Professional Documents
Culture Documents
in Pharmaceutical Industry
by
Eugene Liu
Email : eugene.liu@century-water.com
Mobile : (+65) 9112 0380
Grade of Steam
Generation
Distribution
Sterilization
Regulation
Grades of Steam
Plant Steam
Plant Steam
• Known as Plant Steam, Industrial Steam, Black Steam
• Generated from fired water, either fire-tube and water-tube boiler
• No standards governing the quality of plant steam
• Boiler sequencing.
Scale & Corrosion
• Scale deposits:
• Build up of calcium carbonate on boiler tubes,
Scale deposits
steam distribution system, plate heat
exchangers, etc.
• Potential particle contamination in
process/product.
• Reduce efficiency
Corrective Action:
• Adherence to an approved water treatment programme.
Top of boiler
Water line
Corrective Action
A turbidity/conductivity meter
will detect many contaminants,
such as oil/fat, TDS, etc
Filtered (culinary) Steam
Filtered steam
• ‘Filtered steam', is plant steam that has passed
through a fine stainless steel filter, (typically 5
microns).
Steam inlet
Flow
Filtered
Steam
A 5 micron filter will remove particulates larger than 2 microns, but is not
designed to remove water or chemicals from the steam e.g. carryover.
Filtered Steam – Case Study
m
i
c
r
o
n
Filtered steam
Filtered steam quality is still dependant upon many other factors:
• Raw water quality - Water softening equipment
• Demineralised/deionised (DI)
HTM:2010
HTM:2031
EN:285
Filtered Steam v Clean Steam
Controlled Hazards Filtered (Culinary) Steam Clean Steam
Limited by filter System materials of
Particulates rating construction
Hospital
Food & Beverage
Pharmaceuticals
& Personal
Care/Cosmetics
Hospital Application
Every day steam sterilisers are
preparing medical devices for patient
use around the world
Repeatability is needed day in, day out
97% dryness
Food & Beverage Applications
Pure Steam
Separator
Plant Steam
Feedwater
Plant Condensate
Blow Down
Multi-Effect Distillation
Pre-Heaters Condenser
Feed
Water
Pure
Steam Cooling
Water
Plant
Steam
WFI
Condensate
Drain
CSG v PSG
CSG v PSG – general points
Typically clean steam generators will produce steam of the
same quality as the feed water if no additional separation
techniques are employed
• Generation orientation is vertical vs horizontal for CSG
• Complete segregation of heating medium and product
• Increased fabrication control – material traceability,
surface finish etc
• Multiple separation stages for complete removal of
endotoxins and other impurities
Where pure steam is not required an economic alternative
may be to utilise clean steam from a clean steam
generator.
Clean Steam v Pure Steam
USP EP USP EP
Bacterial
N/A N/A <0.25 EU/ml(1) <0.25 IU/ml (1)
Endotoxins
pH 5-7 N/A 5-7 N/A
Conductivity <1.1 µS/cm (20°C) <4.3 µS/cm (20°C) <1.1 µS/cm (20°C) <1.1 µS/cm (20°C)
Total Organic
<0.5 mg/l <0.5 mg/l <0.5 mg/l <0.5 mg/l
Carbon
<10 cfu per
Micro-organisms N/A(2) <100 cfu per 1ml(3) N/A(2)
100ml(3)
Nitrate N/A <2 ppm N/A <2 ppm
(1) 1 USP Endotoxin Unit (EU) = 1 EU (& WHO) International Unit of Endotoxin (IU)
(2) USP monographs for PW and WFI does not state micro-organism limit. <1231> Water For Pharmaceutical Purposes
gives guidance for an upper limit of 100 cfu per 1ml (PW) and 10 cfu per 100ml (WFI)
(3) cfu: Colony Forming Unit
Pure Steam Distribution
Distribution Design
Steam
Quality Test
Point
PI PI PI
Autoclave SIP
Clean/
Pure Sample
Steam Cooler
Generator
SIP (Sterilize In Place) is a timed sterilization of the process piping and vessels
with pure steam.
Every square inch of all process piping and vessels that comes in direct, or
indirect contact with the process is sterilized to insure that there is no
microbiological activity in the system.
Steam typically is circulated through all the process tubing during this stage,
and enters large vessels through spray balls (engineered nozzles) imbedded in
the vessel ceiling.
121°C
commences
Time
Time and temperature graph showing phases of sterilization
SIP Cycle
If the SIP temperature validation fails (if recorded temperature falls below
121°C), the sterilization time may be extended, but only if the temperature
fault can be determined and fixed.
SIP Characteristics
Vessels: 10L to 50,000L
Steam pressure: 1-2 barg
Flow rates/loads
• up to 1500 kg/hr for start-up loads
• <15 kg/hr for maintenance loads
Steam
• Start-up of system vessel/space is full of
air
• Air needs to be removed rapidly and
completely
• Failure of air removal can delay or
prevent reaching operating/ sterilisation
temperatures
• For some cases air venting may be
necessary…
Steam
Liquid
Product
Steam
Liquid Liquid
Product Product
Temperature
& Trap
Condensate Monitoring
SIP – Liquid Filter
Temperature Temperature
& Trap & Trap
Monitoring Monitoring
Steam Trap Selection & Monitoring
Float
Most traps retain some condensate to
(Mechanic)
allow operation
WATER
Thermodynamic RETENTION
Inverted
Bucket
(Mechanic)
Balanced
Bimetallic Pressure
(Thermostatic) (Thermostatic)
Steam Traps
Mechanical Thermodynamic Thermostatic
Blockage
resistance
Cleanability OK
Drainability /
Water Retention
Air venting
Liquid Fill
Element
QUALITY PURITY
• It is a problem
• Load should be dry before the
sterilizer door is opened
• The presence of water will
compromise the sterility of the
product.
Pure Steam
Intake
Autoclave
Steam Separator
Sample Cooler
Steam Quality (EN:285)
Dryness
• Clean and pure steam is generated with
dryness value >0.95
• Excess moisture, where droplets are present
may cause:
- damp loads in porous materials
- uneven temperature distribution in non-
porous materials
• Can be maintained by:
Reducing the pressure just prior to
point of use - false
The use of an inline moisture
separator before control valves,
autoclaves and freeze dryers
Non-Condensable Gases
• NCGs are gases which cannot be liquefied by
compression under normal sterilisation conditions.
• Typically Air and Carbon Dioxide
• They have no latent heat, so even if they have the same
temperature of steam, they provide no heating effect.
• They can collect as a film on surfaces, and act as an
insulator inhibiting the flow of heat from the steam.
• They lower the steam temperature
Degree of Superheat
Prevention of superheat
• Not usually a concern in clean/pure
steam distribution systems as low
operating pressures
• Commonly occurs during pressure
reduction
• Superheated steam will not give up its
heat until the temperature has reduced to
saturation temp – ineffective for
sterilisation
• Rule of thumb should not reduce
pressure more than 50%
• Carefully consider distribution operational
pressure
Dryness (EN:285)
Non-condensables (EN:285)
T2
T1 T1 T2
PI PI PI
Autoclave SIP
Clean/
Pure Sample
Steam Cooler
Generator