You are on page 1of 1

RPR 415A 3-Phase/Single-Phase Reverse Power Relay User Manual

a b c Typical Application Diagram


Reset Button
I
I
Reset button is for resetting the relay after L1
d S1
Generator
L1
tripping. To reset, press Reset button once. L2
L2
S1
Generator
L3 3~
L3 3~
N 415V

Connection Setting
240V
1 2 3 4 5 6 7

a) 3-Phase 4-wire (star) Connection R1


1 2 3 4 5 6 7

S2 S1 R1
S2 S1
In this configuration, L1 and Neutral wire is 8 9 10 11 12 13 14
8 9 10 11 12 13 14
connected directly to the relay.
f e g
Front panel overview While pressing Test button, power up the relay
and hold the button for more than 2 seconds to 3-Phase 4-wire / single-phase system 3-Phase 3 wire system
a – AUX LED set to 3-Phase 4-wire (star) system. After 2
b – DELAY LED seconds, Delay LED on, release the button to
run normally. Technical Data
c – TRIP LED
d – Reverse current setting b) 3-Phase 3-wire (delta) Connection Input Accuracy
e – Delay time setting Protection thresholds : ± 3%
In this configuration, L2 and L3 is stepped down Rated Phase-neutral voltage : 220V to 240V AC
f – TEST Button Hysteresis :1%
to 240V and connected to the relay. The relay is Rated Phase-phase voltage : 380V to 415V AC : 0-0.5s, ± 15%,
g – RESET Button Delay time
internally offset 90º for this connection. Rated frequency : 50 or 60Hz 40ms minimum.
Rated current (In) : 5A
1. General Description >0.5s, ± 3%
While pressing Reset button, power up the relay Burden : < 0.3 VA at In
Measurements : ± 3%
and hold the button for more than 2 seconds to Thermal withstand : 1.2 x Un, 2 x In continuous
RPR 415A relay is a directionally controlled : 1.2 x Un, 10 x In for 3 sec
set to 3-Phase 3-wire (delta) system. After 2
timing relay used to protect AC generators from Power consumption : 3 VA maximum
seconds, Trip LED on, release the button to run Indicators
motoring. When such condition occurs and the
normally.
reverse current exceeded the reverse current Power supply On : Green indicator
setting, Delay LED blinks and countdown Output Contacts
Delay : Red indicator
started. After longer than delay time setting, the Rated voltage : 250V AC Trip : Red indicator
Case Dimensions Contact rating : 5A
relay trips, Trip LED on and trip contact
energised to disconnect the circuit. 71 mm 70 mm Expected electrical life : 100,000 operations at
rated current Environmental Conditions
6
The trip contact will be released once the 20 mm Expected mechanical life : 5 x 10 operations Temperature : -5ºC to +55ºC
reverse current fall below the preset limit. Humidity : 56 days at 93% RH and
However, the TRIP light is latched. Press the 40ºC non-condensing
Setting Ranges
85 mm
45 mm

reset button to reset the light indicator to normal Front Side


Reverse Power : 2% to 20% reverse
Test Button current with 1% hysteresis Mechanical
20 mm Delay time : 0 sec to 20 sec Mounting : DIN rail
Press the test button for 2 seconds to simulate 3-Phase 4-wire (star) or 3-Phase 3-wire (delta) Dimension (mm) : 71(w) x 85(h) x 70(d)
a trip condition. 30 mm 20 mm 20 mm Weight : ~0.3kg

1 2

You might also like