E 20 CALCULATION

Customer:CADDCENTRE, PUTHUR, TRICHY By Pass Factor : 0.1


Estimated by: ___________________________ Contact Factor : 0.9
Space Dimensions: 30 L X 60 W = 1800 Sq.ft X 15 H = 27000
cft. COOLING LOAD CALCULATION SHEET - SUMMER SEASON
SENSIBLE HEAT GAINS Design Conditions
1. SUN GAIN GLASS - DIRECT EXPOSURE Conditions DB WB %RH DP W
Orientation Source - Area U A ∆T Q Outside 104 81 38 73 123.6
North Glass 0.215 27 39 226.5 Room 75 62.53 50 55 64.9
South Glass 0.215 27 14 81.27 Difference 29 18.47 -12 18 58.7
East Glass 0.215 137 158 4653.89 10.49
West Glass 0.215 137 158 4653.89 Latitide:
10.4 North-East Glass - Daily Range 20
South-East Glass - CFM Ventilation
North-West Glass - 45
_____ People X _______
10 450
cfm / person = ______
South-West Glass - 180 sq. ft X _________
_____ 0.18 cfm / sq. ft = _________
324
2. SOLAR GAIN - WALLS AND ROOF - DIRECT EXPOSURE No. of fresh air changes / hour
Source Area Orientation U A ∆T Q 27000 cu. Ft X _______
________ 12 5400
X 1/60 = ________
Wall N 0.746 423 19 5995
Wall S 0.746 423 31 9782 CFM Infiltration
Wall E 0.746 763 40 22768 Windows
Wall W 0.746 763 27 15368 _____
96 0.37 cfm / windows = _______
Perimeter X _______ 35.52
Roof 0.746 1800 50 67164 Open Doors
3. TRANS GAIN THROUGH PARTITION 256 Sq. ft X _______
_______ 1 256
cfm / door = _______
Source Area U A ∆T Q ACH
All Glass - _________
0.6 27000V /60 = _________
ACH X _______ 270
Wall -
Ceiling
-
Floor -
4. INTERNAL HEAT
People (No.) 45 250
____ X _________ SH / person 11250
Air Flow Calculation
Lights (Watts) _________
2520 X 3.41 8593
5. INFILTRATION AND BY PASSED AIR
270
Infiltration _________ 29
cfm X _______ ΔT X 1.08 8456.4
0.9 (75-48)
Ventilation Air _____
5400 cfm X _____
29 ΔT X ___
0.1 BF X 1.08 16913 Dehumidifie 24.3
(1 - BF) (Room Temperature -
SENSIBLE HEAT GAIN TOTAL (SHGT) 175905 d Air Rise =
ADP)48
Safety Factor % (5-10%) 17590.5 (DAR)
EFFECTIVE SENSIBLE HEAT GAIN TOTAL (ESHGT) 193495.5
LATENT HEAT GAINS Effective (Effective Sensible Heat Gain
270
Infiltration _________ 58.7 ΔW X 0.68
cfm X _______ 10777 Sensible Total + Outside Air Sensible
=
5400cfm X _____
Ventilation Air _____ 58.7ΔW X ___0.1BF X 0.68 21555 Heat Factor Heat Gain) / Grand Total Heat
45 X _________
People (No.) ____ 250 LH / person 11250 (ESHF) Gain
Appliances etc
LATENT HEAT GAIN TOTAL (LHGT) 43582 (Effective Sensible Heat Gain
Supply Duct Loss Leakage Loss Safety Factor (2.5-5%) 2179.1 Air Flow = Total + Outside Air Sensible
EFFECTIVE LATENT HEAT GAIN TOTAL (ELHGT) 45761.1 Heat Gain) / (1.08 X DAR)
EFFECTIVE ROOM TOTAL HEAT GAIN (ERTHG) 239257
OUTSIDE AIR HEAT / VENTILATION LOAD CADDCENTRE,
Sensible _____ 29 ΔT X 0.9
5400 cfm X ______ ____ (1-BF)X1.08 152215 1C, E.V.R. ROAD,
Latent _____
5400 cfm X ______
58.7 ΔW X ____
0.9 (1-BF)X0.68 193992 Opp. CHINTHAMANI,
OUTSIDE AIR HEAT GAIN (OAHG) 346207 NEAR G.H.
GRAND TOTAL HEAT GAIN (GTHG) 478518 PUTHUR, TRICHY
TONS = GRANT TOTAL HEAT GAIN / 12000 39.87