Professional Documents
Culture Documents
SCADA Software
0600-0056-0015 Rev. L ©2013-2015 Watlow Electric Manufacturing, Inc. All rights reserved.
December 2015
TC Table of Contents
Chapter 1: Introduction ..................................................................................3
Additional Resources .................................................................................3
Chapter 2: About Setting up Communications ............................................3
Protocol Drivers .........................................................................................3
Automatic and Manual Configuration .........................................................4
Naming Instruments ...................................................................................5
Saving Settings in Non-Volatile Memory ....................................................5
Using F4T Controllers ................................................................................5
Using EZ-ZONE Controllers with Standard Bus .........................................5
Using EZ-ZONE Controllers with Modbus® ................................................6
Chapter 3: Setup Procedures ...................................................................... 10
Automatically Detect an F4T .................................................................... 10
Automatically Detect a New Standard Bus, 485 or 232 Network.............. 13
Manually Set up or Modify an EZ-ZONE Standard Bus Network ............. 16
Manually Set up or Modify a Modbus® RTU, 485 or 232 Network ............ 19
Manually Set up or Modify a Modbus® TCP Network ............................... 23
Adjust the Displayed Decimals................................................................. 26
Chapter 4: Instrument Reference ................................................................ 28
F4T Instruments ....................................................................................... 28
EZ-ZONE Standard Bus Instruments ....................................................... 29
EZ-ZONE Standard Bus Instrument Views .............................................. 38
EZ-ZONE Modbus® Instruments .............................................................. 42
® ® ®
WATLOW , EZ-ZONE and INTUITION are registered trademarks of Watlow Electric Manufacturing, Incorporated
®
Modbus is a registered trademark of Schneider Automation, Incorporated.
Additional Resources
In addition to this addendum the following resources are available for learning about SpecView and
other products available from Watlow:
• SpecView User Manual—available on the SpecView installation disk and at Watlow.com in the
Download Center’s User Manuals section; Keyword: SpecView.
• SpecView Secrets Video Tutorials—available at Watlow.com in the Download Center’s Training
and Education section.
• SpecView Frequently Asked Questions—available at Watlow.com in the Download Center’s
Training and Education section; Keyword: SpecView.
• SpecView Software Download—the latest version of SpecView is always available at
Watlow.com in the Download Center’s Software and Demos section; Keyword: SpecView.
• SpecView Software Field Upgrade Order Form—guides you through the process of adding
features to a copy of SpecView you already own. Get the form at Watlow.com in the Download
Center’s Software and Demos section; Keyword: SpecView.
Protocol Drivers
SpecView includes support for hundreds of different devices. The protocol drivers included with
SpecView tell it how to communicate with specific devices. You will need to choose the appropriate
driver whenever you want to automatically or manually set up communications between SpecView and
one or more devices.
There are several protocol drivers that support Watlow products. The table below lists these protocol
drivers and the Watlow models supported by each.
If your configuration requires communicating with controllers supported by different protocols via serial
communications ports, each protocol must have its own network connected to SpecView via a separate
communications port. Support for multiple communication ports is an ordering option for SpecView,
and is field upgradeable.
SpecView can automatically detect F4T controllers using Modbus® TCP or Modbus® RTU and EZ-
ZONE controllers using the Standard Bus protocol. When using Modbus® with EZ-ZONE controllers
create the configuration manually.
When you create a project or add instruments to one by automatically detecting controllers, SpecView
prompts you to name the instruments as it adds them. You must name any instruments that you add
manually. You can change an instrument’s name whenever you like. However, changing an instrument’s
name makes logged data associated with the old name inaccessible going forward; it is best to name
instruments up front.
Note! Run the 32-bit version of SpecView for compatibility with the Watlow EZ-ZONE Standard Bus
driver. This driver is not supported by the 64-bit version of SpecView.
For Modbus® RTU specify the controller or gateway’s Modbus® slave address (1 to 247). This is set in
the controller or gateway’s Setup Communications menu. Each controller or gateway on the network
must have a unique Modbus® address.
Decimal Places
Specify zero (0) to display whole numbers for parameters such as process variable and set point. Specify
one (1) to display these parameters with tenths precision, two (2) to display hundredths and so on. Valid
settings range from zero (0) to four (4).
Gateway Offset
Be careful not to set up instruments that attempt to read Modbus® registers that are mapped over by the
configuration of the gateway.
6) Click OK.
3) Launch SpecView.
5) In the Projects
dialog click Test
Comms for New
Project.
7) Click OK.
5) Click OK.
3) In New Instruments
List click to
expand Watlow EZ-
ZONE Standard
Bus.
9) Click Create.
5) Click OK.
3) In New Instruments
List click to
expand the protocol
driver that includes
the instrument you
want to add. See the
table below.
6) In the Add/Rename
Instrument dialog
type a Name for the
instrument.
5) Click OK.
3) In New Instruments
List click to
expand the protocol
driver that includes
the instrument you
want to add. See the
table below.
6) In the Add/Rename
Instrument dialog for
COM Port select
TCP/IP.
7) In the TCP/IP
Address field enter
the IP Address.
8) In Decimal Places
enter the number of
decimals to show.
Note this procedure does not apply to EZ-ZONE controllers communicating with SpecView by Watlow
EZ-ZONE Standard Bus because with that protocol the decimal places are automatically displayed
according to the controller setting.
When communicating with F4T or EZ-ZONE controllers via Modbus® the Decimal Places setting in
SpecView determines the precision with which numbers are displayed; it does not shift the decimal
placement relative to the digits. For older Watlow controllers it is necessary to set the Decimal Places
setting according to the controller setting so that numbers are scaled correctly and not off by orders of
magnitude.
To make the number of decimal places displayed in SpecView match the controller display:
1) Set the decimal
setting in the
controller as desired.
(See the table for
details about each
controller.
5) Click Properties.
7) Click Save.
Note: The possible decimal settings may depend on other controller settings such as the sensor type.
Not all parameters are affected by the decimal places setting.
F4T Instruments
The following sections list the instruments that support F4T controllers.
F4TxxxxxxxxUxxx
F4T Control Loop (setup and monitor control loop 1) 1
U = (1, 2, 3, 4, 7, 8, 9, B or C)
F4TxxxxxxxxUxxx
F4T Control Loop (setup and monitor control loop 2) 2
U = (2, 3, 4, 8, 9 or C)
F4Txxxxxxxx(3, 4 or 9)xxx F4T Control Loop (setup and monitor control loop 3) 3
F4TxxxxxxxxUxxx
F4T Cascade Loop (setup and monitor cascade loop 1) 1
U = (6, 7, 8, 9, A. B or C)
F4Txxxxxxxx(A, B or C)xxx F4T Cascade Loop (setup and monitor cascade loop 2) 2
CAUTION: This feature may not be available for all instruments, so take
the appropriate precautions to insure fail-safe system operation.
PM Zone
Auxiliary Input
PM Function Blocks
PM Profiling
The RM Zone, Control Loop, Stand Alone and RM Limit, Auxiliary Input, Single Current Input and RMC
Profile Operation instruments and a sample of the four Digital I/O instruments are illustrated below.
RM Zone
Control Loop
Auxiliary Input
Digital I/O
ST Controller
ST Profiling