Plant room

ventilation
Paul Walker looks at the ventilation
provisions for boiler houses and plant rooms
in accordance with British Standard 6644

Commercial/non-domestic boilers are non-domestic premises need to be Air supply to the boiler house/plant
often installed in purpose designed and competent in the work activity that they room needs to ensure that maximum
built boiler houses/plant rooms, which are engaged in and registered with CORGI. temperatures within the boiler house/plant
serve one or more buildings and which Many gas operatives and installing room are limited to:
usually contain other services for the business reading this article on boiler
building concerned. houses/plant rooms ventilation will be • 250C at floor level (100mm above
This article reviews the ventilation aware of various ventilation scenarios floor level)
provisions for boiler houses/plant rooms where ventilation requirements are not • 320C at mid level (1.5 m above
in accordance with British Standard achievable, neither have they had much floor level)
(BS) 6644: 2005 Specification for consideration in design or its application. • 400C at ceiling level (100 mm below
installation of gas-fired hot water boilers Ventilation provisions, as with any other ceiling level).
of rated inputs between 70kW (net) and aspect of the installation, can not be
1.8MW (net) (2nd and 3rd family gases). designed in isolation as the type of boiler, Where boiler/plant is likely to be used
its burner assembly (i.e. atmospheric, throughout the summer months at or near
Note: Additional guidance for boiler forced draught, pre-mix, dual fuel, etc.), maximum capacity it may be necessary to
houses/plant rooms ventilation and the controls being utilised (on/off, high install additional ventilation, to that
that of a ‘space’ can also be found in low, modulating), the manufacturer’s required for combustion purposes, to
an Institution of Gas Engineers and instructions etc, should all be considered achieve the temperatures specified above.
Managers (IGEM) publication, to ensure that any particular requirements
IGE/UP/10 Part 1 (Edition 2) for the equipment being installed has The ventilation provisions can be
Installation of gas appliances in been accounted for (cooling air as well as afforded by one or more of the following:
industrial and commercial premises. for combustion).
Part 1. Flued appliances. The boiler installation needs to be 1. Air to be supplied by one or more
designed so that it does not cause low level free air vents and discharged
The person(s) responsible for designing adjacent spaces to exceed their design by one or more free air vents at high
the installation should have the necessary temperature during operation of the level.
knowledge and understanding of the boiler’s. The boiler needs to be sited on
standards and regulations that apply to floors/walls capable of withstanding 2. Air to be supplied by a fan via one or
ensure any plans provided produce a temperatures of at least 650C and be more low level free air vents and
safe and satisfactory installation. capable of supporting the weight of discharged naturally at high level (fan
Gas operatives installing, commissioning boilers and ancillary controls when filled needs to be interlocked to boiler with a
and maintaining gas installations in with water. proving device).
continued on next page >

www.corgi-group.com February 2007 39


TECHNICAL FEATURE

Note: Under no circumstances should Table 1: Cooling air for boiler NOT fitted with Draught Diverter
air be supplied naturally at low level
with extraction being provided by Cooling air Temperature 0C Airflow per kW net heat input m3/sec
means of a fan at high level, as this
Low Level 15 318 x 10 -4
can create negative pressures in the
boiler house/plant room leading to High Level 40 3.47 x 10 -4
flue reversal problems.

3. Air to be supplied by a fan via one or Table 2: Cooling air for boiler fitted with Draught Diverter
more low level free air vents and
discharged by means of a second fan Cooling air Temperature 0C Airflow per kW net heat input m3/sec
at high level (fans need to be
Low Level 15 3.79 x 10 -4
interlocked to boiler with a proving
device to each fan). Additionally, fans Outlet (via Draught 32 1.90 x 10 -4
need to be selected and controlled so
Diverter
as not to cause a negative pressure in Outlet (High Level) 40 2.07 x 10 -4
the boiler house/plant room, relative to
outside atmosphere. Natural ventilation requires sufficient free to enter and exit the boiler/plant room for
area ventilation provided at high and low boilers fitted with and without draught
4. Where balanced compartment level to allow combustion and cooling air diverters as detailed in Tables 1 and 2.
installations are installed, air is supplied
and discharged by means of purpose
designed flueing and ventilation Table 3: Natural ventilation for a boiler NOT fitted with a
Draught Diverter
system based on high and low
permanent openings, located
Volume Flow Calculated open Rounded up open area
immediately below the flue outlet
m3/sec/ kW area vent of vent
(specialist advice should be sought).

Low level
All inlet and extract fans should be fitted
with automatic controls causing boiler Combustion air 3.89 x 10 -4
shut down in the event of either individual
or total fan failure. Cooling air 3.18 x 10 -4
The ventilation provisions need to Low level Total 7.07 x 10 -4 3.54 cm2/kWnet heat input 3.5 cm2/kWnet heat input
ensure that the temperature of the boiler
house/plant room meets the requirements
of BS 6644 and shall not be less than High Level
2 cm2 free area per kW of the net heat
input at both high and low level. Combustion air 0
The high and low level ventilation
Cooling air 3.34 x 10 -4
should be direct to outside air on the
same wall. The vertical distance between High Level Total 3.47 x 10 -4 1.74 cm2/kWnet heat input 2 cm2/kWnet heat input
high and low level ventilation should be as
great as possible to achieve convection
airflow.
When calculating ventilation
requirements we must take into account
whether or not the boiler has a draught
diverter fitted. 50% of air leaves through
the draught diverter at mid level
temperature of 320C and 50% of high level
temperature of 400C, therefore “mean” exit
temp is 360C. This includes 1% for heat
emitted from ancillary pumps, pipework
etc fitted within the boiler house/plant
room.

40 February 2007 www.corgi-group.com


TECHNICAL FEATURE

Table 4: Natural ventilation for a boiler fitted with a Draught Diverter Mechanical ventilation.
From calculations in Table 3. Table 5 gives
Volume Flow Calculated open Rounded up open area the mechanical ventilation flow rates
m3/sec/ kW area vent of vent required to supply boiler/plant room
combustion air and cooling air and
Low level extracting heated cooling air from the
boiler/plant room. When using extraction
Combustion air 3.89 x 10 -4
fans it’s important not to create a negative
Cooling air 3.79 x 10 -4 pressure in the boiler/plant room in
relationship to the outside pressure.
Low level Total 7.68 x 10 -4 3.84 cm2/kW net heat input 4 cm2/kW net heat input In order to ensure a correct balance
between inlet and extract air flow the
differences have been specified in column
High Level e of Table 5. This is specified as a
Combustion air 0 normative requirement in BS 6644:2005.
All figures and calculations have
Cooling air 2.07 x 10 -4 assumed CO2 in the flue gases is 8.5%
High Level Total 1.03 cm2/kW net heat input 1 cm2/kW net heat input then air requirement for one volume of
2.07 x 10 -4
gas will be 13.2 volumes.
NOTE: 50% of the cooling air exits via the draught diverter. 1% for heat emitted from ancillary
pipework and pumps within the boiler
house/plant room. This is calculated on
Ventilation Free Opening for Low level free opening is taken from the net heat input of the boilers
boilers with or without draught Table 4 (4cm2 open area/kW of heat input) (0.01kW/kW of net heat input). Where
diverters colarifiers and other items of heat emitting
For simple calculations, the rounded up Note: Ventilation requirements equipment are sited in boiler house/plant
open area value from Tables 3 and 4 are to specified in BS 6644:2005 are therefore rooms, additional cooling air may be
be selected. for natural ventilation of boiler houses/ required to comply with current standards.
Therefore the requirement for: plant rooms in which boilers with or It may be necessary to increase
High level free opening is taken from without draught diverters are installed. ventilation rates where boilers run at near
Table 3 (2cm2 open area/kW of heat input) or full load conditions during summer
periods. Conversely, it may also cause
abnormal cooling, through winter periods.
Table 5: Mechanical ventilation flow rates.

Inlet air. Combustion Extract air. Ventilation


Difference
ventilation between inlet &

Type of Boiler
calculated
value
Required calculated Required extract air. (Inlet
inlet air
flow
value extract air minus extract
flow
to sum up
ventilation)
m3/s (b - d) • The person(s) responsible
a b c d e for designing the installation
With should have the necessary
m3/(sec1000kW) 0.0768 0.80 0.202 0.25 0.55 +/- 0.05
Draught knowledge and understanding
Diverter 3
m /(hr/kW) 2.765 2.8 0.727 0.73 2.07 +/- 0.18 of the standards and regulations
that apply
With m3/(sec1000kW) 0.707 0.75 0.347 0.35 0.4 +/- 0.05
Draught
Diverter m3/(hr/kW) 2.545 1.249 1.249 1.25 1.35 +/- 0.18 • Ventilation provisions, as
with any other aspect of the
installation, can not be
Note: contains information supplied in designed in isolation
columns b & c of this table. The inlet
air flow and the difference between it • The ventilation provision needs
and the extract air flow forms part of to ensure that the temperature
BS 6644: 2005. of the boiler house/plant room
meets the requirements of
BS 6644