| Slide 2
Challenges in Power Grids in Nordic Grids (Added Renewable Sources)
Source: Challenges and Opportunities for the Nordic Power Systems (August, 2016) published by Statnet, Fingrid, Energinet/DK, Svenska
Slide 3 Kraftnet (links: www.svk.se)
Nordic Countries-Example of Lower Inertia and Frequency Quality
Decreasing
Source: Challenges and Opportunities for the Nordic Power Systems (August, 2016) published by Statnet, Fingrid, Energinet/DK, Svenska
Slide 4 Kraftnet
Power System Challenges in Developing Countries
China, India, South Africa, Brazil, etc.
-Sources are located quite far away from the load centers
Long transmission lines are needed
-Multiple Connections from source to the load centers (HVAC+HVDC)
-High Short Circuit Currents reach to the Circuit breaker interruption capability
-Simultaneous commutation failure in HVDC links
-Power system low frequency oscillations
Slide 5
Typical Example of Long Distance Transmission Systems
China South Grid-Actions on UHV transmission systems
CSG total installed capacity=243 GW by end of 2015. Source: IEEE Power &Energy Magazine, Volume 14, Nr.4,
P72-78, July/August,2016
Slide 6 From source side to load side:
500 kV Transmission lines=8, +/- 800/500 kV lines=8, transmission system capacity=35 GW
Larger Disturbance Workshop-Records
243 GW
| Slide 7
Source: CIGRE 2014 B4 Session in Paris
Power System Protection Requirement
Speed, Selectivity, Sensitivity, Reliability
• AC Transmission line Distance Protection • Digital Substation Structure and
• Power system • Fault analysis and •
protection Communication
dynamics Power System
Transient Calculation • Differential Protection
• Generator/Transformer/ • Protection Algorithms
Rationale
• Frequency
Control • Speed/Sensitivity Bus protection • Travelling Wave
Proteciton • Phasor/Time domain Signal
• DC Transmission line Calculation
• Subsynchronous • Reliability
resonance protection • Sensitive Fault protection
• Voltage/current transformer
• Wide Area Protection transient
• Voltage stability
Application Knowledge Power System Stability: System Blackout related with Generator Damages Due to failure
Critical Fault Clearing time protection in US & Canada in in protection
2H d
2
Pm Pmax Sin 2003/08/14
dt 2
| Slide 8
Market Requirement and Trends for Power System Protection
Market Requirement:
Power system availability (reliability, stability).
Speed, selectivity, Sensitivity and reliability of a protection system
Renewable sources added in power transmission systems with new requests
Main Trends
Conventional protection function improvement
High sampling rate related applications and Function integrations
Further improvement in protection dependability and security
System related issues are combined such as subsequence resonance
detections
Monitoring and diagnosing using protection platform
IEC61850 applications and Digital Substations
Wide area protection(System Integrity protection) and Cyber Security
HVDC and FACTS related Protection Solutions
| Slide 9
Power System Protection-Evolution on protection technology
Phasor Time Traveling
Electromechanical
domain domain wave
• Reaction time • Reaction time • Reaction
• Reaction
depends on the can be traded depends on
depends on
energy between security measurement
filtering method
• Highly reliable and equipment time
• Well developed
dependability scale
technology set
| Slide 10
Travelling Wave and Time Domain Applications
Fault location and protection
Bus 1 Bus 2
Time
Travelling wave based high speed protection for AC transmission lines
Travelling wave based HVDC protection
Time domain protection based on directional detection
Superimposed principle
Others
PVPH PTTR
24 49
PSCH RED 670
RSYN
25
RREC
79
RBRF
50BF
Communication
REB 670
CSWI MMTR MMXU
RET 670
RED 670
RET 670
Kent Wikström
October 11, 2009 | Slide
3
| Slide 14
Proofs – Example of Functional consolidation
Reduced footprint, hardware and infrastructure
Reduction in panels from 3 to 1
Conventional Digital
Control Protection -
subsystems
79-2 87L
Control 67N
21 79-2
BBP & CBF
21 50 87B, 50BF
14 protection & control devices 2 protection & control devices Advanced protection solution
(Electro-Mechanical system could add 3 including busbar From 3 panels to 1 panel
devices per function) protection/backup
| Slide 15
Applications - ABB‘s process bus applications
Process level equipment – sensor technology
AIS / GIS Voltage level Current/ Application Description Status
voltage
ABB NCITs with IEC 61850-9-2 merging units
ELK-CP3, GIS 170 – 550kV Current & voltage Protection, control, Redundant, combined U/I Commercial operation
ELK-CP14 revenue metering NCIT, since 1998. Since 2011
U: capacitive divider, I: with IEC 61850
Rogowski coil
FOCS LTB AIS 420kV Current Protection, control Redundant optical CT Pilot installation since
integrated in 2010
disconnecting circuit
breaker
FOCS FS AIS 72 – 800kV Current Protection, control, Redundant optical CT, free- Under development
revenue metering standing
SAM600 GIS & AIS any Current & voltage & Protection, control, Modular IEC 61850 process Under development
breakers, revenue metering bus I/O system with
disconnectors… modules per primary
object
Slide 16
ABB‘s digital substation product portfolio-Overview
Remote control
Substation interface and HMI (Station level)
ABB SAS 600 systems
Slide 17
Proofs - ABB’s experience with NCITs and process bus
Some project highlights …..
Slide 18
Wide Area Monitoring (WAM) Systems
Today’s ABB Solutions
PSGuard
Wide Area
Protection
RES521
RES670
Slide 19
HVDC Line Protection-For Multi-terminal Systems and Embedded HVDC
System
• HVDC transmission will be more and more in the power systems
• Voltage source converter (VSC) based HVDC links shows advantages in
interconnections.
• Protection solution for HVDC lines is naturally required with the
development of HVDC connections, especially for Multi-terminal HVDC
(MTDC) transmission systems.
• Topics related with HVDC protection: Fast Protection, Line Differential
Protection, System Wide Protection, High sensitive protection, etc.
| Slide 20