Professional Documents
Culture Documents
To protect synchronous generator from damage that could In order to differentiate the setting between the protection
occur due to out-of-step and loss of field, offset mho relay is used. for 2 different yet similar situation an impedance relay is used
Out-of-Step Relay is used for both relay but because the nature to monitor the voltage and current in generator’s terminal.
of their setting they are differentiated. This paper will discuss Voltage and current will be used to read the mechanical terms
how out-step-relay and loss of field relay works in general and from the prime mover, such as torque and angle speed of the
calculate the recommended setting value based on manufacture prime mover. This 2 value will then be used to determine
handbook. After calculation, the recommended calculated value whether the generator is better suited for loss of excitation
for out-of-step relay setting is the following Diameter with the
protection or out-of-step protection. The value of which the
value of 11.3Ohm, Offset with the value of -8.4Ohm, Blinder
offset mho impedance relay must set is calculated from the
Impedance with the value of 2Ohm and Impedance Angle with
the value of 90o. The recommended calculated value for loss of
property of generator to best suit its operation.
synchronism relay setting is the following: Diameter with the
value of 31Ohm, Offset with the value of -2.1Ohm, Trip Delay for II. THEORY
30 cycles dan directional element angle with the value of 18Ohm.
A. Synchronous Generator
Keywords— Synchronous Generator, Out-of-Step, Loss of
Many important features of synchronous-machine behavior
Field, Offset Mho Relay
can be understood from the analysis of a single machine
connected to an infinite bus. The steady-state behavior of a
I. INTRODUCTION synchronous machine can be visualized by the following terms
Synchronous generator is one of the most important part of torque equation.
any power generating unit. Thus this component must be
properly protected from any problem that could occurred
(1)
during its operation, so that it could still operate at any time
and if it has to be stopped from running it could be restarted in Where
no time. One of the problem that any big generator could faced
is running out of step and the loss of its excitation field. ϕR = resultan flux celah udara per kutub
Any generator could run out of step if its prime mover Ff = mmf dari belitan medan DC
torque exceeds its electromechanical torque induced in its air δRF = beda fasa elektrik antara sudut ϕR dan Fff
gaps. This situation could occur when there is massive power
swing in the system that caused change in frequency of the
system, or because the electromechanics torque is suddenly As the prime-mover torque is increased, the magnitude of
reduced to nothing because there is no current running in the δRF must increase until the electromechanical torque balances
stator winding. This problem is also known as loss of the shaft torque. The oscillation that is caused by this process
excitation. of readjustment is called hunting transient.
Loss of excitation mostly caused by failure in the generator The characteristic of torque-angle relationship from torque
excitation system. Be it from short circuit, rectifier failure, or equation could be observed from Fig.1. An increase in prime-
any other reasons unknown. When loss of excitation happened, mover torque will result in a corresponding increase in the
the stator winding will suddenly loss its magnetic field, hence torque angle. When ~RF becomes 90 °, the electromechanical
removing any electromechanical coupling between its rotating torque reaches its maximum value, known as the pull-out
magnetic field and rotating prime mover shaft. torque. Any further increase in prime-mover torque cannot be
balanced by a corresponding increase in synchronous power on generator terminals. When the under-excitation limit
electromechanical torque, with the result that synchronism will is achieved, the loss of synchronism occurs (the relation
no longer be maintained and the rotor will speed up. This between the stator and rotor is already very week at this time).
phenomenon is known as loss of synchronism or pulling out of This whole process is similar to loss of static stability of
step [1]. synchronous machine. The loss of excitation is a transient
phenomenon of medium speed with the time interface of
several seconds [2][3].
The loss of excitation can have adverse effect not only on
the generator itself, but also on the whole grid and adjacent
generators — mainly if they are connected to common point
with the generator that lost excitation (i.e.generators in one
power plant). if generator lost excitation it changes into
significant consumer of reactive power. If this generator is not
shut down, the adjacent generators start increasing the
production of reactive power up to the limit when their limiters
of rotor and stator currents act.
If the grid cannot cope with increased supply of reactive
Fig. 1 Torque-angle characteristic power, it can cause overloading and subsequent the
transmission lines outages in cascades. Significant decrease of
When a generator is operating at a leading power factor, the voltage in individual nodes of the grid and the resultant threat
excitation and hence the flux produced by the rotor is weak. of voltage collapse could have another adverse effect.[2]
Consequently the magnetic coupling between rotor and stator
rotating magnetic fields is also weak. If the generator is loaded Loss of excitation protection is the so called impedance
under this condition, a large torque is produced. When this load type of protection. Their first installations reach back to 50-ties
angle reaches 90°, the generator is producing the maximum of the last century. The impedance principle is with good
amount of power for the excitation being used and is said to be results used also nowadays, since it has high ability to detect
operating at its steady state stability limit. loss of excitation and at the same time is very reliable.
However, there is an area of generator operation when this type
When the generator is operating at a leading power factor, of protection can function improperly. These are the cases
the flux produced by the rotor is weaker and more flux is able when generator operated in under excited condition, during
to leak out from the ends of the stator core. When this flux stable transient power swings in the grid and during significant
leaks out from the ends of the stator core, it passes through the system outages with frequency drop.
face of each lamination and causes large eddy currents to flow
in these laminations. These eddy currents can cause excessive Example of measured impedance on generator terminals is
heating. [2] shown on Fig. 2. It can be seen that the impedance trajectory
seen by the protection on machine terminals crosses the
B. Generator Loss of Excitation (LoE) characteristic of loss of excitation protection and enters into it.
Typical operation characteristics of loss of excitation protection
The essential function of excitation system is to supply are presented in Fig. 3. The characteristics shown on Fig. 2a
direct current for the power of synchronous machine excitation and b are defined by the IEEE standard [9]. The characteristic
winding. Basic components of static excitation systems are (b) has an extra directional element built in in order to prevent
thyristor rectifiers, controlled with excitation regulator by undesirable operation of protection during some swing effects
means of thyristor ignition impulse circuits. This can be in the grid or close faults [2].
performed in two ways via the transformer, namely either from
an independent source (so called independent excitation) or
directly from the generator (so called dependent excitation).
The main benefit of static excitation systems is the speed with
which the excitation voltage responds to the change of
regulator voltage.
Loss of excitation of synchronous generator can be caused
by several factors, such as power supply outage, exciter
damage or short circuit in the excitation winding. Regardless of
the reason the loss of excitation represents a high risk with
regard to synchronous generator damage. In addition, outage of
synchronous generator with high unit power represents a
significant risk for the stability of electricity grid. During loss Fig. 2 Measured trajectory in the impedance plane during loss of excitation
of excitation the current in excitation winding decreases
(exponentially). Proportionally also the internal electromotive
force and the electromagnetic relation between the stator and
rotor decrease. This is reflected in gradual decrease of reactive
time, then an OOS is declared and an outof-step blocking
signal is issued to block the distance relay element operation.
Impedance measurement elements with different shapes have
been used over the time[4]. These shapes include double
blinders, concentric polygons, and concentric circles as shown
in Fig. 4
Typical Setting is 90o Then from the reactance parameter above we could
calculate the relay setting of generator. The primary impedance
5. Setting of Delay %Z (%) is converted to relay side impedance Z ( Q) by the
Typical setting is 3 to 6 cycles, setting = 6 cycles following formula:
2. Circle Offset
The large circle offset is set to the generator
transient reactance Xd'/2.
IV. CONCLUSION
Thus after calculation has been performed for both relay
setting, the recommended calculated value for out-of-step relay
setting is the following Diameter with the value of 11.3Ohm,
Offset with the value of -8.4Ohm, Blinder Impedance with the
value of 2Ohm and Impedance Angle with the value of 90o.
The recommended calculated value for loss of synchronism
relay setting is the following: Diameter with the value of
31Ohm, Offset with the value of -2.1Ohm, Trip Delay for 30
cycles dan directional element angle with the value of 18Ohm.
It is advised to ensure the usage of terms offset for both relay to
prevent dangerous misunderstanding that may caused relay
operating in wrong region.