressed more completely in IEC 60599
[IEC 60599, 2007, 7.]which uses Ostwald coecients to convert headspace Fault Gas con-
centrations to a DG equivalent.
26 Found in Tables 5 and 6 of ANSI/IEEE 57.104-1978
26
Figure 15: IEEE DGA diagnostic guidelines (Taken from [Jakob, 2008, Slide
29])
Figure 16: IEEE denitions for transformer condition based on TDCG (Taken
from[Jakob, 2008, Slide 33])
27
Figure 17: IEEE recommendations for transformer operation and maintenance
action, based on TDCG (Taken from [Jakob, 2008, Slide 34])
For new transformer oil TDCG baseline acceptance criteria, both IEC and
IEEE guidelines allow the transformer operators to set their own thresholds
[Jakob, 2008, Slide 31].
A popular [Bandhopadhyay, 2006, Field et al, 2002] method that has been noted
to be more accurate [Serveron, 2007, Table 7, p10]
28 than the above three,
the Duval triangle
29 provides DGA fault diagnosis simply based on relative
percentages of CH4 , C2 H4 and C2 H2 , where the fault codes are [Delta-X, 2008]:
PD : Partial discharge
28
T1 : Low-range thermal fault (below 300
o
C)
T2 : Medium-range thermal fault (300-700
o
C)
T3 : High-range thermal fault (above 700
o
C)
Figure 18: The Duval Triangle (Taken from [Blackburn, 2008, Slide 22])
29
4.1.5 Single ratios
CO2 30 O2 31 C2 H2 32
, and ratios may indicate paper insulation involvement in
CO N2 H2
faults, excessive heating or contamination by OLTC oil respectively [Serveron, 2007,
CO2 O2
p11]. However, the diagnosis accuracy of
CO and N2 have been disputed.
The
CO2 33 because of its temperature depen-
CO ratio is particularly nebulous
dency and CO2 's higher absorption rate into insulation paper relative to CO
at higher temperatures [Kan et al, 1994, 5. Conclusion]. For example, one nor-
CO2 CO2
mal
CO range has been dened as > 7, with CO < 3 [IEC 60599, 2007, 5.4:
CO2/CO ratio]indicating severe overheating of paper insulation [Jakob, 2008,
Slide 28]. However, studies by Kan et al have proposed that incipient faults may
CO2
actually be occuring at
CO ratios < 10 because CO2 gets absorbed into insulat-
ing the paper [Kan et al, 1995] at higher temperatures, depriving DGA samples
CO2
of a representative CO2 concentration. In addition to the
CO temperature de-
CO2
pendence skew, Kan et al also noted that a
CO ratio method: (a) cannot apply
accurately to new transformer oil for the rst six months because of a lack of
chemical equilibrium, and (b) cannot apply accurately to naturally circulated oil
because of the greater likelihood of localised hotspots [Kan et al, 1995, "Cases
where CO2/CO method does not apply",].
O2
When applying the
N2 ratio, it must be noted that ransformers that have not
been Nitrogen-purged may have signicant amount of Oxygen already inside
O2
[Woolley et al, 2994]. A
N ratio of < 3 may indicates excessive oxygen con-
2
sumption within the transformer [IEC 60599, 2007, 5.5].
IEC 60599 also noted that transformers with breahing apparatus (i.e. non-
hermetically sealed transformers) may have CO2 coming in from external air
that could falsify diagnostic results [IEC 60599, 2007, 5.4].
CO2 O2
In short, DGA involving these single ratios of
CO and N2 must be supplemented
by one of the methods mentioned in Section 4.1.
30 This ratio has been noted to vary depending on transformer model and its operational
mode [Failhauer et al, 2006]. Due to a lack of diagnostic consistency or distinguishable pat-
CO2
terns, the ratio was removed from a data mining technique by Esp et al [Esp et al, 1998].
CO
31 Transformers that have not been Nitrogen-purged may have signicant amount of Oxygen
already inside [Woolley et al, 2994]
32 C2 H2 ratios higher than 2 or 3 in the main tank indicates oil contamination from the
H2
OLTC tank [IEC 60599, 2007, 5.5]
33 It has also been shown that CO2 levels in headspace can uctuate by up to 500ppm per
day [Ward et al, 2000], depending on transformer loading.
30
2. Some gas combinations do not t into the specied range of values and
thus a diagnosis of the fault type cannot be given
Studies of DGA technique relative accuracies have shown that the Duval Tri-
angle method has relatively good consistency and accuracy when taking into ac-
count cases that are undiagnosable by the other methods [Muhamad et al, 2007].
Although the Dornenburg method appears more accurate than the Rogers,
Thang et al noted that [Thang et al, 2000]:
Although the Duval Triangle oers relative greater accuracy, it forces the
user into a transformer fault diagnosis because it has no area to account
for gase ratios due to operational aging. Thus the Duval triangle should
only be applied after the gases have been scrutinized for normalcy.
31
Figure 20: Plot showing DG reading errors increase as DG concentrations get
lower for factory () and routine (-) testing (Taken from [Duval et al, 2005,
Figure 1])
However, correction factors may be applied to minimise this [Duval et al, 2005].
Duval et al also noted that DG reading errors for controlled medium and low DG
concentration oil samples varied signicantly from laboratory to laboratory
34 :
Figure 21: Table showing variations in laboratory reading errors for medium
and low DG concentrations (Taken from [Duval et al, 2005, Table 2])
34 IEC 60567 [IEC 60567, 2006, 9.3]mentions methods of how to minimize this, including
the storage of oil samples in fridges
32
To reduce the likelihoods of false readings resulting in incorrect DGA diag-
nosis
35 , both IEC 60567 [IEC 60567, 2006, 10] and Duval et al recommend
that DGA laboratories publish their lab's accuracy gures on all test reports
[Duval et al, 2005].
Figure 22: DG concentration limits for transformers and separate OLTC tanks
requiring attention (Taken from [Blackburn, 2008, Slide 14])
Figure 23: Cinergy Monthly Watch Criteria for DG in LTCs (Taken from
[Jakob et al, 2008, Slide 19])
35 Incorrect DGA diagnosis would also result in unnecessary downtime and resources wasted
to inspect a transformer [Duval et al, 2005]
36 C2 H2 ratios higher than 2 or 3 in the main tank indicates oil contamination from the
H2
OLTC tank [IEC 60599, 2007, 5.5]
33
Youngblood et al of Cinergy have also provided LTC DGA ratio limits based
on empirical data [Youngblood, 2003]:
Figure 24: 90th percentile Fault Gas Ratios (Taken from [Jakob et al, 2003])
and winding dier, some work has been done by Zama et al on estimating the
C 2 H4
likelihood of the fault lying in the windings or the core, based on
C2 H6 ratioss
[Zama et al, 2008, Part F].
34
5 Case Study
A case study involving an 11kV transformer
37 trip at in 2008 is referred [Makhtar et al, 2008].
Pre and post trip DG results are presented, and an interpretation suggested via
application of the Duval Triangle method.
5.1 Pre-trip DG
DG concentrations from a sample taken on 28 March 2008 are as follows:
Figure 25: 11kV pre-trip DG concentrations (Taken from [Makhtar et al, 2008]).
5.2 Post-trip DG
DG concentrations from a sample taken on 8 July 2008 after a trip incident are
as follows:
37 Transformer is sealed but not Nitrogen packed, and has on o-circuit LTC in the same oil
compartment as the transformer main winding [Makhtar et al, 2008].
35
Figure 26: 11kV post-trip DG concentrations (Taken from
[Makhtar et al, 2008]).
Gas 4ppm %
Methane (CH4 ) 546-2=544 34.4
Ethylene(C2 H4 ) 430 27.1
Acetylene (C2 H2 ) 607 38.4
36
Figure 28: Duval Triangle applied to case study (Taken from
[Makhtar et al, 2008]).
we obtain a Duval Triangle that suggests a D2 Fault: High energy arcing with
power follow-through, and possible carbonization and metal fusion [IEC 60599, 2007,
5.2].
37
Gas ratio Limit Pre-incident Post-incident Pf ailure
Ethylene(C2 H4 ) N IL
0.3378 0.708 210%
Acetylene(C2 H2 ) N IL
Ethylene(C2 H4 )
0.500 0 0.878 176%
Acetylene(C2 H2 )+Hydrogen(H2 )
Ethylene(C2 H4 )+Ethane(C2 H6 )+M ethane(CH4 )
0.9157 0.004 0.205 22.3%
Acetylene(C2 H2 )+Hydrogen(H2 )
Ethane(C2 H6 )
0.2067 0 0.051 24.7%
M ethane(CH4 )
Ethylene(C2 H4 )
4.83 0 15.36 318%
Ethane(C2 H6 )
38
6 Future developments in DGA
Some future developments in DGA include [Blackburn, 2008, Slide 33]:
3. Since lab DGA often contains air, online monitoring will have much better
resolution of actual air leaks in the transformer
Some disadvantages are that [Duval et al, 2003, "On-Line Monitoring Devices"]:
1. Many of the online DGA monitors mentioned in [Duval et al, 2003, Table
VI] do not detect all Fault Gases, i.e. they detect mainly H2 , C2 H2 , CHX ,
CO , CO2 which ag arcing faults well, but are less eective for detecting
low and medium overheating
2. Being mostly located outdoors, they may have have poorer maintenance,
resulting in poorer accuracy relative to indoor DGA lab equipment
3. Detection responses for online DGA monitors utilising fuel cells are dier-
ent for each Fault Gas
Online DGA systems should use one of the more accurate extraction [Duval et al, 2003]
and diagnostic techniques mentioned in Section 4.1 [Serveron, 2007, p11-12].
38 Duval in 2003 estimated that about 18000 online DGA monitors had been installed world-
wide [Duval et al, 2003].
39
6.2 New analysis methods
The DGA interpretation techniques mentioned in Section 4 utilize DG ratios
involving C1 and C2 bonds. However, IEC 60599 mentions that more precise
analysis methods are possible if the DG ratios involving C3 bonds are scruti-
nized as well [IEC 60599, 2007, 5.7]. This implies that methods such as the
Duval Triangle (Section 4.1.4) could be modied and rened to involve an anal-
ogous, square shaped percentage-ratio-reference chart, given enough forensic
DGA data [IEC 60599, 2007, 8.1.2] to verify the chart's demarcations and diag-
nostic accuracy.
40
C 2 H4
Figure 30: Proposed graphical interpretation of IEC 60599
C2 H6 ratio applied
to biodegradeable oil (Taken from [IEC 60599, 2007, Annex B] and edited to
reect ethane production data from [Muhamad et al, 2008, Fig. 8]).
41
7 Conclusion
DGA methods have been used since the 1980s to gauge transformer condition
for:
The extraction of gas from oil requires calibrated lab equipment compliant to
IEC 60567.
The actual DGA interpretation technique may rely on many dierent methods
mentioned in IEC and IEEE standards; the Duval Triangle method being one
of the more consistent methods.
42
References
[Alamo Transformer, 2008] Alamo Transformer, 2008, "Dissolved Gas Test-
ing", http://www.alamotransformer.com/DGA1.
htm, viewed 21 October 2008
[Belanger et al, 1977] Belanger, G. and Duval, M. 1977, Monitor for hy-
drogen dissolved in transformer oil, IREQ
[Esp et al, 1998] Esp, D.G. and Carillo, M. et al, 1998, Data mining
applied to transformer oil analysis data, Conference
Record of the 1998 IEEE International Symposium
on Electrical Insulation, Arlington, Virginia, USA,
June 7-10, 1998
[Duval et al, 2003] Duval, M. and CIGRÉ, 2003, New Techniques for
Dissolved Gas-in-Oil Analysis, IEEE Electrical In-
sulation Magazine, March/April 2003 Vol. 19,
No. 2
43
[Duval et al, 2005] Duval, M. and Dukarm, J. et al, 2005, Im-
proving the Reliability of Transformer Gas-in-Oil
Diagnosis, IEEE Electrical Insulation Magazine,
July/August 2005 Vol. 21, No. 4.
[Gibeault et al, 1995] Gibeault, J.P. and Kirkup, J.K. 1995, Early de-
tection and continuous monitoring of dissolved key
fault gases in transformers and shunt reactors,
Electrical Electronics Insulation Conference, 1995
[Jakob et al, 2003] Jakob, F. and Jakob, K. et al, 2003, "Use of gas
concentration ratios to interpret OLTC and OCB
ieeexplore.ieee.org/iel5/
dissolved gas data",
8829/27951/01247901.pdf?arnumber=1247901,
viewed 13 September 2008
44
[Jakob et al, 2008] Jakob, K. and Jakob, F. 2008, LTC Diagnostics,
Transcomma 2008, 20 April 2008, Kuala Lumpur
45
[Miranda et al, 2005] Miranda, V. and Castro, A.R.G. 2005, Improving
the IEC Table for Transformer Failure Diagnosis,
IEEE transactions on Power Delivery, Vol. 20, No.
4, October 2005
[Muhamad et al, 2007] Muhamad, N.A. and Phung, B.T. et al, Compara-
tive Study and Analysis of DGA Methods for Trans-
former Mineral Oil, Powertech 2007
[Muhamad et al, 2008] Muhamad, N.A. and Phung, B.T. et al, Dis-
solved Gas Analysis of Faults in Biodegradable
Oil Transformer Insulating Systems, 2008 Inter-
national Conference on Condition Monitoring and
Diagnosis, April 21-24, 2008, Beijing, China.
46
sid-2947734/mid-68/tid-5/ct-0/q-DGA//k-/
et-4/rpp-3/sar-False/t-/p-0/ap-True/cat-/
cr-0/pr-0/icp-False/icc-False/ifc-False/
sl-2/sp-0/cs-/ ( DGA search), 20 August 2008
[Rogers, 1975] Rogers, R.R. 1975, U.K. Experience in the Inter-
pretation of Incipient Faults in Power Transformers
By Dissolved Gas-in-Oil. Chromatographic Analy-
sis, Doble Conference Index of Minutes, Sec 10-201,
1975
[Thang et al, 2000] Thang, K.F. and Aggarwal, R.K. et al, 2000, Sta-
tistical and Neural Network Analysis of Dissolved
Gases in Power Transformers, Dielectric Materials,
Measurements and Applications Conference Publi-
cation No. 473.
47
[Ward, 2003] Ward, S.A. 2003, Evaluating Transformer Condi-
tion Using DGA Oil Analysis, Conference on Elec-
trical Insulation and Dielectric Phenomena, 2003
48
International Conference on Roperties and Applica-
tions of Dielectric Materials, July 3-8, 1994, Bris-
bane Australia
49
Appendix A
Graphical representation of IEC 60599 DGA ratios39
Figure 31: Graphical representation of IEC 60599 DGA ratios (Taken from
[IEC 60599, 2007, Annex B])
39 Gas volume production is nearly quadratic with voltage, and linear with arc duration
50
Appendix B
IEC 60599 DGA interpretation owchart
Figure 32: IEC 60599 DGA interpretation technique owchart (Taken from
[IEC 60599, 2007, Figure 1])
51