Professional Documents
Culture Documents
Technical Note
TN 013: 2015
This technical note is issued by the Asset Standards Authority as a notification to remove from
use RailCorp document EP 08 00 00 02 SP Overhead Wiring Maintenance Standards, Version
4.0.
EP 08 00 00 02 SP is a legacy document and shall be used for reference purposes only. ASA
standard T HR EL 08011 ST Overhead Wiring Maintenance Standards, Version 1.0 supersedes
this document.
Authorisation
Technical content Checked and Interdisciplinary Authorised for
prepared by approved by coordination release
checked by
Signature
Engineering Standard
EP 08 00 00 02 SP
Disclaimer
This document was prepared for use on the RailCorp Network only.
RailCorp makes no warranties, express or implied, that compliance with the contents of this document shall be
sufficient to ensure safe systems or work or operation. It is the document user’s sole responsibility to ensure that the
copy of the document it is viewing is the current version of the document as in use by RailCorp.
RailCorp accepts no liability whatsoever in relation to the use of this document by any party, and RailCorp excludes
any liability which arises in any manner by the use of this document.
Copyright
The information in this document is protected by Copyright and no part of this document may be reproduced, altered,
stored or transmitted by any person without the prior consent of RailCorp.
Document control
Version Date Summary of change
July 2008 Last Technical Review
3.0 May 2010 Application of TMA 400 format
4.0 June 2013 See Table below
© RailCorp Page 2 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
Contents
© RailCorp Page 3 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
This document sets out maintenance policies and parameters associated with the OHW
system including:
• Vegetation management
• Maintenance tolerances with respect to design
• Contact wire
• Catenary and contact splices
• Section insulators
• Insulated knuckles
• Surge arresters
• Wood pole support structures
It also includes
• OHW maintenance tolerances and conditions that trigger corrective maintenance
actions that do not require urgent repair work. The maximum times to complete
the corrective actions are also specified.
• Base safety or operating limits , which are the threshold conditions at or below
which urgent repair work to the overhead wiring work shall be carried out.
Except where immediate repair action is required as per this document, a risk analysis
shall be carried out immediately after a breach of any of the base safety and operating
limits is found. Restrictions on overhead wiring and/or train operations may have to be
imposed prior to the completion of the repair work. Such restrictions may include:
This document does not include maintenance triggers for overhead wiring structures and
their associated bonding arrangements. Overhead wiring structures are maintained by
the Civil discipline. Maintenance triggers for structure bonding arrangements are covered
in EP 12 20 00 01 SP “Bonding of overhead wiring structures to rail”. However, this
document requires the overhead wiring maintainer to report obvious visual defects to the
maintainers of these assets.
The following documents have been incorporated into this document and with the release
of this document are withdrawn:
© RailCorp Page 4 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
2 References
3 Definitions
Contact wire Ratio of the difference in height of the contact wire at two successive supports
gradient to the length of the bay.
Contact wire elastic The elastic limit for a material is the stress beyond which permanent
limit deformation will occur. For the purpose of this document, the elastic limit of a
contact wire is the thickness of a contact wire at a localised wear point below
which permanent deformation will result when the wire is subjected to the
maximum tension at the limits of design operating conditions.
Heel height The vertical distance between the contact wire at the pull off arm and the pivot
point at the heel of the pull off arm.
Passing clearance The minimum clearance required between live parts of overhead wiring
equipment and any earthed material or rail vehicle, or between the pantograph
and any earthed material, under any permissible conditions of operation and
maintenance of vehicles, track and overhead wiring equipment.
Static clearance The minimum distance required between live parts of overhead wiring
equipment (under any permissible conditions of maintenance when not subject
to uplift from a pantograph) and a structure or earthed part of the overhead
wiring equipment.
© RailCorp Page 5 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
4 Vegetation clearances
Vegetation near overhead wiring shall be maintained and controlled so that it is not
within:
Vegetation that has been assessed to be at risk of falling into the overhead wiring shall
also be removed, even if it is located outside of the clearance envelopes specified above.
Allowance for regrowth between inspection and maintenance cycles shall be made when
undertaking vegetation control activities.
All vegetation control activities shall be undertaken in accordance with the requirements
of RailCorp’s Environmental Management System and Safety Management System.
After commissioning, the OHW shall be maintained so that deviations from the approved
and accepted design are within the tolerances set out in 0. These tolerances are
required to ensure pantograph security with an effective pantograph half-width of 700mm
(see drawing CV 0131343), and with the allowable vehicle movement and track
tolerances specified in ESR 0001-100 and ESC 210 (see drawings EL 0006421-2).
The OHW design geometry at a structure is defined with reference to the relevant Track
Control Mark (TCM) for the structure. Within the Electrical discipline, this TCM is also
referred to as the “reference nail” (when installed on a mast) or “brass bar” (when
installed in rock foundation). Critical dimensions of the design track geometry relative to
the TCM at the structure location are given in the survey plaque associated with the TCM.
Refer to RailCorp documents ESC 210 and TMC 212.
© RailCorp Page 6 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
6 Contact wire
Except as noted below, tin bearing copper contact wire in accordance with
EP 08 00 00 24 SP shall be used for replacement of existing contact wires.
Replacement of localised worn hard drawn copper contact wire by a short piece (< 10m)
of tin bearing copper contact wire is permissible.
6.2.1 Measurements
The severity of localised contact wire wear is generally determined by measuring the
contact wire thickness at the thinnest point of the localised wear area. The thickness is
measured along an axis perpendicular to the bottom (wearing surface) of the contact
wire. However, where contact wire side wear (eg at wire junctions) is also observed, a
measurement along the axis perpendicular to the side wear surface shall also be made
and recorded. The cross section area of the contact wire at the thinnest point, and the
corresponding safety factor at limiting operating conditions, shall be determined from
these two measurements for contact wire with side wear.
Contact wire thickness measurement shall be taken with an instrument with an accuracy
of ± 0.05mm, and recorded in units of millimetres to the first decimal place, eg 8.9mm.
Contact wire thickness measurements shall be taken periodically in accordance with the
RailCorp Electrical Technical Maintenance Plan. Measurements shall be made at the
thinnest point as close as practicable at the following locations:
© RailCorp Page 7 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
Condemning sizes of contact wires in the RailCorp overhead wiring network are given in
Table 2 and Table 3. The condemning sizes are determined with the following criteria:
The nominated contact wire condemning sizes are not applicable to conductor systems
26 and 35 (fixed anchored with 137mm2 contact wire at a tension of 12.46kN at 21oC).
Refer to RailCorp Engineering if such systems are encountered in maintenance.
The values given in Table 2 and Table 3 are only valid for contact wires with no side
wear. For contact wires with side wear, the cross section area shall be determined using
the two measurements as set out in section 6.2.1. The wire shall be "condemned" if the
cross section area is less than or equal to the "Section area at condemning" listed in
Table 2 and Table 3.
It is unlikely to have a contact wire run to be uniformly worn down to the “50% worn”
section area in accordance with EP 19 00 00 01 SP before part or all of the wire run has
to be replaced to remove localised wear points. Contact wire resistance is therefore not
considered in the determination of condemning sizes.
© RailCorp Page 8 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
Table 3 - Condemning sizes for 193 mm2 contact wire with no side wear
Where it is not practicable to have the localised wear point removed within the time
specified in Table 8, a contact wire wear strip may be installed in accordance with
RailCorp Drawing EL 0026992 as a temporary measure.
The nominated elastic limits are not applicable to conductor systems 26 and 35 (fixed
anchored with 137mm2 contact wire at a tension of 12.46kN at 21oC). Refer to RailCorp
Engineering if such systems are encountered in maintenance.
The nominated limits are also not applicable to contact wires with side wear. For contact
wires with side wear, the cross section area of the wire shall be determined in
accordance with section 6.2.1. The maximum stress at the localised wear point shall be
calculated to determine if the elastic limit has been exceeded.
© RailCorp Page 9 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
Table 5 – Elastic limits for 193 mm2 contact wire with no side wear
7 Conductor splices
Droppers, in-span feeders, and other fittings that clamp on the catenary wire may have to
be relocated so that they are clear of the helical fitting.
© RailCorp Page 10 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
For worn contact wires, copper shims are installed in the mouth of the splice fitting to
ensure that the running edge of the contact wire is flush with the underside of the splice.
Table 6 gives a guide to the number of shims to be used. The contact wire splice is not
suitable for contact wires with a thickness less than 9.9mm. Hence contact wire
replacement may have to be extended beyond the localised wear point.
As contact wire splices are “hard spots” for pantograph running, no more than 3 contact
splices shall be installed between two adjacent support structures.
Number of shims
Contact wire thickness
(Drawing EL 0034703)
(mm)
Fitting 462/6 (Long) Fitting 462/16 (Short)
16.4 – 15.5
0 0
(New 193mm2)
15.4 – 14.6 1 0
14.5 – 13.5
2 0
(New 137mm2)
13.4 – 12.5 1 1
12.4 – 11.5 2 1
11.4 – 10.5 1 2
10.4 – 9.9 2 2
Table 6 – Guide to shim installation requirements for contact wire full splice
8 Dropper arrangements
Where existing droppers have to be replaced, they shall be replaced by insulated
droppers in accordance with EP 08 00 00 01 SP.
9 Section insulators
Where existing section insulators have to be replaced, they shall be replaced by “Type 6”
section insulators in accordance with EP 08 00 00 01 SP.
10 Insulated knuckles
There is currently no suitable replacement for insulated knuckles with timber beams.
Existing overhead wiring with such insulated knuckles may need to be re-configured
when the knuckles are no longer suitable to remain in service. The Maintainer shall plan
the required modifications with sufficient time allowed for design and construction.
© RailCorp Page 11 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
11 Surge arresters
Surge arresters had been installed on the overhead wiring at approximately mid-way
between substations in some areas of the RailCorp network. This practice is no longer
required. Existing “mid-way” surge arresters shall be removed at the next hands-on
inspection or when the overhead wiring in the area is modified.
Surge arresters are still required at cable to aerial feeder junction locations. See
EP 08 00 00 01 SP.
Where an existing overhead wiring wood pole support structure has to be replaced, it
shall be replaced by one or more structure(s) satisfying the requirements of ESC 330 and
TMC 331.
The values listed under “time to complete corrective action” are maximum allowable
times. Depending on the nature and extent of the defect, shorter time periods may need
to be applied for individual cases to ensure that the risks to personnel safety and train
operations caused by failure of the identified defect(s) are as low as reasonably
practicable. Longer time periods to complete corrective action may be approved by the
relevant Maintenance Engineer Electrical on a case by case basis if the time extension is
justified by a risk analysis.
© RailCorp Page 12 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
13.1 General
Time to complete
Parameter Corrective maintenance trigger
corrective action
Note 1 – An assessment should be made of the rate of vegetation growth. A shorter time
frame for completion of corrective action may be required as a result of the assessment.
© RailCorp Page 13 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
13.2 Conductors
Time to complete
Parameter Corrective maintenance trigger
corrective action
Contact wire > 460mm (Priority 2 exceedence for OHW geometry measuring
6 months
stagger vehicle)
Contact wire Contact wire gradient exceeds maximum values listed in Table 1
6 months
gradient of EP 08 00 00 15 SP.
Contact wire Contact wire thickness at or below condemning size. See section
6 months
thickness 6.2
Catenaries
Clearance between catenary conductors < 20mm 3 months
crossing
Auxiliary Clearance of auxiliary feeder at support < 400mm above tie rod
6 months
feeder chain or portal boom
Note 1 – For fixed anchored overhead wiring, minimum contact height at the maximum
design conductor temperature (generally 55oC for open route and 45oC in tunnels) shall
be determined by height and temperature measurements. RailCorp program MinCont
may be used to calculate the minimum contact height from these measurements.
© RailCorp Page 14 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
Over-run
Signs of damage or incorrect alignment 3 months
protection
Note 1 – Consideration should be taken for possible long lead times to implement
corrective maintenance actions for insulated knuckles with timber beams. See section 10.
© RailCorp Page 15 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
Surge
Damaged or missing connection to earth electrode 1 week
arresters
Structure
earthing Switch or feeding structure not earthed or bonded to rail in 3 months
and accordance with design (Note 2)
bonding
© RailCorp Page 16 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
© RailCorp Page 17 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
Note 1 – Temporary warning signs and / or access barriers to be in place within one day
Note 2 - Temporary labels to be in place for critical structures (eg structure with switch)
within one day
The values listed for “time to complete corrective action” are maximum allowable times.
Immediate action should be initiated if there is a risk of imminent failure. The maximum
allowable times may be varied by the Maintenance Engineer Electrical as a result of a
risk analysis with consideration given to the applicable site specific operating environment
and/or the implementation of temporary measures.
© RailCorp Page 18 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
14.1 General
Base safety or operating Immediate checks and / or Time to complete
Parameter
limit temporary measures corrective action
© RailCorp Page 19 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
14.2 Conductors
Base safety or operating Immediate checks and / or Time to complete
Parameter
limit temporary measures corrective action
< 4.9m at a public road level Advise Police (for public road
crossing, or at a service road level crossings) and use traffic
Contact 1 day
level crossing without a controllers to exclude high
wire height
warning frame vehicles from the level crossing.
Note 1 – Do not reduce speed on curve if excessive stagger is at structure but midbay
stagger is acceptable.
© RailCorp Page 20 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
© RailCorp Page 21 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
© RailCorp Page 22 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0
RailCorp Engineering Standard — Electrical — Overhead wiring
Superseded by T HR EL 08011 ST Overhead wiring maintenance standards EP 08 00 00 02 SP
Where urgent repairs are carried out, the maintainer shall ensure that the data set
associated with the overhead wiring is updated in accordance with the as-built
configuration as soon as practicable, and not less than one month after the completion of
the repairs.
© RailCorp Page 23 of 23
Issued June 2013 UNCONTROLLED WHEN PRINTED Version 4.0