Professional Documents
Culture Documents
3
Safety Instructions
Please read this manual and the related documentation thoroughly and familiarize
yourself with product information, safety instructions and other directions before
installing, operating, performing inspection and preventive maintenance.
Please be aware that the instructions are marked with either a warning symbol or
attention symbol.
4
Overview
Features
The high-speed counter module (hearafter, HSC module) is a special module for
high speed counting feature. It provides a high-speed response of 100 Kcps. The
LX70-HSC1 module provides also the 40 KHz pulse output function.
R Y OU T
D C IN
D C IN
HSC
POWER
POWER
INIT
TEST
C=P conversion
40 39 1 2 1 2 1 2
RUN
RMT
PROG input
LX
Programmable
Controller
COM
COM
RS232C
RS23 2C C>P stop input
OPEN
Input the output from rotary
TOOL
TOOL
RS232C
RS23 2C encoder with phase differential
2 1 39 40 39 40 39 40 input mode (4 x) of high-speed
counter
5
High Speed Counting Configuration for LX70 PLC System
Inverter
C=P conversion
input
LX
Pulse Output Configuration for LX70 PLC System (for LX70-HSC1 only)
LX
Input reverse current
Encoder output
6
Hardware Description
LX-HSC1 and LX-HSC2 Hardware Description
HSC2 HSC1
1
HSC
HSC
= > = > = >
A B P I A B P I A B P I
CH0 CH1 CH0
CH0 CH0
C=P C=P
C>P C>P
+ +
- - 3
INA+ INA+
INA- INA-
INB+ 2 INB+
INB- INB-
PR/INH+ PR/INH+
PR/INH- PR/INH-
C=P
8 7 6 5 4 3 2 1 NO
C>P
+
-
INA+
OFF ON
INA-
INB+
INB-
PR/INH+
PR/INH-
CH1
7
3. Mode switch
DIP switch for shifting counter unit function.
Preset as SW1: ON, SW5: ON, others OFF
(phase differential input, 4 x mode)
8
LX70-HSC1 Hardware Description
9
LX70-HSC2 Hardware Description
10
3. Mode switch
DIP switch for shifting counter unit function.
Preset as SW1: ON, SW5: ON, others OFF
(phase differential input, 4 x mode)
11
LISTED
General Specifications UL 62Y6
C ®
US IND. CONT. EQ.
Item Specifications
Operating 0 °C to +55 °C (32 °F to 131 °F)
Temperature
Storage -25 °C to +70 °C (-13 °F to 158 °F)
Operating 30 to 85 % RH (Non-condensing)
Humidity
Storage 30 to 85 % RH (Non-condensing)
500V AC for 1 minute between I/O terminal (DC) and frame ground
Withstand voltage
(power unit)
100 MΩ or more at 500 mege V DC between I/O terminal (DC) and
Insulation resistance
frame ground (power unit)
10 to 55 Hz, 1 cycle/minute: double amplitude of 0.75 mm, 10
Vibration immunity
minutes per axis (X, Y, Z)
Peak acceleration and duration 15g/11 ms, 3 times for each X, Y, Z
Shock immunity
direction
1500 Vp-p with 50ns to 1µs pulse width (generated by noise
Noise immunity
simulator)
Ambience No corrosive gas, no excessive dust
Performance Specifications
Specifications
Item
LX-HSC1 LX-HSC2 LX70-HSC1 LX70-HSC2
6 points
3 points, 6 points, 6 points,
Number of (INA, INB, RST,
(INA, INB, (INA, INB, (INA, INB,
input points INH, ZERO,
PR/INH) PR/INH) x 2 PR/INH) x 2
SUB)
5 to 12V DC
Input voltage 5 to 24V DC 5 to 24V DC
12 to 24V DC
Allowable
4.75 to 13.2V DC
voltage 4.75 to 25.0V DC 4.75 to 25.0V DC
Input 10.2 to 26.4V DC
variation range
spec.
4.5 V or less/
ON voltage/ 4.5 V or less/ 3 mA or less 4.5 V or less/
current 3 mA or less 9.6 V or less/ 3 mA or less
3 mA or less
1.5 V or more/
OFF voltage/ 1.5 V or more/ 0.6 mA or more 1.5 V or more/
current 0.6 mA or more 2.5 V or more/ 0.6 mA or more
0.6 mA or more
12
Specifications
Item
LX-HSC1 LX-HSC2 LX70-HSC1 LX70-HSC2
Number of 1 point 2 points 1 point 2 points
counter (UP-DOWN (UP-DOWN (UP-DOWN (UP-DOWN
channels COUNTER) COUNTER) COUNTER) COUNTER)
24-bit signed integer (binary format)
Counting range
(-16,777,216 to 16,777,215)
Max. counting
100 kcps (Recommended counter input: within 30 kcps)
speed
Counter
spec. 3 modes
(direction discrimination: Pulse + Direction,
Input mode
individual input: CW, CCW,
phase differential input (1 x, 4 x mode)
Min. input pulse
5 µs (individual input)
width
Multiplication
1 x, 4 x mode (phase differential input mode)
function
Output Specifications
Specifications
Item
LX-HSC1 LX-HSC2 LX70-HSC1 LX70-HSC2
Isolation
Photo coupler
method
Output format Transistor output (NPN, open collector)
Rated use
5 to 24V DC
voltage
Allowable
General voltage N/A 4.75V to 26.4V DC
variation range
Max. load
100 mA 50 mA 100 mA
current
Residual
0.5V or less
voltage
Leakage current 10 µA
Number of 2 points 4 points 2 points 4 points
output points (C=P, C>P) (C=P, C>P) x 2 (C=P, C>P) (C=P, C>P) x 2
Control COMMON
2 points/COMMON
Output terminal
OFF -> ON: 10 µs or less,
Response time
ON -> OFF: 100 µs or less
Number of 2 points
N/A N/A
output points (OUT0, OUT1)
200 to 40 KHz
Output
N/A DUTY 50% ±25%, N/A
frequency
variation ±5%
Pulse
Output Low-frequency N/A 200 to 5 KHz N/A
4K to 40 KHz
High-frequency N/A N/A
(Min. 36 KHz)
Variation time N/A 100 to 500 ms N/A
Rise/fall time N/A 2 us or less N/A
13
Other Specifications
Specifications
Item
LX-HSC1 LX-HSC2 LX70-HSC1 LX70-HSC2
Operation indicator LED
Internal current consumption
400 mA 350 mA 350 mA 400 mA
(5 V)
Removable terminal block
External connection method Terminal block (20-pin)
(20-pin)
Suitable cable size 0.5 to 1.25 mm2
Terminal block terminal screw M3.5 screw M3.0 screw
Occupied I/O points 32 points (16 input points, 16 output points)
14
Installation
Installation Dimensions
LX700 PLC System Dimensions (mm)
B
TR OUT
TR OUT
TR OUT
TR OUT
TR OUT
DC IN
DC IN
DC IN
CPU
LX
115.5 118.5
unit (mm)
111.0 Dimensions
Slot Type
A B
3-slot type 205.0 184.0
5-slot type 276.0 254.0
8-slot type 381.0 360.0
10-slot type 452.0 430.0
12-slot type 522.0 501.0
5.0 * 4
27.5
81.0
unit (mm)
Slot Type P L
3-slot type 205.0 153.8
5-slot type 276.0 224.2
7.0
15
LX700 CPU, HSC Module Dimensions (mm)
HSC2
CPU750B NX-TC8 NX-TC4
TC
CPU
HSC
= > = >
RUN
A B P I A B P I
CH0 ERROR
CH1
CH0
C=P
C>P
+
-
INA+
INA-
INB+
INB-
115.5 PR/INH+
PR/INH-
C=P
C>P
+
-
INA+
INA-
INB+
INB-
PR/INH+
PR/INH-
CH1
35.0 104.0
LX
A
105.0
30.0
38.0
C
4 - M5
16
unit (mm)
Catalog Dimensions Dimensions
Slot Types Dimensions (B)
Number (A) (C)
2-slot type LX70-BASE02 157.2 128.6 114.6
3-slot type LX70-BASE03 192.4 153.8 149.8
5-slot type LX70-BASE05 262.8 234.2 220.2
6-slot type LX70-BASE06 298.0 269.4 255.4
8-slot type LX70-BASE08 368.4 339.8 325.8
10-slot type LX70-BASE10 438.8 410.2 396.2
12-slot type LX70-BASE12 508.6 480.6 466.6
CPU70
CPU
105.0
RS232C
Ⅰ Ⅱ
35.0
17
Installing a HSC Module on a PLC System:
1. Wire I/O cables to the terminal block.
2. Turn on the power connected to the HSC module.
3. Turn on the main PLC power.
ATTENTION
Precautions for Electrostatic Discharges
Excessive static electricity can be generated in dry conditions, so
please make sure to discharge electrostatic charges by touching a
grounded metal bar before contacting the module.
18
Mounting/Dismounting Module
Mounting Dismounting
1. Insert the module by inserting the 1. Unfasten the screw that holds the
tab into the groove first and pushing module in place using a
the module against the backplane. screwdriver.
2. Push the top of the module toward 3. Hold on pressing the locking button
the backplane until it is clamped in on the top edge of the module, and
place. pull the module from the backplane
Locking button
screwdriver
19
Wiring
LX70-HSC1 Wiring Diagram
Internal wiring
External wiring
Load
Maximum 100 mA
C=P Load
C>P
+
-
DC- DC+
20
INA, INB, PR/INH Input
Open Collector
External Power DC5 to 24V
Pulse Generator DC- DC+ High-speed counter
OUT +
Voltage Output
Pulse Generator High-speed counter
OUT
Line Driver
Pulse Generator High-speed counter
OUT+ +
-
OUT-
21
Electrical & Electronics Division (EBG), Gate No.7
Powai Campus, Mumbai 400 072