Manual Book of
Mechanical System
Medical Gas
Pipeline System
ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

VERSION: 1.0

MOH/ESD/2018-2

Disclaimer: Any pictures of equipment, brand and model of equipment depicted in this guideline shall not
be considered as an acceptance or approval from the Ministry of Health Malaysia. It shall only serve as an
example or illustration for the relevant issues and matter of interest.

Buku Sistem Mekanikal MOH v3.indd 1 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

ACKNOWLEDGEMENT

The CPD Mechanical Committee, Ministry of Health would like to express the warmest
gratitude to all the contributors in any forms from various organizations as well as all
Ministry of Health Mechanical Engineers towards the successful drafting, formation and
completion of this manual book of mechanical system.

The greatest appreciation to the organizing and review committee comprising of following
personnel mechanical engineer from various sections in the Engineering Services Division,
State Health Offices and Hospitals in putting enormous effort and thoughts in the process
of completing this document in particular those who were involved in the workshop
BENGKEL MANUAL ASAS REKABENTUK & PENYELENGGARAAN SISTEM MEKANIKAL DI
PREMIS KESIHATAN held at Bukit Fraser, Pahang.

Engineering Services Division, Ministry of Health Malaysia (MOH)

1. Ir. Tauran Zaidi bin Ahmad Zaidi


2. Ir. Rosmahadi bin Ali
3. Ir. Suhaimi bin Rashid
4. En. Mohd Kamalluddin bin Hashim
5. En. Mohd Fairuz bin Mohd
6. En. Abu Bakar bin Abdullah
7. En. Mohd Fahril bin Mokhy
8. En. Mohd Hilmi bin Abdullah
9. En. Alif Riduan bin Khalid @ Othman
10. Ir. Rasyidi bin Mohd Tahir
11. En. Amir Ikram bin Muhammad
12. Ir. Zulfadli bin Mohd Jais
13. En. Yusuf bin Zubir
14. En. Adie Azhar bin Rustam
15. Ir. Ts. Mohd Hisam bin Sa’at (Editor)
16. Ir. Mohammad Faizal bin Khalid (Member of Editorial Board)
17. En. Adli Faiz bin Ramli (Member of Editorial Board)

Buku Sistem Mekanikal MOH v3.indd 2 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

CONTENT

1. Introduction
1.1. Standard And Regulations 5
1.2. Tenets Of Medical Gas Safety 6
1.3. Type Of Medical Gas 6
1.4. Coloring Coding And Orientation 7

2. Type Of Systems

2.1. Oxygen System


2.1.1 Overview Of Oxygen System 8
2.1.2 Vie Tank 10
2.1.3 Manifold 14
2.1.4 Main Parameter 16
2.1.5 Alarm Indication 17

2.2. Nitrous Oxide (N₂O) And Entonox (N₂O + O₂)


2.2.1 Overview Of Nitrous Oxide And Entonox 18
2.2.2 Components Of Nitrous Oxide And Entonox System 19
2.2.3 Main Parameter 20
2.2.4 Alarm Indication 21
2.2.5 Nitrous Oxide And Entonox Inspection 22

2.3. Medical Air (Ma4) And Surgical Air (Sa7)


2.3.1 Overview Of Ma 4 And Sa 7 System 23
2.3.2 Component Of Ma 4 And Sa 7 System 26
2.3.3 Main Parameter 27
2.3.4 Alarm Indication 27
2.3.5 Ma 4 And Sa 7 System Inspection 28

2.4. Vacuum System


2.4.1 Overview Of Vacuum System 31
2.4.2 Component Of Vacuum System 33
2.4.3 Main Parameter 34
2.4.4 Alarm Indicator 35
2.4.5 Vacuum System Inspection 36

Buku Sistem Mekanikal MOH v3.indd 3 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

2.5. Aneastethic Gas Scaveging System (AGSS)


2.5.1 Overview Of Agss 39
2.5.2 Component Of Agss 39
2.5.3 Main Parameter 40
2.5.4 Alarm Indication 41
2.5.5 Agss Inspection 41

3. Operation And Maintenance

3.1. Rules And Responsibility 44


3.2. Alarm Indication Check 45
3.3. System Test – Leakage Test 46
3.4. Avsu Zoning Test 47
3.5. Valve Closure Test 48
3.6. Inspection Checklist 49
3.6.1 Oxygen System (Vie) 49
3.6.2 Oxygen System (Manifold) 53
3.6.3 Nitrous Oxide System 55
3.6.4 Entonox System 57
3.6.5 Medical Air (4 Bar) 59
3.6.6 Surgical Air (7 Bar) 64
3.6.7 Vacuum System 69
3.6.8 Aneastethic Gas Scaveging System (Agss) 73

Buku Sistem Mekanikal MOH v3.indd 4 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

FRAME WORK FOR MANUAL BOOK


OF MECHANICAL SYSTEM
MEDICAL GAS PIPELINE SYSTEM

1. INTRODUCTION

1.1 STANDARD & REGULATIONS

List of references:

• Factory and Machinery Act (FMA) 1967

• MS 2675-1:2017 Medical Gas Systems – Part 1 : Code of Practice For The


Design, Installation, Validation and Verification

• MS 2675-2:2017 Medical Gas Systems – Part 2 : Code of Practice For Operation


and Maintenance

• Health Technical Memorandum 02-01 : Medical Gas Pipeline Systems, Part A :


Design, installation, validation and verification

• Health Technical Memorandum 02-01 : Medical Gas Pipeline Systems, Part B :


Operational management

• Health Technical Memorandum 2022 : Medical Gas Pipeline Systems, Part A :


Design, installation, validation and verification

• Health Technical Memorandum 2022 : Medical Gas Pipeline Systems, Part B :


Operational management

Buku Sistem Mekanikal MOH v3.indd 5 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System


1.2 TENETS
OF MEDICAL GAS SAFETY
1.2 TENETS OF MEDICAL GAS SAFETY
There are four (4) tenets of medical gas safety should be done in practice of Medical Gas
There are four 1.2
(4) tenets of medical gas safety
TENETS OF MEDICAL GASshould be done in practice of
SAFETY
and Pipe System.
Medical Gas and Pipe System.
There are four (4) tenets of medical gas safety should be done in practice of
1. Adequacy – accurate
Medical Gas and Pipe System. Adequacy
assessment of demand and

2.
– accurate assessment of demand and appropriate of
appropriate of plant selection;
Continuity – continuity of
1. Adequacy – accurate
plant selection;
supply is achieved, assessment
duplicate of demand and
component, emergency appropriate
or reserveof plant selection;
Continuity
supply, with alarm system;
2. Continuity – continuity of
3. – continuity of supply is achieved, duplicate component,
Identity – non detachable
supply gas-
is achieved, duplicate
specific connectioncomponent,
(TUs, emergency or reserve
emergency or reserve supply, with alarm system;
connectors, etc); supply, with alarm system;
4. Quality – correct 3. supply of – non detachable gas-
Identity
gases and maintain specific
Identity
cleanliness connection (TUs,
– non detachable gas-specific connection (TUs,
throughout the installation and etc);
connectors,
complete T&C
connectors, etc); 4. Quality – correct supply of
gases and maintain cleanliness
Quality throughout the installation and
complete T&C
– correct supply of gases and maintain cleanliness
throughout the installation and complete T&C
ACIQ
Figure 1: Tenets of Medical Gas Safety ACIQ
1.3 TYPE OF MEDICAL GAS Figure 1: Tenets of Medical Gas Safety
Figure 1: Tenets of Medical Gas Safety

There are seven


1.3(7) type OF
TYPE of medical
MEDICALgases
GASthat been use in hospital. They
1.3
are: TYPE OF MEDICAL GAS
There are seven (7) type of medical gases that been use in hospital. They
are:
There are seven (7) type of medical gases that been use in hospital. They are:

O Oxygen (O2)

N Nitrus Oxide (N2O)

E Entonox (N2O+O2)
ONE47VA 4 Medical Air(MA4)

7 Surgical Air (SA7)


Figure 2: Type of Medical Gas
Page 7 of 86
V Figure 2: Type of Medical Gas
Vacuum

Page 7 of 86

A Anesthetics Gas Scavenging System (AGSS)

Figure 2: Type of Medical Gas

Buku Sistem Mekanikal MOH v3.indd 6 29/08/2019 10:28 AM


standard in orientation of the medical gas for wall mounted and pendan

OLOUR CODING AND ORIENTATION


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA
ch of the medical
gas type been identify with different colour code. These

e the colour code for the cylinder
1.4 COLOUR CODING and the pipeline. There are also
AND ORIENTATION
1.4 COLOUR CODING AND ORIENTATION
ndard in orientation of the medical gas for wall mounted and pendant.
Each of the medical gas type been identify with different colour code. These
Each of the medical gas type been identify with different colour code. These are the

are
theforcolour
colour code the code and
cylinder for thethepipeline.
cylinderThere and are thealsopipeline. There
standard are alsoof the
in orientation
1.4 COLOUR CODING AND ORIENTATION
standard
medical gas forinwall
orientation
mounted ofand
thependant.
medical gas for wall mounted and pendant.
Each of the medical gas type been identify with different colour code. These

are the colour code for the cylinder and the pipeline. There are also

standard in orientation of the medical gas for wall mounted and pendant.













CYLINDER_COLOUR










IDENTIFY
CYLINDER_COLOUR








IDENTIFY





CYLINDER_COLOUR

CYLINDER_COLOUR

CYLINDER_COLOUR


IDENTIFY
CYLINDER_COLOUR
IDENTIFY

CYLINDER_COLOUR

IDENTIFY

CYLINDER_COLOUR





IDENTIFYIDENTIFY





IDENTIFY
















Figure 3: Colour coding and orientation
Figure 3: Colour coding and orientation

Page 8








7
Figure 3: Colour coding and orientation

Page 8 of 86
Figure 3: Colour coding and orientation

Page 8 of 86
Figure 3: Colour coding and orientation
Buku Sistem Mekanikal MOH v3.indd 7 29/08/2019 10:28 AM
Page 8 of 86

Manual Book of Mechanical System


2. TYPE OF SYSTEMS
Medical Gas Pipeline System
2.1 OXYGEN SYSTEM
2. TYPE OF SYSTEMS
2.1.1 OVERVIEW OF OXYGEN SYSTEM
2.1 In
OXYGEN
oxygen,SYSTEM
there are two type of system that normally been use in hospital
2.1.1depends on the
OVERVIEW OFcapacity of oxygen usage. These are the type of oxygen
OXYGEN SYSTEM
system:
In oxygen, there are two type of system that normally been use in hospital depends on the
capacity of oxygen usage. These are the type of oxygen system:

PROPOSE
PROPOSE AND
AND AREA OF AREA
OXYGENOF OXYGEN SYSTEM
SYSTEM
1) Ventilation therapy
1) Ventilation therapy
Operating
• • Operating theatres
Theatres
• Intensive Care Units
• Intensive Care Units
• Recovery Rooms
• • Surgical
RecoveryWards
Rooms

2) • Surgical
Inhalation Wards
therapy
• Emergencies
• Ambulances
2)
• Inhalation therapy
Hospital Departments
• Emergencies
• Ambulances
• Hospital Departments

Buku Sistem Mekanikal MOH v3.indd 8 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

Figure 4: Central Medical Gases for Oxygen System - Manifold and ERM
Figure 4: Central Medical Gases for Oxygen System - Manifold and ERM
Figure 4: Central Medical Gases for Oxygen System - Manifold and ERM

Figure 5: Central Medical Gases for Oxygen System - VIE and ERM
Figure 5: Central Medical Gases for Oxygen System - VIE and ERM
Figure 5: Central Medical Gases for Oxygen System - VIE and ERM

Page 10 of 86

Page 10 of 86
9

Buku Sistem Mekanikal MOH v3.indd 9 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

2.1.2 VIE TANK

• Process for liquid oxygen refill, it shall be topup before operating alarm signal level
(before risk assessed stock – 25%) and every refilling liquid oxygen, it shall be full
level (90%).


Nominal
VIE Tank Pressure
10.5~16 bar
(refer to
Pressure
manufacturing
Gauge templated)

Full Level

Liquid
Contents
Min Level Gauge

Figure 6: VIE tank and accessories

10

Buku Sistem Mekanikal MOH v3.indd 10 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

• Make sure pressure in tank within nominal pressure (10.5 ~ 16 bar) (refer to
manufacturing templated).
• The range of level (min level & max level) shall be marked on Liquid Contents Gauge
for supervision and monitoring purpose.
• Icing on vaporizer need to be remove regularly. The ideal condition of icing is not
more than 1/3 of vaporizer length size.



Length on
Allowable length
vaporizer, which
of icing on
should be no icing
vaporizer
at all time

2/3 1/3
Figure 7: Icing on VIE vaporizer

11

Buku Sistem Mekanikal MOH v3.indd 11 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

Rules & Responsibility Of Supplier/Gas Provider, Concession And Hospital During VIE
Tank Refilling

Work Parties Rules

Request Concession To inform hospital pharmacy for ordering liquid oxygen


with estimation amount.

Ordering Hospital Hospital pharmacy contact supplier/gas provider for


delivery liquid oxygen with estimation amount.

Delivering Supplier/ Gas To confirm date and time of delivery to hospital pharmacy
Provider and concession

Concession • Unlock the plant and escort gas provider during


refilling
• Check and witness the receipt of filled amount
complete with Certificate of Conformity (COC)
• To monitor VIE are refilling process until the pressure
stable and everything in order.
• Pass the receipt to hospital
Receiving

Supplier/ Gas • Contact concession when reach to VIE plant.


Provider • Filling the liquid oxygen until full capacity of VIE tank.
• Inform concession if any problem/failure during refill
• Provide the receipt of filled amount complete with
Certificate of Conformity (COC)

Record Hospital • To verify the receipt of filled amount complete with


Certificate of Conformity (COC)
• Plan and contact supplier/gas provider for next
refilling or receive request from concession or which
ever come first.

12

Buku Sistem Mekanikal MOH v3.indd 12 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

Basic Vessel Construction & Pressure Relief

Figure 8: VIE Tank Vessel

• Nominal Pressure for VIE Tank is 10.5 ~ 16 bar (refer to manufacturing templated).

• Once pressure on VIE tank built up and reach to 16.5 bar, the safety valve will purge
first, then if the pressure still increasing and reach to 24.5 bar, the bursting disc will
active and burst.

• In this situation, immediate action shall be taken to manually change over the valve
on bursting disc to another side.

• If the pressure still increasing and over to 24.5 bar, other side of bursting disc will
active and burst.

13

Buku Sistem Mekanikal MOH v3.indd 13 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

2.1.3 MANIFOLD

Figure 9: Central Medical Gases for Oxygen System - Manifold and ERM Diagram

Figure 10: Cylinder Manifold System

14

Buku Sistem Mekanikal MOH v3.indd 14 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

Figure 11: Central Medical Gases for Oxygen System - Manifold and ERM

Figure 12: Flow for Oxygen System

• Area Valve Service Unit (AVSU) is function to isolate the or continuously source of
supply by using Non-Interchangeable Screw Thread (NIST) during maintenance/
rectification works or in the event of emergency.

15

Buku Sistem Mekanikal MOH v3.indd 15 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

2.1.4 MAIN PARAMETER

VIE tank
• Gas pressure 10.5~16 bar
• Duplicated Pressure Relief Valve 16.5 bar
• Busting Disc 24.5 bar

Automatic Manifolds and Emergency Reserve (Manual) Manifolds


• Cylinder Bank Pressure (Duty or Standby): ~13700kPa / 137 bar
• Line Pressure Gauge: between 410kPa and 420kPa
• Low Pressure Alarm: 370kPa
• High Pressure Alarm: 500kPa
• Reserve Low Alarm: 1400kPa / 14.0 bar
• Pressure Safety Valve Setting: 530kPa

Gas Terminal Units (GTUs)


• Operating Pressure: 400kPa ± 10kPa / 4.0 ± 0.1 bar
• Operating Flow: 10 litres per minute (lpm).

Area / Local Alarm Panel at User Departments


• Low Pressure Alarm: 3.6 bar

*Note: 1.0 bar = ~100kPa = 14.7 psi

16

Buku Sistem Mekanikal MOH v3.indd 16 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

2.1.5 ALARM INDICATION

2.1.5.1 VIE ALARM INDICATION

Figure 13: VIE Liquid Level Classification and Alarm Signal

2.1.5.2 MANIFOLD SYSTEM ALARM INDICATION

Figure 14: Oxygen Manifold Alarm System

17

Buku Sistem Mekanikal MOH v3.indd 17 29/08/2019 10:28 AM


2.2.1 OVERVIEW OF NITRIOUS OXIDE AND ENTANOX

Nitrous Oxide (N2O) is a sedative agent used for anaesthetic and analgesic
Manual Book of Mechanical System
purposes,
Medical Gas when
Pipeline mixed with air, oxygen, and nebulised agents.
System

They OXIDE
2.2 NITRIOUS are commonly
(N2O) &used in:
ENTONOX (N2O +O2)
• Delivery / Labour Suites
2.2.1 OVERVIEW OF NITRIOUS OXIDE AND ENTONOX
• Operating Theatres.
Nitrous Oxide (N2O) is a sedative agent used for anaesthetic and analgesic purposes,
• Oral Surgery Facilities,
when mixed with air, oxygen, and nebulised agents.
• Burns Units,
• They are commonly used in:
• • Critical
Delivery / Labour SuitesCare Areas,
• Operating Theatres.
• Resuscitation Rooms at Accident & Emergency Department,
• Oral Surgery Facilities,
• Burns Units,• Diagnostic Departments (MRI, CAT, Angiography & Endoscopy
• Critical Care Areas,
• Units)at Accident & Emergency Department,
Resuscitation Rooms
• Diagnostic Departments (MRI, CAT, Angiography & Endoscopy Units)

Where
Where nitrous nitrous
oxide (N2O) oxide for(N
is provided 2O) is purposes,
anaesthetic providedscavenging
for anaesthetic
systems shall purposes,
be installedscavenging
to minimise occupational exposure.
systems shall Where nitrous
be installed oxide (N2O)occupational
to minimise is provided for exposure.
analgesic purposes, mechanical ventilation is sufficient for controlling its pollution.
Where nitrous oxide (N2O) is provided for analgesic purposes, mechanical
Colour of Nitrous Oxide (N2O) Cylinders: Blue
ventilation is sufficient for controlling its pollution.
Colour of Entonox (N2O + O2) Cylinders: Blue + White

Colour of Nitrous Oxide (N2O) Cylinders: Blue


Colour of Entanox (N2O + O2) Cylinders: Blue + White

Nitrous Oxide (N2O)



Nitrous Oxide (N2O)
• • Pain
Painkiller
killer
• • Operation
OperationTheatre (OT)
Theatre(OT)

Entonox (N2O
Entonox (N+OO+2)O ) 2 2
• • Pain
Painrelease
release
• • Labour
LabourRoom
Room

18
Page 20 of 86

Buku Sistem Mekanikal MOH v3.indd 18 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

2.2.2. COMPONENTS OF NITROUS OXIDE AND ENTONOX SYSTEMS

a. Nitrous Oxide (N2O) / Entonox (N2O + O2) Cylinders come with Cylinder Valve
b. Automatic Manifold, comprising:
c. Emergency Reserve (Manual) Manifold, typically comprising:

Nitrous Oxide (N2O)


Figure 15: Central Medical Gases for N20


Entonox (N2O + O2)

19

Buku Sistem Mekanikal MOH v3.indd 19 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

2.2.3. MAIN PARAMETERS

Automatic Manifolds and Emergency Reserve (Manual) Manifolds

• Cylinder Bank Pressure (Duty or Standby): ~13700kPa / 137 bar


• Line Pressure Gauge: between 410kPa and 420kPa
• Low Pressure Alarm: 370kPa
• High Pressure Alarm: 500kPa
• Reserve Low Alarm: 1400kPa / 14.0 bar
• Pressure Safety Valve Setting: 530kPa

Gas Terminal Units (GTUs)

• Operating Pressure: 400kPa ± 10kPa / 4.0 ± 0.1 bar


• Operating Flow: 10 litres per minute (lpm).

Area / Local Alarm Panel at User Departments

• Low Pressure Alarm: 7 bar

*Note: 1.0 bar = ~100kPa = 14.7 psi

20

Buku Sistem Mekanikal MOH v3.indd 20 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

2.2.4. ALARM INDICATION

User Area Plant


Area
Alarm Status @ Nitrous Oxide (N2O) Manifold Plant

Check that none of the following alarms are activated:

o Change Cylinders (duty bank empty, standby running)

o Change Cylinders Immediately (duty bank empty, standby low @ 10% capacity)

o Reserve Low (signal turns on when Emergency


- Reserve Manifold is at 14 bar)

o Pressure Fault (pipeline pressure fault)

o System Fault (alarm panel faulty)

21

Buku Sistem Mekanikal MOH v3.indd 21 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

2.2.5 NITROUS OXIDE AND ENTONOX INSPECTION

Cylinder
Manifold System

Figure 17: Nitrous Oxide and Entonox Manifold Inspection

22

Buku Sistem Mekanikal MOH v3.indd 22 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

2.3 MEDICAL AIR (MA4) AND SURGICAL AIR SYSTEM (SA7)

2.3.1 OVERVIEW OF MA4 AND SA7 SYSTEM

2.3.1.1 CONFIGURATION OF MEDICAL SUPPLY SYSTEMS

PRIMARY SUPPLY SECONDARY SUPPLY REVERSE SUPPLY


(THIRD SOURCE OF SUPPLY)
Duplex compressor Automatic manifold Automatic manifold system
system system.
May be sized to support high- dependency
To come on-line area or whole size
automatically in the event
of plant failure. OR

Number of cylinders Locally based integral valve cylinders with


based on ability to regulators/ flow meters attached.
provide 4 hours supply at
average use.
Two compressors of Third compressor of a Automatic manifold system.
a triplex compressor triplex system. To support whole size.
system
Two compressors of Other two compressors of Automatic manifold system.
a quadruplex system. a quadruplex system. To support whole size.
Note :
Duplex – 2 Compressor
Triplex – 3 Compressor
Quadruplex – 4 Compressor

23

Buku Sistem Mekanikal MOH v3.indd 23 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

2.3.1.2 PROPOSE AND AREA OF USES FOR MEDICAL AIR (MA4) AND SURGICAL AIR
SYSTEM

MEDICAL AIR (MA4) SURGICAL AIR (SA7)


Medical air is mainly used in respiratory Surgical air (of medical air quality) is also
therapy as a power source for patient used, at a higher pressure, to power a variety
ventilators, and for blending with oxygen. It of surgical tools and other devices such as
is also used as the driving gas for nebulised tourniquets. (As an alternative, nitrogen can
drugs and chemotherapy agents. be used for this purpose.)
• Ventilator; • Driving of medical devices;
• Driving of such medical devices; • Surgical tools;
• Operation of OT Pendant (selectable);
• All wards (Bedhead panel) • Operation Room
• A&E
• Operation Room
• Maternity
• Radiology
• Critical Care Area
• HDW
• Renal
• Dental
Colour Code Piping

• Colour Code Cylinder

24

Buku Sistem Mekanikal MOH v3.indd 24 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

2.3.1.3 LAYOUT OF MEDICAL AIR PLANT

Figure 19: Overview Layout of Medical Air Plant Room

Figure 20: Layout of Medical Air Plant Room

25

Buku Sistem Mekanikal MOH v3.indd 25 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

2.3.2 COMPONENT OF MEDICAL AIR (MA4) AND SURGICAL AIR SYSTEM

MA4 & SA7


Main Components


Compressor Dryer


Bedhead Panel Air Receiver Ot Pendant

Regulator Bacteria Filter Dust/Carbon Filter

26

Buku Sistem Mekanikal MOH v3.indd 26 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

2.3.3 MAIN PARAMETER

MEDICAL AIR (MA4) SURGICAL AIR (SA7)


AUTOMATIC i- Cylinder bank pressure (Duty i. Cylinder bank pressure (Duty
MANIFOLD AND and Standby) :~13700kPa and Standby) :~13700kPa
EMERGENCY ii- Line pressure gauge: 410 kPa- ii- Line pressure gauge: 410 kPa-
RESERVE (MANUAL) 420kPa 420kPa
MANIFOLD iii- Low pressure alarm: 370kPa iii- Low pressure alarm: 650kPa
iv- High pressure alarm: 500kPa iv- High pressure alarm:
v- Reserve low alarm: 1400kPa 1050kPa
vi- Pressure Safety Valve Setting: v- Reserve low alarm: 1400kPa
530kPa vi- Pressure Safety Valve Setting:
1100kPa
GAS TERMINAL i. Operating pressure: 400kPa ± i. Operating pressure: 700kPa ±
UNITS (GTUs) 10kPa / 4.0 ± 0.1bar 10kPa / 7.0 ± 0.1bar
ii. Operating flow: 10 litres per ii. Operating flow: 10 litres per
minute (lpm) minute (lpm)
AREA / LOCAL Low pressure alarm : 3.6 bar Low pressure alarm :6.5 bar
ALARM PANEL AT
USER DEPARTMENTS

2.3.4 ALARM INDICATION


27

Buku Sistem Mekanikal MOH v3.indd 27 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

2.3.5 MA 4 AND SA 7 SYSTEM INSPECTION

i. Compressor Panel

Figure 21: Checking Item on Compressor Panel

28

Buku Sistem Mekanikal MOH v3.indd 28 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

ii. Dryer Panel

Figure 22: Checking Item on Dryer Panel

29

Buku Sistem Mekanikal MOH v3.indd 29 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

iii. Emergency Supply Manifold

Figure 22: Checking Item on Dryer Panel

30

Buku Sistem Mekanikal MOH v3.indd 30 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

iv. NIST connector.

• Pressure switch
on both banks

• Non-return valves on header


and line
!

• Pin indexed tail pipes with


NIST to header

Figure 24: NIST connector

2.4 VACUUM SYSTEM

2.4.1 OVERVIEW OF VACUUM SYSTEM

In vacuum system, there are three type of system that normally been use in hospital
depends on the capacity of vacuum usage. These are the type of vacuum system:

31

Buku Sistem Mekanikal MOH v3.indd 31 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

Figure 25: Vacuum System - Duplex

Figure 26: Vacuum System - Triplex

Figure 27: Vacuum System -Quadruplex

32

Buku Sistem Mekanikal MOH v3.indd 32 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

2.4.2 COMPONENTS OF VACUUM SYSTEM

VACUUM
Main Components

Vacuum Pump Air Receiver



Bacteria Filter OT Pendant Regulator


Bedhead

33

Buku Sistem Mekanikal MOH v3.indd 33 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

2.4.3 MAIN PARAMETER

Component Pump Receiver Bacteria Filter Pressure Terminal unit


switch

Symbol

Parameter Cut-in= 450 mmHg Shall be in N/A 300mmHg


500 mmHg green mark 40L/min
Cut-out=
650mmHg

Other All systems Valid Cert of Complete with Working in a N/A


requirement should PMT No. drainage flask setting range
comprise
pumps and
motors of
identical
type that are
suitable for
continuous
running and
stop/start
operation

1. Running Amp (Amp meter)


2. Start/Stop Button Auto/Manual Selector
3. Start/Stop/Fault Indicator
4. Running Hours
5. Pressure Reading (mmHg)

34

Buku Sistem Mekanikal MOH v3.indd 34 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

2.4.3 ALARM INDICATOR

Supply Alarm conditions Legend Colour Audible


System System

Medical Normal – all system / components Normal Green No


vacuum function
plant
Plant fault – any fault due to Plant fault Yellow Yes
pumps/control panel/motor trip/
other safety devices

Plant emergency - receiver vacuum Plant emergency Yellow Yes


has fallen,

for example, by 50 mm Hg below


the cut-in

setting for the pump;

Pressure Fault - pipeline vacuum Pressure Fault Red Yes


less

than 360 mm Hg.

35

Buku Sistem Mekanikal MOH v3.indd 35 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

2.4.4 VACUUM SYSTEM INSPECTION

36

Buku Sistem Mekanikal MOH v3.indd 36 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

37

Buku Sistem Mekanikal MOH v3.indd 37 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

Notes:
Pump operating and indicating System

• Pneumatic components should have ventilation. All functions should be appropriately


identified. Indicators should have a design life of at least five years. The operating
system should be capable of automatically restarting after reinstatement of the
power supply.

• The vacuum supply system should be connected to the stand-by electrical supply. The
control system should ensure that pumps restart in sequence to avoid overloading
the power supply.

Plant status monitoring

• A monitoring system must be provided to detect the following faults in the vacuum
supply system:

a) Plant fault for each pump:

i. Control circuit failed;


ii. Motor tripped;
iii. Pump failed to go on load;
iv. Activation of other safety devices supplied by the manufacturers;

b) Plant emergency – receiver vacuum has fallen, for example, by 50 mmHg below
the cut in setting for the pump;

c) Pressure fault (pipeline) – pipeline vacuum less than 360 mmHg.

38

Buku Sistem Mekanikal MOH v3.indd 38 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

2.5 ANEASTETHIC GAS SCAVEGING SYSTEM (AGSS) –

2.5.1 OVERVIEW OF AGSS

AGGS
• Active AGSS Systems provide full removes of waste gas
• Installed in operation theatres and where N20 is used

#Extraction of waste anaesthetic gases at :


• Operating Theatre
• Delivery Room
• Point Use

2.5.2 COMPONENTS OF AGSS

• Collecting System
• Transfer System
• Receiving System
• Disposal System

Figure 28: AGSS System

39

Buku Sistem Mekanikal MOH v3.indd 39 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

Figure 29: AGSS System

2.5.3 MAIN PARAMETER

40

Buku Sistem Mekanikal MOH v3.indd 40 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

2.5.4 ALARM INDICATOR

A simplified (alarm) system is required for the AGSS, with the warning/indication panel
located in the operating room referring to HTM 02-01 Part A

Alarms are triggered by a pressure switch or some other type of flow monitor

2.5.5 AGSS INSPECTION

41

Buku Sistem Mekanikal MOH v3.indd 41 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System


Figure 30: AGSS Checking Item
Figure 30: AGSS Checking Item

Plant Plant
controlcontrol indication
indication - indicators
- should be should beto indicators to show
show the following the following
conditions:
conditions:
a) green “mains on”
b) a) “air
green green “mains
flow” on”;
normal; inititated by either a pressure switch or air flow detection
device
b) at the pump.
green “air flow” normal; initiated by either a pressure switch or air
c) yellow “duty pump failed” (palnt fault)
d) flow failed”
red “system detection device
(plant at the pump.
emergency)
c) yellow “duty pump failed” (plant fault);
d) red “system failed” (plant emergency).

42

Page 49 of 86
Buku Sistem Mekanikal MOH v3.indd 42 29/08/2019 10:28 AM

ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

3.

Max Static Vacuum -20kPa


Flow 80-130 litres min

Discharge Outlets
Discharge - sited
outlets - sitedatatroof
roof level, wellaway
level, well awayfrom
from ventilation
ventilation inlets,
inlets, opening windows
and other apertures, to prevent pollution re-entering the building.
opening windows and other apertures, to prevent pollution re-entering
the building.

43

Buku Sistem Mekanikal MOH v3.indd 43 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

3.0 OPERATION AND MAINTENANCE

3.1 RULES AND RESPONSIBILITY

3.1.1 Responsibilities of the authorised person (MGS) for the permit-to work
procedure

The responsibilities of the authorised person (MGS) are as follows:

a) Obtaining permission for interruption of supplies and affixing “do not use” or other
prohibition notices;
b) Preparing permit;
c) Supervising isolation of section on which work is to be carried out;
d) Explaining details of work to competent person (MGS);
e) Supplying drawings of existing sections of the installation “as fitted”;
f) Supervising performance, cross-connection and identity tests of completed work as
appropriate;
g) Supervising purging with working gas;
h) Final testing, assisted by the QC in the case of high hazard work;
i) Final testing in the case of low and medium hazard work;
j) Restoring service;
k) Supervising or making final connection of any extension;
l) Notifying designated medical officer or designated nursing personnel of completion
of work and removal of “do not use” notices;
m) Obtaining corrected copy of drawings;
n) Supervising amendments of office copy of ”as-fitted” drawings;
o) Retaining original copy of permit and all permit books; and
p) Obtaining designated medical or nursing personnel signature on Part 6 and return
the system to service.

44

Buku Sistem Mekanikal MOH v3.indd 44 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

3.1.2 Responsibilities of the competent person (MGS) for the permit-to work
procedure

The responsibilities of the competent person (MGS) are as follows:

a) signing Part 2 of the permit, acknowledging responsibility for the work;


b) Obtaining and understanding instructions on work to be done;
c) Isolating section of system on which work is to be carried out, under direct supervision
of authorised person (MGS);
d) Carrying out the work;
e) Carrying out system integrity tests on completed work under direct supervision of
authorised person (MGS); and
f) Signing Part 3 on both the original permit (held by the authorised person (MGS)) and
the copy 1 declaring that the work is completed as indicated on the permit.

3.2 ALARM INDICATION CHECK

– Check that the Visual Indicators and Sounder / Buzzer are working normally - there is
a “test” button which may be pressed.

i. Check the physical condition of pressure switches. To test the functionality


and setting of the low-pressure switches at user departments, shut off the gas
supply at the AVSU and purge the nitrous oxide (N2O) gas at any GTU until the
pressure reaches 3.6 bar, at which the low-pressure alarm shall be raised. The
pressure switches shall be tested at least once a year.

ii. Open the Alarm Panel to inspect the connection modules – ensure there are no
bypasses.

45

Buku Sistem Mekanikal MOH v3.indd 45 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

3.3 SYSTEM TEST – LEAKAGE TEST

46

Buku Sistem Mekanikal MOH v3.indd 46 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

3.4 AVSU ZONING TEST

47

Buku Sistem Mekanikal MOH v3.indd 47 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

3.5 VALVE CLOSURE TEST

48

Buku Sistem Mekanikal MOH v3.indd 48 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

3.6 INSPECTION CHECKLIST

3.6.1. OXYGEN SYSTEM (VIE)



SENARAI SEMAK PEMERIKSAAN SISTEM MEKANIKAL
KHIDMAT SOKONGAN HOSPITAL
SISTEM BEKALAN GAS PERUBATAN - LIQUID OXYGEN :
DELIVERY INFORMATION
SEKSYEN OPERASI HOSPITAL
CAWANGAN PERKHIDMATAN
BAHAGIAN PERKHIDMATAN
KEJURUTERAAN
KEMENTERIAN KESIHATAN MALAYSIA

HOSPITAL : _____________________________________

Month

Dis 2015 Jan-16 Feb-16 Mac 2016

Liquid Liquid Liquid Liquid


Date Content Content Content Content
Level Quantity Level Quantity Level Quantity Level Quantity
before of Topup before of Topup before of Topup before of Topup
Topup (m3 gas) Topup (m3 gas) Topup (m3 gas) Topup (m3 gas)
(Inch of (Inch of (Inch of (Inch of
Water) Water) Water) Water)

10

49

Buku Sistem Mekanikal MOH v3.indd 49 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

Total 0 0 0 0 0 0 0 0

PREPARED BY (MoH) : _______________________________ DATE OF PREPARED : _______________________________


(name & signature)

PREPARED BY (CONCESSION) : _______________________________ DATE OF PREPARED : _______________________________


(name & signature)

50

Buku Sistem Mekanikal MOH v3.indd 50 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

SENARAI SEMAK PEMERIKSAAN SISTEM MEKANIKAL


KHIDMAT SOKONGAN HOSPITAL
SISTEM BEKALAN GAS PERUBATAN - OKSIGEN (VIE)
SEKSYEN OPERASI HOSPITAL
CAWANGAN PERKHIDMATAN
BAHAGIAN PERKHIDMATAN
KEJURUTERAAN
KEMENTERIAN KESIHATAN MALAYSIA


NAME OF HOSPITAL : DATE OF INSPECTION :
_____________________________________ ______________________________________
INSPECTED BY (MoH) : ACCEPTED BY (CC) :
_____________________________________ ______________________________________
(name & signature) (name & signature)

No Item Yes No Remarks


1 Vacuum Insulated Evaporator (VIE)
1.1 Plant Room is locked and
secured
1.2 The compound and external
area is clean and free from
combustible materials
1.3 Safety signage and instruction
is available and in good
condition.
1.4 Log Book & Log Sheet are
available and updated
1.5 PMT No. is appear & visible on
VIE Tank
1.6 Validity of certificate of fitness PMT No. : _______________________________
(PMT). Record the expiry date Expired Date : ___________________________
1.7 Vessel physical are clean and
in good condition (no fungal/
mold on outside tank)
1.8 VIE Tank under working Working Pressure (bar) : __________________
pressure (record the pressure) (Nominal pressure : 10.5 ~ 16 bar)
1.9 Liquid in stock level (record Liquid Level : ___________________________
reading) (Inches Of Water : 120)
1.10 A pipework and installation
diagram (P&ID) of the plant is
displayed clearly to indicate
the appropriate valves that are
necessary to operate the plant
safely.

51

Buku Sistem Mekanikal MOH v3.indd 51 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

1.11 All valves in good condition


without any leakage indicator
1.12 Build up pressure regulator
in good condition and clean
without any leakage.
1.13 Vessel pressure relief valve in
good condition
1.14 Vessel bursting discs in good
condition
1.15 Vaporizer physical are clean
and in good condition (no
fungal/mold)
1.16 Minimal ice and frost
accumulated on piping and
vaporizer is acceptable
condition and pressure
building coil and piping are
free from dents and damage.
1.17 Liquid low level signal to
Engineering Control Room is
working properly, if applicable.
1.18 Other findings :

1.19 Recommendations :

52

Buku Sistem Mekanikal MOH v3.indd 52 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

3.6.2. OXYGEN SYSTEM (MANIFOLD)



SENARAI SEMAK PEMERIKSAAN SISTEM MEKANIKAL
KHIDMAT SOKONGAN HOSPITAL
SISTEM BEKALAN GAS PERUBATAN - OKSIGEN (MANIFOLD)
SEKSYEN OPERASI HOSPITAL
CAWANGAN PERKHIDMATAN
BAHAGIAN PERKHIDMATAN
KEJURUTERAAN
KEMENTERIAN KESIHATAN MALAYSIA

NAME OF HOSPITAL : DATE OF INSPECTION :


_____________________________________ ______________________________________
INSPECTED BY (MoH) : ACCEPTED BY (CC) :
_____________________________________ ______________________________________
(name & signature) (name & signature)

No Item Yes No Remarks

1 Cylinder Manifold Oxygen

1.1 Plant Room is locked and


secured

1.2 Lighting is adequate and


functioning

1.3 Safety signage and instruction


is available and in good
condition.

1.4 Fire detector (smoke) are


install and working properly/
in good condition in plant (if
applicable)

1.5 Log Book & Log Sheet are


available and updated

1.6 Noise level is adequately Noise level : <80dB


controlled or hearing
protection provided (if
applicable)

1.7 Ventilation is adequate and Room Temp : <35°C


functioning (if applicable)

1.8 Cylinders are sitting Right Bank Cylinder : _____________


adequately and properly in the
right/left bank. Record right Left Bank Cylinder : ______________
and left bank contain cylinder.

53

Buku Sistem Mekanikal MOH v3.indd 53 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

1.9 Additional cylinders for one


complete bank change should
be held in the manifold room

1.10 Line valve on both bank shall


be Turn-On at all time

1.11 All stage regulators (1st 1st stage regulator for right bank pressure (bar):
& 2nd stage regulator) __
are functioning and good 2nd stage regulator for right bank pressure (bar):
condition without any leakage. __
Record right and left bank 1st stage regulator for left bank pressure
contain pressure. (where (bar): __
applicable) 2nd stage regulator for left bank pressure
(bar): __

1.12 Auto changeover function and


in good condition

1.13 Non-return valve are install


and in correct operation

1.14 All joints and tailpipes are free


from leakage

1.15 Master/Area alarm panel are


tested and in good working
condition.

1.16 Line pressure relief valve in


good condition

1.17 Other findings :

1.18 Recommendations :

54

Buku Sistem Mekanikal MOH v3.indd 54 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

3.6.3. NITROUS OXIDE SYSTEM



SENARAI SEMAK PEMERIKSAAN SISTEM MEKANIKAL
KHIDMAT SOKONGAN HOSPITAL
SISTEM BEKALAN GAS PERUBATAN - NITRUS OKSIDA N2O
(MANIFOLD)
SEKSYEN OPERASI HOSPITAL
CAWANGAN PERKHIDMATAN
BAHAGIAN PERKHIDMATAN
KEJURUTERAAN
KEMENTERIAN KESIHATAN MALAYSIA

NAME OF HOSPITAL : DATE OF INSPECTION :


_____________________________________ ______________________________________
INSPECTED BY (MoH) : ACCEPTED BY (CC) :
_____________________________________ ______________________________________
(name & signature) (name & signature)

No Item Yes No Remarks


1 Cylinder Manifold Nitrus Oxyde
1.1 Plant Room is locked and
secured
1.2 Lighting is adequate and
functioning
1.3 Safety signage and instruction
is available and in good
condition.
Plant Room is free from
combustible materials
1.4 Fire detector (smoke)
are installed and working
properly/in good condition in
plant (if applicable)
1.5 Log Book & Log Sheet are
available and updated
1.6 Noise level is adequately Noise level : <80dB
controlled or hearing
protection provided (if
applicable)
1.7 Ventilation is adequate and Room Temp : <35°C
functioning (if applicable)
1.8 Cylinders are properly stored /
Right Bank Cylinder : _____________
secured in the right/left bank.
Record right and left bank
Left Bank Cylinder : ______________
contain pressure.

55

Buku Sistem Mekanikal MOH v3.indd 55 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

1.9 Cylinders on both banks are


Turn-On to regain normal
supply to hospital
1.10 All stage regulators (1st 1st stage regulator for right bank pressure
& 2nd stage regulator) (bar) : __
are functioning and good 2nd stage regulator for right bank pressure
condition without any leakage. (bar) : __
Record right and left bank 1st stage regulator for left bank pressure
contain pressure. (where (bar) : __
applicable) 2nd stage regulator for left bank pressure
(bar) : __
1.11 Auto changeover is functioning
and in good condition
1.12 Non-return valve are installed
and in correct operation
1.13 All joints and tailpipes are free
from leakage
1.14 Master/Area alarm panel are
tested and in good working
condition.
1.15 Line pressure relief valve in
good condition
1.16 Liquid low level signal to
Engineering Control Room is
working properly, if applicable.
1.18 Other findings :

1.19 Recommendations :

56

Buku Sistem Mekanikal MOH v3.indd 56 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

3.6.4. ENTONOX SYSTEM


SENARAI SEMAK PEMERIKSAAN SISTEM MEKANIKAL


KHIDMAT SOKONGAN HOSPITAL
SISTEM BEKALAN GAS PERUBATAN - ENTONOX (MANIFOLD)
SEKSYEN OPERASI HOSPITAL
CAWANGAN PERKHIDMATAN
BAHAGIAN PERKHIDMATAN
KEJURUTERAAN
KEMENTERIAN KESIHATAN MALAYSIA

NAME OF HOSPITAL : DATE OF INSPECTION :


_____________________________________ ______________________________________
INSPECTED BY (MoH) : ACCEPTED BY (CC) :
_____________________________________ ______________________________________
(name & signature) (name & signature)

No Item Yes No Remarks


1 Cylinder Manifold Entonox
1.1 Plant Room is locked and
secured
1.2 Lighting is adequate and
functioning
1.3 Safety signage and instruction
is available and in good
condition.
Plant Room is free from
combustible materials
1.4 Fire detector (smoke)
are installed and working
properly/in good condition in
plant (if applicable)
1.5 Log Book & Log Sheet are
available and updated
1.6 Noise level is adequately Noise level : <80dB
controlled or hearing
protection provided (if
applicable)
1.7 Ventilation is adequate and Room Temp : <35°C
functioning (if applicable)
1.8 Cylinders are properly stored /
Right Bank Cylinder : _____________
secured in the right/left bank.
Record right and left bank
Left Bank Cylinder : _____________
contain pressure.

57

Buku Sistem Mekanikal MOH v3.indd 57 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

1.9 Cylinders on both banks are


Turn-On to regain normal
supply to hospital
1.10 All stage regulators (1st 1st stage regulator for right bank pressure
& 2nd stage regulator) (bar) : __
are functioning and good 2nd stage regulator for right bank pressure (bar)
condition without any leakage. : __
Record right and left bank 1st stage regulator for left bank pressure
contain pressure. (where (bar) : __
applicable) 2nd stage regulator for left bank pressure
(bar) : __
1.11 Auto changeover is functioning
and in good condition
1.12 Non-return valve are installed
and in correct operation
1.13 All joints and tailpipes are free
from leakage
1.14 Master/Area alarm panel are
tested and in good working
condition.
1.15 Line pressure relief valve in
good condition
1.16 Liquid low level signal to
Engineering Control Room is
working properly, if applicable.
1.18 Other findings :

1.19 Recommendations :

58

Buku Sistem Mekanikal MOH v3.indd 58 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

3.6.5. MEDICAL AIR (MA4)


SENARAI SEMAK PEMERIKSAAN SISTEM MEKANIKAL


KHIDMAT SOKONGAN HOSPITAL
SISTEM BEKALAN GAS PERUBATAN - MEDICAL AIR (4 BAR)
SEKSYEN OPERASI HOSPITAL
CAWANGAN PERKHIDMATAN
BAHAGIAN PERKHIDMATAN
KEJURUTERAAN
KEMENTERIAN KESIHATAN MALAYSIA

NAME OF HOSPITAL : DATE OF INSPECTION :


_____________________________________ ______________________________________
INSPECTED BY (MoH) : ACCEPTED BY (CC) :
_____________________________________ ______________________________________
(name & signature) (name & signature)

No Item Yes No Remarks


1 Medical Air System (Compressor)
1.1 Plant Room is locked and
secured
1.2 Lighting is adequate and
functioning
1.3 Safety signage and instruction
is available and in good
condition.
1.4 Fire detector (smoke) are
install and working properly/
in good condition in plant (if
applicable)
1.5 Log Book & Log Sheet are
available and updated
1.6 Noise level is adequately Noise level : <80dB
controlled or hearing
protection provided (if
applicable)
1.7 Ventilation is adequate and Room Temp : <30°C
functioning (if applicable)
1.8 Compressor oil are change
accordingly as per schedule
and tagout.

59

Buku Sistem Mekanikal MOH v3.indd 59 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

1.9 Oil filter and air filter are


change accordingly as per
schedule and tagout.
1.20 All pressure gauges are
functioning and in good
condition
1.21 Motor and compressor
housing are clean
1.22 After-cooler intake grill fins are
clean
1.23 After cooler auto drain valve
and solenoid are functioning
and in good condition
1.24 Motor aligned and without
any abnormal vibration. Drives
coupling/pulleys and belt
tension are in good condition
1.25 Observe motor & compressor Running current (amp) : ___________
running accordingly. Record Pressure setting (cut in) for MA4 (bar) : _____
motor running current & (nominal pressure setting for cut in : 9 ~ 9.5bar)
pressure setting Pressure setting (cut off) for MA4 (bar) : ____
(nominal pressure setting for cut off : 10 ~
11bar)
1.26 All control panel, indicator
light and alarm panel are
functioning
1.27 All joints and connection is
free from any leakage
2 Medical Air System (Receiver)
2.1 Auto drain and manual bypass
valve are functioning in good
condition
2.2 Safety valve are functioning
and in good condition
2.3 Discharge vent from safety
valve is satisfactory and not
obstructed
2.4 All external part of receiver
are clean
2.5 Strainer are clean if applicable

60

Buku Sistem Mekanikal MOH v3.indd 60 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

2.6 External sign of damage or


wear and for secure supports
are in good condition
2.7 Validity of certificate of fitness PMT No. : ___________________________
(PMT). Record the expiry date Expired Date : ___________________________
2.8 Record receiver pressure Receiver Pressure (bar) : _____
(nominal pressure : 7 ~ 10 bar)
3 Medical Air System (Dryer, Filter,
Regulator)
3.1 Safety valve are functioning
and in good condition
3.2 Automatic air release on
column prior to drying out
process are functioning
properly
3.3 Check automatic re-
pressurization of column after
drying out process
3.4 Change over sequence operate
accordingly
3.5 Desiccant are in good
condition and replaced
accordingly
3.6 Heating element drying
out column are operate
accordingly if applicable
3.7 Thermostatic controls of
heating element are operating
accordingly if applicable.
3.8 All gauges are functionality
3.9 Bacteria pressure in
acceptable limit
4 Medical Air System (Cylinder
Manifold)
4.1 Plant Room is locked and
secured
4.2 Lighting is adequate and
functioning
4.3 Safety signage and instruction
is available and in good
condition.

61

Buku Sistem Mekanikal MOH v3.indd 61 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

4.4 Fire detector (smoke) are


install and working properly/
in good condition in plant (if
applicable)
4.5 Log Book & Log Sheet are
available and updated
4.6 Noise level is adequately Noise level : <80dB
controlled or hearing
protection provided (if
applicable)
4.7 Ventilation is adequate and Room Temp : <35°C
functioning (if applicable)
4.8 Cylinders are sitting Right Bank Cylinder : _____________
adequately and properly in the Left Bank Cylinder : ______________
right/left bank. Record right
and left bank contain pressure.
4.9 Cylinders on both banks are
Turn-ON to regain normal
supply to hospital
4.10 All stage regulators (1st 1st stage regulator for right bank pressure
& 2nd stage regulator) (bar) : __
are functioning and good 2nd stage regulator for right bank pressure (bar)
condition without any leakage. : __
Record right and left bank 1st stage regulator for left bank pressure
contain pressure. (where (bar) : __
applicable) 2nd stage regulator for left bank pressure
(bar) : __
4.11 Auto changeover function and
in good condition
4.12 Non-return valve are install
and in correct operation
4.13 All joints and tailpipes are free
from leakage
4.14 Master/Area alarm panel are
tested and in good working
condition.
4.15 Line pressure relief valve in
good condition
4.16 Ice formation on vaporizer
under supervise (by spraying
water) and pressure building
coil and piping fee from dents
or damage.

62

Buku Sistem Mekanikal MOH v3.indd 62 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

4.17 Liquid low level signal to


Engineering Control Room is
working properly, if applicable.
4.18 Other findings :

4.19 Recommendations :

63

Buku Sistem Mekanikal MOH v3.indd 63 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

3.6.6. SURGICAL AIR (SA7)



SENARAI SEMAK PEMERIKSAAN SISTEM MEKANIKAL
KHIDMAT SOKONGAN HOSPITAL
SISTEM BEKALAN GAS PERUBATAN - SURGICAL AIR (7/10
BAR)
SEKSYEN OPERASI HOSPITAL
CAWANGAN PERKHIDMATAN
BAHAGIAN PERKHIDMATAN
KEJURUTERAAN
KEMENTERIAN KESIHATAN MALAYSIA

NAME OF HOSPITAL : DATE OF INSPECTION :


_____________________________________ ______________________________________
INSPECTED BY (MoH) : ACCEPTED BY (CC) :
_____________________________________ ______________________________________
(name & signature) (name & signature)

No Item Yes No Remarks


1 Surgical Air System (Compressor)
1.1 Plant Room is locked and
secured
1.2 Lighting is adequate and
functioning
1.3 Safety signage and instruction
is available and in good
condition.
1.4 Fire detector (smoke) are
install and working properly/
in good condition in plant (if
applicable)
1.5 Log Book & Log Sheet are
available and updated
1.6 Noise level is adequately Noise level : <80dB
controlled or hearing
protection provided (if
applicable)
1.7 Ventilation is adequate and Room Temp : <35°C
functioning (if applicable)
1.8 Compressor oil is change
accordingly as per schedule
and tag out.
1.9 Oil filter and air filter are
change accordingly as per
schedule and tag out.

64

Buku Sistem Mekanikal MOH v3.indd 64 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

1.20 All pressure gauges are


functioning and in good
condition
1.21 Motor and compressor
housing are clean
1.22 After-cooler intake grill fins are
clean
1.23 After cooler auto drain valve
and solenoid are functioning
and in good condition
1.24 Motor aligned and without
any abnormal vibration. Drives
coupling/pulleys and belt
tension are in good condition
1.25 Observe motor & compressor Running current (amp) : ___________
running accordingly. Record Pressure setting (cut in) for SA7 (bar) : _____
motor running current & (nominal pressure setting for cut in : 9 ~ 9.5 bar)
pressure setting Pressure setting (cut off) for SA7 (bar) : ____
(nominal pressure setting for cut off : 10 ~ 11
bar)
Running current (amp) : ___________
Pressure setting (cut in) for SA10 (bar) : _____
(nominal pressure setting for cut in : 9 ~ 9.5 bar)
Pressure setting (cut off) for SA10 (bar) : _____
(nominal pressure setting for cut off : 10 ~ 12
bar)
1.26 All control panel, indicator
light and alarm panel are
functioning
1.27 All joints and connection is
free from any leakage
2 Surgical Air System (Receiver)
2.1 Auto drain and manual bypass
valve are functioning in good
condition
2.2 Safety valve are functioning
and in good condition
2.3 Discharge vent from safety
valve is satisfactory and not
obstructed
2.4 All external part of receiver
are clean
2.5 Strainer are clean if applicable

65

Buku Sistem Mekanikal MOH v3.indd 65 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

2.6 External sign of damage or


wear and for secure supports
are in good condition
2.7 Validity of certificate of fitness PMT No. : ___________________________
(PMT). Record the expiry date Expired Date : ___________________________
2.8 Record receiver pressure Receiver Pressure (bar) : _____
(nominal pressure : 7 ~ 11 bar)
3 Surgical Air System (Dryer, Filter,
Regulator)
3.1 Safety valve are functioning
and in good condition
3.2 Automatic air release on
column prior to drying out
process are functioning
properly
3.3 Check automatic re-
pressurization of column after
drying out process
3.4 Change over sequence operate
accordingly
3.5 Desiccant are in good
condition and replaced
accordingly
3.6 Heating element drying
out column are operate
accordingly if applicable
3.7 Thermostatic controls of
heating element are operating
accordingly if applicable.
3.8 All gauges are functionality
3.9 Bacteria pressure in
acceptable limit
4 Surgical Air System (Cylinder
Manifold)
4.1 Plant Room is locked and
secured
4.2 Lighting is adequate and
functioning
4.3 Safety signage and instruction
is available and in good
condition.

66

Buku Sistem Mekanikal MOH v3.indd 66 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

4.4 Fire detector (smoke) are


install and working properly/
in good condition in plant (if
applicable)
4.5 Log Book & Log Sheet are
available and updated
4.6 Noise level is adequately Noise level : <80dB
controlled or hearing
protection provided (if
applicable)
4.7 Ventilation is adequate and Room Temp : <30°C
functioning (if applicable)
4.8 Cylinders are sitting Right Bank Cylinder : _____________
adequately and properly in the Left Bank Cylinder : ______________
right/left bank. Record right
and left bank contain pressure.
4.9 Cylinders on both banks are
Turn-On to regain normal
supply to hospital
4.10 All stage regulators (1st 1st stage regulator for right bank pressure
& 2nd stage regulator) (bar) : __
are functioning and good 2nd stage regulator for right bank pressure
condition without any leakage. (bar) : __
Record right and left bank 1st stage regulator for left bank pressure
contain pressure. (where (bar) : __
applicable) 2nd stage regulator for left bank pressure
(bar) : __
4.11 Auto changeover function and
in good condition
4.12 Non-return valve are install
and in correct operation
4.13 All joints and tailpipes are free
from leakage
4.14 Master/Area alarm panel are
tested and in good working
condition.
4.15 Line pressure relief valve in
good condition
4.16 Ice formation on vaporizer
under supervise (by spraying
water) and pressure building
coil and piping fee from dents
or damage.

67

Buku Sistem Mekanikal MOH v3.indd 67 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

4.17 Liquid low level signal to


Engineering Control Room is
working properly, if applicable.
4.18 Other findings :

4.19 Recommendations :

68

Buku Sistem Mekanikal MOH v3.indd 68 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

3.6.7. VACUUM SYSTEM



SENARAI SEMAK PEMERIKSAAN SISTEM MEKANKAL
KHIDMAT SOKONGAN HOSPITAL
SISTEM BEKALAN GAS PERUBATAN - VACUUM SYSTEM

SEKSYEN OPERASI HOSPITAL


CAWANGAN PERKHIDMATAN
BAHAGIAN PERKHIDMATAN
KEJURUTERAAN
KEMENTERIAN KESIHATAN MALAYSIA

NAME OF HOSPITAL : DATE OF INSPECTION :


_____________________________________ ______________________________________
INSPECTED BY (MoH) : ACCEPTED BY (CC) :
_____________________________________ ______________________________________
(name & signature) (name & signature)

No Item Yes No Remarks


1 Medical Vacuum System (Vacuum Pump)
1.1 Plant Room is locked and
secured
1.2 Lighting is adequate and
functioning
1.3 Safety signage and instruction
is available and in good
condition.
1.4 Fire detector (smoke) are
install and working properly/
in good condition in plant (if
applicable)
1.5 Log Book & Log Sheet are
available and updated
1.6 Noise level is adequately Noise level : <80dB
controlled or hearing
protection provided (if
applicable)
1.7 Ventilation is adequate and Room Temp : <35°C
functioning (if applicable)
1.8 Motor oil is changed
accordingly as per schedule
and tag out.
1.9 Oil filter and air filter are
change accordingly as per
schedule and tag out.

69

Buku Sistem Mekanikal MOH v3.indd 69 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

1.20 All pressure gauges are


functioning and in good
condition
1.21 Motor and pump housing are
clean
1.22 Observe pump motor running Running current (amp) : ___________
accordingly. Record hours run pump flow rate : _____ l/m
for each pump. Ensure no
signs of oil leakage.
1.23 Vacuum pump oil level is
visible between the top and
bottom edges of oil level sight
glass.

1.24 Plant control panels are


functioning and no alarm
conditions. All indicating lights
are functioning.
1.25 All joints and connection is
free from any leakage
2 Medical Vacuum System (Vacuum
Vessel)
All pressure gauges are
functioning and in good
condition
Panel board is functioning and
in normal condition
Vessel drain is functioning
3 Medical Vacuum System (Filter)
Bacteria filter is clean and not
contain liquid
4 Medical Air System (Cylinder
Manifold)
4.1 Plant Room is locked and
secured
4.2 Lighting is adequate and
functioning
4.3 Safety signage and instruction
is available and in good
condition.

70

Buku Sistem Mekanikal MOH v3.indd 70 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

4.4 Plant Room is free from


combustible materials
4.5 Fire detector (smoke)
are installed and working
properly/in good condition in
plant (if applicable)
4.6 Log Book & Log Sheet are
available and updated
4.7 Noise level is adequately Noise level : <80dB
controlled or hearing
protection provided (if
applicable)
4.8 Ventilation is adequate and Room Temp : <35°C
functioning (if applicable)
4.9 Cylinders are properly stored / Right Bank Cylinder : _____________
secured in the right/left bank. Left Bank Cylinder : ______________
Record right and left bank
contain pressure.
4.10 Cylinders on both banks are
Turn-ON to regain normal
supply to hospital
4.11 All stage regulators (1st 1st stage regulator for right bank pressure
& 2nd stage regulator) (bar) : __
are functioning and good 2nd stage regulator for right bank pressure
condition without any leakage. (bar) : __
Record right and left bank 1st stage regulator for left bank pressure
contain pressure. (where (bar) : __
applicable) 2nd stage regulator for left bank pressure
(bar) : __
4.12 Auto changeover is functioning
and in good condition
4.13 Non-return valve are installed
and in correct operation
4.14 All joints and tailpipes are free
from leakage
4.15 Master/Area alarm panel are
tested and in good working
condition.
4.16 Line pressure relief valve in
good condition
4.17 Liquid low level signal to
Engineering Control Room is
working properly, if applicable.

71

Buku Sistem Mekanikal MOH v3.indd 71 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

4.18 Other findings :

4.19 Recommendations :

72

Buku Sistem Mekanikal MOH v3.indd 72 29/08/2019 10:28 AM


ENGINEERING SERVICES DIVISION
MINISTRY OF HEALTH MALAYSIA

3.6.8. ANEASTETHIC GAS SCAVEGING SYSTEM (AGSS)



SENARAI SEMAK PEMERIKSAAN SISTEM MEKANKAL
KHIDMAT SOKONGAN HOSPITAL
SISTEM BEKALAN GAS PERUBATAN - ANEASTETHIC GAS
SCAVEGING SYSTEM (AGSS)
SEKSYEN OPERASI HOSPITAL
CAWANGAN PERKHIDMATAN
BAHAGIAN PERKHIDMATAN
KEJURUTERAAN
KEMENTERIAN KESIHATAN MALAYSIA

NAME OF HOSPITAL : DATE OF INSPECTION :


_____________________________________ ______________________________________
INSPECTED BY (MoH) : ACCEPTED BY (CC) :
_____________________________________ ______________________________________
(name & signature) (name & signature)

No Item Yes No Remarks


1 Medical Air System (Compressor)
1.1 Plant Room is locked and
secured
1.2 Lighting is adequate and
functioning
1.3 Safety signage and instruction
is available and in good
condition.
1.4 Fire detector (smoke) are
install and working properly/
in good condition in plant (if
applicable)
1.5 Log Book & Log Sheet are
available and updated
1.6 Noise level is adequately Noise level : <80dB
controlled or hearing
protection provided (if
applicable)
1.7 Ventilation is adequate and Room Temp : <35°C
functioning (if applicable)
1.8 Pump securing bolts are tight
1.9 All pressure gauges are
functioning and in good
condition
1.1 Motor and pump housing are
clean

73

Buku Sistem Mekanikal MOH v3.indd 73 29/08/2019 10:28 AM


Manual Book of Mechanical System
Medical Gas Pipeline System

1.11 Observe pump motor running Running current (amp) : ___________


accordingly. Record hours run pump flow rate : _____ l/m
for each pump. Ensure no
signs of oil leakage.
1.12 Motor windings and bearings
condition are in good
condition
1.13 Flow-regulating valve and
mesh filter in good condition
1.14 Low flow detector is
functioning
1.15 Plant control panels are
functioning and no alarm
conditions. All indicating lights
are functioning.
1.16 All joints and connection is
free from any leakage
1.17 All indicating light are
functioning
1.18 All joints and connection is
free from any leakage
1.19 Other findings :

1.2 Recommendations :

74

Buku Sistem Mekanikal MOH v3.indd 74 29/08/2019 10:28 AM