This document discusses clearance requirements for commercial cooking exhaust discharge to prevent fires. It states that exhaust discharge must be at least 3 feet horizontally from any openings in the exterior wall, such as windows or doors. Additional clearance is required if the opening is operable and above the discharge point. The duct must also be installed so grease drains back into the hood to prevent it from accumulating outside. National standards are intended to confine any fires to the duct system and prevent flames from reentering the building downstream of the exhaust fan.
This document discusses clearance requirements for commercial cooking exhaust discharge to prevent fires. It states that exhaust discharge must be at least 3 feet horizontally from any openings in the exterior wall, such as windows or doors. Additional clearance is required if the opening is operable and above the discharge point. The duct must also be installed so grease drains back into the hood to prevent it from accumulating outside. National standards are intended to confine any fires to the duct system and prevent flames from reentering the building downstream of the exhaust fan.
This document discusses clearance requirements for commercial cooking exhaust discharge to prevent fires. It states that exhaust discharge must be at least 3 feet horizontally from any openings in the exterior wall, such as windows or doors. Additional clearance is required if the opening is operable and above the discharge point. The duct must also be installed so grease drains back into the hood to prevent it from accumulating outside. National standards are intended to confine any fires to the duct system and prevent flames from reentering the building downstream of the exhaust fan.
Topic: Exhaust Discharge from Commercial Cooking Equipment Learning objective: The student shall be able to identify minimum dimensions between exhaust duct outlets and building openings.
Commercial cooking equipment presents a serious fire hazard.
Burning grease temperatures can reach 2,000°F, hot enough to ignite nearby combustibles.
Exhaust removal equipment that meets nationally recognized
standards is intended to confine a fire to the duct system. The exhaust point must be arranged so flames will not reenter the building downstream of the exhaust fan.
For horizontal discharge, openings
(windows, doors, air intakes, or similar penetrations of the exterior wall) must be at least 3 feet from the discharge point. NFPA 96 requires additional clearance if the opening is “operable” and located above the exhaust discharge.
The duct must be installed so grease will
drain back into the hood, where a drip cup This installation does not meet clearance standards. or drain to a remote grease trap is required.
For additional information, refer to the International Mechanical Code
for Type I hood and duct systems or NFPA 96, Ventilation Control and Fire Protection of Commercial Cooking Operations.
Commercial Cooking Equipment For archived downloads, go to: www.usfa.fema.gov/training/nfa/coffee-break/