Air Circuit Breakers

HWT up to 6300A
Tailored ACB types and associated accessories
The ACB is delivered factory assembled. Various data can be displayed on LCD:
• Phase current (A) of I1, I2, I3 and their max. peak current
• Line voltage (V) of V12, V23, V31 and their max. peak voltage
(or Phase voltage (V) of V1N, V2N, V3N and their peak voltage)
• Demand active power max. (kW)
• Power factor (cos Ø)
• Electric energy (kWh)
• Frequency (Hz)
• Trip history
The complete data can be displayed via the cummunication module as well.

The advantages for you


you: Technical data
data:
• Lorperiu
Over-current release,
scillam LSIconsectet
in eratio or LSIG orpraessi.
with LCD display, ammeter • Lorperiu
Wide range of ACBs,
scillam from
in eratio 800A to 6300A.
consectet praessi.High breaking
or multimeter capacity, from 50 to 120kA
• Lore vullum zzrit, commy nis nos adiat la feugiam etummodo do • Lore vullum zzrit, commy nis nos adiat la feugiam etummodo do
• For all ACBs: lcu = lcs = lcw (1s) • Available in draw-out or fixed type
• Dolobor si tis accumsandre exer iril inci blamcon ulpute modolor • Dolobor si tis accumsandre exer iril inci blamcon ulpute modolor
• perostis
Easy connection
amconulla in ad
thedel
switchboards
ut ulputem thanks to 2 connection
vero odigna amcor iriliqu • perostis
Double breaking
amconullacontacts
ad del ut ulputem vero odigna amcor iriliqu
types: rear connection or front connection to save space in
• ismodiamet,
depth sismolore dui et illumsan ent utat, si. • ismodiamet,
Wide range of accessories:
sismolore dui etcoils, contacts,
illumsan interlocks,
ent utat, si. motors…
Quick
tips
1 5
A complete Adjustable rated current
implementation system • Adjustable from 0.4 to 1.0
• Draw-out or fixed mounting type • Rated current: 800A to 6300A
• Front connection to allow easy • Integrated current transformer:
wiring access 400A to 6300A
• Vertical or horizontal terminals
for rear connection

Standard over-current

2 6
Terminal blocks
Are positioned to allow easy release with
wiring/access to: adjustment dial
• Control circuit • Ground fault trip function
• Auxiliary switches • Neutral protection
• Position switches • Tripping display
• Coil voltage display

Enhanced over-current

3 7
Auxiliaries
• Under-voltage trip device release with
• Motorised control and LCD-“Analyser”
closing coil Same features as standard over-
current release with LCD, plus:
• Undervoltage alarm
• Contact temperature monitoring

4
“Double break”

8
Standard over-current
• Double circuit current breaking release with LCD-“Ammeter”
• 50% reduced arc voltage plus additional features:
• Contacts increase service life • Tripping display for type of tripping
• Extremely fast interruption of • Pre-trip alarm
short circuit currents • Phase rotation protection
• Data exchange via Modbus RTU
• Ammeter
Air Circuit Breakers
HWT up to 6300A

Increased accessibility from the front


• The double insulated design ensures that most accessories can be
safely and easily installed
• Control, auxiliary and position switch terminals are mounted at the
front on the ACB body for easy access
• The switchboard panel door can be kept closed in the
CONNECTED, TEST, and ISOLATED positions

Implementation
• Easy connection in the switchboard thanks to 3 types of main
circuit terminal arrangements:
- Front connection to save space in depth
- vertical and / or horizontal rear connections for busbars.
• The draw-out type allows visible breaking on the “Isolated”
position (NFC14-100). The “Test” position allows to test the ACB
while having all the control circuits connected.
• The main circuit safety shutters automatically conceal the main
circuit contacts on the draw-out cradle when the ACB is drawn out.
- The top and bottom shutters operate independently and can be
separately padlocked in the closed position.
- Up to three padlocks (with ø6 hasp) can be installed on each side
using padlocking unit. (Padlock not supplied)

Control and signalisation auxiliary switches


• Shunt trip devices are available for different voltage supplies.
2 versions are available: “Continuously rated shunt trip” and
“Instantaneously rated shunt trip”. This shunt trip can be itted
together with an undervoltage trip to the same ACB
• The trip control device is available in two types: one provides an
instantaneous trip to the ACB when the control voltage drops below
the opening voltage, the other provides a delayed trip to the ACB
when the control voltage remains below the opening voltage for at
least 500 ms.
• The auxiliary switches operate during the ACB ON/OFF operation.
They are available in 4, 7 and 10 contacts versions.
• The position switch operates to give an indication of the breaker
position: CONNECTED, TEST, ISOLATED, and INSERT.

Security and padlocking


• OFF padlock: Permits the ACB to be padlocked in the OFF
position. Max. three padlocks with ø6 hasp can be itted.
Padlocking is possible only when ON-OFF indicator shows OFF.
When the ACB is padlocked in the OFF position both manual and
electrical closing become inoperative, but the charging of the
closing spring by manual or motor operation is still possible.
• An ON-OFF button cover prevents inadvertent or unauthorised op-
eration of the ON or OFF button. It can be locked with up to three
padlocks with ø6 hasp.
• Cable interlock for all the ACBs sizes:
– mutual mechanical interlock for 2 or 3 ACBs
– horizontal interlock for ixed or draw-out type ACBs
– vertical interlock only for draw-out type ACBs
• Front key lock:
- cylinder lock
- castell lock.

3.108
Air Circuit Breakers
HWT up to 6300A

The range
• 3 sizes up to 6300A
• 2 width up to 4000A
• 3P and 4P with neutral on the left
• Standard breaking capacity (S) 65, 85 and 120kA and high
level capacity (H) 80 and 100kA according to the size
• One single mounting depth for fixed type
• Same cut-out on front panel for all the sizes.

Technical characteristics

HWT2 HWT3 HWT6


Series S H S H SB S
In 800/1250/ 1250/1600/ 2500/3200 1600/2000/ 4000 5000/6300
Rated current (A) 1600/2000 2000 2500/3200
In 800/1250/ 1250/1600/ 2500/3200 1600/2000/ 4000 5000/6300
Neutral pole amperes frame (A) 1600/2000 2000 2500/3200

Main Incomers
Reference HWT208S/ HWT212H/ HWT325S/ HWT316H/ HWT440SB HWT650S/
HWT212S/ HWT216H/ HWT332S HWT320H/ HWT663S
HWT216S/ HWT220H HWT325H/
HWT220S HWT332H
Ics = Icu breaking capacity in case of short-circuit
(kA, symmetrical peak 690V 50 55 65 85 85 85
current value) 440V 65 80 85 100 100 120
400/415V 65 80 85 100 100 120
Icm rated short-circuit breaking current
(kA, asymmetrical peak 690V 105 121 143 187 187 187
current value) 440V 143 176 187 220 220 264
400/415V 143 176 187 220 220 264
Icw rated short time withstand current
(kA r.m.s) 1 second 65 80 85 100 100 120
3 seconds 50 55 65 75 85 85
No of operating cycles
Mechanical life (with maintenance) 30000 30000 20000 20000 15000 10000
Mechanical life (without maintenance) 15000 15000 10000 10000 8000 5000
Electrical life (with maintenance AC 460V) 12000 12000 7000 7000 3000 1000
Electrical life (without maintenance AC 690V) 10000 10000 5000 5000 2500 500
Time
Max. opening time (sec.) 0,03 0,03 0,03 0,03 0,03 0,03
Max. spring charging time (sec.) 10 10 10 10 10 10
Max. closing time (sec.) 0,08 0,08 0,08 0,08 0,08 0,08
Dimensions
Fixed type (mm) width 3P 360 360 466 466 - -
width 4P 445 445 586 586 - -
height 460 460 460 460 - -
depth 290 290 290 290 - -
Draw-out type (mm) width 3P 354 354 460 460 460 799
width 4P 439 439 580 580 580 1034
height 460 460 460 460 460 460
depth 345 345 345 345 345 380

The following values are the same for all the sizes : Standards :
Rated operational voltage Ue (50/60Hz) - 690V CEI 60947-2
AC rated insulation voltage Ui (50/60Hz) - 1000V EN 60947-2
Rated impulse withstand voltage Uimp - 12 kV

3.109