Professional Documents
Culture Documents
MSR127
The MSR127 safety relay goes into a lockout state when it detects a fault condition. The fault condition can be either
external or internal to the MSR127, as the MSR127 monitors external devices as well as itself. This lockout state
prevents the safety outputs from being energized, until the fault condition is corrected and the MSR127 is satisfied.
In many cases, the fault will be either an open-circuit or a short-circuit condition. In these cases, a digital multimeter
can be used to accomplish the troubleshooting. An oscilloscope is needed when timing issues are suspected of
causing lockouts.
To begin the process, a block diagram of the MSR127 and an application schematic is needed. We also need to know
which type of reset is being used. The MSR127 comes with either Monitored Manual reset or automatic/manual reset.
The internal sequence of events is slightly different for each.
For monitored manual reset, the input devices must be closed prior to the closing of the reset circuit. For
automatic/manual, the reset circuit can be closed either before or after the inputs are closed.
In this guide, the reader is asked to make measurements with a multimeter. An example of the terminology used is
“S12/S22”, where one test lead is placed on terminal S12 and the other terminal is placed on terminal S22.
!
Troubleshooting safety relay based systems sometimes requires the application of power.
Troubleshooting must be performed by trained persons familiar with safety publications ANSI
NFPA70E and ANZI Z244.1 and local applicable codes.
11 12 11 12 A1 A2
24-33
21 22 21 22 VDC + ~
Brown/Green Pwr
33 34 33 34
S11
CH2
S52 CH2
White/Green
S22
S34 Logic
Blue S21
White/Yellow CH1 CH2 A1 A2
13 14 K2
23 24 K1
A1 A2
33 34 Red
41 42
Start Stop Safety System
De-energized
13 14 13 14 Reset
51 52 51 52
K1 K2
K1 K2 Machine ON
L1 T1 L1 T1
K1 K2 Green
Brown Brown
1 2
A1 A2
24-33
VDC + ~
Pwr
S11
Gray (OSSD1) CH2
5 S52 CH2
S22
S34 Logic
3
Green S21
CH1 CH2 A1
K2 A2
Sender GuardShield Receiver 13 14
440L-P4K****YD
23 24 K1
A1 A2
33 34 Red
41 42
Safety System
Start Stop De-energized
13 14 13 14
Reset
K1 K2 51 52 51 52
K1 K2 Machine ON
L1 T1 L1 T1
K1 K2
Green
3) Power Supply
The power supply is protected by a PTC (positive temperature coefficient) electronic fuse in the A1 circuit - as the
current increases, the resistance increases. If a short circuit or overload occurs, the resistance goes up to prevent
damage to the MSR127. When the fault is cleared, the resistance returns to normal, and the MSR127 begins to
operate properly.
Step P1
Is power LED on?
If yes, go to Step P3.
If not, go to Step P2.
Step P2
Measure supply voltage at A1/A2 for 24VDC, 115VAC, or 230VAC.
DMM
24VDC, 24 Example for 24VDC
115VAC or Volts Ground Reference Information: Power Supply Current
230VAC
The power supply current depends on the type of
input and short circuit faults. Use an ammeter to
measure the current. Values shown with safety
Ammeter A1 A2 outputs energized.
24-33
VDC + ~
Pwr
Light Curtain 1.6mADC @ 19.2VDC
S11 2.1mADC @ 24.0VDC
CH2
S52 CH2 2.3mADC @ 26.4VDC
S22
S34 Logic Check Power 2 NC Contacts 31mADC @ 19.2VDC
Supply on 39mADC @ 24.0VDC
S12 CH1
CH1
Side Label 44mADC @ 26.4VDC
As a reference, the current used by the MSR127, with its safety outputs energized, is shown in the side
table. This tables shows the typical current when the MSR127 is functional and its safety outputs are
energized.
A1 A2
24-33
VDC
+ ~
Pwr
S11
CH2
S52 CH2
DMM
S22
24
S34 Logic
Volts
CH1
S12 CH1
S21
Should be CH1 CH2
13 14
17 to 33 VDC 23 24
depending 33 34
on Supply Voltage 41 42
Step P4
Did the Power LED on?
If yes, pop out the top terminal block. Use your ohm meter and check for shorts between the following
terminals.
If a short is found, trace the input wiring and remove the short. Re-insert the top connector. Go to Input
Circuits.
When troubleshooting 2NC circuits, the easiest approach is to measure the cross channel voltage at each of the
devices. Open the cover of an interlock to expose the wiring terminals. . The two contacts closest to the
actuator are the safety contacts. Using a voltmeter, measure the voltage from Channel 1 to Channel 2.
9 ²
898R-P68MT
J2 J8 J7 J3 J1
Brown/Green 1 5 1 5 1 5 1 5 1 5 Brown/Yellow
6-Pin QD
White/Yellow 2 6 2 6 2 6 2 6 2 6 White/Green
898D-48LT
J8 J7 J2 J1
Blue 3 1 3 1 3 1 3 1 Brown
4-Pin QD
Black 4 2 4 2 4 2 4 2 White
If either S12 or S52 measures zero volts, check the wiring going back to the light curtain.
Step LC2
Press the reset button. Do CH1 and CH2 :LEDs turn on?
If yes, go to Step O1.
If not, go to Step R1.
Note: Light curtains perform their own diagnostics. For example, a crossfault from Ch1 to Ch2 will be detected by
the light curtain, not by the MSR127. Faults detected by the light curtain are usually indicated by red blinking LEDs
on the light curtain. This troubleshooting guide is not intended to cover light curtain troubleshooting.
For applications using automatic reset with a jumper from S12 to S34, the reset circuit should be opened
momentarily to confirm 0V between S34 and S21. Go to Step R2.
Step R2
Measure the circuit resistance of each component in the reset circuit. Pop out the top and bottom wiring
terminals, and measure the resistance of the reset wiring.
If circuit is O.L when the button is pressed, then follow the circuitry, point by point until the open circuit is
found. In Example Schematic #1, the following points should be tested.
To be more precise, the reset actually takes place at the tail end of the reset voltage signal. This can be
shown by placing a resistor in reset signal and measuring at the voltage across that resistor. For automatic
reset MSR127, the duration of the reset current is 22ms and it has a peak amplitude of 18ma.
Channel 1
30ms 22mA
Peak
Reset
30ms Complete
Reset
Complete
Step O3
DMM DMM
0.235 120
Amps Volts
120VAC
Power Gnd
CH1 CH2
A1 A2
13 14 K1
A1 K2 A2
23 24
34 A1 A2
33 K3
A1 A2
41 42 K4
MSR138.1DP
DMM DMM
120 120
Volts Volts
Step O1 Step O2
Step O1
Check the supply side of the output contacts. Does the voltage at terminals 13, 23, 33 and 41 with respect to the
appropriate power supply reference (this may not be the same as A2 or S21), meet expectations?
Step O2
With the CH1 and CH2 LEDs on, do the voltages on the load side of the safety relay meet expectations?
If yes, go to Step O3.
If not, then the output contact in the MSR127 may be worn or contaminated. To confirm this, remove the
power wires from the terminals (both the supply and load side) and use an ohm meter to measure the
contact resistance. [This is not shown in the figure above.] Cycle the inputs and measure the resistance a
few times, as the circuit may be intermittent.
Step O3
The output voltage is ok. Does the load energize?
If yes, then MSR127 works OK. EOT.
If not, the trouble resides with the wiring to the load or the load itself. The load may be disconnected or not
functioning properly. Measure the voltage at the load. Measure the current going to the load. Replace the
load, if necessary.
A demand is placed on the safety relay when the input is opened. For example, opening a safety gate, pressing an e-
stop, or breaking a light curtain places a demand on the safety relay. The safety relay responds by opening its safety
output – this is known as the response time. Now the safety relay must get ready for the closing of the input circuit,
that is, get ready for the next demand. This is known as the recovery time.
Recovery Time
Closed
Input Open
Closed
Output
Open
Response Time
In the following schematic, a three position switch is used to place the machine in either the Run, Safe or Jog state.
The user will likely want to switch from Run to Jog Mode, without having to create a safety stop. When this happens,
the rotation of the switch must pass through the safe position each time. Switching from Run to Jog can easily be
accomplished within the recovery time of the safety relay. When this happens the safety relay goes into lockout. In
this example, an e-stop would have to be pushed and then released to reset the safety relay and allow the user to jog
the machine.
To fix this, the switch must be rewired to move the Safe stop to an outside position. In addition, a keyed switch
should be used to allow the operator to lock the machine in a safe state.
Recovery time lockouts can also occur when using light curtains, as objects can pass through the light curtain in less
than 100ms.
MSR127 Toubleshooting Guide Rev D.doc Page 14 of 14 November 11, 2005