You are on page 1of 9

30th International Conference on Lightning Protection - ICLP 2010

(Cagliari, Italy - September 13th -17th, 2010)

ASSESSMENT OF LIGHTNING CURRENT PARAMETERS


SUITABLE FOR ANALYSIS OF HV SUBSTATION
OVERVOLTAGE PROTECTION
Petar Sarajcev
University of Split
Faculty of Electrical Engineering, Mechanical Engineering and Naval Architecture
Rudjera Boskovica bb, HR-21000 Split, Croatia
petar.sarajcev@fesb.hr

ABSTRACT neighboring towers of the incoming overhead


transmission lines [3]. If they should produce a
This paper will present theoretical and mathematical backflashover, associated overvoltage wave on the phase
background of the process which aims at evaluation of conductor would have a significant steepness of the surge
lightning current parameters suitable for the analysis of front (i.e. very short wave crest duration – almost
high voltage transformer station overvoltage protection. It is
vertical). Since there is no time for the attenuation of this
a well appreciated fact that the analysis of overvoltage
protection for the high voltage substation stems from the
wave (due to the short distance), upon its arrival, it exerts
backflashover analysis on several first neighboring towers maximum amount of stress on the associated HV
of the incoming overhead transmission line. Statistical substation equipment. Whence, backflashover analysis on
distribution of lightning current parameters is employed in the several first towers of the incoming HV overhead
the process of deriving analytical expression which transmission lines is often necessary for the efficiency
expresses a probability of lightning current with specific assessment of the HV substation overvoltage protection
parameters (striking several first towers as seen from the (or as a part of its design process).
substation) being exceeded only once during the specified For example, lightning protection design for the 275
time frame. A typical numerical example will corroborate
kV substations in Japan necessitates a lightning stroke of
the analysis with concrete results.
100 kA amplitude having front duration of 1 µs and wave
1 INTRODUCTION duration of 70 µs, hitting the very first tower from the
substation. Such strict lightning current parameters might
High voltage (HV) transformer stations and not be necessary in all cases of HV substations (e.g.
switchyards necessitate overvoltage protection, which is 110 kV and 220 kV), except perhaps in some special
designed by means of metal-oxide (MO) surge arresters. instances.
Analysis of the HV transformer station (i.e. substation) This paper thus provides a complete mathematical
overvoltage protection needs to be carried out in regards background of the process which aims at the evaluation
to the switching and lightning overvoltages which could of the lightning surge current parameters (e.g. amplitude,
be expected for the site. This analysis is often performed front duration and wave duration) suitable for the
with a sophisticated software package, such as the well- analysis of the backflashover on the several first towers
known EMTP (ElectroMagnetic Transients Program) of the incoming HV transmission lines. The model itself
software package, e.g. [1, 2]. stems from the statistical distribution of lightning stroke
Especially important is a lightning surge analysis, due current parameters, lightning incidence and geometrical
to its emphasized traveling wave phenomena, which in- constraints associated with the HV transmission lines. It
turn results with a confined (i.e. short) protection zones needs to be stated that, apart from lightning surge current
of the installed MO surge arresters. Hence, lightning amplitude, other lightning parameters, such as front
induced overvoltages exert significant stress on the HV duration (or current front steepness), have significant
substation equipment [3]. Due to the fact that a direct influence on the probability of occurrence of a
lightning strike to the HV substation is not allowed (by backflashover (as well as tower footing surge impedance
means of the LPS), lighting overvoltages on the incoming and other associated phenomena), e.g. [4, 5].
HV overhead power transmission lines provide inputs for This paper therefore provides a statistical probability
the overvoltage analysis (and arrester selection of lightning surge current (striking several first
procedures). Whence, especially important are the so- transmission line towers) being exceeded only once
called near-by lightning strikes, hitting one of the first

1001-1
during the specified time frame. This lightning surge the log-normal distribution are not uniquely defined for
current, in addition to the amplitude, has a specific the entire world. Significant differences exist between
duration of the surge front (and the wave duration as different regions, influenced by orographic and other
well). In other words, correlation between lightning surge parameters. Additionally, there are appreciable seasonal
current amplitude and front duration (or steepness) is differences in some regions, such as for example
taken into account while deriving the probability of infamous winter lightning in Japan [8]. Also, differences
transmission line tower lightning incidence. Only the arise between statistical data provided by different
downward lightning is considered is this process, as is researchers due to differences in measuring equipment
customarily done. and other factors, which subsequently influence derived
parameters of the log-normal distributions. Whence,
2 MATHEMATICAL MODEL definition of a median value and a standard deviation for
Derivation of the mathematical model for the the log-normal distribution of the lightning surge
assessment of lightning surge current parameters parameters (e.g. amplitudes) is still a matter of ongoing
associated with backflashover analysis on transmission research throughout the world.
line towers incoming to the HV substation is hereafter In order to appreciate the differences between lightning
presented. surge parameter distributions, a brief summary
aggregated from several different sources, is presented in
2.1 Lightning stroke current parameters Table I. Approximately 90% of all lightning strokes are
negative in polarity, while the remaining 10% of the
Lightning is a stochastic natural phenomenon, which lightning strokes are positive. Due to the fact that
has a distinct waveshape, described by four basic negative polarity lightning strikes will be hereafter
parameters: amplitude, duration of the current front, mainly treated, only the parameters for the statistical
duration of the current wave and polarity. It has been distribution of amplitudes, of the first negative lightning
established that a cumulative probability distribution of strokes, are given in Table I. Exclusion of positive
the lightning surge parameters (e.g. peak values) follow a polarity lightning from the analysis renders this paper
logarithmic - normal distribution [6, 7]. Statistical more legible, while maintaining full generality of the
variation of the logarithm of random variable from log- matter at hand.
normal distribution follows the normal (Gaussian)
distribution. Hence, one can easily determine the Table I: Parameters of log-normal distribution of lightning
cumulative probability that a certain value of random current amplitudes.
variable will be exceeded, e.g. [7].
In accordance with the above stated facts, mentioned
cumulative probability of log-normal distribution (e.g. Parameter Iµ (kA) σ ln I Lightning stroke type
probability that a certain value of lightning current First negative, from
amplitude will be exceeded) can be evaluated by the 30.1 0.76
[7, 9]
following expression [6, 7]:
I (kA) 31.1 0.48 First negative, from [7]
P ( I ) = 0.5 ⋅ erfc(u 0 ) (1)
First negative (Japan),
39.2 0.76
where from [10]

2 ∞
(−1) n ⋅ u 02 n+1 It needs to be accentuated that Table I presents data for
erfc(u 0 ) = 1 − ∑ (2)
the lightning current distributions to HV transmission
π n =0 n!⋅( 2n + 1)
lines and should not be used instead of the so-called
represents a complementary error function, with ground level distributions, e.g. [11, 12].
Above introduced log-normal distribution (first
ln( I ) − ln( I µ )
u0 = (3) negative current amplitudes) is often approximated with a
2 ⋅ σ ln I well-known Anderson-Eriksson expression [13, 14]:
This expression holds both for negative and positive 1
P( I ) = 2.6
(4)
polarity lightning strikes. The median value ( I µ ) and ⎛ I ⎞
1+ ⎜ ⎟
standard deviation ( σ ln I ) of the lightning current peak ⎝ 31 ⎠
values from (3) are defined in e.g. [6, 7], both for the first
negative, subsequent negative and first positive polarity A comparison between log-normal distributions given
lightning strikes. by: Iµ = 31.1 kA, σlnI = 0.48 and Iµ = 30.1 kA, σlnI = 0.76,
It needs to be stated, however, that this parameters of with Anderson-Eriksson expression is given in Figure 1.

1001-2
It can be appreciated from Figure 1 that there are Portal of the transmission line in the substation is
significant differences between these distributions, owing numbered with 0, while subsequent towers bear
to the adopted median value and standard deviation. First consecutive numbers; with arbitrary tower described by
above given set of values (Iµ = 31.1 kA, σlnI = 0.48) for the value k. Span lengths between neighboring towers are
the log-normal distribution is often recommended [7], also denoted in this figure, with spans associated with k-
although better approximation could be obtained for th tower having lengths ℓk (left) and ℓk+1 (right).
specific region (and season if needed). Anderson- An expected number of lightning strikes into the
Ericsson expression agrees well with a log-normal arbitrary k-th span of the HV overhead transmission line,
distribution described by the parameters Iµ = 30.1 kA, during the specific time window, can be determined by
σlnI = 0.76, which can be nicely observed from Figure 1 the following general expression:
as well. It can also be deduced from Figure 1 that this
later distribution as well as equation (4) give higher
k
N s = N g ⋅k S s ⋅τ (5)
probabilities for high-amplitude lightning currents.
where:
Ng - ground flash density, nr. strokes /( km 2 ⋅ year ) ,
k
Ss - surface of the electric shadow (attractive
surface) of the k-th span, km2,
τ - time window, years.
Ground flash density can be obtained from the
following well-known expression [14]:

N g = 0.04 ⋅ Td1.25 (6)

where Td signifies a average number of thunderstorm


days per year, usually obtained form the isokeraunic
maps of the region.
Attractive surface for the k-th span of the transmission
line is (in case of single shield wire) defined by the
following expression [15]:
Figure 1. Statistical distribution of lightning current k
S s = 28 ⋅ hk0.6 ⋅ l k ⋅ 10 −3 (7)
amplitudes.
where:
Apart from amplitude, lightning current is defined with ℓk - length of the k-th span, km,
a front duration (or steepness) and wave duration (as well hk - average height of the shield wire along the k-th
as with polarity, which is here chosen to be negative). span, m; this value is obtained from the height of
Detailed treatment of these additional lightning current the towers at both end of the span, m.
parameters, especially the current front duration, will be
given later in this paper. By introducing (6) and (7) into (5), following
expression is obtained:
2.2 Tower lightning stroke incidence k
N s = 1.12 ⋅ 10 −3 ⋅ Td1.25 ⋅ hk0.6 ⋅ l k ⋅ τ (8)
Figure 2 graphically depicts a situation of the several
first transmission line towers from the HV substation. According to the analysis, similar to that outlined
This portion of the line (several first towers as seen from above, another expression is obtained, which defines an
the substation) is under scrutiny for the backflashover average number of lightning strikes into the (k+1)-th
analysis, and subsequent assessment of the HV substation span:
overvoltage protection. k +1
N s = 1.12 ⋅ 10 −3 ⋅ Td1.25 ⋅ hk0+.61 ⋅ l k +1 ⋅ τ (9)

Lightning stroke incidence (stroke probability density)


is not uniformly distributed along the span of the
transmission line shield wire. More frequent are lightning
strikes into the tower tops and parts of the span close to
the towers. According to [16], only 20% - 25% of all
Figure 2. Graphical depiction of the transmission line direct lightning strikes end-up near the mid-span sections
towers incident to the HV substation. of the shield wire, while almost 75% - 80% of the

1001-3
lightning strikes end-up on tower tops and shield wires in k
nt ( I = I k ) = 1 (15)
the near-vicinity of the towers. More elaborate analysis of
the lightning stroke distribution along the transmission then equation (14) yields the associated probability, as
line spans can be found in [17]. Hence, expected number follows:
of lightning strikes into the k-th tower (and shield wire in
its near-vicinity) can be approximated with a following 1.11
P( I k ) = k
(16)
expression: Nt
k
Nt = ξ ⋅ (N
k
s+
k +1
Ns ) (10) By introducing (13) into equation (16), it yields:

Here, a coefficient ξ is introduced in order to account 992


P( I k ) = (17)
for the above mentioned facts, regarding the distribution ξ ⋅ Td1.25 ⋅ ( hk0.6 ⋅ l k + hk0+.61 ⋅ l k +1 ) ⋅ τ
of the lightning stroke incidence into the shield wire,
along the spans of the transmission line. In accordance From the obtained value of probability, given by (17),
with [16], this coefficient can be drawn from the one can subsequently obtain the warranted value of the
following range: lightning stroke current amplitude (which should not be
exceeded within the observed time frame), i.e.:
ξ ∈ [0.375 − 0.4] (11)
P( I k ) ⇒ I k (18)
Furthermore, according to [17], following equation has
been derived for the estimation of the lightning stroke This can be done graphically (e.g. by using Figure 1),
incidence to the HV transmission line towers: or even analytically in case of using the expression (4).
For the known value of P(Ik), in this latter case, one can
ξ = 5.486 ⋅ 10 −7 ⋅ l 2 − 7.452 ⋅ 10 −4 ⋅ l + 0.3587 (12) obtain lightning current amplitude as follows:
1
where ℓ is the length of the transmission line span. It
needs to be stated that expression (12) is valid for 230 kV ⎛ 1 ⎞ 2.6
I k = 31 ⋅ ⎜⎜ − 1⎟⎟ (19)
transmission lines and above. For the lower voltages, the ⎝ P( I k ) ⎠
value obtained from (12) should be increased by 0.02,
[17]. Hence, this expression relates the span length with Previously introduced analysis is given for the negative
the probability of lightning strikes to the tower (and its polarity lightning strikes, but could be easily
vicinity). According to this relation, the probability of reconfigured and extended to account for the positive
lightning strikes to towers (i.e. tower lightning incidence) lightning strokes as well. As has been already mentioned,
decreases with longer spans. the exclusion of positive polarity lightning from this
theoretical analysis renders this paper more legible, while
By introducing (8) and (9) into (10), following maintaining full generality of the matter at hand.
expression is obtained: Additionally, one needs to acknowledge the fact that
there are cases where the overhead transmission line
k
N t = 1.12 ⋅ 10 −3 ⋅ ξ ⋅ Td1.25 ⋅
terminates in short cable connection to the switchyard
( )
(13)
⋅ hk0.6 ⋅ l k + hk0+.61 ⋅ l k +1 ⋅ τ (transformer station). Here a similar analysis could be
carried out as presented above. In the mentioned case,
It has been already mentioned that negative polarity only strikes to the first tower (closest to the substation
lightning currents account for the 90% of all lightning warrants different treatment, since from this tower a
strikes. Whence, a number of (negative polarity) (buried) cable line connects to the HV substation. Hence,
lightning strikes, ending-up on the k-th tower top and its expression (17), for the first tower, in case of a cable
near-vicinity, accompanied with currents which exceed a termination, transforms into the following expression:
certain value I (kA), can be estimated by the following
expression: 992
P ( I1 ) = (20)
ξ ⋅ Td1.25 ⋅ h20.6 ⋅ l 2 ⋅ τ
k
nt = 0.9⋅ N t ⋅ P ( I )
k
(14)
where h2 is an average height of the shield wire in the
Here, a probability function P(I) of the current amplitudes second span (including sag correction), m, while ℓ2 is a
feature prominently. It can be taken either from length of the second span, km.
expression (1) or from approximate expression (4). All other towers (except this first one) are treated even
If one should assume a single lightning strike into the in this case in the same way as above, which means that
k-th tower (and its near-vicinity) during the period of τ expression (17) holds for every one of them.
years, i.e.:

1001-4
2.3 Correlation of lightning current parameters Equation (21), with introduction of (22) – (24), present
conditional probability for the first positive lightning
Analysis carried out in the previous section does not
stroke as well, only the parameters of the statistical
say anything about front duration (or steepness) of the
distributions are different, along with a correlation
lightning current front or wave duration, associated with
coefficient, [7]. Table II summarizes several median
a direct lightning strike into the tower top and its vicinity.
values and standard deviations for the log-normal
Hence, any lightning surge current front / crest duration
distribution of the (negative polarity) lightning current
(or steepness) and wave duration can be associated with
front duration.
this negative lightning strike current amplitude.
It is a known fact that the front duration of the Table II: Parameters of log-normal distribution of lightning
lightning current has a significant influence on the current front durations.
backflashover analysis, e.g. [5, 7]. Lightning strikes with
shorter front times generate larger voltages across
insulator strings during backflashover phenomenon, and Parameter t fµ (µs) σ ln t Lightning stroke type
vice versa. Additionally, a lightning protection design of
First negative, from
a substation is greatly affected by the assumed lightning 3.83 0.55
[7, 9]
stroke current front duration [11]. Whence, it would be
appreciable to correlate probability of lightning strike t f (µs) 5.5 0.70 First negative, from [7]
amplitude occurrence with a specific wave crest (front) First negative (Japan),
4.5 0.37
duration (or steepness). Less important is the lightning from [10]
current wave duration, which might be of interest in cases
where the energy absorption of the MO surge arrester is In order to emphasize the influence of the current front
studied. duration on the distribution of the lightning current
In order to achieve this correlation of lightning surge amplitudes, conditional distribution obtained from
current parameters one needs to employ a conditional equations (21) – (24) with several different lightning
probability. Conditional probability of two mutually current front durations, is plotted in Figure 3. Here, eight
dependent lightning stroke current parameters, e.g. different (consecutive) current front durations were
amplitude and front / crest duration, both drawn from the selected, ranging from 1 µs to 8 µs. Following values of
log-normal distribution, is given by the following the statistical distributions were utilized: Iµ = 30.1 kA,
equation [7]: σlnI = 0.76, tfµ = 3.83 µs, σlnt = 0.55 and ρc = 0.47, as
P ( I ≥ I k | t = t f ) = 0.5 ⋅ erfc(u 0 ) (21) recommended in [7].

with variable u0 now given by the following expression:


ln( I k ) − b
u0 = (22)
2 ⋅σ
where:

b = ln( I µ ) + ρ c ⋅
σ ln I
σ ln t
[
⋅ ln(t f ) − ln(t fµ ) ] (23)

σ = σ ln I ⋅ 1 − ρ c2 (24)

Here, Iµ and σlnI again represent median value and


standard deviation for the log-normal distribution of the
lightning current amplitude, respectively. These values
were introduced in Table I. Values tfµ and σlnt represent
median value and standard deviation for the log-normal Figure 3. Statistical distribution of lightning current
distribution of the lightning current front duration, amplitudes with different front duration.
respectively. The coefficient ρc in equations (23) and (24)
represent a correlation coefficient between these random It can be seen from Figure 3 that there is a higher
variables, depicting lightning current amplitude and front probability of occurrence of lightning strokes with large
duration. This parameter has the following value [7]: amplitudes having longer front durations. Whence,
lightning strokes with very high current amplitudes,
ρ c = 0.47 (25) having front duration of 1 µs or less, are far less probable

1001-5
than those with longer front duration. At the same time,
shorter front duration of lightning stroke current produces
greater probability of the backflashover (especially in
combination with other unfavorable tower parameters,
e.g. high footing resistance). Additionally, conditional
probability relating lightning current amplitude and other
lightning parameters, such as: front steepness and stroke
charge (again both for the negative and positive polarity
lightning strokes) is given by the expression analog to
(21), but with different median values and standard
deviations of log-normal distributions (as well as
different correlation coefficients between statistical
parameters), [7].
However, it needs to be stated here that, apparently,
there is no correlation between lightning current
amplitude and wave duration, which means that they are
treated as two independent statistical variables [7]. This Figure 4. Statistical distribution of lightning current
means that following equation for expressing cumulative amplitudes exceeding different wave durations.
probability holds:
Previously presented mathematical model,
P( I ≥ I k , t ≥ t h ) = 0.25 ⋅ erfc(u 0 I ) ⋅ erfc(u 0t ) (26) accompanied with conditional probabilities of occurrence
with of lightning stroke currents having different front
durations (or steepness) as well as wave durations, gives
ln( I k ) − ln( I µ ) a basis for the estimation of probabilities associated with
u0 I = (27) occurrence of lightning currents striking several first
2 ⋅ σ ln I
transmission lines towers extending from the HV
ln(t h ) − ln(t hµ ) transformer station (switchyard). Hence, this
u 0t = (28) mathematical model facilitates definition of all lightning
2 ⋅ σ ln th stroke parameters of negative polarity (i.e. amplitude,
front duration and wave duration), associated with direct
Here, Iµ and σlnI again represent median value and
lightning strikes into the transmission line towers
standard deviation for the log-normal distribution of the
incoming to the HV substation.
lightning current amplitude, respectively. These values
were introduced in Table I. Values thµ and σlnth represent 3 NUMERICAL EXAMPLE
median value and standard deviation for the log-normal
distribution of the lightning current wave duration, A rather typical double-circuit 2x220 kV overhead
respectively. Table III summarizes two different set of transmission line, incoming to the TS 220/110 kV, will
parameters for the log-normal distribution of the be employed for the numerical example. This
(negative polarity) lightning current wave duration. transmission line has a single shield wire. Table IV
presents average heights (hk) and span lengths (ℓk) of the
Table III: Parameters of log-normal distribution of lightning shield wire for the several first transmission line spans, as
current wave durations. seen from the transformer station at hand.

Table IV: Average heights and span lengths of the shield


Parameter t hµ (µs) σ ln th Lightning stroke type wire for the several first transmission line spans.
First negative, from
77.5 0.58 Span
[7, 9] l k (km) hk (m)
th (µs) (k)
75 0.58 First negative, from [7]
1 0.100 26.6

Figure 4 presents cumulative (i.e. joint) probability of 2 0.260 34.3


exceeding lightning current amplitude having (exceeding) 3 0.250 34.8
several different values of lightning current wave
durations, according to the equation (26) and parameters 4 0.250 33.8
of log-normal distribution: Iµ = 30.1 kA, σlnI = 0.76, thµ = 5 0.260 34.4
77.5 µs, σlnth = 0.58.

1001-6
Keraunic level of the region where this portion of the tower, while other three towers have basically identical
transmission line (as well as associated transformer current amplitude distributions, as a function of time.
station) is located has a level of Td = 50. Furthermore,
due to small variations in span length and other
uncertainties in tower parameters, the coefficient ξ is
chosen to have a value of 0.3 in all cases.
According to the presented theoretical background and
above derived mathematical model, probability of
occurrence of the lighting current amplitudes, striking
first four towers from the substation at hand, have been
computed by equation (17). Computation results are
presented in Table V, for three different time windows of
100, 200 and 400 years. From these probabilities, in
accordance with expression (19), current amplitudes were
derived. These current amplitudes, of negative polarity,
will not be exceeded more than once during the selected
time windows of 100, 200 and 400 years. These
computation results are presented in Table VI. It needs to
be mentioned at this point that currents with amplitudes
from Table VI could have arbitrarily long front durations Figure 5. Expected lightning current amplitudes, striking
as well as wave durations. first four transmission line towers, as a function of time.

Table V: Probability of exceeding lightning current In order to associate the specific lightning current front
amplitudes striking first four transmission line towers, durations with above computed lightning current
during time window of 100, 200 and 400 years. amplitudes (according to the data presented in Table V
and Table VI), a conditional probability, graphically
Tower P( I k ) depicted in Figure 3, must be employed. Hence, by using
(k)
τ = 100 years τ = 200 years τ = 400 years
data from Table V and Table VI in combination with
Figure 3, specific front durations associated with each of
1 0.0862 0.0431 0.0216 the current amplitudes have been obtained. Computed
results are presented in Table VII.
2 0.0582 0.0291 0.0146

3 0.0596 0.0298 0.0149 Table VII: Expected lightning current front durations
striking first four transmission line towers, during time
4 0.0587 0.0293 0.0147 window of 100, 200 and 400 years.

Table VI: Expected lightning current amplitudes striking Tower


t f (µs)
first four transmission line towers, during time window of (k)
τ = 100 years τ = 200 years τ = 400 years
100, 200 and 400 years.
1 4 4.2 4.8
Tower Ik (kA)
2 4 4.5 5.2
(k)
τ = 100 years τ = 200 years τ = 400 years
3 4 4.5 5
1 77 102 134
4 4 4.5 5
2 90 119 157

3 90 118 155 It can be seen from Table VII that the expected front
duration for lightning currents ranges mainly between
4 90 119 156
4 µs and 5 µs.
If one should for example warrant a lightning current
Additionally, Figure 5 presents expected lightning with 100 kA amplitude and front duration of exactly 1 µs,
current amplitudes striking first four transmission line than the above described mathematical model could
towers as a function of time window. Again, these current produce an expected number of lightning strikes (during
amplitudes could have arbitrarily long front duration and specified time window) into the treated towers. Analysis
wave duration. It can be seen from this figure that lower carried out with the input data from Table IV suggests
values of current amplitudes are associated with the first that it would take, statistically speaking, over 8000 years

1001-7
for a single lightning stroke with 100 kA amplitude and protection analysis, with its associated lightning stroke
1 µs front duration to be expected to strike the first current parameters. This is due to high probability of
transmission line tower (as seen from the substation). occurrence of a backflashover on this tower.
This is a very long time frame, which suggests that
lightning current with such strict parameters (100 kA 4 DISCUSSION OF RESULTS
amplitude and 1 µs front duration) is highly unlikely to It is quite obvious that the selection of parameters for
strike the first tower in the concrete example. the log-normal distribution of lightning currents will
Additionally, a single lightning stroke with 100 kA affect the above presented analysis. This is due to
amplitude and 2 µs front duration is expected to strike the differences found between these parameters, emanating
first tower once every 950 years. Hence, less severe from measurements carried out on different structures,
lightning stroke current parameters are more appropriate with different measuring equipment and conducted in
in this case, such as for example: 134 kA amplitude with different regions of the world. The correlation coefficient
front duration of 4.8 µs for the first transmission line between lightning current amplitude and front duration
tower. This analysis could be extended to and any other (or front steepness) is of paramount significance. It can
transmission line tower as well. be appreciated from the above presented data that it
In order to facilitate a complete definition of lightning varies in a rather broad range, which further complicates
stroke current, the current wave duration should be lightning related analysis. Additionally, lightning current
provided as well, although it is less important for the distributions to HV transmission lines and those to
mentioned backflashover analysis. Hence, by using data ground level differ substantially. Hence, notwithstanding
from Table V and Table VI, along with Figure 4, the huge amount of research carried out in this field, it is
mathematical model produces expected duration of the still obvious that a unified set of parameters for the log-
current wave for the first four towers within the same normal distributions of lightning current parameters are
time windows of 100, 200 and 400 years. Obtained needed. However, this might prove to be a difficult task
computation results are presented in Table VIII. to accomplish, especially in the light of the different
influential factors affecting these statistical variables. The
Table VIII: Expected lightning current wave durations
numerical example given in this paper is thus processed
striking first four transmission line towers, during time
window of 100, 200 and 400 years. with the latest set of parameters of the associated log-
normal distribution, proposed by the IEEE Working
t ≥ th (µs)
Group [7].
Tower Furthermore, a distribution of lightning strikes along
(k)
τ = 100 years τ = 200 years τ = 400 years the HV transmission line spans is of significant
importance. It is known that this distribution is not
1 45 45 40
uniform and that the lightning strikes tend to be
2 50 42 20 concentrated around the transmission line towers. A
value of 0.6 (i.e. ξ = 0.3) has been often associated with
3 48 42 20
the probability of lightning strikes to the towers and their
4 50 42 20 vicinity, although with longer spans this probability
decreases in accordance with the equation (12). It needs
Finally, from the above presented results, one can to be accentuated here that the exactly defined boundary
conclude that lightning stroke parameters appropriate for on the transmission line span, beyond which a lightning
the transmission line tower backflashover analysis (and strike would not produce a backflashover on the tower,
subsequent HV substation overvoltage protection does not exist. Statistically speaking, even the lightning
analysis) could be selected as follows: strikes on the middle of the span could produce a
- negative polarity direct lightning stroke into the backflashover on the associated towers. However, this
top of the first transmission line tower, imaginary length of the span, which determines the above
- 134 kA amplitude, mentioned probability of lightning strikes to the tower, is
- 4.8 µs front duration, according to [17] estimated to be a 55% of the half span
- wave duration in excess of 40 µs. on each side of the tower.
In order to appreciate the influence of the lightning
A lightning stroke current with these parameters will strike distribution along the transmission line span, the
occur (statistically speaking) only once every 400 years. lightning incidence of the second tower from the treated
Additionally, if one of the neighboring transmission line example is again computed, but now with three different
towers have significantly high tower footing resistance values of the parameter ξ. Different values of this
(i.e. impulse impedance), it should be considered as a parameter in turn define different concentrations of the
viable candidate for the HV substation overvoltage lightning strikes in the near-vicinity of the tower at hand.

1001-8
Computed results are graphically displayed in Figure 6. 6 REFERENCES
[1] H. W. Dommel, "Electromagnetic Transients Program
Theory Book", MicroTran Power System Analysis
Corporation, Vancouver, British Columbia, 1992.
[2] L. Prikler, H. K. Høidalen, "ATPDRAW version 3.5 for
Windows 9x/NT/2000/XP – Users’ Manual", European
EMTP ATP Users Group, 2002.
[3] IEEE TF, “Modeling Guidelines for Fast Front
Transients”, IEEE Transactions on Power Delivery, Vol.
11, No. 1, pp. 493-506, 1996.
[4] A. Ametani, T. Kawamura, “A Method of a Lightning
Surge Analysis Recommended in Japan Using EMTP”,
IEEE Transactions on Power Delivery, Vol. 20, No. 2, pp.
867-875, 2005.
[5] F. M. Gatta, A. Geri, S. Lauria, “Backflashover Simulation
of HV Transmission Lines With Concentrated Tower
Grounding”, Electric Power Systems Research, Vol. 73,
pp. 373-381, 2005.
[6] IEC 62305-1, Protection against lightning - Part 1: General
principles, 2006.
Figure 5. Expected lightning current amplitudes striking the
[7] Lightning and Insulator Subcommittee of the T&D
second tower computed with different values of the
Committee, “Parameters of Lightning Strokes: A Review”,
parameter ξ.
IEEE Transactions on Power Delivery, Vol. 20, No. 1, pp.
346-358, 2005.
Hence, it can be appreciated from this figure that there
[8] Y. Yasuda, N. Uno, H. Kobayashi, T. Funabashi, “Surge
are differences between computed lightning currents on Analysis on Wind Farm When Winter Lightning Strikes”,
the second tower, which are a direct consequence of the IEEE Transactions on Energy Conversion, Vol. 23, No. 1,
selected value of the parameter ξ. This value depends on pp. 257-262, 2008.
the transmission line tower and span geometry and other [9] R. B. Anderson, A. J. Eriksson, “Lightning Parameters for
factors [17]. Engineering Applications”, Electra, No. 69, pp. 65-102,
1980.
5 CONCLUSIONS [10] T. Narita, T. Yamada, A. Mochizuki, E. Zaima, M. Ishii,
“Observation of Current Waveshapes of Lightning Strokes
This paper presented a generally applicable on Transmission Towers”, IEEE Transactions on Power
mathematical model for the assessment of the probability Delivery, Vol. 15, No. 1, pp. 429-435, 2000.
of occurrence of the (negative polarity) lightning strike [11] G. W. Brown, “Joint Frequency Distribution of Stroke
currents, having specific parameters (i.e. amplitude, front Current Rates of Rise and Crest Magnitude to
duration and wave duration), and striking the several first Transmission Lines”, IEEE Transactions on Power
transmission line towers as seen from the HV substation, Apparatus and Systems, Vol. 97, No. 1, pp. 53-58, 1978.
within the certain time window. Hence, this mathematical [12] A. M. Mousa, “The Frequency Distribution of the
Amplitudes of Lightning Currents”, presented to IEEE
model facilitates computation of lightning stroke current
Task Force on Parameters of Lightning Strokes, San
amplitude, with associated front duration (or steepness) Francisco, USA., July 1994.
and wave duration, which will strike several first towers [13] IEEE WG, “A Simplified Method for Estimating Lightning
only once during the certain (selected) time frame. These Performance of Transmission Lines”, IEEE Transactions
lightning current parameters could represent input data on Power Apparatus and Systems, Vol. 104, No. 4, pp.
for the backflashover analysis and subsequent analysis 919-932, 1985.
(or design) of the HV substation overvoltage protection. [14] IEEE WG, “Estimating Lightning Performance of
This model, if needed, could be easily extended to Transmission Lines II – Updates to Analytical Models”,
include the positive lightning strikes as well, although IEEE Transactions on Power Delivery, Vol. 8, No. 3, pp.
1254-1267, 1993.
these are far less important.
[15] L. L. Grigsby, "The Effective Power Engineering
Here presented analysis acknowledges once more the Handbook", IEEE Press, Alabama, 2001.
fact that the parameters of the log-normal distributions [16] CIGRE WG 33.01, "Guide to Procedures for Estimation of
(including the associated correlation coefficient) of the Lightning Performance of Transmission Lines",
lightning currents need to be scrutinized with care. CIGRE Monograph No. 63, 1991.
Furthermore, distribution of lightning strikes along the [17] A. M. Mousa, K. D. Srivastava, "The distribution of
transmission line spans is of significant importance, as it lightning strokes to towers and along the span of shielded
influences both the backflashover analysis and the and unshielded power lines", Canadian Journal of
subsequent HV substation overvoltage protection design. Electrical & Computer Engineering, Vol. 15, No. 3, pp.
115-122, 1990.

1001-9

You might also like