TRANSMISSION CORPORATION OF TELANAGANA LIMITED

From To
Divisional Engineer, The Divisional Engineer,
O&M Division, Load Dispatch, V.S, TS TRANSCO,
Nalgonda - 508 001. Hyderabad.

Lr.No.DE/O&M/NLG/Tech/F.No. /D.No.Special One /2020, Dt. 25.05.2020.


Sir,
Sub: - - TSTransco-O&M Division, Nalgonda –132KV Nalgonda-Munugode feeder
tripped at 132KV SS Nalgonda at 09:37Hrs on 25.05.2020 only at 132KV
Nalgonda feeder end with No Relay Indications - Charging of 132KV
Nalgonda-Munugode feeder -Permission -Requested– Reg.

*****

132KV Nalgonda-Munugode feeder tripped at 132KV SS Nalgonda at 09:37Hrs


on 25.05.2020 only at 132KV Nalgonda feeder end with No Relay Indications. The Diploma
Operator working at 132KV SS Nalgonda forgot to intimate the situation at 132KV SS
Nalgonda to 220KV SS Narketpally. The Assistant Engineer/Maint/132KV SS Nalgonda
newly recruited. And the Assistant Divisional Engineer/Maint/Nalgonda on leave due to
Ramzan Festival.

Now Charging of 132KV Nalgonda feeder after rectifying the problem by MRT wing.

132KV SS Munugode feeds 3 No's 33KV feeders which has no interruption, as


backfeeding was taken from one of the 33KV Narsingbhatla feeder till now. And also feeds
other 2 No's 33 KV feeders (33KV Chikatimamidi & 33KV Gudapur ) through 33KV Bus.

In view of the above it is requested to accord permission to charge the 132KV


Nalgonda-Munugode feeder at 132KV SS Nalgonda.

Submitted for favor of taking further necessary action please.

Yours faithfully,
Sd/-
(K.VENKATESWARA RAO)
DIVISIONAL ENGINEER,
O&M DIVISION, NALGONDA.

Copy submitted to the Superintending Engineer/OMC/TS TRANSCO/Nalgonda.