Professional Documents
Culture Documents
Gavr 12 PDF
Gavr 12 PDF
Features
● <±1% Regulation
● 220/400 VAC Programmable Input
● Rugged Compact Design
● With Under Frequency Protection
● Soft Start Voltage Ramping
● EMI Suppression
● Built-in Hihg Capacity 10Amp Fuse
Specifications
SensingInput Voltage 180~260VAC,1phase 2wire VoltageBuild-up Residualvolts at AVR teminal>5VAC
PowerInput Volage 180~260VAC,1phase2wire External Volts Adjustment ±7% with 1KΩ 1with trimmer
Output Voltage Max.90VDC@240VACinput SoftStartRampTime 2sec.
Current Continuous 4A Unit power Dissipation Max.8Watt
Intermittent 7A for 10SEE. EMI Suppression Internal Electromagnetic Interference Filtering
Resistance Min.12Ω Max.100Ω Thermal.Drift 0.03%per℃ chage in AVR ambient
Under Frequency Protection 60Hz system presets knee point at 55Hz
(Factoey Settings) 50Hz system presets knee point at 45Hz
Volts Regulation <±1%(with 4%engine governing)
Environment
Vibration 3G@100~2K Hz Relative Humidity <95%
Operating Temperatuer -40~65℃ Storage Temperature -40~85℃
Mechanical Specifications
AVR Controls
VolTS Voltage Adjustment
STAB Stability Adjustment
U/F TO Set the U/F*Knee Point
*U/F:Under Frequency Prorection
Physical Specification
Dimensions 121.0(L)92.0(W)60.0(H)mm
121
110
92
81
STAB
T
R2 VOLT
R1
∅5
N N
S S
380VAC 220VAC
R GEN R GEN
T T
FIELD FIELD
N T F- F+ N T F- F+
GAVR-12A GAVR-12A
R1 R2 R1 R2
EXT
VR
1K
POWER 120
FIELD
100
50Hz
60Hz
80
60
N T F- F+
3-12V
40
20Ω/5W
AVR 20
R1 R2
0 10 20 30 40 50 60
EXT
VR
1K