Model Implementation Conformance Statement
for the IEC 61850 interface in PCS-902

Jun 8, 2016

UCA International Users Group


Testing Sub Committee

         
INDEX
page

INDEX ...........................................................................................................ii 

1. Introduction .............................................................................................3 

2. Logical Nodes List ..................................................................................4 

3. Logical Node Extensions .......................................................................5 


3.1. New Logical Nodes........................................................................5 
3.1.1 RRTC: RRTC .........................................................................5 
3.2. Extended Logical Nodes ................................................................6 
3.2.1 LLN0: Logical node zero ........................................................6 
3.2.2 LPHD: Physical device information ........................................7 
3.2.3 GGIO: Generic process I/O ...................................................8 
3.2.4 GGIO: Generic process I/O ...................................................9 
3.2.5 GGIO: Generic process I/O .................................................10 
3.2.6 MMXU: Measurement ..........................................................10 
3.2.7 MMXU: Measurement ..........................................................11 
3.2.8 PDIS: Distance ....................................................................11 
3.2.9 PDIS: Distance ....................................................................13 
3.2.10 PHAR: Harmonic restraint .................................................15 
3.2.11 PSCH: Protection scheme .................................................15 
3.2.12 PTOC: Time overcurrent....................................................17 
3.2.13 PTOC: Time overcurrent....................................................18 
3.2.14 PTRC: Protection trip conditioning .....................................19 
3.2.15 RDIR: Directional element .................................................20 
3.2.16 RFLO: Fault locator ...........................................................21 
3.2.17 RREC: Autoreclosing .........................................................22 
3.2.18 RSYN: Synchronism-check ...............................................24 
3.2.19 TCTR: Current transformer ................................................26 
3.2.20 TVTR: Voltage transformer ................................................27 
3.2.21 XCBR: Circuit breaker .......................................................28 

 
1. Introduction

This model implementation conformance statement is applicable for PCS-902


This MICS document specifies the modelling extensions compared to IEC 61850. For
the exact details on the standardized model please compare the ICD substation
configuration file: "device.icd", version 1.00.

Clause 2 contains the list of implemented logical nodes.


Clause 3 describes the new and extended logical nodes.
Clause 4 describes the new and extended common data classes (if any).
Clause 5 describes the new and extended enum types.
Clause 6 describes any other extensions.

 
2. Logical Nodes List

The following table contains the list of logical nodes implemented in the device:

G:Logical nodes for generic references


GGIO (Generic process I/O)
L:System logical nodes LN group
LLN0 (Logical node zero)
LPHD (Physical device information)
M:Logical nodes for metering and measurement
MMXN (Non-phase-related measurement)
MMXU (Measurement)
MSQI (Sequence and imbalance)
P:Logical nodes for protection functions
PDIS (Distance)
PHAR (Harmonic restraint)
PSCH (Protection scheme)
PTOC (Time overcurrent)
PTRC (Protection trip conditioning)
R:Logical nodes for protection related functions
RDIR (Directional element)
RDRE (Disturbance recorder function)
RFLO (Fault locator)
RREC (Autoreclosing)
RRTC (RRTC)
RSYN (Synchronism-check)
T:Logical nodes for instrument transformers and sensors
TCTR (Current transformer)
TVTR (Voltage transformer)
X:Logical nodes for switchgear
XCBR (Circuit breaker)

 
3. Logical Node Extensions

The following table use


M : Data is mandatory in the IEC-61850-7-4.
O: Data is optional in the IEC-61850-7-4 and is used in the device.
E: Data is an extension to the IEC-61850-7-4.

3.1. New Logical Nodes

New logical nodes have the lnNs attribute in the Name plate. The value of lnNs is a
reference to the MICS document.

3.1.1 RRTC: RRTC

RRTC class
Attribute Attribute Explanation M/O/E Remarks
Name Type

RRTC
Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Status Information
Str ACD Start M
Op ACT Operate M
Settings
StrVal ASG Start Value O
StrVal3I0 ASG Zero sequence undervoltage block value E
(3U0)
StrValI2 ASG negative sequence undervoltage block E
value
StrVal3U0 ASG zero sequence undervoltage block value E
(3U0)
StrValU2 ASG negative sequence undervoltage block E
value

 
LoA ASG Low current value E
LoW ASG Low active power value E
LoPFAng ASG Angle setting of low power factor E
element
RTCDlTmms ING Operate delay time with the criterion E
RTDlTmms ING Operate delay time without the criterion E
AVStrEna SPG Start by current and voltage E
LoAWStrEna SPG Start by low current or active power E
LoPFAngEna SPG Start by low power factor angle E
NoCrtrnEna SPG Remote trip without criterion E
TVFDisCEna SPG Disable criterion when TV Fail E

3.2. Extended Logical Nodes

The following logical nodes have been extended with extra data. All extra data has
been highlighted in the tables and marked as "E" (Extended), these data contains the
"dataNs" attribute.

3.2.1 LLN0: Logical node zero

LLN0 class
Attribute Attribute Explanation M/O/E Remarks
Name Type

LLN0 Logical node zero


Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Status Information
Loc SPS Local operation for complete logical O
device
RemSetEna SPS Remotely Modify Setting E
RemGoEna SPS Remotely Control Goose E
Controls
LEDRs SPC LED reset O

 
FuncEna1 SPC Function 1 enabled E
FuncEna2 SPC Function 2 enabled E
FuncEna3 SPC Function 3 enabled E
FuncEna4 SPC Function 4 enabled E
FuncEna5 SPC Function 5 enabled E
FuncEna6 SPC Function 6 enabled E
FuncEna7 SPC Function 7 enabled E
FuncEna8 SPC Function 8 enabled E
FuncEna9 SPC Function 9 enabled E
FuncEna10 SPC Function 10 enabled E
CBFlt SPC Current Breaker Flaut E
Settings
DPFCStr ASG DPFC start value E
ROCStr ASG Residual current start value E
N0CStr ASG Negtive current start value E
Z3AuxStr SPG Z3 auxiliary start value E

LinNo STG Line No E


Measured and metered value
DelayTRtg SAV SV Delay time E
 

3.2.2 LPHD: Physical device information

LPHD class
Attribute Attribute Explanation M/O/E Remarks
Name Type

LPHD Physical device information


Data
Descriptions
PhyNam DPL Physical device name plate M
Status Information
PhyHealth INS Physical device health M
OutOv SPS Output communications buffer overflow O
Proxy SPS Indicates if this LN is a proxy M
InOv SPS Input communications buffer overflow O
NumPwrUp INS Number of Power ups O
WrmStr INS Number of Warm Starts O

 
WacTrg INS Number of watchdog device resets O
detected
PwrUp SPS Power Up detected O
PwrDn SPS Power Down detected O
PwrSupAlm SPS External power supply alarm O
Controls
RsStat SPC Reset device statistics O
Settings
SettingGrp ING Setting Group E
GooseEna SPG GOOSE DI Enable E
OthGoEna SPG Other GOOSE DI Enable E

DeviceName STG Device name E


StationNs STG Station name E
Measured and metered value
ActSGST MV Active Setting Group E
 

3.2.3 GGIO: Generic process I/O

GGIO class
Attribute Attribute Explanation M/O/E Remarks
Name Type

GGIO Generic process I/O


Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Settings
ASG01 ASG Setting 1 E
ASG02 ASG Setting 2 E
ASG03 ASG Setting 3 E
ASG04 ASG Setting 4 E
ASG05 ASG Setting 5 E
ASG06 ASG Setting 6 E
ASG07 ASG Setting 7 E

 
ASG08 ASG Setting 8 E
ING01 ING Setting 1 E
ING02 ING Setting 2 E
ING03 ING Setting 3 E
ING04 ING Setting 4 E
ING05 ING Setting 5 E
ING06 ING Setting 6 E
ING07 ING Setting 7 E
ING08 ING Setting 8 E
SwRev STG software version informaion E
SwCrc STG software crc informaion E
 

3.2.4 GGIO: Generic process I/O

GGIO class
Attribute Attribute Explanation M/O/E Remarks
Name Type

GGIO Generic process I/O


Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Settings
ASG01 ASG Setting 1 E
ASG02 ASG Setting 2 E
ASG03 ASG Setting 3 E
ASG04 ASG Setting 4 E
ASG05 ASG Setting 5 E
ASG06 ASG Setting 6 E
ASG07 ASG Setting 7 E
ASG08 ASG Setting 8 E
ING01 ING Setting 1 E
ING02 ING Setting 2 E
ING03 ING Setting 3 E
ING04 ING Setting 4 E

 
ING05 ING Setting 5 E
ING06 ING Setting 6 E
ING07 ING Setting 7 E
ING08 ING Setting 8 E
 

3.2.5 GGIO: Generic process I/O

GGIO class
Attribute Attribute Explanation M/O/E Remarks
Name Type

GGIO Generic process I/O


Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Controls
SPCSO1 SPC General indication E
SPCSO2 SPC General indication E
SPCSO3 SPC General indication E
SPCSO4 SPC General indication E
SPCSO5 SPC General indication E
SPCSO6 SPC General indication E
SPCSO7 SPC General indication E
SPCSO8 SPC General indication (binary input) E
 

3.2.6 MMXU: Measurement

MMXU class
Attribute Attribute Explanation M/O/E Remarks
Name Type

MMXU Measurement
Data
Common Logical Node Information
Mod INC Mode M

 
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Measured and metered value
Hz MV Frequency O
PhV WYE Phase to ground voltages O
A WYE Phase currents O
OthV CMV Voltage of Other Side E
 

3.2.7 MMXU: Measurement

MMXU class
Attribute Attribute Explanation M/O/E Remarks
Name Type

MMXU Measurement
Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Measured and metered value
TotW MV P O
TotVAr MV Q O
TotVA MV S O
TotPF MV PF O
Hz MV Frequency O
PPV DEL Line Voltage O
PhV WYE Phase to ground voltages O
A WYE Phase currents O
HzBus MV Bus Frequency E
OthV CMV Voltage of Other Side E
 

3.2.8 PDIS: Distance

PDIS class

 
Attribute Attribute Explanation M/O/E Remarks
Name Type

PDIS Distance
Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Status Information
Str ACD Start M
Op ACT Operate M
Settings
PhStr ASG Impedance setting of phase-to-phase O
GndStr ASG Groud Start Value O
RisLod ASG Resistive Reach for Load Area O
OpDlTmms ING Operate Time Delay O
PhDlTmms ING Phase Operate Time Delay O
GndDlTmms ING Groud Operate Time Delay O
R0 ASG Zero -sequence line resistance O
R1 ASG Positive-sequence line resistance O
X0 ASG Zero -sequence line reactance O
X1 ASG Positive-sequence line reactance O
LinAng ASG Line Angle O
K0Fact ASG Residual Compensation Factor K0 O
StrVal ASG Start Value E
ZPsMagVal ASG Positive sequence line impedance E
ZZerMagVal ASG Zero sequence line impedance E
LinAng0 ASG Zero sequence line angle E
Enable SPG Enable E
SpdupEna SPG Speedup Enable E
RisLodEna SPG Resistive Reach for Load Area Enable E
AngOfsPG ASG PG Line Angle E
AngOfsPP ASG PP Line Angle E
RisPP ASG Resistance setting of phase-to-phase E
ZmPPEna SPG phase-to-phase distance protection E
enabled
ZmPGEna SPG phase-to-ground distance protection E
enabled

 
QuadStr ASG Quad Valve E
RealK0 ASG Real component of zero-sequence E
ImagK0 ASG Iimaginary component of zero-sequence E
PBlkRecEna SPG Phase Block Recloe Enable E
GBlkRecEna ING Groud Block Recloe Enable E
PGDlTmms ING Short time delay of phase-to-ground E
PPDlTmms ING Short time delay of phase-to-phase E
DlyTmms ING t_Dly_CurRev E
ExtTmms ING t_Ext_CurRev E
POTTEna SPG En_POTT E
PUTTEna SPG En_PUTT E
PPEna SPG PP Enable E
PGEna SPG PG Enable E
QuadEna ING Quad Enable E
BIEna SPG En_BI_Z1_Vld E
DlEna SPG Fixed accelerate enable E
BlkRecEna SPG Block Reclose Enable E
OUTMATR ING Output Matrix E
MhoPosRch ASG Mho Positive Reach E
MhoRevRch ASG Mho Reverse Reach E
FVolVal ASG Forward Voltage Value E
ChgZVal ASG Out of range Impendance Change Value E
CZ0Val ASG Zero Sequence Compensation E
Impendance Value
PSBBlkEna SPG Control by power swing blocking E
 

3.2.9 PDIS: Distance

PDIS class
Attribute Attribute Explanation M/O/E Remarks
Name Type

PDIS Distance
Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M

 
Status Information
Str ACD Start M
Op ACT Operate M
PDFOp ACT Pole discrepancy conditions operate E
Settings
Enable SPG Enable E
I0Val ASG Current setting of pilot directional E
earth-fault protection
ManClsMod ING Option of manual SOTF mode E
ManClsTmms ING Time delay of distance protection E
accelerating to trip when manual closing
TPARTmms ING Time delay of distance protection E
accelerating to trip when 3-pole
reclosing
PARTmms ING Time delay of distance protection E
accelerating to trip when 1-pole
reclosing
PDFTmms ING Time delay of distance protection E
operating under pole discrepancy
conditions
ManClsEna SPG Enabling/disabling distance SOTF E
protection for manual closing
Z2MaClsEna SPG Enabling/disabling zone 2 of distance E
SOTF protection for manual closing
Z3MaClsEna SPG Enabling/disabling zone 3 of distance E
SOTF protection for manual closing
Z4MaClsEna SPG Enabling/disabling zone 4 of distance E
SOTF protection for manual closing
TPAREna SPG Enabling/disabling distance SOTF E
protection for 3-pole reclosing
Z2TPAREna SPG Enabling/disabling zone 2 of distance E
SOTF protection for 3-pole reclosing
Z3TPAREna SPG Enabling/disabling zone 3 of distance E
SOTF protection for 3-pole reclosing
Z4TPAREna SPG Enabling/disabling zone 4 of distance E
SOTF protection for 3-pole reclosing
Z2PSBREna SPG Enabling/disabling zone 2 controled by E
PSB of distance SOTF protection for
3-pole reclosing
Z3PSBREna SPG Enabling/disabling zone 3 controled by E
PSB of distance SOTF protection for
3-pole reclosing
Z4PSBREna SPG Enabling/disabling zone 4 controled by E

 
PSB of distance SOTF protection for
3-pole reclosing
PAREna SPG Enabling/disabling distance SOTF E
protection for 1-pole reclosing
PDFEna SPG Enabling/disabling distance SOTF E
protection under pole discrepancy
conditions
 

3.2.10 PHAR: Harmonic restraint

PHAR class
Attribute Attribute Explanation M/O/E Remarks
Name Type

PHAR Harmonic restraint


Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Status Information
Str ACD Start(Active when restraint is needed) M
Settings
HaRst ING Number of harmonic restrained O
PhStr ASG Start Value O
PhStop ASG Stop Value O
OpDlTmms ING Operate Delay Time O
RsDlTmms ING Reset Delay Time O
BlkMod ING Block mode E
HReOpnValA ASG Current setting of releasing harmonic E
blocking function
HaBlkCff ASG Harmonic blocking coefficient E
 

3.2.11 PSCH: Protection scheme

PSCH class

 
Attribute Attribute Explanation M/O/E Remarks
Name Type

PSCH Protection scheme


Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Controls
OpStrp SPC Op strap
Status Information
ProTx SPS Teleprotection signal transmitted M
ProRx SPS Teleprotection signal received M
Str ACD Carrier Send M
Op ACT Operate M
OpEx ACT Zone extension protection operates O
TxSigPhA SPS Phase A signal to be transmitted to the E
other side
TxSigPhB SPS Phase B signal to be transmitted to the E
other side
TxSigPhC SPS Phase C signal to be transmitted to the E
other side
RxSigPhA SPS Phase A signal received from the other E
side
RxSigPhB SPS Phase B signal received from the other E
side
RxSigPhC SPS Phase C signal received from the other E
side
UnBlk SPS Unblocking signal received E
ExTrp SPS initiating sending permissive signal from E
external tripping signal received
AbnorCh SPS indicating abnormal signal received E
Settings
CrdTmms ING Co-ordination timer for blocking scheme O
WeiMod ING Mode of Weak End O
RvATmms ING Pickup time in ms for current reversal O
logic
RvRsTmms ING Dropoff time delay for current reversal O
UnBlkTmms ING Pickup time delay of unblocking scheme O

 
UVWeiVal ASG Low-voltage setting of weak infeed logic E
PilotMod ING Option of pilot scheme E
Type ING Channel Type E
LocChnID ING Local channel ID E
RemChnID ING Remote channel ID E
ZXTmms ING Pickup time delay for zone extension E
ChkTmhF ASG Channel check time E
PermSchTyp SPG Permissive scheme type E
UnBlkEna SPG Unblock Enable E
WeakEnd SPG Mode of Weak End E
IntClkMod SPG Internal Clock Mode E
AutChk SPG Auto check Mode E
ChnSpd SPG Channel Speed,0:64K,1:2M E
ChPhSegMod SPG Phase segregated channel mode E
ZXEna SPG Enabling/disabling unblocking scheme E
IndepChEna SPG independent pilot channel Enable E
Enable SPG Enable E
StrEnaRT SPG Remote Trip Blocked by Local Startup E
ChnPhsMode SPG Phase segregated channel mode E
 

3.2.12 PTOC: Time overcurrent

PTOC class
Attribute Attribute Explanation M/O/E Remarks
Name Type

PTOC Time overcurrent


Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Status Information
Str ACD Start M
Op ACT Operate M
Settings
StrVal ASG Start Value O

 
MinOpTmms ING Minimum Operate Time O
OpDlTmms ING Operate Delay Time O
DirEna SPG Directional Mode Enable E
Enable SPG Enable E
VolBlk ASG zero sequence voltage blocking E
ZroINVTFac ASG current time factor E
ZroINVTInd ASG current time index E
ZroINVBRec SPG trip blocking recloser E
SpdupEna SPG Speedup Enable E
OvIBlkRec SPG rip blocking recloser E
InvertMod ING Invert Time Mode E
StrMult ASG Start Value E
VolBlkEna SPG Voltage Block Enable E
BlkRecEna SPG Block Reclose Enable E
SClcZeEna SPG Self-Calculation Zero sequence current E
Enable
InvertEna SPG Invert Over Current Enable E
OUTMATR ING Output Matrix E
TVFailEna SPG Reserve over current Enable E
 

3.2.13 PTOC: Time overcurrent

PTOC class
Attribute Attribute Explanation M/O/E Remarks
Name Type

PTOC Time overcurrent


Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Status Information
Str ACD Start M
Op ACT Operate M
Settings
StrVal ASG Start Value O

 
TmMult ASG current time factor O
MinOpTmms ING Minimum Operate Time O
OpDlTmms ING Operate Delay Time O
DirEna SPG Directional Mode Enable E
Enable SPG Enable E
VolBlk ASG zero sequence voltage blocking E
ZroINVTFac ASG current time factor E
ZroINVTInd ASG current time index E
ZroINVBRec SPG trip blocking recloser E
SpdupEna SPG Speedup Enable E
OvIBlkRec SPG rip blocking recloser E
InvertMod ING Invert Time Mode E
DirMod ING Direction Mode O
StrMult ASG Start Value E
ConsK ASG The constant K E
ConsC ASG The constant C E
ConsAlpha ASG The constant Alpha E
VolBlkEna SPG Voltage Block Enable E
HaBlkEna SPG Harmonica Block Enable E
ZroACalEna SPG Zero sequency current is calculated E
BlkRecEna SPG Block Reclose Enable E
SClcZeEna SPG Self-Calculation Zero sequence current E
Enable
InvertEna SPG Invert Over Current Enable E
OUTMATR ING Output Matrix E
TVFailEna SPG Reserve over current Enable E
 

3.2.14 PTRC: Protection trip conditioning

PTRC class
Attribute Attribute Explanation M/O/E Remarks
Name Type

PTRC Protection trip conditioning


Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M

 
Health INS Health M
NamPlt LPL Name Plate M
Controls
TrStrp SPC Trip strap E
StrBFStrp SPC Start breaker failure strap E
BlkRecStrp SPC Block recloser starp E
Status Information
Tr ACT Trip M
Op ACT Operate M
Str ACD Sum of all connected Logical Nodes O
StrBF ACT Start breaker failure E
BlkRecST SPS Block reclosing E
Settings
TPTrMod ING Three Pole Trip Mode E
TPTrModB SPG Three Pole Trip Mode E
Z2BlkRec SPG Zone 2 fault blocking recloser E
MPFBlkRec SPG multi-phase fault blocking recloser E
TPFBlkRec SPG triple-phase fault blocking recloser E
OUTMATR ING Output Matrix E
 

3.2.15 RDIR: Directional element

RDIR class
Attribute Attribute Explanation M/O/E Remarks
Name Type

RDIR Directional element


Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Status Information
Dir ACD Direction M
Settings
ChrAng ASG Characteristic Angle O
MinFwdAng ASG Minimum phase angle in Forward O

 
direction
MinRvAng ASG Minimum phase angle in Reverse O
direction
MaxFwdAng ASG Maximum phase angle in Forward O
direction
MaxRvAng ASG Maximum phase angle in Reverse O
direction
BlkValA ASG Minimum operating current O
BlkValV ASG Minimum operating voltage O
MinPPV ASG Min Phase-Phase Voltage O
ROCChrAng ASG Characteristic Angle O
NgOCChrAng ASG Characteristic Angle O
Z0CVal ASG The compensated zero-sequence O
impedance
Z2CVal ASG The compensated negative-sequence O
impedance
ROCTVFEna SPG VTS disable DOC E
 

3.2.16 RFLO: Fault locator

RFLO class
Attribute Attribute Explanation M/O/E Remarks
Name Type

RFLO Fault locator


Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Measured and metered value
FltZ CMV Fault Impedance M
FltDiskm MV Fault Distance in km M
MaxFltA MV Max Fault Phase Current E
MaxFltI0A MV Max Fault I0 Current E
MaxFltDifA MV Fault Different Current E
FltValV MV Fault voltage E
FltImbValV MV Imbanlance fault voltage E
FltImbValA MV Imbanlance fault current E

 
FltAPhA MV Fault Phase A Current E
FltAPhB MV Fault Phase B Current E
FltAPhC MV Fault Phase C Current E
FltVPhA MV Fault voltage Phase A E
FltVPhB MV Fault voltage Phase B E
FltVPhC MV Fault voltage Phase C E
FltValV0 MV Fault voltage U0 E
Status Information
FltLoop INS Fault Phase O
Settings
LinLenKm ASG Line length in km O
R1 ASG Positive-sequence line resistance O
X1 ASG Positive-sequence line reactance O
R0 ASG Zero -sequence line resistance O
X0 ASG Zero -sequence line reactance O
Rm0 ASG Mutual resistance O
Xm0 ASG Mutual reactance O
 

3.2.17 RREC: Autoreclosing

RREC class
Attribute Attribute Explanation M/O/E Remarks
Name Type

RREC Autoreclosing
Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Status Information
Op ACT Operate M
AutoRecSt INS Auto Reclosing Status M
Str ACD In progress O
Op1 ACT Operate E
Op2 ACT Operate E
Op3 ACT Operate E

 
Op4 ACT Operate E
Settings
StopRec SPG Recloser Stoped E
Rec1Tmms ING Reclos Time for shot 1 O
Rec2Tmms ING Reclos Time for shot 2 O
Rec3Tmms ING Reclos Time for shot 3 O
PlsTmms ING Close Pulse Time O
RclTmms ING Reclaim Time O
UseCyc ING User actual set maximum number of E
Reclose cycles
MaxTmms ING Maximum time after fault dection during E
which autoreclosing is permitted
BrdenTmms ING Extend block AR time E
CBHlthTmms ING Wait CB healthy time E
SynRsDTmms ING Synchronousness Reset time delay E
SOTFEnTmms ING Timer to enable switch onto fault E
SPRecTmms ING single pole reclose time delay in ms E
TPRecTmms ING triple pole reclose time delay in ms E
RecDifAng ASG Reclose Angle E
Enable SPG Recloser Enabled E
RecChkSyn SPG Reclose check synchronousness E
RecChkDea SPG Reclose check dead line E
SPRChkLiv SPG SP recolse check live line E
OpnStrSPR SPG Breaker open start SP recloser E
OpnStrTPR SPG Breaker open start TP recloser E
ChkLivLin SPG Following reclose check live line E
SPRecMod SPG Single pole recloser mode E
TPRecMod SPG Triple pole recloser mode E
InhRec SPG Inhibit recloser E
CBClsTmms ING t_CBClsd_AR E
SynChkTmms ING t_Wait_SynChk E
UnsucTmms ING t_Unsuc_AR E
PWTmms ING t_PW_AR E
ARRclmTmms ING t_Reclaim_AR E
TrDurTmms ING Maximum Trip Command Duration Time E
BlkRecTmms ING Block Reclose Time E
ExDlTmms ING Extend Delay Time E
WtMTmms ING Wait Master Time E
Flt2Tmms ING Second Fault Discriminant Time E

 
RecCnt ING Reclosing Counter E
PriorOpt ING Optional Priority E
ExtCtrlEna SPG External Control Enable E
ExDlEna SPG Extend Delay Enable E
PlsWidEna SPG Pulse Width Enable E
USucChkEna SPG unsuccessful Position Check Enable E
EVFlBlkEna SPG EV Fault Block Reclosing Enable E
SPTPRecMod SPG SP and TP pole recloser mode E
RecEna SPG Recloser Enable E
InRecMod SPG In Recloser mode E
NoChkEna SPG No Check Enable E
AdpRecEna SPG Adaptation recloser enable E
OpTrgRec SPG Op trip enable recloser E
TVFBlkRec SPG TV Fail Block recloser E
LnDeaEna SPG Dead Line and Live Bus Enable E
BsDeaEna SPG Dead Bus and Live Line Enable E
LnBsEna SPG Dead Bus and Dead Line Enable E
AngOfs ASG Angle Offset between Ux and Ua E
LnDeaVal ASG Dead Line Value E
BsDeaVal ASG Dead Bus Value E
DbLnLvEna SPG Double line live check Enable E
Controls
OpStrp SPC Operate strap E
PhRecEna SPC Phase Reclosing E
StopRecEna SPC Stop Reclosing E
 

3.2.18 RSYN: Synchronism-check

RSYN class
Attribute Attribute Explanation M/O/E Remarks
Name Type

RSYN Synchronism-check
Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M

 
NamPlt LPL Name Plate M
Status Information
Rel SPS Release M
VInd SPS Voltage Difference Indicator O
AngInd SPS Angle Difference Indicator O
HzInd SPS Frequency Difference Indicator O
SynPrg SPS Synchronising in progress O
Measured and metered value
DifVClc MV Calculated Difference in Voltage O
DifHzClc MV Calculated Difference in Frequency O
DifAngClc MV Calculated Difference of Phase Angle O
RteHzClc1 CMV Calculated Difference of df/dt E
RteHzClc2 MV Calculated Difference of df/dt E
Settings
DifV ASG Difference Voltage O
DifHz ASG Difference Frequency O
DifAng ASG Difference Phase Angle O
LivDeaMod ING Live Dead Mode O
DeaLinVal ASG Dead Line Value O
LivLinVal ASG Live Line Value O
DeaBusVal ASG Dead Bus Value O
LivBusVal ASG Live Bus Value O
PlsTmms ING Close Pulse Time O
BkrTmms ING Closing time of breaker O
Enable SPG Enable E
ChkDeaPct ING Check Line Dead Percent E
ChkLivPct ING Check Line Live Percent E
SynRsTmms ING Synchronousness Reset time delay E
RteHz ASG df/dt Value E
TVFBlkDea SPG TV failure Block Check Dead Line E
TVFBlkSyn SPG TV failure Block Check E
Synchronousness
PhEna SPG En_PhVolt_Syn E
AngCor ASG Compensate Angle O
VolCor ASG Voltage Compact factor E
LnDeaEna SPG En_LvB_DdL_AR E
BsDeaEna SPG En_DdB_LvL_AR E
LnBsDeaEna SPG En_DdB_DdL_AR E

 
OpCmd ING Operate Command Type E
SynVTyp ING Synchronousness Voltage Type E
ChkVTmms ING Voltage Check time delay E
SynDlTmms ING Synchronousness Check time delay E
Lin1VoltPh ING Line 1 Voltage Phase Select E
Bus1VoltPh ING Bus 1 Voltage Phase Select E
Lin2VoltPh ING Line 2 Voltage Phase Select E
Bus2VoltPh ING Bus 2 Voltage Phase Select E
CfgMod ING Config Mode E
SynComFact ASG Voltage Compensation Factor E
DfHzChkEna SPG Difference Frequency Check Enable E
FixDifAng ASG phi_Fix_Diff E
RecChkSyn SPG Reclose check synchronousness E
RecChkDea SPG Reclose check dead line E
VBlk ASG Voltage Block E
 

3.2.19 TCTR: Current transformer

TCTR class
Attribute Attribute Explanation M/O/E Remarks
Name Type

TCTR Current transformer


Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Status Information
EEHealth INS External equipment health O
OpTmh INS Operation time O
Descriptions
EEName DPL External equipment name plate O
Measured and metered value
Amp SAV Current (Sampled value) M
AmpChB SAV Current (Sampled value from another E
channel)

 
Settings
ARtg ASG Rated Current O
HzRtg ASG Rated Frequency O
ARtgSnd ASG Secondary Rated Current E
ECVTDelay ASG ECVT Delay time E
IROCCTFail ASG CT Fail over current value O
BlkCTFail SPG CT Fail Block Protection E
CTPAB SPG CT Phase AB E
CTPBC SPG CT Phase BC E
CTPCA SPG CT Phase CA E
 

3.2.20 TVTR: Voltage transformer

TVTR class
Attribute Attribute Explanation M/O/E Remarks
Name Type

TVTR Voltage transformer


Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Status Information
EEHealth INS External equipment health O
OpTmh INS Operation time O
FuFail SPS TVTR fuse failure O
Descriptions
EEName DPL External equipment name plate O
Measured and metered value
Vol SAV Voltage (sampled value) M
VolChB SAV Voltage (sampled value from another E
channel)
Settings
VRtg ASG Rated Voltage O
HzRtg ASG Rated frequency O
VRtgSnd ASG Secondary Rated Voltage E

 
LinTVMod SPG Line TV MODE E
TVFChkEna SPG TV Failure Check Enable E
 

3.2.21 XCBR: Circuit breaker

XCBR class
Attribute Attribute Explanation M/O/E Remarks
Name Type

XCBR Circuit breaker


Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Status Information
Loc SPS Local operation (local means without M
substatcommunication, hardwired direct
control) ion automation
EEHealth INS External equipment health O
OpCnt INS Operation counter M
CBOpCap INS Circuit breaker operating capability M
POWCap INS Point On Wave switching capability O
MaxOpCap INS Circuit breaker operating capability O
when fully charged
Alm SPS Alarm O
TCCSAlm SPS TCCS alrm E
Descriptions
EEName DPL External equipment name plate O
Controls
Pos DPC Switch position M
BlkOpn SPC Block opening M
BlkCls SPC Block closing M
ChaMotEna SPC Charger motor enabled O
Settings
DPUTmms ING DPU time set E
DDOTmms ING DDO time set E
TPCBEna SPG TPCB enable E

 
 