Customer:CADDCENTRE, PUTHUR, TRICHY By Pass Factor : 0.1
Estimated by: ___________________________ Contact Factor : 0.9 Space Dimensions: 30 L X 60 W = 1800 Sq.ft X 15 H = 27000 cft. COOLING LOAD CALCULATION SHEET - SUMMER SEASON SENSIBLE HEAT GAINS Design Conditions 1. SUN GAIN GLASS - DIRECT EXPOSURE Conditions DB WB %RH DP W Orientation Source - Area U A ∆T Q Outside 104 81 38 73 123.6 North Glass 0.215 27 39 226.5 Room 75 62.53 50 55 64.9 South Glass 0.215 27 14 81.27 Difference 29 18.47 -12 18 58.7 East Glass 0.215 137 158 4653.89 10.49 West Glass 0.215 137 158 4653.89 Latitide: 10.4 North-East Glass - Daily Range 20 South-East Glass - CFM Ventilation North-West Glass - 45 _____ People X _______ 10 450 cfm / person = ______ South-West Glass - 180 sq. ft X _________ _____ 0.18 cfm / sq. ft = _________ 324 2. SOLAR GAIN - WALLS AND ROOF - DIRECT EXPOSURE No. of fresh air changes / hour Source Area Orientation U A ∆T Q 27000 cu. Ft X _______ ________ 12 5400 X 1/60 = ________ Wall N 0.746 423 19 5995 Wall S 0.746 423 31 9782 CFM Infiltration Wall E 0.746 763 40 22768 Windows Wall W 0.746 763 27 15368 _____ 96 0.37 cfm / windows = _______ Perimeter X _______ 35.52 Roof 0.746 1800 50 67164 Open Doors 3. TRANS GAIN THROUGH PARTITION 256 Sq. ft X _______ _______ 1 256 cfm / door = _______ Source Area U A ∆T Q ACH All Glass - _________ 0.6 27000V /60 = _________ ACH X _______ 270 Wall - Ceiling - Floor - 4. INTERNAL HEAT People (No.) 45 250 ____ X _________ SH / person 11250 Air Flow Calculation Lights (Watts) _________ 2520 X 3.41 8593 5. INFILTRATION AND BY PASSED AIR 270 Infiltration _________ 29 cfm X _______ ΔT X 1.08 8456.4 0.9 (75-48) Ventilation Air _____ 5400 cfm X _____ 29 ΔT X ___ 0.1 BF X 1.08 16913 Dehumidifie 24.3 (1 - BF) (Room Temperature - SENSIBLE HEAT GAIN TOTAL (SHGT) 175905 d Air Rise = ADP)48 Safety Factor % (5-10%) 17590.5 (DAR) EFFECTIVE SENSIBLE HEAT GAIN TOTAL (ESHGT) 193495.5 LATENT HEAT GAINS Effective (Effective Sensible Heat Gain 270 Infiltration _________ 58.7 ΔW X 0.68 cfm X _______ 10777 Sensible Total + Outside Air Sensible = 5400cfm X _____ Ventilation Air _____ 58.7ΔW X ___0.1BF X 0.68 21555 Heat Factor Heat Gain) / Grand Total Heat 45 X _________ People (No.) ____ 250 LH / person 11250 (ESHF) Gain Appliances etc LATENT HEAT GAIN TOTAL (LHGT) 43582 (Effective Sensible Heat Gain Supply Duct Loss Leakage Loss Safety Factor (2.5-5%) 2179.1 Air Flow = Total + Outside Air Sensible EFFECTIVE LATENT HEAT GAIN TOTAL (ELHGT) 45761.1 Heat Gain) / (1.08 X DAR) EFFECTIVE ROOM TOTAL HEAT GAIN (ERTHG) 239257 OUTSIDE AIR HEAT / VENTILATION LOAD CADDCENTRE, Sensible _____ 29 ΔT X 0.9 5400 cfm X ______ ____ (1-BF)X1.08 152215 1C, E.V.R. ROAD, Latent _____ 5400 cfm X ______ 58.7 ΔW X ____ 0.9 (1-BF)X0.68 193992 Opp. CHINTHAMANI, OUTSIDE AIR HEAT GAIN (OAHG) 346207 NEAR G.H. GRAND TOTAL HEAT GAIN (GTHG) 478518 PUTHUR, TRICHY TONS = GRANT TOTAL HEAT GAIN / 12000 39.87