Professional Documents
Culture Documents
www.grinnell.com
Contacts
General Technical
Description Data
The GRINNELL Figure 71H Hinged Sizes
Flange Adapter allows a direct tran- 2 to 12 in. (DN50 to DN300 ANSI
sition from flanged components to Class 125/150)
GRINNELL grooved components. The Approvals
two segment design comes with a pre- UL and ULC Listed
pressed ring at one of the mating ends UL, C-UL Listed Water Quality Classified
which facilitates a hinged action. This FM Approved
allows for an easy and quick installa- Certified to all requirements of
tion. The specially designed gasket NSF/ANSI 61
enables the transition from a grooved IAPMO UPC Certified
system to a flanged system with a
single flange adapter. The flange bolt Maximum Pressure
patterns conform to ANSI Class 125 Refer to Figure 1.
and 150. Housing
Ductile iron conforming to
NOTICE ASTM A536, Grade 65-45-12 and/or
ASTM A395, Grade 65-45-15
The GRINNELL Products Figure 71H
Hinged Flange Adapter described Protective Coatings
herein must be installed and main- • Non-lead orange paint
tained in compliance with this docu- • RAL3000 red non-lead paint (optional)
ment, in addition to the standards of • Hot-dipped galvanized conforming to
any authorities having jurisdiction. ASTM A153 (optional)
Failure to do so may result in serious
personal injury or impair the perfor- Gasket
mance of these devices. • Grade “E” EPDM, Green color code
-30°F to 230°F (-34°C to 110°C)
Never remove any piping component • Grade “T” Nitrile, Orange color code
nor correct or modify any piping defi- -20°F to 180°F (-29°C to 82°C)
ciencies without first de-pressurizing • Grade “O” Fluoroelastomer, blue color
and draining the system. Failure to do code +20°F (-7°C) to +300°F (+149°C)
so may result in serious personal injury, • Grade “L” Silicone, red gasket
property damage, and/or impaired -30°F (-34°C) to +350°F (+177°C)
device performance.
Refer to Technical Data Sheet G610 for
It is the designer’s responsibility aid in selecting proper gasket.
to select products suitable for the
intended service and to ensure that NOTICE
pressure ratings and performance
data are not exceeded. Material and Factory supplied bolt and nut must be For fire protection pressure rating,
gasket selection should be verified to used at the non-hinged mating end listing and approval information, contact
be compatible for the specific applica- when assembling the flange segments. your Grinnell representative.
A C
B
D E
NOTES:
a. Dimensions D and E represent minimum and maximum sealing surfaces.
b. Maximum pressure and end load are total from all loads based on standard weight steel pipe. Pressure ratings and end loads may differ on other pipe materials and/or
wall thickness. Contact GRINNELL Products for details.
FIGURE 1
FIGURE 71H FLANGE ADAPTER - HINGED
FOR USE WITH ANSI CLASS 125 AND 150 FLANGES