Professional Documents
Culture Documents
RHE/2_15_0020
Draft for Public Comment For comment/vote - Action Due Date: 2015/03/23
Form 36
DPC: 15 / 30297495 DC
Latest date for receipt of comments: 25 March 2015 Project No. 2014/00278
Responsible committee: RHE/2 Ventilation for buildings, heating and hot water services
Please notify the secretary if you are aware of any keywords that might assist in classifying or identifying the standard or if the
content of this standard
i) has any issues related to 3rd party IPR, patent or copyright
ii) affects other national standard(s)
iii) requires additional national guidance or information
WARNING: THIS IS A DRAFT AND MUST NOT BE REGARDED OR USED AS A BRITISH STANDARD.
THIS DRAFT IS NOT CURRENT BEYOND 25 March 2015
This draft is issued to allow comments from interested parties; all comments will be given consideration prior to publication. No
acknowledgement will normally be sent. See overleaf for information on the submission of comments.
No copying is allowed, in any form, without prior written permission from BSI except as permitted under the Copyright, Designs
and Patent Act 1988 or for circulation within a nominating organization for briefing purposes. Electronic circulation is limited to
dissemination by e-mail within such an organization by committee members.
Further copies of this draft may be purchased from BSI Shop http://shop.bsigroup.com
or from BSI Customer Services, Tel: +44(0) 20 8996 9001 or email cservices@bsigroup.com.
British, International and foreign standards are also available from BSI Customer Services.
Information on the co-operating organizations represented on the committees referenced above may be obtained from
http://standardsdevelopment.bsigroup.com
Even if this draft standard is not approved by the UK, if it receives the necessary support in Europe, the UK will be obliged to
publish the official English Language text unchanged as a British Standard and to withdraw any conflicting standard.
UK Vote
Please indicate whether you consider the UK should submit a negative (with reasons) or positive vote on this draft.
Submission of Comments
- The guidance given below is intended to ensure that all comments receive efficient and appropriate attention by the responsible
BSI committee. Annotated drafts are not acceptable and will be rejected.
- All comments must be submitted, preferably electronically, to the Responsible Committee Secretary at the address given on the
front cover. Comments should be compatible with version 6.0 or version 97 of Microsoft Word for Windows, if possible;
otherwise comments in ASCII text format are acceptable. Any comments not submitted electronically should still adhere
to these format requirements.
- All comments submitted should be presented as given in the example below. Further information on submitting comments and
how to obtain a blank electronic version of a comment form are available from the BSI website at:
http://drafts.bsigroup.com/
Template for comments and secretariat observations Date: xx/xx/20xx Document: ISO/DIS xxxx
EXAMPLE
ONLY
3.1
6.4
Definition 1
Paragraph 2
ed
te
Definition is ambiguous and needs clarifying. Amend to read '...so that the mains connector
Microsoft and MS-DOS are registered trademarks, and Windows is a trademark of Microsoft Corporation.
EUROPEAN STANDARD DRAFT
NORME EUROPÉENNE prEN 16798-7
EUROPÄISCHE NORM
November 2014
English Version
Performance énergétique des bâtiments - Partie 7: Energieeffizienz von Gebäuden - Teil 7: Modul M5-1, M 5-5,
Ventilation des bâtiments - Modules M5-1, M5-5, M5-6, M5- M 5-6, M 5-8 - Berechnungsmethoden zur Bestimmung der
8 - Méthodes de calcul pour la détermination des débits Luftvolumenströme in Gebäuden inklusive Infiltration
d'air dans les bâtiments y compris les infiltrations
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 156.
If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United
Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.
Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.
© 2014 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 16798-7:2014 E
worldwide for CEN national Members.
prEN 16798-7:2014 (E)
Contents Page
Foreword ..............................................................................................................................................................3
Introduction .........................................................................................................................................................4
1 Scope............................................................................................................................................................5
2 Normative references .................................................................................................................................6
3 Terms and definitions .................................................................................................................................7
4 Symbols and abbreviations .......................................................................................................................8
4.1 Symbols .......................................................................................................................................................8
4.2 Subscripts ................................................................................................................................................. 10
5 Description of the methods..................................................................................................................... 11
5.1 Output of the methods............................................................................................................................. 11
5.2 Methods..................................................................................................................................................... 11
6 Method 1 – Determination of air flow rates based on detailed building characteristics .................. 12
6.1 Output data ............................................................................................................................................... 12
6.2 Calculation time steps ............................................................................................................................. 12
6.3 Input data .................................................................................................................................................. 13
6.4 Calculation procedure ............................................................................................................................. 18
7 Method 2 – Determination of air flow rates based on statistical approach ....................................... 30
7.1 Output data ............................................................................................................................................... 30
7.2 Calculation time steps ............................................................................................................................. 30
7.3 Input data .................................................................................................................................................. 30
7.4 Calculation procedure ............................................................................................................................. 31
8 Quality control .......................................................................................................................................... 31
9 Compliance check .................................................................................................................................... 32
Annex A (normative) Template for input data and choices ......................................................................... 33
Annex B (informative) Default input Data ...................................................................................................... 40
Bibliography ..................................................................................................................................................... 47
2
prEN 16798-7:2014 (E)
Foreword
This document (prEN 16798-7:2014) has been prepared by Technical Committee CEN/TC 156 “Energy
performance of buildings related TC”, the secretariat of which is held by BSI.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association.
3
prEN 16798-7:2014 (E)
Introduction
This European Standard is part of a set of standards developed to support EPBD directive implementation,
hereafter called "EPB standards".
EPB standards deal with energy performance calculation and other related aspects (like system sizing) to
provide the building services considered in the EPBD directive.
TC 156 deals with ventilation and air conditioning systems in buildings. Subjects covered by TC 156 are:
a) energy performance calculation for ventilation, air conditioning and cooling systems;
This standard replaces EN 15242, which was developed during the first EPBD mandate and was published in
2007.
The revision for inclusion in the second mandate package was performed by CEN TC 156 WG 21.
The revision includes changes:
rearrangement of content versus EN 15241:2007, in order to better fit in the modular structure given in
prEN 15603:2014. This standard is restricted to emission and control of the ventilation air flow rates (M5-
5)
clarification of possibility to use 2 methods to calculate the airflow rates: method 1 based on detailed
building characteristics; and method 2 using a statistical approach complying with specific rules;
in method 1, addition of several options for the calculation of the airflow rates through windows, including
cross-ventilation
formatting according to the new rules set in prCEN/TS 16629 Detailed Technical Rules
4
prEN 16798-7:2014 (E)
1 Scope
This European Standard describes the methods to calculate the ventilation air flow rates for buildings
Passive duct ventilation systems for residential and low-rise non-residential buildings;
Combustion appliances;
This European Standard is applicable to hybrid systems combining mechanical and passive duct ventilation
systems in residential and low-rise non-residential buildings.
This European Standard applies to buildings smaller than 100 m and rooms where vertical air temperature
difference is smaller than 15 K.
the air flow rates required to be distributed by the mechanical ventilation system, if present.
The definition of ventilation and airtightness requirements (as indoor air quality, heating and cooling, safety,
fire protection…) is not covered by this standard.
The following information can be found in other standards and technical reports:
Table 1 shows the relative position of this standard within the EN EPB package of standards.
5
prEN 16798-7:2014 (E)
Descriptions
Descriptions
PV, wind, ..
Ventilation
Humidifi
Lighting
Heating
Cooling
control
cation
sub1 M1 sub1 M2 sub1 M3 M4 M5 M6 M7 M8 M9 M10 M11
1 General 1 General 1 General
Common terms and
definitions; Building Energy
2 2 2 Needs
symbols, units and Needs
subscripts
(Free) Indoor
Maximum Load
3 Applications 3 Conditions without 3
and Power
Systems
Ways to Express Ways to Express Ways to Express
4 Energy 4 Energy 4 Energy
Performance Performance Performance
Building Functions
Heat Transfer by Emission &
5 and Building 5 Transmission
5 control
Boundaries
Building Occupancy Heat Transfer by
Distribution &
6 and Operating 6 Infiltration and 6
control
Conditions Ventilation
Aggregation of
Energy Services
7 7 Internal Heat Gains 7 Storage & control
and Energy
Carriers
Generation &
8 Building Partitioning 8 Solar Heat Gains 8
control
Load dispatching
Calculated Energy Building Dynamics
9 Performance
9 (thermal mass)
9 and operating
conditions
Measured Energy Measured Energy Measured Energy
10 10 10
Performance Performance Performance
11 Inspection 11 Inspection 11 Inspection
Ways to Express
12 12 -- 12 BMS
Indoor Comfort
External
13 Environment
Conditions
Economic
14 Calculation
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
prEN15603:2013 Energy performance of buildings – Overall energy use and definition of energy ratings.
6
prEN 16798-7:2014 (E)
EN 13141-5, Ventilation for buildings — Performance testing of components/products for residential ventilation
— Part 5: Cowls and roof outlet terminal devices
3.1
ventilation zone
conditioned space which can be considered as air flow independent from other conditioned spaces (i.e. the air
leakages between two adjacent zones are sufficiently low to be neglected, and there is no possibility of air
transfer between two zones)
3.2
building height
height of the building from the entrance ground level to the roof top level
3.3
building envelope airtightness
overall leakage air flow rate for a given test pressure difference across building
3.4
building volume
volume within internal outdoor walls of the purposely conditioned space of the building (or part of the building)
Note 1 to entry: This generally includes neither the attic, nor the basement, nor any additional structural annex of the
building.
3.5
zone air temperature
average air temperature in the zone
3.6
iterative calculation
calculation method that requires a mathematical solver to solve an equation by iteration
3.7
direct calculation
calculation method that can be applied without iterations
3.8
vent
opening intended to act as an air transfer device
3.9
reference wind speed at site
wind speed at site, at a height of 10 m, in undisturbed shielding conditions
3.10
shielding
effect classified according to the relative height, width and distance of relevant obstacle(s) in relation to the
building
7
prEN 16798-7:2014 (E)
3.11
airing
natural ventilation by window opening
3.12
passive duct ventilation system
natural ventilation by means of a duct mounted vertically or mounted with an angle of less than 45° or less
with the vertical
3.13
single-sided ventilation
airing with windows located on only one side of the ventilation zone. The projections on the horizontal plane of
the normal vectors of the windows are within a 90° angle or less
3.14
cross-ventilation
airing with windows located on several sides of the ventilation zone. The projections on the horizontal plane of
the normal vectors of the windows are not within a 90° angle or less
3.15
transverse (non-transverse) zone
zone that can (cannot) be cross-ventilated
3.16
Mechanical ventilation
ventilation with the aid of powered air movement components.
4.1 Symbols
For the purposes of this European Standard, the symbols given in prEN15603:2013 and EN 12792 and the
specific symbols listed in Table 2 apply.
A Area m²
Aw Window opening free area m²
Ccowl;tot Pressure at roof level taking into account the height [-]
of the cowl above the roof level
n
Clea Leakage coefficient of the ventilation zone m3/(h∙Pa )
3 n
Clea;fde Leakage coefficient of the façades of the ventilation m /(h∙Pa )
zone
n
Clea;path,i Flow coefficient of leakage "i" m3/(h∙Pa )
8
prEN 16798-7:2014 (E)
P Pressure Pa
T Absolute temperature K
9
prEN 16798-7:2014 (E)
4.2 Subscripts
For the purposes of this European Standard, the subscripts given in prEN 15603:2013, EN 12792 and the
specific subscripts listed in Table 3 apply.
Table 3 — Subscripts
10
prEN 16798-7:2014 (E)
This standard gives the air flow rates entering and leaving each ventilation zone in a building including
infiltration for the following given operating conditions:
Air flow rates required to be supplied to or extracted from the ventilation zone;
Air flow rates entering or leaving the ventilation zone through the mechanical system;
Conventionally, air entering the ventilation zone is counted positive; air leaving is counted negative.
The time step of the output for energy calculation procedures can be:
hourly,
monthly.
Depending on the application of the standard and time-step of the input data.
5.2 Methods
method 1 estimates the air flow rates based on detailed building characteristics;
method 2 specifies rules to fulfil to apply a statistical approach to be defined at national level for the
determination of air flow rates including infiltration. It may be based on calculations with method 1 or on
measurements.
All equations of method 1 are given for a single ventilation zone without sub-divisions into elementary spaces.
They may be applied to elementary spaces if:
additional equations and rules are defined to characterize the airflows between the elementary spaces.
Selection between method 1 or method 2 is defined at national level. Selection shall be based on the
availability and relevance of a statistical approach in the specific national context for the buildings considered.
11
prEN 16798-7:2014 (E)
Intended
Name Symbol Unit Range Varying
destination
Airflow entering through window opening qV;arg;in 3
m /h 0…∞ M2-6 Yes
Extract air flow rate required at the air terminal devices of qV;ETA;dis;req 3
m /h -∞…0 M5-6 Yes
the mechanical ventilation system
Airflow entering through envelope leakage qV;lea;in 3
m /h 0…∞ M2-6 Yes
Supply air flow rate required at the air terminal devices of qV;SUP;dis;req 3
m /h 0…∞ M5-6 Yes
the mechanical ventilation system
Airflow entering through vents (openings in the external qV;vent;in 3
m /h 0…∞ M2-6 Yes
envelope)
Airflow leaving through vents (openings in the external qV;vent;out 3
m /h -∞…0 M2-6 Yes
envelope)
Maximum design required supply air volume flow rate for q 3
ventilation zone V;SUP;dis;max;des m /h M5-6 No
Design supply outdoor air volume flow rate for ventilation qV;ODA;req;des 3
m /h M5-6 No
zone
Required ventilation zone supply air temperature for the ϑ SUP;dis;out;req °C 0...∞ M5-6 Yes
case of SUP_TEMP_CTRL = LOAD_COMP
The method described in Clause 6 is suitable for the following calculation time steps:
Hourly
Monthly
For this method, the output time step is the same as the input time-step.
12
prEN 16798-7:2014 (E)
This method does not take into account any dynamic effect.
It may be used to obtain instantaneous air flow rates for the specific inputs assuming steady-state conditions.
Input data about products that are required for the calculation described in this standard shall be the data
supplied by the manufacturer if they are declared according to relevant EN product standards.
If no such data from the manufacturer is available or if the required data are not product data, default values
are given in Annex B.
Default informative data given in Annex B may be replaced by other data, for example nationally determined
data. To ensure consistency with this calculation method, input data shall be presented according to the
template given in normative Annex A.
NOTE Compliance with the template given in Annex A does not guarantee that the new data set is consistent.
Not applicable.
The product data shall be the value declared by the manufacturer according to certified measurements
performed according to the relevant product standards. If values declared by the manufacturer are not
available, then default values are given in informative Annex B.
Declared values are given at standard reference test conditions. Declared values shall be adjusted according
to actual operating conditions. This adjustment is part of the calculation procedure. This applies both to
standard test values and to field test measurements.
Required technical data for this calculation procedure are listed in Table 5.
13
prEN 16798-7:2014 (E)
The distribution system correction factor fsys (≥1) is a correction factor that takes into account the uncertainty
in the delivered air flow rate compared to the desired air flow rate.
Code Meaning
BALANCED Balanced mechanical system with supply and extract flow
EXTRACT Extract air system only
SUPPLY Supply air system only
NATURAL Natural ventilation, no mechanical system
14
prEN 16798-7:2014 (E)
Computed Validity
Characteristics Symbol Unit Ref. Varying
Unit interval
Equivalent area of the air terminal device AATD cm² 0..100 Local No
Surface area of the façades of the ventilation zone Afde m² 0…∞ Local No
Reference area of the envelope airtightness index Alea m² 0…∞ EN 13829 No
qv;∆Plea;ref (depends on national context)
Surface area of the roof of the ventilation zone Aroof m² 0…∞ Local No
2
Cross-sectional area of the passive duct As;pdu m 0…2 Local No
Area of vents Avent cm² 0..100 Local No
2
Maximum window opening area Aw;max m 0…∞ Local No
Pressure coefficient when the cowl is installed at roof Cp;cowl;roof - -1…1 Local No
height (see Annex B.1.3.5)
Wind pressure coefficient for air flow path "i" Cp;path,i - 0…1 Local Yes
Mid-height of the air flow path "i" relative to ventilation
hpath,i m 0…100 Local No
zone floor level
Height of passive duct hpdu m 0…100 Local No
Free area height of the window "i" hw;fa,i m 0…100 Local Yes
Mid-height of the window "i" relative to ventilation zone
hw;path,i m 0…100 Local No
floor level
Mid-height of the part "j" of window "i" relative to
hw;path,i,j m 0…100 Local No
ventilation zone floor level
Height of ventilation zone hz m 0…100 Local No
Air flow exponent for leaks nlea - 0,5…1,0 Local No
Number of windows Nw - 0…∞ Local No
Flow exponent of window nw - 0.5…1 Local No
Number of window divisions Nw;div - 1…∞ Local No
Design zone cooling need to be covered by the QC;des kWh 0…∞ M4-3 Nn
mechanical ventilation system
Design zone heating need to be covered by the QH;des kWh 0…∞ M3-3 No
mechanical ventilation system
3
Envelope airtightness index of the ventilation zone qV;∆Plea;ref m /h 0…∞ EN 13829 No
Correction of cowl pressure factor accounting for height
∆Ccowl;height - -1…1 Local No
above roof level (see Annex B.1.3.6)
Difference of wind pressure coefficients between the
∆Cp - 0…2 Local No
windward and leeward sides
Window orientation (0° = South, 90°= West, 270° = East,
αw - 0°…360° Local No
180°= North)
Window angle (0° = horizontal, 90° = vertical) βw - 0°…90° Local No
15
prEN 16798-7:2014 (E)
6.3.2.2 Control
VENT_OAFLOW_CTRL
This identifier indicates how the outdoor air flow is controlled, see Table 8.
ON/OFF_TIME On/off time control On/off control depending on a given time program (schedule), which has been
programmed in advance by an operator or occupant and is acting on a zone
level device
MULTI_STAGE_TIME Multistage time control Multistage control depending on a given time program (schedule), which has
been programmed in advance by an operator or occupant and is acting on a
zone level device
VAR_SENS_PEOPLE Continuous control based on Continuous feed-forward control based on an sensor which counts or estimates
the number of people the number of people in the zone
VAR_SENS_IAQ Continuous control based on Continuous closed loop control based on an IAQ sensor (e.g. CO2 or VOC
an IAQ sensor sensor)
SUP_TEMP_CTRL: This identifier indicates how the supply temperature is controlled, see Table 9.
Code Meaning
NO_CTRL No supply temperature control
CONST Constant supply air temperature
ODA_COMP Variable set point with outdoor temperature compensation
LOAD_COMP Variable set point with load dependent compensation
SUP_FLW_CTRL: This identifier indicates how the supply flowrate is controlled, see Table 10.
Code Meaning
ODA Flow rate controlled according to outdoor air requirements only
LOAD Flow rate controlled according to heating/cooling load with a minimum set by outdoor air requirements
16
prEN 16798-7:2014 (E)
Origin
Name Symbol Unit Range Varying
Module
Combustion appliance heating fuel input power Ph;fi kW 0…∞ M3-3 Yes
Ventilation zone cooling need to be covered by the QC;req kWh 0…∞ M2-2 Yes
mechanical ventilation system
Ventilation zone heating need to be covered by the QH;req kWh 0…∞ M2-2 Yes
mechanical ventilation system
Thermal zone set point temperature ϑzt;set °C 0…50 M2-2 yes
3
Extract volume flow from a ventilation zone qV;ETA;dis m /h -∞…0 M5-6 Yes
3
Duct leakage volume flow extracted from a ventilation zone qV;lea;ETA;dis m /h -∞…0 M5-6 Yes
3
Duct leakage volume flow going to a ventilation zone qV;lea;SUP;dis m /h 0…∞ M5-6 Yes
Required design air flow rate to be supplied to or extracted
3
from the ventilation zone assuming a ventilation effectiveness qV;ODA;req;des m /h 0…∞ M1-6 Yes
of 1 (perfect mixing).
3
Supply volume flow rate going to ventilation zone qV;SUP;dis m /h 0…∞ M5-6 Yes
Ratio of window area to maximum window opening area Rw;arg - 0,5 Local Yes
Shielding class (see B.1.3.2) SHIELD_CLASS - List Local Yes
External temperature Te K 223…323 M1-13 Yes
Terrain class (see B.1.4.1) TER_CLASS - List Local No
Ventilation zone temperature Tz K 273…323 M2-2 Yes
17
prEN 16798-7:2014 (E)
Hourly
Monthly
For this method, the output time step is the same as the input time-step.
This method does not take into account any dynamic effect.
It may be used to obtain instantaneous air flow rates for the specific inputs assuming steady-state conditions.
Tref
ρT = ⋅ ρa;ref (1)
T
The meteorological wind speed at 10 m is corrected as follows to obtain the reference wind speed at site:
18
prEN 16798-7:2014 (E)
The pressure coefficients shall be determined for each air flow path taking into account:
The pressure difference between the outside and the inside for air flow path "i" at its level is given by:
2 T
pe;path,i = ρa,ref 0,5 × Cp;path,i ⋅ u site - hpath,i ⋅ g ⋅ e;ref (4)
Te
Te;ref
p z;path,i = p z;ref − ρa,ref ⋅ hpath,i ⋅ g ⋅ (5)
Tz
External pressure at the floor level of the ventilation zone is taken equal to 0.
The required supply air temperature provided to the ventilation zone in case of local load dependent control is
given by:
if SUP_TEMP_CTRL = LOAD_COMP
QH;req QC;req
ϑSUP;dis;out;req = ϑzt;set + − (6)
ρ a ca ⋅ q V;SUP;dis ⋅ t ci ρ a ca ⋅ q V;SUP;dis ⋅ t ci
with
QH;req kWh heating energy to be supplied to the thermal zone by the ventilation system at the
current time step;
QC;req kWh heating energy to be extracted from the thermal zone by the ventilation system at
the current time step;
NOTE 2: It is assumed that either the required heating or the required cooling energy is 0.
19
prEN 16798-7:2014 (E)
NOTE 3: This calculation requires that the thermal and ventilation zone are identical.
6.4.3.1 General
All equations of Clause 6 apply to a single ventilation zone the pressure of which at floor level can be
considered as homogenous and equal to pz;ref. The technical report CEN/TR 16798-8 gives guidance to
assess the relevance of this assumption.
Establish the equations giving the air flow rates for a given internal reference pressure through:
Combustion appliances
Windows opening
Vents, i.e., openings in the external envelope intended for ventilation (other than windows)
Envelope leakage
Calculate the internal reference pressure for the ventilation zone pz;ref balancing mass air flow rates
leaving and entering the ventilation zone
Calculate the air flow rates for this internal reference pressure
If the ventilation zone is divided into elementary spaces, equations of 6.4.3 shall be applied for each
elementary space and the air flow rates between elementary spaces shall be taken into account in the mass
balance equations of the airflows. Additional information is given in the technical report CEN/TR 16798-8 to
consider this case.
6.4.3.2.1 Required outdoor ventilation air flow rates for energy calculations
f ctrl ⋅ f sys
q V;ODA;req = ⋅ q V;ODA;req;des (7)
εV
with
fsys - the uncertainty in the delivered air flow rate compared to the desired air flow
rate;
3
qV;ODA;req;des m /h design outdoor air flow rate.
20
prEN 16798-7:2014 (E)
If VENT_OAFLOW_CTRL = CONST_OA_FLOW
fctrl = 1 (8)
if focc > 0
fctrl = 1
else
fctrl = 0 (10)
else
with
fsens - correction factor for the sensor quality. Annex B gives default values.
For monthly calculations fctrl shall be taken from tabled values. The technical report CEN/TR 16798-8 gives
additional information to estimate fctrl for various control options.
If VENT_SYS_OP= BALANCED
If VENT_SYS_OP=EXHAUST
qV;SUP;req = 0 (14)
21
prEN 16798-7:2014 (E)
If VENT_SYS_OP=SUPPLY
q V;ETA;req = 0 (17)
If VENT_SYS_OP=NATURAL
qV;SUP;req = 0 (18)
q V;ETA;req = 0 (19)
6.4.3.2.3 Mechanical air flow rates to the ventilation zone required to be distributed through air
terminal devices
The mechanical air flow rates required to be supplied to the ventilation zone through the air terminal devices
of the distribution system are calculated by:
If SUP_FLW_CTRL = ODA
else
QH;req QC;req
q V;SUP;dis;req = f op;V ⋅ max ; ; q V;SUP;req (22)
ρ a ca (ϑSUP;dis;out − Tz + T0;abs ) t ci ρ a ca (Tz − T0;abs − ϑSUP;dis;out ) t ci
if VENT_SYS_OP = BALANCED
else
qV;ETA;dis;req = 0 (24a)
The maximum design mechanical air flow rates required to be supplied to the ventilation zone through the air
terminal devices of the distribution system are calculated by:
QH;des QC;des
q V;SUP;dis;max.des = max ; ; q V;ODA;req;des (25)
ρ a ca (ϑSUP;dis;out − Tz + T0;abs ) t ci ρ a ca (Tz − T0;abs − ϑSUP;dis;out ) t ci
The supply outdoor air flow rate provided to the ventilation zone is given by:
22
prEN 16798-7:2014 (E)
6.4.3.3.1 General
The pressure loss at an internal air terminal device shall be characterised taking into account the total air flow
rate passing through the device:
1
q V;pdu nATD
∆pATD = − sign(q V;pdu )⋅ (27)
CATD
or, for externally mounted air transfer devices, by the test results according to EN 13141-1 and EN 13141-2 if
applicable.
The coefficient of the air terminal device may be calculated from the equivalent area AATD value, according to
EN 13141-1 and EN 13141-2, as follows:
0,5 nATD −0 , 5
3600 2 1
C ATD = × CD;ATD ⋅ AATD ⋅
⋅
(28)
10000 ρ a;ref ∆pATD;ref
A method shall be defined at national level to calculate the pressure drop through the ductwork ∆ppdu from the
inside space to the outside near the cowl or passive duct outlet.
The pressure drop of linear ducts, take-off and singularities shall be calculated. If they are unknown, they may
be estimated according to CR 14378.
6.4.3.3.4 Cowl characteristics and corrections according to roof angle and position and height of
the cowl
Its pressure factor Ccowl which is a function of vertical wind approach angle and air speed in the duct.
The pressure factor taken at the roof outlet or cowl Ccowl;tot is given by:
23
prEN 16798-7:2014 (E)
B.1.3.5 and B.1.3.6 give default values for Cp;roof;cowl and ∆Ccowl;height respectively.
If usite = 0
2
1 qV;pdu
∆pcowl = − × sign(qV;pdu ) ⋅ ζ cowl ⋅ ρ a;ref ⋅ (30)
2 3600 ⋅ As;pdu
Else
1
∆p cowl = − × sign(q V;pdu ) ⋅ C cowl;tot ⋅ ρ a;ref ⋅ u site
2
(31)
2
q V;pdu;out = 0 (34)
Else
q V;pdu;in = 0 (35)
Conditions shall be defined at national level to switch to mechanical ventilation. These may be based on wind
velocity and temperature difference between the elementary spaces considered and the outside.
The additional outside air flow rate needed for the operation of the combustion appliance qv;comb shall be
calculated from the following:
fop;comb = 1 (38)
24
prEN 16798-7:2014 (E)
qV;comb;in = 0 (39)
The air temperature associated with qV;comb;out is the ventilation zone temperature.
fop;comb = 0 (41)
6.4.3.5.1 General
The air flow rates due to windows opening may be calculated using any of the following options:
Nw
Aw;tot = ∑ Aw (43)
i =1
With this option, the air flow rate entering the ventilation zone through windows opening is:
ρ a;ref
qV;arg;in = f ⋅q (44)
ρ a;e arg V;ODA;req
The air flow rate leaving the ventilation zone through windows opening is:
ρ a;ref
qV;arg;out = − f ⋅q (45)
ρ a;z arg V;ODA;req
25
prEN 16798-7:2014 (E)
6.4.3.5.4 Direct calculation of ventilation through windows using wind velocity and temperature
difference as inputs
6.4.3.5.4.1 General
With this option, the calculation depends whether the singled-sided ventilation occurs or not.
Both for single-sided and cross-ventilation, the wind speed used to calculate the air flow rates due to airing
may differ from the meteorological wind speed.
The useful height for stack effect for airing is given by:
h h
hw;st = max i =1 to N w hw;path,i + w;fa,i − min i =1 to N w hw;path,i − w;fa,i (46)
2 2
The air flow rate entering the ventilation zone through windows opening is:
ρ a;ref Aw;tot
⋅ (Ct + C w ⋅ u 2 + Cst ⋅ hw;st ⋅ abs (Tz − Te ))
0,5
qV;arg;in = 3600 × ⋅ (47)
ρ a;e 2 10
The air flow rate leaving the ventilation zone through windows opening is:
ρ a;ref Aw;tot
⋅ (Ct + C w ⋅ u 2 + Cst ⋅ hw;st ⋅ abs (Tz − Te ))
0,5
qV;arg;out = −3600 × ⋅ (48)
ρ a;z 2 10
6.4.3.5.4.3 Cross-ventilation
The air flow rate entering the ventilation zone through windows opening is:
0.5
2
qV;arg;in
ρ
= 3600 × a;ref
(
⋅ CD;w ⋅ Aw;cros ⋅ u10 ⋅ (∆Cp )
0,5 2
+ )
Aw;tot 0,5
⋅ (Cst ⋅ hw;st ⋅ abs (Tz − Te )) (49)
ρ a;e 2
The air flow rate leaving the ventilation zone through windows opening is:
0.5
2
qV;arg;out
ρ
= −3600 × a;ref
(
⋅ CD;w ⋅ Aw;cros ⋅ u10 ⋅ (∆Cp )
0,5 2
+ )
Aw;tot 0,5
⋅ (Cst ⋅ hw;st ⋅ abs (Tz − Te )) (50)
ρ a;e 2
For i = 1 to 2
For j = 1 to 4
Aw;ori,j = 0
26
prEN 16798-7:2014 (E)
For k = 1 to Nw,
End For k
End For j
1 1
Aw;cros,i = × ∑ (53)
4 j =1to 4 1 1
+
A w;ori, j >0
2
Aw;ori, j (A w;tot − Aw;ori, j )
2
End For i
6.4.3.5.5 Iterative calculation of ventilation through windows using internal pressure as input
With this option, the air flow rate for each part "j" of a window "i" (delimited by a division, see Nw;div) is given
by:
C w; path,i
⋅ sign(∆pw;div;path,i , j ) ⋅ ∆pw;div;path,i , j
nw
qV ;w;div;path,i,j = Rw;arg ⋅ (55)
N w;div + 1
nw
2
C w; path,i = 3600 × CD;w ⋅ Aw,i ⋅ (56)
ρ a;ref
The air flow rate entering the ventilation zone through windows opening is the sum of positive airflows through
the windows parts:
The air flow rate leaving the ventilation zone through windows opening is the sum of negative air flow rates
through the windows parts:
27
prEN 16798-7:2014 (E)
6.4.3.6.1 General
The air flow rates through leaks shall be calculated iteratively solving for the internal reference pressure.
The vents shall be distributed to obtain a set of flow characteristics (Cvent;path,i) for given couples of heights
and wind pressure coefficient values (h, Cp). This distribution shall be done at elementary space level if
airflows between elementary spaces of the ventilation zone are considered. Default values are given in
B.1.3.13.
The envelope leakage shall be distributed to obtain a set of leakage coefficients (Clea;path,i) for given couples
of heights and wind pressure coefficient values (h, Cp). This distribution shall be done at elementary space
level if airflows between elementary spaces of the ventilation zone are considered. Default values are given in
B.1.3.17.
6.4.3.6.4 Airflow through vents (openings in the external envelope intended for ventilation (other
than windows)
For each couple "i" of height and wind pressure coefficient associated with vents, the air flow rate is given
either by:
or, for externally mounted air transfer devices, by the test results according to EN 13141-1 and EN 13141-2 if
applicable.
The coefficient of the vent may be calculated from the equivalent area Avent value, according to EN 13141-1
and EN 13141-2, as follows:
0,5 nvent −0 , 5
3600 2 1
Cvent = × CD;vent ⋅ Avent ⋅
⋅
(61)
10000 ρ a;ref ∆pvent;ref
The air flow rate entering the ventilation zone through vents is the sum of positive airflows through the vents:
qv;vent;in = ∑q v;vent;path,i
qv;vent;path,i >0
(62)
The air flow rate leaving the ventilation zone through vents is the sum of negative airflows through the vents:
qv;vent;out = ∑q v;vent;path,i
qv;vent;path,i <0
(63)
For each couple "i" of height and wind pressure coefficient used to characterize the envelope leakage
distribution, the air flow rate is given by:
28
prEN 16798-7:2014 (E)
The air flow rate entering the ventilation zone through leaks is the sum of positive airflows through the leaks:
q V;lea;in = ∑q V;lea;path,i
qV;lea;path >0
(65)
The air flow rate leaving the ventilation zone through leaks is the sum of negative airflows through the leaks:
qV;lea;out = ∑q V;lea;path,i
qv;lea;path <0
(66)
If applicable, other airflows supplied to or extracted from the ventilation zone may be taken into account.
A volume air flow rate q shall be converted to a mass air flow rate qm with the following equation:
If q ≥ 0 , qm = ρ a;e ⋅ q (67)
The internal reference pressure used to calculate the mass air flow rates shall be calculated by solving the
following mass balance equation:,
The volumetric or mass air flow rate entering or leaving the ventilation zone through each path described in
6.1 can be obtained by substituting the calculated pz;ref in the relevant equations.
6.4.3.10 Total air flow rate entering and leaving the ventilation zone
qm;V;tot;in
q V;tot;in = (70)
ρ a;e
29
prEN 16798-7:2014 (E)
qm;V;tot;out
q V;tot;out = (71)
ρ a;z
The output data are the total air flow rates entering and leaving the ventilation zone. These air flow rates may
be divided into air flow rates through:
Combustion appliances
Windows opening
Vents, i.e., openings in the external envelope intended for ventilation (other than windows)
Envelope leakage
Air entering the ventilation zone or a given elementary space is counted positive (air leaving is counted
negative).
Monthly
Hourly.
The calculation time steps shall be consistent with the scope and limits of the statistical approach.
The input data are to be defined at national level. The definition of the input data shall be based on a statistical
analysis showing the correlation between the input and output data and the relevance of the proposed method.
The scope shall be specified (for example, detached houses, specified ventilation systems, etc.),
All specific assumptions (such as indoor temperature) or data (for example climate) shall be clearly
described,
The set of cases used for the statistical analysis shall be clearly described,
The input data and assumptions shall be described, including user patterns;
30
prEN 16798-7:2014 (E)
The results of the statistical approach shall be compared to the reference ones for the set of cases taken
into account in the statistical analysis
If the analysis is based on method 1, the remaining input data shall be all or a subset of the ones
described in method 1. For the input data of method 1 not taken into account, the default value used shall be
specified.
The body who has derived the method shall give in a publically available report with two parts:
If the basis for the statistical approach is the calculation of air flow rates through method 1, it shall be possible
to redo and check the calculation.
If the basis for the statistical approach is the field or laboratory measurement of air flow rates, the
measurement data shall be provided.
Definition of the cases taken into account for the statistical analysis, including:
Default values for the input data not kept in the statistical method;
Range of values for the input data kept in the statistical approach;
8 Quality control
The calculation report shall:
state the time step, methods and options used for the calculation
31
prEN 16798-7:2014 (E)
besides the output values of Table 4 transferred to other modules, include the values of the total volume
air flow rates are qv;tot;in and qv;tot;out
in method 1, give an estimate of the convergence of the mass balance, for instance with normalized
residuals of equation (61)
checking that all inputs and outputs are in their expected range
in method 1, checking that the mass balance is obtained with a reasonable degree of convergence
9 Compliance check
Compliance check performed in the context of an energy performance regulation may be based on checks
performed on a selection of input data, in particular those for which a minimum requirement is set at national
level, and/or those that have a significant weight on the calculated energy use.
32
prEN 16798-7:2014 (E)
Annex A
(normative)
A.1 Method 1
Not applicable.
CD;vent =
CD;ATD =
CD;w=
nvent =
nATD =
nw =
33
prEN 16798-7:2014 (E)
Appliance
Combustion air Flue gas Typical combustion system factor
supply situation exhaust situation appliance system fas
Combustion air is taken from Flue gases are exhausted into • Kitchen stove
room air room
• Gas appliance
according to CEN/TR
1749 Type A
Combustion air is taken from Flue gases are exhausted into • Open fire place
room air separate duct
• Gas appliance according
to CEN/TR1749 Type B
Combustion air is taken from Flue gases are exhausted in • Specific gas appliance
room air duct simultaneously with
mechanical ventilation exhaust
air
Combustion air is delivered Flue gases are exhausted into a • Gas appliance according
directly from outside in a separate duct to CEN/TR 1749 Type C
separate duct, sealed from (room air sealed systems)
room air
• Closed fire place (wood,
coal or wood/coal-effect
gas fire)
For residential buildings, the fuel flow factors for combustion air flow are given in Table A.2
Appliance open fire closed open gas open gas open gas closed closed fire
type place with built in with flue kitchen stove wood/coal fire
fan balancer effect gas fire
Fuel flow
factor, fff
[l/s per kW]
For the calculations of the mechanical system ventilation air flow rates, the default values are as follows:
34
prEN 16798-7:2014 (E)
Table A.3 — Default values for fsens depending on control and sensor type
VAR_SENS_PEOPLE
VAR_SENS_IAQ
fsys =
This identifier indicates the exposure to wind of an air flow path on a facade.
Code Meaning
Open
Normal
Shielded
Table A.5 gives Cp values for transverse ventilation zones depending on the height of the path on the façade
and its shielding class.
35
prEN 16798-7:2014 (E)
Low Open
hpath< 15 m
Normal
Shielded
Medium Open
15 ≤ hpath < 50 m Normal
Shielded
High Open
hpath ≥ 50 m
NOTE The wind pressure coefficients given are valid for a wind sector of approx. ± 60° to the facade axis. The
wind direction is not considered more specifically.
The value for the difference of wind pressure coefficients between the windward and the leeward sides of the
ventilation zone is estimated with one of the options below:
The default value for the pressure coefficient of the cowl at roof height is:
Cp;cowl;roof = .
A.1.3.6 Correction coefficient for accounting for height of cowl above roof level
Table A.7 provides default values for ∆Ccowl;height values. By default, these values do not depend on the
distance to the roof top and the wind angle of attack.
36
prEN 16798-7:2014 (E)
εV =
This factor has to be defined at national level especially if a window opening is considered as a possible
ventilation system alone.
farg =.
Cross-ventilation may be considered in a ventilation zone if doors can be opened between two facades with
different orientations of the external envelope of the ventilation zone.
Table A.8 gives default values for the cross-ventilation factor based on building categories.
If at least half of the floor area of the ventilation zone can be cross-ventilated, fcros =
Else, fcros=
37
prEN 16798-7:2014 (E)
Nw;div =
The default useful height of stack effect depends on air transfers between levels of the ventilation zone:
If there is no air transfer between levels of the ventilation zone or its height is smaller or equal to 3 m:
hpdu;st=
Else:
hpdu;st =
hst=
∆plea;ref =
nlea =
Alea
Clea = qV;Δplea;ref nlea
(A.1)
∆plea; ref
38
prEN 16798-7:2014 (E)
Table A.11 gives default values for the wind speed correction factor.
Open terrain
Country
Urban/City
Code Meaning
39
prEN 16798-7:2014 (E)
Annex B
(informative)
B.1 Method 1
Not applicable.
CD;vent = 0,6
CD;ATD = 0,6
CD;w = 0,67
nvent = 0,5
nATD = 0,5
nw = 0,5
40
prEN 16798-7:2014 (E)
Appliance
Combustion air Flue gas Typical combustion
system
supply situation exhaust situation appliance system factor fas
Combustion air is taken from Flue gases are exhausted into • Kitchen stove 0
room air room
• Gas appliance according to
CEN/TR 1749 Type A
Combustion air is taken from Flue gases are exhausted into • Open fire place 1
room air separate duct
• Gas appliance according to
CEN/TR1749 Type B
Combustion air is taken from Flue gases are exhausted in duct • Specific gas appliance See note
room air simultaneously with mechanical
ventilation exhaust air
Combustion air is delivered Flue gases are exhausted into a • Gas appliance according to 0
directly from outside in a separate duct CEN/TR 1749 Type C
separate duct, sealed from room (room air sealed systems)
air
• Closed fire place (wood,
coal or wood/coal-effect
gas fire)
NOTE Considered as a mechanical extraction system, but with variable air flow, depending of both the exhaust
and the combustion appliance.
For residential buildings, the fuel flow factors for combustion air flow are given in Table B.2.
open fire Closed with open gas with open gas open gas/wood/coal
Appliance type closed fire closed fire
place built in fan flue balancer kitchen stove effect gas fire
Fuel flow factor,
2,8 0,38 0,78 3,35 3,35 0,32 0,52
fff [l/s per kW]
For the calculations of the mechanical system ventilation air flow rates, the default values are as follows:
Table B.3 — Default values for fsens depending on control and sensor type
VAR_SENS_PEOPLE 0
VAR_SENS_IAQ CO2 0
fsys = 1,2
41
prEN 16798-7:2014 (E)
This identifier indicates the exposure to wind of an air flow path on a facade.
Code Meaning
Open No obstruction
Normal Partially shielded from wind
Shielded Shielded from wind
Table B.5 gives Cp values for transverse ventilation zones depending on the height of the path on the façade
and its shielding class.
Shielding
Height of air Dimensionless wind pressures Cp
class
flow path on
façade Windward Leeward Roof (depending on slope)
Cp1 Cp2 Cp3
< 10° 10°-30°° > 30°
Low
Open + 0,50 - 0,70 - 0,70 - 0,60 - 0,20
hpath < 15 m
NOTE The wind pressure coefficients given are valid for a wind sector of approx. ± 60° to the facade axis. The
wind direction is not considered more specifically.
42
prEN 16798-7:2014 (E)
The value for the difference of wind pressure coefficients between the windward and the leeward sides of the
ventilation zone is estimated with one of the options below:
The default value for the pressure coefficient of the cowl at roof height is:
Cp;cowl;roof = 0.
B.1.3.6 Correction coefficient for accounting for height of cowl above roof level
Table B.7 provides default values for ∆Ccowl;height values. By default, these values do not depend on the
distance to the roof top and the wind angle of attack.
εV = 1
This factor has to be defined at national level especially if a window opening is considered as a possible
ventilation system alone.
farg = 1.8.
43
prEN 16798-7:2014 (E)
Cross-ventilation may be considered in a ventilation zone if doors can be opened between two facades with
different orientations of the external envelope of the ventilation zone.
Table B.8 gives default values for the cross-ventilation factor based on building categories.
If at least half of the floor area of the ventilation zone can be cross-ventilated, fcros = 1
Else, fcros = 0
Nw;div= 1
The default useful height of stack effect depends on air transfers between levels of the ventilation zone:
If there is no air transfer between levels of the ventilation zone or its height is smaller or equal to 3 m:
Else:
hpdu;st = hz + 2 (B.2)
44
prEN 16798-7:2014 (E)
The default distribution is based on a vent coefficient for the ventilation zone estimated with:
C vent = ∑C
all vents
vent;path,i (B.4)
Air path height = 0,75 hz Cvent;path = 0,25 Cvent Cvent;path = 0,25 Cvent
∆plea;ref = 50 Pa
nlea = 0,667
Alea
Clea = qV;Δplea;ref nlea
(B.5)
∆plea; ref
the leakage coefficient of the façades, which is estimated to be proportional to the ratio of surface area of
the façade to that of the facades plus the roof
the leakage coefficient of the roof, which is estimated to be proportional to the ratio of surface area of the
roof to that of the facades plus the roof
Afde
Clea;fde = Clea ⋅ (B.6)
Afde + Aroof
45
prEN 16798-7:2014 (E)
Aroof
Clea;roof = Clea ⋅ (B.7)
Afde + Aroof
Table B.11 gives default values for the wind speed correction factor.
Terrain class,
fwnd
TER_CLASS
Code Meaning
BALANCED Air is supplied to and exhausted from the space mechanically
EXHAUST Air is exhausted from the space mechanically; air is supplied naturally to the space
SUPPLY Air is supplied to the space mechanically; air is exhausted naturally from to the space
NATURAL Air is naturally supplied to and exhausted from the space
46
prEN 16798-7:2014 (E)
Bibliography
[1] CEN/TR 16798-8 —Energy performance of buildings — Module M5-5 —Ventilation in building —
Emission & Control
[2] CEN/TR 1749, European scheme for the classification of gas appliances according to the method of
evacuation of the products of combustion (Types)
[3] EN 13053, Ventilation for buildings — Air handling units — Rating and performance for units,
components and sections
[4] EN 13141-1, Ventilation for buildings — Performance testing of components/products for residential
ventilation — Part 1 Externally and internally mounted air transfer devices
[5] EN 13141-2, Ventilation for buildings — Performance testing of components/products for residential
ventilation — Part 2: Exhaust and supply air terminal devices
[6] CR 14378, Ventilation for buildings — Experimental determination of mechanical energy loss
coefficients of air handling components
[7] EN ISO 15927-1, Hygrothermal performance of buildings — Calculation and presentation of climatic
data — Part 1: Monthly means of single meteorological elements (ISO 15927-1:2003)
47