You are on page 1of 6

  

 
Model Implementation Conformance Statement
for the IEC 61850 interface in PCS-222

Jun 8, 2016

UCA International Users Group


Testing Sub Committee

         
INDEX
page

INDEX ...........................................................................................................ii 

1. Introduction .............................................................................................3 

2. Logical Nodes List ..................................................................................4 

3. Logical Node Extensions .......................................................................5 


3.1. New Logical Nodes........................................................................5 
3.2. Extended Logical Nodes ................................................................5 
3.2.1 LLN0: Logical node zero ........................................................5 
3.2.2 TCTR: Current transformer ....................................................6 
3.2.3 TVTR: Voltage transformer ....................................................6 

 
1. Introduction

This model implementation conformance statement is applicable for PCS-222


This MICS document specifies the modelling extensions compared to IEC 61850
edition 2. For the exact details on the standardized model please compare the ICD
substation configuration file: "device.icd", version 1.00.

Clause 2 contains the list of implemented logical nodes.


Clause 3 describes the new and extended logical nodes.
Clause 4 describes the new and extended common data classes (if any).
Clause 5 describes the new and extended enum types.
Clause 6 describes any other extensions.

 
2. Logical Nodes List

The following table contains the list of logical nodes implemented in the device:

G:Logical nodes for generic references


GGIO (Generic process I/O)
L:System logical nodes LN group
LLN0 (Logical node zero)
LPHD (Physical device information)
T:Logical nodes for instrument transformers and sensors
TCTR (Current transformer)
TVTR (Voltage transformer)
X:Logical nodes for switchgear
XCBR (Circuit breaker)
XSWI (Circuit switch)

 
3. Logical Node Extensions

The following table use


M : Data is mandatory in the IEC-61850-7-4.
O: Data is optional in the IEC-61850-7-4 and is used in the device.
E: Data is an extension to the IEC-61850-7-4.

3.1. New Logical Nodes

New logical nodes have the lnNs attribute in the Name plate. The value of lnNs is a
reference to the MICS document.

There is no new logical node.

3.2. Extended Logical Nodes

The following logical nodes have been extended with extra data. All extra data has
been highlighted in the tables and marked as "E" (Extended), these data contains the
"dataNs" attribute.

3.2.1 LLN0: Logical node zero

LLN0 class
Attribute Attribute Explanation M/O/E Remarks
Name Type

LLN0 Logical node zero


Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Measured and metered value
DelayTRtg SAV SV Delay time E
 

 
3.2.2 TCTR: Current transformer

TCTR class
Attribute Attribute Explanation M/O/E Remarks
Name Type

TCTR Current transformer


Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Measured and metered value
Amp SAV Current (Sampled value) M
AmpChB SAV Current (Sampled value from another E
channel)
 

3.2.3 TVTR: Voltage transformer

TVTR class
Attribute Attribute Explanation M/O/E Remarks
Name Type

TVTR Voltage transformer


Data
Common Logical Node Information
Mod INC Mode M
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name Plate M
Measured and metered value
Vol SAV Voltage (sampled value) M
VolChB SAV Voltage (sampled value from another E
channel)
 
 

You might also like