You are on page 1of 6

HVAC-BUILDING TECH.

AIR WATER SYSTEM


 In an “Air-Water” system both air and water are used for providing required conditions in
the conditioned space. The air and water are cooled or heated in a central plant.
 The air supplied to the conditioned space from the central plant is called as primary air,
while the water supplied from the plant is called as secondary water.
 The complete system consists of a central plant for cooling or heating of water and air,
ducting system with fans for conveying air, water pipelines and pumps for conveying water
and a room terminal.
 The room terminal may be in the form of a fan coil unit, an induction unit or a radiation
panel. Figure below shows the schematic of a basic air-water system.
 Even though only one conditioned space is shown in the schematic, in actual systems, the
air-water systems can simultaneously serve multi-zones.

Two main delivery approaches are used in air-water systems; the fan-coil & the induction unit.

1 FAN COIL UNIT


 A fan coil unit is a terminal unit that is located inside the conditioned space and consists of
a heating and/or cooling coil, a fan, air filter, drain tray and controls. The cold/hot water
circulates through the finned tube coil while the blower draws air from the conditioned
space and blows it over the coil. As the air flows through the coil it is heated or cooled and
dehumidified.
 An air-water fan-coil system is similar in most respects to an all-water fan-coil with one
major difference. Supply air from a central air handler is provided to each space as well as
conditioned water.
 This supply air is usually intended to meet the ventilation needs of the space, and can either
be delivered independently of the fan-coil unit (through conventional diffusers or registers)
or can be introduced at the fan-coil unit itself. Figure 71 provides a schematic illustration of
an air-water fan-coil system.

1
HVAC-BUILDING TECH.

2 INDUCTION UNIT
 An induction unit the cooling/heating coil is an integral part of the primary air system. The
primary air supplied at medium to high pressure to the induction unit, induces flow of
secondary air from the conditioned space.
 The secondary air is sensibly cooled or heated as it flows through the cooling/heating coil.
The primary and secondary air are mixed and supplied to the conditioned space. The fan
coil units are similar to the ones used
in all water systems.
 Externally, an induction unit looks
very much like a fan-coil unit; the
difference is internal.
An induction unit employs high
velocity air flow from a central air
handling unit to induce a flow of room
air into and through the cabinet.
 This induction effect replaces the
motive force provided by the fan in a
fan coil unit.
 The mixture of central air (termed
primary air) and room air (secondary
air) passes through a coil in the unit
and is conditioned to suit the needs of
the zone.
 Filtration of the secondary room air at the induction cabinet is common. Figure provides a
schematic diagram of an air-water induction system.

2
HVAC-BUILDING TECH.

3. ALL WATER (HYDRONIC) SYSTEM

 This system is based on the distribution of hot or cold-water


to individual heat transfer devices (terminal units) located in
each room of the building. When cooling is required in the
conditioned space then cold water is circulated between the
conditioned space and the plant, while hot water is circulated
through the distribution system when heating is required.
Unlike Air-water systems, no primary air is separately fed
indoors.
Whether heating or cooling, “All –water” or hydronic system uses the following basic components
to control the environment:
1. The use of a chiller (on roofs or plant rooms) to cool water that is circulated via pumps to the
occupied space, where it is passed through fan coils (terminal units) that circulate room air
over the coil, hence absorbing unwanted heat.
2. The use of boilers located in plant rooms to heat water (a separate circuit from cooling) that
is circulated via pumps to the occupied space, where it is passed through the same fan coil
which circulates room air, hence adding heat to the space.

Advantages of this system are as under

• Individual room temperature control is easily achieved.


• Same distribution piping system can be used for heating water and chilled water if
simultaneous heating and cooling is not required.
• Distribution piping requires considerably less space than ductwork.
• System components have a long service life, between 15 to 20 years.

Disadvantages of this system are as under

• It is difficult to provide adequate ventilation to rooms.


• It is difficult to take advantage of outdoor air cooling when conditions are favorable
(economizer).Fan coil units in the occupied space can be noisy.
• An elaborate condensate drainage system may be required for individual F.C cooling units.
• Hydronic cooling is usually not economical for smaller buildings.
• Fan coil units take up space in the room.
3
HVAC-BUILDING TECH.

• It may be difficult to control humidity levels in the rooms.


• Hydronic systems may be subject to freezing when used in air handling units with outdoor
air.

4 UNITARY/ REFERANT BASED SYSTEM

• Unitary systems consist of self-contained units that heat and/or cool a single space.
• Each space may have its own unitary system.
• The units are self-contained and produce heating and/or cooling with the application of the
proper energy source, usually electricity.
• Examples of unitary equipment include window air conditioners, through-the-wall air
conditioners and heat pumps, package rooftop air conditioners, electric baseboard radiators,
and water source heat pumps.

Advantages of unitary system are as under

• Lower installation costs.


• Individual control in each room.
• Units installed on perimeter of building can easily bring ventilation air into building.
• Simple, easy to use temperature controls.
• Easy to service and maintain.

Disadvantages of unitary system are as under

• Units with refrigeration compressors are usually quite noisy.


• Precise temperature and humidity control is difficult, if not impossible.
• Cooling units usually must be located near an outside wall or on the roof in order to reject
heat to the atmosphere.
• Units can be unsightly and aesthetically unpleasant. Condensate drainage can be a problem
with some cooling units. Many units can be very time consuming to maintain.

VRV / VRF
 VRV is a system developed and designed by Daikin Industries and means "variable
refrigerant volume". Daikin protected the term VRV so other manufacturers use the term
VRF "variable refrigerant flow".
 In principle they both work the same and are extremely efficient, reliable, energy saving
ways to heat and cool all types of buildings with minimum installation time or disruption.
 The volume or flow rate of refrigerant is accurately matched to the required heating or
cooling loads thereby saving energy and providing more accurate control.

In short, they are probably the best systems currently available for mid to large applications.

4
HVAC-BUILDING TECH.

 VRV is the latest and most revolutionary technologies used for large sized buildings.
When outdoor-air processing units are connected, the total connection capacity must be
within 50% to 100% of that of the outdoor units.
 When outdoor-air processing units and standard indoor units are connected, the total
connection capacity of the outdoor-air processing units must not exceed 30% of that of the
outdoor units.

VRV ADVANTAGES

1. Individual control
2. Saves energy – Over 30% size reduction
3. Conserves space
4. Offers a wide selection of models (5 to 54 HP)
5. Operates over a broad temperature range
6. Provides superior design flexibility
7. Enhances ease of use
8. Delivers ultimate reliability
9. Simplifies installation

5
HVAC-BUILDING TECH.

You might also like