VAMP40 course – feeder: 5. Current circuits


Search this Site...
supervision, 2nd harmonic blocking function,
free programable current curve
Rimvis S. | April 28, 2019 | News
News, Power industry PLC programing,
programing Relaying
protection,
protection Schneider-electric | No comments
Categories
Categories (16)
In the fourth article we con gured non-directional earth fault protection
Maintenance (5)
and disturbance recorder. Full course of VAMP40 you can nd here.
Measurements (4)

In this article we are going to con gure current circuits supervision, 2nd Power industry PLC programing
harmonic blocking function and free programmable current curve. (10)
Relaying protection (12)
It is important to control currents circuits. Broken currents circuits lead to Companies (13)
damage current transformer. By using current circuit supervision, we avoid ABB (5)
this damage.
Schneider-electric (6)
Siemens (2)
2nd harmonic blocking function is needed if feeder supplies power
transformer. At connecting time of power transformer there appears Maintenance (5)
magnetizing currents in the network. These currents are 5-10 times of Manuals (2)
nominal current In of power transformer. Because of these big magnetizing News (43)
currents overcurrent protection will trip. This is not correct tripping.
Magnetizing currents have 2nd harmonic. 2nd harmonic can be about 30%
from rst harmonic. By using 2nd harmonic blocking function we can avoid
wrong tripping of overcurrent protection at connecting time of power
transformer.

Free programable current curve is used when standard current curves are
not suitable. In this case we can con gure own current curve. VAMP40
terminal has three free programable curves.

Sequence of the article:

1. Current circuits supervision con guration.

2. Testing of current circuits supervision function.

3. 2nd harmonic blocking function con guration.


4. Testing of 2nd harmonic blocking function.

5. Free programable current curve con guration.

6. Testing free programable current curve.

1. Current circuits supervision con guration.

In Vampset program on left right window select option „CT Supervisor“:

                                                     Fig. 1

Set parameters on right side window as shown in the picture:


                                                   Fig. 2

Here:

„Imax> setting“ –current which must be exceed in normal condition

„Imin< setting“ – current which must be not exceeded when current circuit
failure appears In our case to activate current circuit failure, in not
coruppted phase A current should be I>0,8xIn>640 A, and in coruppted
phase, for example phase C, current should be <0.2xIn>160 A (see g.2).

 „Operation delay“ – delay time, t=10 s; after 10 s activates CT supervisor


signal

„CT supervisor event on“ – when activates CT supervisor signal, this event
will be written in event list

„CT supervisor event off“ – when resets CT supervisor signal, this event will
be written in event list

„Fault log“ – here you can check when occured current circuits fault, and
how big currents unbalance was

Send changed con guration to VAMP40 by pressing button


Fig. 3

Now we need to connect „CT supervisor“ signal to A1 binary output.

On left side window select option „Logic“:

                                                     Fig.4

On left side window click left mouse button and select „Yes“:

                                              Fig. 5

Logical element „AND“ appears. Click on it left mouse button and press
„Select input signals“:
                                                                 Fig. 6

On left side window „Input signals available“ select „CT supervisor“:

                                             Fig. 7

Press button „ADD“ to add „CT supervisor“ signal to con guration:

                                            Fig. 8
Press button „OK“.

                                             Fig. 9

In the same manner add output signal „A1“:

                                 Fig. 10

Send changed con guration to VAMP40 by pressing button

 Fig.11

On window „Boot Bending“ press button „Boot now“:


                                                         Fig. 12

Read con guration from VAMP40 to persuade corect con guration. Press
button:

Fig. 13

Con guration sent correct:

                                      Fig. 14

Now we need to connect „CT supervisor“ signal to LED „E“.

On left side window select option „OUTPUT MATRIX“:

                                                         Fig. 15

Pick dots on right side window to signals „Logic output 1“and „LE“ as shown
in the picture:
                                       Fig. 16

Send changed con guration to VAMP40 by pressing button

Fig. 17

Now we need to edit logic outputs events. Make changes as shown in the
picture:

                                      Fig. 18

Here „logic output 3“ is named as CBFP, „logic output 1“ as „CT supervisor“.

Send changed con guration to VAMP40.

2. Testing of current circuits supervision function.

Testing scheme is shown in the article „VAMP40 course – der: 2.


Overcurrent protection rst stage“ gure 1.

Inject currents:

Ia= 4,9 A, φ=0°


(4,9A>0,8xIn=Imax)                                                                    Ib=0,8 A,
φ=240° (0,8A<0,2xIn=Imin)                                                                    Ic=4,9
A, φ=120° (4,9A>0,8xIn=Imax)

On left side window select „Angle diagram“:


                                                      Fig. 19

Press button

Fig. 20

Online measurements in “Vampset” program:

                                                Fig. 21

On left side window select „RELAYS“:

                                                      Fig. 22

Binary output „A1 (Alarm EHA)“ is active:


                                                   Fig. 23

LED „E“ is active (indicates currents circuit fault):

                                   Fig. 24

After currents circuits fault disappearing, LED „E“ and binary output „A1“
resets automatically.

Currents circuits fault is recorded in event list:

                                      Fig. 25

Currents circuit control function is con gured correctly.

3. 2nd harmonic blocking function con guration.

On left side window select option „2nd harmonic stage If2> 51F2“:
                                                      Fig. 26

Set parameters as shown in the picture:

                                            Fig. 27

Send changed con guration to VAMP40 by pressing button

Fig. 28

On left side window select „Block matrix“:

                                                     Fig. 29

Pick dots in the matrix as shown in the picture:


                                                       Fig. 30

2nd harmonic function will block I> and I>> stages.

Send changed con guration to VAMP40 by pressing button

Fig. 31

Now we need to indicate activating of 2nd harmonic blocking function by


LED „F“.

On left side window select „Logic“:

                                                           Fig. 32
Connect 2nd harmonic signals „2.Harm start“ and „2.Harm trip“ connect to
LED „LF“ in logic:

                                           Fig. 33

Send changed con guration to VAMP40 by pressing button

Fig. 34

Press button „Boot now“:

                                                          Fig. 35

On left side window of „Vampset“ select „Stage event enabling“. Pick dots in
the matrix as shown in the picture:

                                     Fig. 36

Now activating of 2nd harmonic blocking function will be recorded in the


event buffer (event list).
Send changed con guration to VAMP40 by pressing button

Fig. 37

2nd harmonic blocking function con guration is completed.

4. Testing of 2nd harmonic blocking function.

Testing scheme is shown in the article „VAMP40 course – der: 2.


Overcurrent protection rst stage“ gure 1.

Inject currents with second harmonic 16%:

Ia = 19,5 A, φ=0° (2nd harmonic


16%)                                                                     Ib = 19,5 A, φ=240° (2nd
harmonic 16%)                                                                 Ic = 19,5 A, φ=120°
(2nd harmonic 16%)

Overcurrent stage I>> didin‘t trip, LED “F“ activated:

                          Fig. 38
                                  Fig. 39

Active LED “F“ indicates that 2nd harmonic blocking function tripped.

2nd harmonic blocking function event is recorded in event buffer:

                                      Fig. 40

5. Free programable current curve con guration.

If you can not use standard currents curves (IEC, IEEE, IEEE1), you can
con gure own current curve.

On left side window select „Programmable delay curves“:


                                      Fig. 41

Here we can to con gure three curves: „Delay curve 1“, „Delay curve 2“ and
„Delay curve 3“.

We arge going to con gure „Delay curve 1“. Set currents curve characteristic
as shown in the picture:

                                     Fig. 42

Send changed con guration to VAMP40 by pressing button

Fig. 43
Press button „Boot now“ to restart VAMP40 terminal:

                                              Fig. 44

Now we need to select and enable con gured „Delay curve 1“.

On left side window select „Overcurrent stage I>“:

                                       Fig. 45

On right side window, option „Delay curve family“ set to from „IEC“ to „Prg1“,
option „Pick-up setting“ set to 0.6xIn:

                              Fig. 46
Send changed con guration to VAMP40 by pressing button

Fig. 47

Current curve is con gured and selected.

Now we are going to test this current curve.

6. Testing free programable current curve.

Testing scheme:

                                  Fig. 48

Testing measurements:

Here Is=0,6xIn=0,6×5=3 A (see g. 48 option „Pick-up setting“).

Testing results show that measured currents characteristic is equal to


con gured „Delay curve 1“.

After selecting „Event buffer“ on left side window, you can explore „Delay
curve 1“:
                     Fig. 49

That‘s all!

Con guration of VAMP40 is easy and convenient. All course of VAMP40


con guration you can nd here.