Warning - Output power greater than 240VA - Installation and Operating Instruction for

- Energy Hazard - MRF2800 Series of Power Supplies


When installing the PSU it is important to observe these installation instructions, Nominal Input Ratings
in particular the requirements of the specification IEC950 / EN60950 must be Input Voltage 230V rms, all models except those listed below
met. 277V rms, MRF28H27#$50, MRF28H54#$50
Input Current 16A
Mounting It is important that the correct length of fixing screw is used, with a maximum Frequency 45 - 65Hz
penetration of 6mm.
Output Ratings

SELV Warning MRF28H54#HN**, MRF28H54#VN** and MRF28E54DN Maximum Output Ratings


Model Number Voltage (d.c.) Current Power
- Output voltage of these units exceeds SELV limits (>60V d.c.)-
MRF28H27#$** 32V 100A 2800W
The output of all other versions is reliably SELV. MRF28H54#$** 58V 50A 2800W
DCPM28HU480** 58V 50A 2800W
CAUTION: Double pole / neutral fusing. MRF28H54#$N** 63V * 50A 2800W
MRF28E27D** 32V 100A 2800W
The CE Mark
MRF28E54D** 58V 50A 2800W
This power supply is CE marked to the European Low Voltage Directive (LVD) MRF28E54DN** 63V * 50A 2800W
73/23/EEC amended by 93/68/EEC, relating to the Safety of Electrical MRF28H32#$** 34V (nom 32V) 50A 1700W
Equipment. This power supply is designed for incorporation within apparatus.
For user safety, the enclosing apparatus must protect the user against accidental * See SELV warning overleaf.
contact with any electrical hazard, cooling fans etc, associated with the power
supply. These units are designed for rack mounting. Ventilation is provided in the front
and back faces to allow for horizontal cooling air provided by the internal fan.

The four final characters of the part number are used to describe individual
nominal output ratings (subject to the maximum output power), or to indicate
variants in the signals functions available on the output connector and front
panel. (# - signals package, $ - unit orientation, ** - custom set-up).
All nominal ratings are valid for a maximum ambient temperature of 55°C for 27V
units, and 65°C for 54V units.

Connector Type

Manufacturer and Part


Function Connector Type Number

Positronic "Power Positronic


Power Input Connection Systems" series SK2791

Elcon
Power Output Tin Plated Brass Busbar
538 17 001 00

Siemens
Signals DIN41612 type B 32-w ay V42254-B1300-B320
American Power Conversion
®

Connector kit including all APC


132 Fairgrounds Road, West Kingston, RI 02892 USA 3 backplane connectors 1MKC2801
990-9004D Rev 6 March 2002
For more detailed information refer to MRF2800 data sheet document.
Signals Connections Rectifier Operating Mode Switches
Mode setting switches are accessed through the side face of the rectifier.
DIN Alarm Option
connector Signals Name
A B&D Switch
Switch Off Switch On Default *
a1 N/C No

a2 3 Fan Fail opto 1 (+) sense remote (+) sense local On


a3 3 3 Post mate enable *
2 (-) sense remote (-) sense local On
a4 3 Standby opto ("E" unit : breaker open)
Reduce output by at least
3 Output set 54.5V/27.25V Off
a5 3 Program down 4.2V/2.1V
a6 3 3 +12V floating auxiliary Voltage droop on (passive
4 Voltage droop off Off
current share)
a7 N/C
5 Constant current limit Foldback current limit On
a8 3 Overtemperature trip opto
a9 3 Thermal control opto * Defaults and voltage quoted refer to standard rectifiers. Specific variant options
a10 3 3 Relay normally closed contact may be different.
a11 3 3 Relay common
a12 3 3 Relay normally open contact Line
a13 3 3 Current Share Input
a14 3 Remote on/off (-ve) (floating input)
a15 3 Remote on/off (+ve) (floating input) L
a16 3 3 Voltage change link (Margin down)
b1 N/C
b2 3 Remote Boost (input)
b3 3 Boost (Equalize) Active Opto
b4 N/C N
b5 N/C
b6 N/C
b7 3 Output current healthy opto
b8 3 3 Negative sense
b9 3 3 Voltage trim Obtaining Support
b10 3 Overvoltage opto To obtain technical assistance, please telephone APC at one of the telephone
b11 3 Current limit opto numbers shown below:
b12 3 Output healthy opto USA: 1-800-800-4272
b13 3 Input healthy opto Outside the USA: (44) (0)1423 320 000
b14 3 3 Opto common emitter (floating auxiliary 0V)
b15 3 3 Analog current signal
b16 3 3 Positive sense

* Pins a3 and b8 must be connected together for unit operation.