Instruction Manual

LX700
Important User Information ............................................................. 3
Safety Instructions ............................................................................ 4
Installation ......................................................................................... 5
Installation Dimensions ................................................................................... 5
Installation Location......................................................................................... 6
Installation Environment and Precaution ...................................................... 7
Mounting/Dismounting Module ..................................................................... 8
Wiring................................................................................................. 9
Power Supply Module Wiring ..................................................................... 9
Grounding....................................................................................................... 11
Operating Condition Setting .......................................................... 12
LX-CPU700p Processor Module.................................................................... 12
Input/Output Modules..................................................................... 14
Digital Input Module Specifications .......................................................... 15
Digital Relay Output Module Specifications ............................................. 16
Digital Transistor Output Module Specifications...................................... 17
Digital SSR Output Module Specifications ............................................... 17
Input/Output Module Wiring Diagrams......................................... 18
LX-X16D Wiring Diagram .............................................................................. 18
LX-X32D Wiring Diagram .............................................................................. 18
LX-X64D Wiring Diagram .............................................................................. 19
LX-X16A110 and LX-X16A220 Wiring Diagram .......................................... 19
LX-Y16R and LX-Y16RV Wiring Diagram ..................................................... 20
LX-Y32RV Wiring Diagram ............................................................................ 20
LX-Y16T Wiring Diagram............................................................................... 21
LX-Y32T Wiring Diagram............................................................................... 21
LX-Y16SSR Wiring Diagram.......................................................................... 22
Important User Information
Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Because of this difference, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying
this equipment must satisfy themselves that each intended application of this
equipment is acceptable.
In no event will L&T be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with any
particular installation, L&T cannot assume responsibility or liability for actual use
based on the examples and diagrams.
No patent liability is assumed by L&T with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written
permission of L&T is prohibited.
Throughout this manual we use the following symbols to make you aware of safety
considerations.
Identifies information about practices or circumstances which may
WARNING
lead to serious personal injury or death, property damage, or
economic loss.

Identifies information that is critical for successful application and


IMPORTANT
understanding of the product.

Identifies information about practices or circumstances that can


ATTENTION
lead to minor personal injury, property damage, economic loss, or
product malfunction. However, depending on the situation, failure
to follow the directions accompanying this symbol may also lead to
serious consequences.

3
4

4
Safety Instructions
Please read this manual and the related documentation thoroughly and familiarize
yourself with product information, safety instructions and other directions before
installing, operating, performing inspection and preventive maintenance.
Please be aware that the instructions are marked with either a warning symbol or
attention symbol.

• If this product is used in a situation that may cause personal


WARNING
injury and/or significant product damage, implement safe
measures such as use of fault-safe equipment.
• Be sure to cutoff outer power source while wiring, maintenance,
and cleaning. Do not touch terminals when electric current is
flowing. Otherwise it may cause an electric shock.
• Do not use this product under any conditions exposed to
explosive gases. It may cause an explosion.

• Use the product under the allowed conditions directed in


ATTENTION
product specifications and be cautious to keep away extraneous
materials from entering the product during installation.
– Do not expose to high temperature, high humidity, dense dust,
salinity, mineral particles, corrosive gas, inflammable gas,
solvent, abrasive materials, and direct sunlight.
– Keep away from vibrations, and contacts of other objects. It is
the cause of damage, malfunction, or aging.
• Fasten the terminal screws tightly to ensure that the cable
connection is secure. Incorrect cable connection may cause
overheating and product malfunction.
• Make sure to use an external device when configuring the
protective circuit breakers for emergencies or interlock circuits.
• Operate the product under the allowed conditions directed in
product specifications. Incorrect conditions can cause abnormal
heat dissipation or product malfunction.
• Do not dissemble or modify the product, or it may cause
malfunctions. Use the service centers for product repairs.
• Do not touch the terminals when the power is on. It may cause
an electric shock.
• Only use the product for functions explicitly specified in the
product and the manual.
• Abide by the industrial waste disposal standard when disposing
the product.

4
5

5
Installation
Installation Dimensions
LX700 PLC System Dimensions (mm)

A
B
TR OUT

TR OUT

TR OUT

TR OUT

TR OUT
DC IN

DC IN
DC IN

CPU750B
CP U

X64D X64D X32D Y32T Y16T Y16T Y16T Y16T

Progrmmable
Controller 115.5 118.5
OPEN

unit (mm)
111.0 Dimensions
Slot Type
A B
3-slot type 205.0 184.0
5-slot type 276.0 254.0
8-slot type 381.0 360.0
10-slot type 452.0 430.0
12-slot type 522.0 501.0

5.0 * 4

27.5

81.0 unit (mm)


Slot Type P L
3-slot type 205.0 153.8
5-slot type 276.0 224.2
22.5 L 7.0 8-slot type 381.0 329.8
10-slot type 452.0 400.2
P
12-slot type 522.0 470.6

5
Installation Location
Be sure to maintain a sufficient distance from wiring ducts, and other machines
below and above the module for proper ventilation.
Do not install the modules stacked up or horizontally. Doing so will prevent proper
cooling of the module and cause overheating inside the PLC (programmable
controller).
Do not install the module above devices which generate heat such as heaters,
transistors or large scale resistors.
In order to eliminate any effects from noise emission, power wires and
electromagnetic devices should be kept at least 100 mm away from the surfaces of
the module. When installing the module behind the doors of the operation panel, be
especially careful to maintain these distances.
Programmable
Controller
OPEN

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
POWER

Duct
RS232C

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
PROG
RMT
RUN
TEST
INIT

40 39
1
2 1 3940
1 2

Min. 50 mm
4039

40 39
1
40 39

1
2

2 1 3940

4039
TR OUT

TR OUT

CPU700p
DC IN

DC IN
DC IN

1 2

X64D X64D X32D Y32T Y16T


CP U

RUN COM1
40 39

PROG COM2
1

TEST ERROR
BATT
2

INIT

TEST

INIT
RUN
RMT
PROG

TEST
RS232C
20

19
18

17
16
15
14
13

12

10
11

9
8
7
6
5
4
3
2
1

RUN
RMT
PROG
POWER

Programmable
Controller

OPEN
20

19
18

17
16
15
14
13

12

10
11

9
8
7
6
5
4
3
2
1

COM 1
RS232C
RS485

COM 1
RS232C
RS485 POWER

20 20

19 19
40 39 40 39 4039
1 2
18 18 INIT

17 17 RS232C
TEST 1 1
16 16 RUN 40 39 1 2 1 2 1 2
15 15 RMT 2 2

14
13

12
14
13

12
OPEN

LX
Programmable
PROG
3

4
5
6
3

4
5
6
11 11

Min. 50 mm
10 10 Controller 7 7
8 8
9 9
9 9
8 8 10 10
7 7 Controller
11 11
6 6 Programmable 12 12
5 5
13 13
4 4 14 14
PROG
3 3 OPEN 15 15
2 2 RMT
RUN 16 16
1 1 RS232C 17 17
2 1 2 1 2 1 3940 TEST
18 18
INIT 19 19
2 1 39 40 39 40 39 40 20 20

POWER

Duct
100 mm or more
Other device

Door
PLC of
rack

Space for Programming Tool Connection


Leave a space of at least 180 mm from the mounting surface for programming tool
connections and wiring.
Approx. 110 mm

Programming Cable

Approx. 180 mm

6
Installation Environment and Precaution

Do not install your multi-wire link modules if any of the following


ATTENTION
conditions are present:
• Ambient temperature out of the range of 0 to 55 °C (32 to 131 °F)
• Humidity out of the range of 30% to 85% (non-condensing)
• Inflammable or corrosive gases
• Excessive or conductive dust, metal particles, or salinity
• Chemicals that may affect electronic parts
• Benzene, thinner, alcohol, other organic solvents or strong
alkaline solutions such as ammonia or caustic soda
• High voltage, strong magnetic fields, or strong electromagnetic
influences
• Direct impact and excessive vibration
• Sudden temperature changes causing condensation
• Direct sunlight
• Location near high-tension wires, high-voltage devices, power
cables, power devices, or other devices with generate large
power surges or electronic fields when starting and stopping
(esp. if within 100 mm)

ATTENTION
Precautions for Electrostatic Discharges
Excessive static electricity can be generated in dry conditions, so
please make sure to discharge electrostatic charges by touching a
grounded metal bar before contacting the module.

ATTENTION
Contacting the Module
Do not use thinners, which can damage or degrade PCB circuit
board.

Proper Compressed Connection Terminal


• Circular type terminal (O type Lug)
• Circular type terminal with insulation resistance
• Open type terminal (Y type Lug)

7
Mounting/Dismounting Module
Mounting Dismounting
1. Insert the module by inserting the 1. Unfasten the screw that holds the
tab into the groove first and pushing module in place using a
the module against the backplane. screwdriver.

2. Push the top of the module toward 3. Hold on pressing the locking button
the backplane until it is clamped in on the top edge of the module, and
place. pull the module from the backplane

Locking button

4. Ensure that the module is in place


against the backplane, and then
fasten the screw using a
screwdriver.

screwdriver

8
Wiring
Power Supply Module Wiring
LX700 power supply module)

Use 2mm2 or thicker

CPU
POWER
twisted pair cable.

FUSE
USE ONLY
Breaker 250V 1.5A
Use an isolation
transformer when effects
from noise are great. 85 to 264 VAC

Frame ground
Use 2mm2 or thicker cable
for grounding +
24V DC 0.5A Output

Control power (24V)


(See Attention below.)

ATTENTION
Control Power (24V)
24V can be supplied to an I/O Module.
Must avoid parallel connections with other 24V power supply
modules or with other power supply modules.

Allowable Voltage Range of the Power Supply Module


The power supply voltage connected to the power supply module must be within
allowable limits.
Rated input Allowable voltage
Catalog number Remarks
voltage range
LX700 Power Supply
LX-POWER 110 to 220V ac 85V to 264V ac
Module

9
Terminal for the Power Supply Module
• The terminal screw M3.5 is recommended.
• The compressed connection terminal is recommended for the wiring.

Open type terminal Circular type terminal


7.0mm or
7.0mm or less
less
Φ 3.7 ~ Φ 4.3

Use 2mm2 or Thicker Twisted Pair Cable


• Use power supply wire that is thicker than 2mm2 to minimize voltage drops.
• Use twisted pair cable to minimize noise effects.

Power Supply System


Use separate wiring systems for the PLC system, external I/O devices, and power
equipment as shown in the following diagram.

Power
equipment

External I/O
device

isolation transformer

PLC

isolation transformer

Use Isolation Transformer in Noisy Environments


• Use a low noise power supply.
• Use an isolation transformer to reduce the noise as illustrated above.

10

10
Grounding
Grounding the PLC in Noisy Environments
• Connected to the metal part of backplane, the frame ground terminal is
connected to a solid earth ground.
• Use ground wires with a minimum of 2mm2 and the triple grounding connection
which has a resistance of less than 100 Ω.
• The point of grounding should be as close to the PLC as possible and the ground
wire should be as short as possible.
• If two devices share a single ground point, it may produce an adverse effect.
Always use an exclusive ground for each device.

Other devices Other devices


PLC PLC
such as AC drive such as AC drive

11
Operating Condition Setting
LX-CPU700p Processor Module
CPU700P
CPU

RUN COM1
PROG COM2
TEST ERROR
BATT

INIT
TEST
RUN
RMT
PROG

COM1
RS232C
RS485
4 3 21
87 6 5 43 2 1

COM1
RS232C
RS485 Operating Condition
Setting Switches
ON

(Front) (Bottom)

Operating Condition Setting Switches


Switch for Termination Resistance Setting (DIP Switch 1)

Pin setting DIP Switch


Pin No. Description
(Pin No.) 1
For RS-485 communication, set both pins 3 and 4 to
ON (4) ON (3) On if the system is a termination station. (Enables
termination for COM1 terminal)
4, 3
For RS-485 communication, set both pins 3 and 4 to
4 3 2 1

OFF (4) OFF (3) Off if the system is not a termination station.
(Disables termination for COM1 terminal)
For RS-485 communication, set both pins 1 and 2 to
ON (2) ON (1) On if the system is a termination station. (Enables ON
termination for COM2 terminal)
2, 1
For RS-485 communication, set both pins 1 and 2 to
OFF (2) OFF (1) Off if the system is not a termination station.
(Disables termination for COM2 terminal)

12

12
Switch for Communication and Program Booting Method Setting
(DIP Switch 2)
Pin setting
Pin No. Description DIP Switch 2
(Pin No.)
Sets the communication speed on COM2 terminal to
OFF (8) OFF (7)
9600 bps
Sets the communication speed on COM2 terminal to
ON (8) OFF (7)
19200 bps
8, 7
Sets the communication speed on COM2 terminal to
OFF (8) ON (7)
38400 bps
Sets the communication speed on COM2 terminal to
ON (8) ON (7)
4800 bps
Sets the communication speed on COM1 terminal to
OFF (6) OFF (5)
9600 bps

8 7 6 5 4 3 2 1
Sets the communication speed on COM1 terminal to
ON (6) OFF (5)
19200 bps
6, 5
Sets the communication speed of COM1 terminal to
OFF (6) ON (5)
38400 bps
Sets the communication speed on COM1 terminal to
ON (6) ON (5)
4800 bps ON

ON (4) Selects RS-485 communications for COM1


4
OFF (3) Selects RS-232C communications for COM1
ON (3) Selects RS-485 communications for COM2
3
OFF (3) Selects RS-232C communications for COM2
2 OFF (2) Always set to Off. (Reserved for system setting)
Loads the program from EEPROM (flash ROM) at
ON (1)
power-on.
1
Operates the system with the program in RAM at
OFF (1)
power-on.

13
Input/Output Modules
The following table shows the general I/O modules that can be used in an LX700
PLC system whose processor module is LX-CPU700p. For more information on
these I/O modules, refer to the LX700 Plus System (LX-CPU700p) User Manual.

Besides those I/O modules, a wide range of special modules including A/D, D/A,
RTD, TC conversion modules are available. For more information on the special
modules that can be used in an LX700 PLC system, refer to the LX700 Plus System
(LX-CPU700p) User Manual and the installation instructions and user manual for
each module.

Category Catalog number Description


LX-X16D 16-point 12 to 24V dc input
LX-X32D 32-point 12 to 24V dc input
Digital input LX-X64D 64-point 12 to 24V dc input
LX-X16A110 16-point 100 to 120V ac input
LX-X16A220 16-point 200 to 240V ac input
LX-Y16R 16-point 2A 250V ac/30V dc relay output
16-point 2A 250V ac/30V dc relay output with varistor as
LX-Y16RV
surge absorber
32-point 1A 250V ac/30V dc relay output with varistor as
LX-Y32RV
Digital output surge absorber
LX-Y16T 16-point 12 to 24V dc transistor output (NPN)
LX-Y32T 32-point 12 to 24V dc transistor output (NPN)
LX-Y64T 64-point 12 to 24V dc transistor output (NPN)
LX-Y16SSR 16-point 100 to 240V ac SSR output

14

14
Digital Input Module Specifications
Input type DC Input AC Input
Catalog number LX-X16D LX-X32D LX-X64D LX-X16A110 LX-X16A220
Number of input
16 points 32 points 64 points 16 points
points
Insulation method Photocoupler
Rated input
12 to 24V dc 100 to 120V ac 200 to 240V ac
voltage
Operating voltage
10.2 to 26.4V dc 85 to 132V ac 170 to 264V ac
range
Max. input current 10 mA or less (at 24V) 20 mA or less
ON voltage/ Min. 80V/ Min. 160V/
Min. 9.6V
current 6 mA 6 mA
OFF voltage/ Max. 30V/ Max. 50V/
Max. 2.5V
current 3 mA 3 mA
Input impedance: Approx. 3KΩ Approx. 15KΩ Approx. 20KΩ
OFF →
10 ms or less 15 ms or less
Response ON
time ON →
10 ms or less 20 ms or less
OFF
Internal current
65 mA or less 130 mA or less 250 mA or less 60 mA or less
consumption (5V)
8 points/1 COM
32 points/1 COM
Common method (Common for 8 points/1 COM
(Common for polarity +, -)
polarity +, -)
LED (indication
Operation
LED by 32 points LED
indicator
conversion)
Removable
External cable Connector Connector Removable terminal block
terminal block
connection type (40 pin x 1 EA) (40 pin x 2 EA) (M3.5, 20 pins)
(M3.5, 20 pins)
Recommended
0.5 to 1.25 mm2 0.2 mm2 0.5 to 1.25 mm2
cable size
Weight 170 g 140 g 200 g 200 g
Type (A) Type (B) Type (C) Type (A) Type

15
Digital Relay Output Module Specifications
Output type Relay Output
Catalog number LX-Y16R LX-Y16RV LX-Y32RV
Number of output points 16 points 32 points
Insulation method Photocoupler
1A 250V ac,
Rated load voltage 2A 250V ac, 2A 30V dc
1A 30V dc
OFF → ON 10 ms or less
Response time
ON → OFF 10 ms or less
Mechanical 30 million times
Life time
Electric 200 thousand times
External power supply 24V 150 mA or less
Surge protection None Varistor
Internal current
120 mA or less 180 mA or less
consumption (5V)
Common method 8 points/1COM 32 points/1COM
Operation indicator LED
External cable connection Connector
Removable terminal block (M3.5, 20 pins)
type (40 pin x 1 EA)
2 0.2 mm2
Recommended cable size 0.5 to 1.25 mm
Weight 225 g 235 g 300 g
Type (A) Type (B) Type

16

16
Digital Transistor Output Module Specifications
Transistor Output
Output type
NPN
Catalog number LX-Y16T LX-Y32T LX-Y64T
Number of input points 16 points 32 points 64 points
Insulation method Photocoupler
Rated load voltage 12 to 24V dc
Operating load voltage range 10 to 30V dc
Max. load current 0.6A/point 0.4A/point 0.2A/point
OFF state leakage current 100 µA or less
OFF → ON 1 ms or less
Response time
ON → OFF 1ms or less
Internal current consumption
120 mA or less 180 mA or less 250 mA or less
(5V)
Surge absorber Zener diode
Common method 8 points/1COM 32 points/1COM
LED (indication by 32
Operation indicator LED
points conversion)
External cable Removable terminal Connector Connector
connection type block (M3.5, 20 pins) (40 pin x 1 EA) (40 pin x 2 EA)
2 2
Recommended cable size 0.5 to 1.25 mm 0.2 mm
Weight 170 g 140 g 205 g
Types (A) Type (B) Type (C) Type

Digital SSR Output Module Specifications


Output type SSR Output
Catalog number LX-Y16SSR
Number of input points 16 points
Insulation method SSR
Rated load voltage 100 to 240V ac
Operating load voltage range 85V to 264V ac
Max. load current 0.5A/point
OFF state leakage current 100 µA or less
OFF → ON 1ms or less
Response time
ON → OFF 0.5 cycle + 1 ms or less
Internal current consumption (5V) 250 mA or less
Fuse rating 3A
Common method 8 points/1 COM
Operation indicator LED
External cable connection type Removable terminal block (M3.5, 20 pins)
Recommended cable size 0.5 to 1.25 mm2
Weight Approx. 240 g
Type (A) Type

17
Input/Output Module Wiring Diagrams
LX-X16D Wiring Diagram
Internal circuit

Vcc

12V to 24V DC

COM

12V to 24V DC

COM
NC NC: No Connection
NC

LX-X32D Wiring Diagram


Internal circuit
X0 X1
1 2
2 3
3 4 0 to 1F
4 5
5 6
6 7
7 8
8 9
9 10
A B
11 12 COM
C D
13 14
XE XF
15 16
X10 X11
17 18 • The COM terminal of a connector has a short inside
12 13 of the unit.
19 20 • For more information on wiring method, refer to the
14 15
21 22 LX700 Plus System (LX-CPU700p) User Manual.
16 17 • Use separate commercial cable harness (LX-
23 24
18 19 CBLDC) and Pin Type Ass'y (LX-PIN40) for external
25 26 connection.
1A 1B • NC: No Connection
27 28
1C 1D
29 30
X1E X1F
31 32
24V NC 33 34 NC
DC NC 35 36 NC
COM COM
37 38
COM COM
39 40

18

18
LX-X64D Wiring Diagram
COM 40 39 COM
X0 1 2 X1
COM 38 37 COM
24V 2
3 4 3 • The internal circuit is the same
NC 36 35 NC 4 with LX-X32D.
DC 5 6 5
NC 34 33 NC 6 7 • The connectors [I] and [II] have
7 8
X0 32 31 X1 8 9
opposite orientation each other,
2 3 9 10 so be careful with wiring.
30 29 A B
4 5 11 12 • The COM terminal of the
28 27 C D
6 7 13 14 connector has a short inside of
26 25 XE XF the unit.
8 9 15 16
24 23 X10 X11 • For more information on wiring
A B 17 18
22 21 12 13 method, refer to the LX700 Plus
C D 19 20
20 19 14 15 System (LX-CPU700p) User
XE XF 21 22 Manual.
18 17 16 17
X10 X11 23 24 • Use separate commercial cable
16 15 18 19
12 13 25 26 harness (LX-CBLDC) and Pin
14 13 1A 1B Type Ass'y (LX-PIN40) for
14 15 27 28
12 11 1C 1D external connection.
16 17 29 30
10 9 X1E X1F • NC: No Connection
18 19 31 32
8 7
1A 1B 24V NC 33 34 NC
6 5
1C 1D DC NC 35 36 NC
4 3 COM COM
X1E X1F 37 38
2 1 COM COM
39 40

(I) (II)

LX-X16A110 and LX-X16A220 Wiring Diagram


Internal circuit

0 F

COM
COM

COM
LX-X16A110: 100 to 120V ac
LX-X16A220: 200 to 240V ac

19
LX-Y16R and LX-Y16RV Wiring Diagram
Internal circuit

250V AC COM
30V DC

COM

24V DC
Varistor
LX-Y16R: Has no varistor
LX-Y16RV: Has a varistor

LX-Y32RV Wiring Diagram


• The internal circuit is the same with LX-Y16RV.
L Y0 1 2 Y1 L
• The COM terminal of the connector has a short
L
2 3 4 3 L
inside of the unit.
L
4 5 6 5 L
• For more information on wiring method, refer to the
L
6
7 8 7 L
LX700 Plus System (LX-CPU700p) User Manual.
8 9 • Use separate commercial cable harness (LX-CBLRY)
L 9 10 L
A B and Pin Type Ass'y (LX-PIN40) for external
L 11 12 L
C D connection.
L 13 14 L
YE YF
L 15 16 L
Y11
L Y10 17 18 L
L 12 19 20 13 L
14 15
L 21 22 L
16 17
L 23 24 L
18 19
L 25 26 L
1A 1B
L 27 28 L
1C 1D
L 29 30 L
L Y1E
Y1F L
31 32 Max.
COM COM 250V ac
33 34
COM
35 36 COM 30V dc
24V DC+ 24V DC+
37 38
24V DC- 24V DC-
39 40

20

20
LX-Y16T Wiring Diagram
Internal circuit
12V to 24V DC COM (-)

Y0 to YF

12 to 24V DC(+)

12V to 24V DC

LX-Y32T Wiring Diagram


Internal circuit
L Y0 1 2 Y1 L COM (-)
L 2 3 4 3
L
L 4 5 6 5 L

L 6 7 8 7
L
Y0 to YF
L 8 9 10
9
L
L A 11 12 B L
L C 13 14
D
L
L YE 15 16
YF
L 12 to 24V DC(+)
L Y10 17 18
Y11
L
L 12 19 20
13 L

L 14 21 22
15
L • COM (VDC-) and VDC+ (12 to 24V) terminals of the
L 16 23 24 17 L connector has a short inside of the unit.
L 18 25 26
19 L • For more information on wiring method, refer to the
LX700 Plus System (LX-CPU700p) User Manual.
L 1A 27 28
1B
L
• Use separate commercial cable harness (LX-CBLTR) and
L 1C 29 30
1D L
Pin Type Ass'y (LX-PIN40) for external connection.
L 1E 31 32 1F L
• NC: No Connection
NC 33 34 NC
NC 35 36 NC
VDC+
37 38 VDC+
VDC - (COM)
39 40 VDC - (COM)

21
LX-Y64T Wiring Diagram
L Y0 1 2 Y1 L
VDC (-COM) 40 39 VDC (-COM) 2 3
L 3 4 L
VDC+ VDC+ • The internal circuit is the
38 37 L 4 5 6 5 L
6 7 same with LX-Y32T..
NC 36 35 NC L 7 8 L
8 9
• COM (VDC-) and VDC+ (12
NC 34 33 NC L 9 10 L to 24V) terminals of the
L Y1F 32 31 Y1E L L A 11 12 B
L connector has a short
1D 1C L
L 30 29 L C 13 14
D
L inside of the unit.
L 1B 28 27 1A L L YE 15 YF • For more information on
16 L
L
19 18 L Y10 Y11 wiring method, refer to
26 25 L 17 18 L
17 16 L the LX700 Plus System
L 24 23 L 12 19 20
13 L
(LX-CPU700p) User
L 15 22 14 L 14 15
21 L 21 22 L Manual.
12 L
L 13 20 19 L 16 23 24 17 L • Use separate commercial
L Y11 18 Y11 cable harness (LX-CBLTR)
17 L L 18 25 26
19 L
L
YF
16 15
YE
L 1A 1B and Pin Type Ass'y (LX-
L 27 28 L
PIN40) for external
C L
L D 14 13 L 1C 29 30
1D L
B A connection.
L 12 11 L L 1E 31 32 1F L
• NC: No Connection
L 9 10 9
8 L
NC 33 34 NC
L 7 8 7
6 L
NC 35 36 NC
5 4 VDC+ VDC+
L 6 5 L 37 38
L 3 4 3
2 L VDC (-COM) 39 40 VDC (-COM)
L Y1 2 1
Y0 L

(I) (II)

LX-Y16SSR Wiring Diagram


Internal circuit VCC

L 0
L 1
L 2
L 3
L 4
L 5
L 6
L 7

L 8
L 9
L A
L B
L C
L D
L F
L F
COM
AC 10 0 t o 2 4 0 V

22

22
Electrical & Electronics Division (EBG), Gate No.7
Powai Campus, Mumbai 400 072

Product improvement is a continuous process at L&T. Tel. No: 022-67050505


For the latest information please contact us
Fax: 022-67051324/1746
For the latest information please contact us Website: www.LNTEBG.com

Publication LX700-IN002B-EN-P-Aug 2007