You are on page 1of 32

Building Automation Industrial Automation Systems

Short Form Catalogue

Safe and Flexible Power Distribution


up to 6300A

CD, BD01, BD2, LD, LX and Cast Resin busbar trunking systems,
networked busbar trunking systems

Think future. Switch to green.


Busbar Trunking Systems

The Complete Range for Innovative


and Future-Proof Power Distribution

Moeller can offer single sourced the CD, BD, LD and LX busbar trunking Thanks to our many years of
automation and power distribution systems with networking capability. experience in designing, engineering,
solutions from medium voltage Moeller systems are type-tested low- manufacturing and commissioning, we
distribution boards (11kV), through voltage switchgear and controlgear can provide you with system solutions
the MODAN and PCC modular assemblies (TTA) to IEC/EN 60439-1 tailored precisely to your requirements.
power distribution systems, to final and 2, thus making it easier to certify
distribution and control, linked using your own installations.

CD system 25A–40A
Attractive and flexible,
CD is ideal for lighting
installations. See page 4.

BD01 system 40A–160A


Power supply to the exact
requirements of service
distribution boards.
See page 8.

BD2 system 160A–1250A


A reliable, flexible solution for
factory power distribution,
rising mains and feeder
applications. See page 13.

LD system 1100A–5000A
Flexible power distribution
for high currents in industry.
See page 18.

LX system 800A–6300A
Power transmission from
the transformer to the
switchboard, and rising
mains in the building.
See page 22. Networked busbar and
trunking systems
Cast Resin busbar 800A–6000A Flexible automation on the
A totally encapsulated busbar busbar trunking system
suitable for use outdoors. using EIB, LON and AS-i
See page 27. open bus systems. See
page 30.

2
Busbar Trunking Systems

Plus Points in Every Respect –


Busbar offers Advantages over Cables

Simpler in design Quicker to install

Busbar trunking systems are easier to Busbar trunking systems can reduce
design as the power distribution system on-site installation times by up to
can be planned just on the basis of the 50% compared to cable installations.
total connected load and the number A single run of busbar can replace
and type of individual loads. The linear several runs of cable, along with
network structure with tap-offs to the their associated cable trays, junction
Cable installation means higher load at regular intervals produces a boxes and fixings. No special tools are
combustive energy. clear system configuration, further required. Moeller’s busbar systems
simplifying engineering. By are simple to secure and have
using angles, sets and tees wide fixing intervals
to change direction (busbars up to every
Q
or negotiate LE U 4m, cable every
obstacles, busbar P 1.5m), further
IC
M

can conform to reducing


K
SI

any shape of a installation


building. times.

Installation times are reduced as


busbar is simple to secure, with
wide fixing intervals. Safer,
thanks to a
high short-
LE

circuit rating More flexible


S

IB

and minimal F
A

for modification
E X
combustive energy E and expansion
FL
Busbar trunking systems Where a power
from Moeller offer clear safety distribution system has to match
With a cable installation, new loads advantages in terms of both changing requirements, busbars
have to be connected via an additional short-circuit ratings and combustive offer a fast solution. As demand
sub-distribution board, involving more energy. For example, BD2 A-250 busbar changes, tap off devices can be added
time and expense. trunking systems have a combustive or relocated with minimal disruption
energy of just 1.32kWh/m, whereas for and downtime. The installation can
comparable cable installations (NYY be expanded and modified without
4 x 95/50mm2) this is 5.19kWh/m. difficulty. Flexibility is increased still
Furthermore, Moeller busbar trunking further thanks to the wide range of
systems are halogen-free and have a tap-off units and system components
high short-circuit rating as standard. available. Cost-intensive downtimes are
The short-circuit protection close to the eliminated or kept to a minimum. At
load also simplifies trouble-shooting. all times the power distribution system
Busbar trunking systems enable tap-off Errors during assembly are practically ensures trouble-free operation with
points to be installed close to the load, eliminated thanks to safe, design- a high level of user friendliness and
providing greater transparency at the imposed connection sequences. reliability.
location concerned.

3
CD System

CD System 25A–40A
Attractive Lighting Busbar Trunking

The CD system is designed for interconnection of phases, CD lighting


applications from 25A to 40A. It is trunking represents a new concept in
used particularly where attractive miniature plug-in busbars.
appearance is important, such as in
department stores, supermarkets or Quick and easy to install
furniture stores, and offers efficient
power supply to lighting installations The universal hanger bracket designed
and small loads. Any commercially to support the busbar trunking or the
available lighting system can be easily luminaire is normally required at 3
supended from any point along the metre centres, making installation quick
Suitable and safe for all climatic trunking unit. and easy. Tap-off units are available
conditions – power distribution in fused or unfused, 16 Amp TP & N + E
greenhouses. Flexible and reliable or phase selectable SP & N + E. Tapping
outlets are provided at either 500mm or
The CD lighting trunking range features 1 metre intervals, each complete with a
snap-fit joints and brackets for rapid non-removable hinged cover complete
installation, an aesthetically pleasing with locking fastener to prevent
white finish which eliminates the need accidental contact with the live parts
for painting, and IP54 protection which and ensure the opening remains free
ensures exceptionally long life, even from debris for future use.
in hostile environments. Even when
installation requirements change, the
totally recoverable CD lighting trunking
can easily be removed and re-installed
Woodworking applications – in a new location.
solutions for machines and lighting
systems – wherever accuracy is Available in 2 x 25, 30 and 40 amp
crucial. ratings at 415V with a wide choice
of copper conductor configurations
and an interlock to ensure correct

The attractive design lends itself to


use in stores and shopping centres.

4
CD System

■ With the CD system, the current can ■ Push-fit joints enable rapid, ■ Any commercially available lighting
be fed in at the beginning or the uncomplicated assembly of the system can be easily suspended from
end of the trunking units. trunking units without tools being any point along the trunking unit.
required.

Typical specification
All lighting trunking shall be of approved manufacture and comply with
The following is intended as a guide to specifying degree of ingress protection IP54 as defined in IEC/EN 60529. The current
CD Lighting Trunking: ratings shall be as defined on drawings and schedules.
The system shall be totally enclosed. The trunking shall be suitable for
use on a 400 volt 1, 2, 3 phase (2, 3, 4 wire; PE=housing), 50/60Hz
supply and for the installation to meet the requirements of the IEE Wiring
Regulations (BS7671) and IEC/EN 60439-1 and -2. The enclosure
shall be manufactured from zinc-coated sheet steel, finished in white
(similar to RAL 9002), rectangular in section with flanges to accept the
manufacturer’s standard suspension and luminaire support brackets. Phase
and neutral conductors shall be tinned copper, of equal cross section, fully
insulated and supported at both the tapping outlet positions and at each end
of the trunking.
The lighting trunking shall be manufactured in 2 or 3 metre lengths each
complete with a self-aligning electrical joint sleeve, interlocked to prevent
phase reversal.
Tapping outlet positions shall be provided at 0.5 and 1 metre intervals
each complete with a non-removable hinged cover complete with locking
screw to ensure IP54 rating and preventing accidental contact with the live
conductors.
All end feed units, end caps, joint sleeves and tap-off units shall be
manufactured from non-hygroscopic, self-extinguishing halogen-free
insulating material and designed such that IP54 degree of protection is
maintained.
Tap-off Units
Tap-offs shall be plug-in and designed so as to permit phase selection
on site by the insertion of prewired contact blocks into the appropriate
positions. Fused or unfused tap-off units shall be provided as required.
The lighting trunking shall be the CD range from Moeller or equal and
approved.

5
CD System

Technical Data and Part Numbers for CD Busbar Trunking


Current Rating A 30 30 30 2 x 25 40 40 40
Product Reference (CD-K-…) 1302 1303 1304 2254 1402 1403 1404
Ambient temperature (min/max) ºC -5ºC to +40ºC
Degree of protection IP54; IEC/EN 60529
Mounting Edgewise, with tap-off points on the side

Conductors
Rated Operational Voltage Ue V~ 400 400 400 400 400 400 400
Frequency Hz 50–60 50–60 50–60 50–60 50–60 50–60 50–60
Rated Current Ie therm. Rated current at max. 40ºC and Amps 30 30 30 2 x 25 40 40 40
35ºC averaged over 24 hours
Conductor impedance at 50Hz and 20ºC busbar temperature
Resistance R20 mΩ/m 5.79 5.79 5.79 4.56 3.55 3.55 3.55
Reactance X20 mΩ/m 0.26 0.26 0.26 0.15 0.40 0.40 0.40
Impedance Z720 mΩ/m 5.80 5.80 5.80 4.56 3.57 3.57 3.57
Conductor impedance in the event of a fault
AC Resistance RF mΩ/m 8.24 8.24 8.24 7.50 5.61 5.61 5.61
Reactance XF mΩ/m 0.44 0.44 0.44 0.32 0.80 0.80 0.80
Impedance ZF mΩ/m 8.25 8.25 8.25 7.51 5.67 5.67 5.67
Zero Impedance tested to IEC 60 909, DIN VDE 0102
Resistance R0 Phase to N mΩ/m 24.24 24.24 24.24 18.59 14.85 14.85 14.85
Reactance X0 Phase to N mΩ/m 1.77 1.77 1.77 0.82 0.99 0.99 0.99
Impedance Z0 Phase to N mΩ/m 24.30 24.30 24.30 18.61 14.88 14.88 14.88
Resistance R0 Phase to PE mΩ/m 12 12 12 13.49 9.87 9.87 9.87
Reactance X0 Phase to PE mΩ/m 1.8 1.8 1.8 0.82 1.02 1.02 1.02
Impedance Z0 Phase to PE mΩ/m 12.13 12.13 12.13 13.52 9.92 9.92 9.92
Trunking Weight kg/m 0.75 0.78 0.81 1.06 0.78 0.83 0.88

Short Circuit Rating


Rated peak withstand Ipk kA 2.4 2.4 2.4 3 3.6 3.6 3.6
Rated short time withstand current Icw (t=1 s) kA 0.56 0.56 0.56 0.69 0.85 0.85 0.85
Rated short-time withstand current Icw (t=0.1 s) kA 1.6 1.6 1.6 2 2.4 2.4 2.4

Number of active conductors 2 3 4 2x4 2 3 4


Terminal Capacity
L1, L2, L3 mm2 3.2 3.2 3.2 4 5 5 5
N mm2 3.2 3.2 3.2 4 5 5 5
PE (enclosure) Cu mm2 11 11 11 11 11 11 11
Conductor Material Cu Cu Cu Cu Cu Cu Cu

Tap-off Plugs
Tap-off point Offset every 0.5 m, 1 m or 0.5 m on each side; max. 16 A
Tap-off plug 3- and 5-pole; with or without permanently attached cable; with or without fuse holders for 8.5 mm x
31.5 mm; type gG (IEC) and type gL (VDE) fast cylinder fuses.
All tap-off plugs are of utilization category AC-20B to IEC/EN 60 947-3.
The PE operates as an early-make contact during connection, and as a late-break contact during removal
of the tap-off plug.

Terminal Capacities
Designation Type L1, L2, L3 N PE
Min mm2 Max mm2 Min mm2 Max mm2 Min mm2 Max mm2
Entry Feeder Unit CD-K-…-EA 2.5 6 (f) 2.5 6 (f) 2.5 6 (f)
(Complete with end cap) 10 (st, so) 10 (st, so) 10 (st, so)
Entry Feeder Unit CD-K-…-EE 2.5 6(f) 2.5 6(f) 2.5 (6(f)
10 (st, so) 10 (st, so) 10 (st, so)

Notes so = solid, st = stranded, f = flexible with ferrule

Suspension Bracket CD-B

6
CD System

Dimensions Trunking units

Feeder units

CD-K-...-EE

CD-K-...-EA

Tap-off plugs

Fixing brackets

CD-B CD-BC

7
BD01 System

BD01 System 40A–160A


Simple and Safe Distribution of Power

The BD01 system is designed for Combined with pre-wired ancillary


applications from 40A to 160A. It is equipment units, the result is a wide
primarily used in trade and industry to range of solutions for many different
provide a safe power supply for small applications. Furthermore, the
loads and to feed Moeller’s CD lighting galvanised and painted enclosure of
trunking. the trunking unit ensures optimum
protection against corrosion.
The asymmetrical design of the
connection points ensures fault-free Simple design
installation of the trunking units. The
Fault-free operation thanks to design imposed fitting of the tap- Just one size for five different current
reliable power distribution in a offs on the trunking unit ensures a ratings means minimum stockholding
modern noodle factory. high degree of safety for operating and uncomplicated design. The variable
personnel. The tap-off points only open mounting position – edgewise or flat
automatically when the tap-off units – ensures straightforward engineering
are fitted. They close automatically without derating.
when the tap-off units are removed.
The well thought-out BD01 system,
Flexible power supply with the mechanical and electrical
connection of the trunking units
The power supply for the BD01 accomplished in a single operation,
system is provided via end or centre saves on installation time and thus
feeder units as required. These can be reduces assembly costs.
positioned at junction points on the
BD01 provides power where it’s trunking run and ensure flexibility to
needed in a professional photo match changing site conditions. The
studio. flexible junction unit enables the run to
be adapted to any building layout.

Tap-off units are available in four sizes


for equipping with devices of your
choice or ready-fitted with protective
devices (fuses, MCBs) or protective
devices combined with CEE sockets.

Energy always where it’s needed


– adapted to the different
requirements of workshop
operation.

8
BD01 System

■ The feeder unit can be fitted to any ■ Flexible in every direction. ■ Ancillary equipment units create
junction point. space for additional fittings along-
side tap-off units and feeder units.

Typical Specification
All busbar trunking shall be of approved manufacture, current rating as detailed
The following is intended as a guide to specifying on the drawings/schedules and complying to degree of protection IP54 defined
BD01 busbar trunking: in IEC/EN 60529 when edgewise (tap-off points at side and bottom) and IP50
when flat (tap-off points on top).
The busbar shall be designed and manufactured to comply with IEC/EN
60439-1 and -2. For use on a 400 volt, 3 phase, 4 wire (PE=housing), 50/60 Hz
supply, and capable of withstanding prospective fault level currents as detailed
on the drawings/schedules.
The busbar trunking shall be manufactured in 2 or 3 metre lengths. The
enclosure shall be manufactured from pale grey (RAL 7035) painted galvanised
sheet steel and is the protective earth conductor. The busbar trunking shall have
solid conductors with silver-plated aluminium and copper connection points
at all tap-off outlets and joint positions. Tap-off outlets shall be spaced at 0.5
or 1 metre distance and shall have automatic opening and closing shutters.
They will also ensure that correct polarity is maintained. The joint section
shall provide electrical and mechanical connection by four screws. The joint
section shall absorb any differential expansion between the trunking and the
conductors.
When a change in direction, rating or termination occurs in a busbar run,
manufacturer’s purpose-made fittings shall be used.
Where detailed on the drawings/schedules interlocking coding sets shall
be installed into the tap-off outlets and tap-off units to provide non-
interchangeability of tap-off units to non-designated tap-off outlets.
Tap-off Units
Tap-off units shall be plug-in type suitable to accept HRC fuses, MCBs, DIN
rail mounted devices and socket outlets as detailed on the drawings/schedules.
The enclosure shall be constructed from anodised aluminium and/or insulation
material, complying to degree of protection IP54, as defined in IEC/EN 60529.
The earth connection of the tap-off unit shall provide the opening of the
automatic shutter and make before and break after the live connections are
made.
Where required tap-off units shall be extendible to allow additional
components to be installed on to the internal DIN rail.
The busbar trunking system shall be the BD01 range from Moeller or equal and
approved.

9
BD01 System

Technical Data and Part Numbers for BD01 Busbar Trunking


Product Reference – Current Rating BD01-40 BD01-63 BD01-100 BD01-125 BD01-160
Current paths
Rated Operational Voltage Ue V~ 400 400 400 400 400
Frequency Hz 50–60 50–60 50–60 50–60 50–60
Rated Current Ie therm. Rated current at max. 40ºC and 35ºC averaged over A 40 63 100 125 160
24 hours
Conductor impedance at 50Hz and 20ºC busbar temperature
Resistance R20 mΩ/m 3.960 1.936 0.938 0.910 0.578
Reactance X20 mΩ/m 0.280 0.324 0.286 0.300 0.273
Impedance Z720 mΩ/m 3.970 1.968 0.994 1.000 0.642
Conductor impedance in the event of a fault
AC Resistance RF mΩ/m 5.991 4.128 2.841 2.420 2.189
Reactance XF mΩ/m 1.396 1.248 1.186 0.940 0.973
Impedance ZF mΩ/m 6.151 4.312 3.078 2.600 2.395
Zero Impedance tested to IEC 60 909, DIN VDE 0102
Resistance R0 Phase to N mΩ/m 15.904 7.911 4.115 3.810 3.167
Reactance X0 Phase to N mΩ/m 2.128 2.058 1.797 1.630 1.656
Impedance Z0 Phase to N mΩ/m 1.045 8.175 4.490 4.140 3.574
Resistance R0 Phase to PE mΩ/m 10.086 8.565 6.648 5.430 5.343
Reactance X0 Phase to PE mΩ/m 2.909 3.338 3.067 2.320 2.355
Impedance Z0 Phase to PE mΩ/m 10.498 9.183 7.322 5.910 5.839

Short Circuit Rating


Rated peak withstand Ipk kA 2.55 6.30 15.30 15.30 15.30
Rated short time withstand current Icw (t=1 s) kA 0.58 1.15 2.50 2.50 2.50
Rated short-time withstand current Icw (t=0.1 s) kA 1.70 4.20 9.00 9.00 9.00

Number of active conductors 4 4 4 4 4


Conductor cross-section
L1, L2, L3 mm2 7.9 15.7 34.1 34.1 34.1
N mm2 7.9 15.7 34.1 34.1 34.1
PE (enclosure) Cu mm2 20.0 20.0 20.0 20.0 20.0
Conductor Material Al Al Al Al Cu
Max. interval between trunking unit edgewise m 3 3 3 3 3
supports at normal mechanical load flat m 1.5 1.5 1.5 1.5 1.5
Combustive Energy kWh/m 0.76 0.76 0.76 0.76 0.76
Trunking Weight kg/m 1.45 1.55 1.75 1.75 2.65

Tap-off Units
Rated Operational Voltage Ue V 230 or 400
Rated Current Ie max. A 63
Switching capacity of the built-in switch-disconnector AC-20B

Terminal Capacities L1, L2, L3 N PE


Type min mm2 max mm2 min mm2 max mm2 min mm2 max mm2
Feeder units BD01-E 6 (e, m) 50 (m) 6 (e, m) 50 (m) 6 (e, m) 50 (m)
BD01-160-E 25 (m) 95 (m) 25 (m) 95 (m) 16 (m) 50 (m)
Tap-off units BD01-AK01X/ZS 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st)
BD01-AK02X/ZS3 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st)
BD01-AK02M0/A163 0.75 (so, st) 16 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st)
BD01-AK02M0/A323 0.75 (so, st) 16 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st)
BD01-AK1M1/A101 0.75 (so, st) 16 (so) 0.75 (so, f) 2.5 (so, f) 0.75 (so, f) 2.5 (so, f)
BD01-AK1M1/A161 0.75 (so, st) 17 (so) 0.75 (so, f) 2.5 (so, f) 0.75 (so, f) 2.5 (so, f)
BD01-AK1M1/A321 0.75 (so, st) 18 (so) 0.75 (so, f) 2.5 (so, f) 0.75 (so, f) 2.5 (so, f)
BD01-AK1M1/A... 0.75 (so, st) 16 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)
BD01-AK1M1/A...N 0.75 (so, st) 16 (so) 0.75 (so, st) 16 (so) 0.75 (so, st) 16 (so)
BD01-AK1X/S14 0.50 (f, st) 4 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)
Notes: BD01-AK1X/S18 0.50 (f, st) 16 (f, so, st) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)
BD01-AK1X/GB... 0.75 (so, st) 16 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)
so = solid BD01-AK2X/F1451 0.75 (so, st) 16 (so) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)
st = stranded BD01-AK2X/S27 0.75 (f, st) 10 (f, so, st) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so)
f = flexible with ferrule BD01-AK2HX/S33 1.50 (f, st) 25 (f, st) 0.75 (f, st) 10 (f, so, st) 0.75 (so, st) 16 (so, st)

10
BD01 System

Dimensions Trunking units

No of
l a tap-off points
500 4
2000
1000 2
500 6
3000
BD01-… 1000 3

Flexible junction units

BD01…R

Type l l1 l2
BD01-…-R1 500 165 316
BD01-…-R2 1000 665 –

Note These are the dimensions for some of the more popular items in the BD01 range. For details of
the full range please refer to Moeller’s Power Distribution Catalogue (HPL0214–2003/2004 GB-INT). Continued overleaf

11
BD01 System

Feeder units

M32, M40, M50

BD01-E

BD01-160E

Tap-off units

BD01-AK01X/ZS BD01-AK02X/ZS3

Please enquire for further tap-off unit options.

12
BD2 System

BD2 System 160A–1250A


Power in the Smallest of Spaces

The BD2 system was developed for Low space requirements


applications from 160 A to 1250 A. It
is used in large buildings and in every The variety of trunking lengths and
field of industry to provide the power angles of the trunking units and the
supply for medium-size loads as well flexible junction units enable the
as to supply the smaller systems BD01 busbar trunking system to be optimally
and CD. adapted to the layout of your building.

Double the safety A large number of ready-made tap-off


units with a wide range of components
Charles de Gaulle airport, Paris: The orientation feature of the tap- fitted make the BD2 system suitable
Intelligent infrastructure with the off unit and the design-imposed for universal use. The compact design
BD2 system for optimum safety. connection sequences promote the of the BD2 system means that space is
With the kind permission of “Aéroports de Paris” safety of your personnel. saved when installing the busbar runs
vertically in small riser ducts. There are
In the event of fire, Moeller busbar only two sizes for a total of nine current
system fire barriers maintain integrity ratings, which means less stockholding
against the propagation of fire, gases, and simplified work for the designer.
vapours and fluids for up to two hours The inherently low combustive energy
under defined fire conditions. The significantly reduces the amount of
combustive energy of a typical busbar damage resulting from a fire.
trunking system such as the BD2-
250 is less than a third of that for a The use of busbar trunking systems
comparable cable installation. is also increasing in the field of ship
building. Busbar trunking is suitable
Specific requirements for use on The ability of the power distribution for use in the riser zones of all decks
ships – no problem for Moeller system to continue to supply power for power supply to the cabins
systems. when subjected to fire conditions because of its safety during operation,
is crucial in maintaining supplies to the considerably lower combustive
extractor fans, lighting systems or energy involved, the reduced space
sprinkler pumps during an emergency. requirements, the fast and simple
BD2 has been tested to show engineering and installation, and the
performance equivalent to S classified unmatched flexibility.
products as specified in BS 6387:1994,
Annex D, Resistance To Fire Alone – the
standard specifically applied to cables.

High system and personnel


protection due to reduced
combustive energy at the Basle
Exhibition Centre, Switzerland.

13
BD2 System

Typical Specification
All busbar trunking shall be of approved manufacture, current rating as
The following is intended as a guide to specifying detailed on the drawings/schedules and complying to degree of ingress
BD2 busbar trunking: protection IP52 defined in IEC/EN 60529 and IP54 with accessories.
The busbar shall be designed and manufactured to comply with IEC/EN
60439-1 and -2. For use on a 690 volt, 3 phase, 5 wire (3L, N or 1⁄2 N, PE or
1⁄2 PE), 50/60 Hz supply, and capable of withstanding prospective fault level
currents as detailed on the drawings/schedules.
The busbar trunking shall be manufactured in 1.25, 2.25 or 3.25 metre
lengths or optional lengths from 0.5 up to 3.24 metres. The enclosure shall
be manufactured from pale grey (RAL 7035) painted galvanised sheet steel.
The busbar trunking shall have solid conductors, nickel-plated and tinned
aluminium or copper, with insulated tap-off outlets and busbar supports.
Tap-off outlets shall be spaced at 0.5 or 1 metre distance and shall have
automatic opening and closing shutters. They will also ensure that correct
polarity is maintained. The joint section shall provide electrical and
mechanical connection by four screws. The joint section shall absorb any
differential expansion between the trunking and the conductors.
When a change in direction, rating or termination occurs in a busbar run,
manufacturer’s purpose-made fittings shall be used.
Tap-off Units
■ Compact feeder units are available Tap-off units shall be plug-in type suitable to accept HRC and BS fuses,
for the incoming supply. MCBs, MCCBs, switch disconnectors, DIN rail mounted devices and socket
outlets as detailed on the drawings/schedules.
The enclosure shall be constructed from painted steel and/or insulation
material, complying to degree of protection IP54, as defined in IEC/EN
60529.
The earth connection of the tap-off unit shall provide the opening of the
automatic shutter and make before and break after the live connections are
made.
Where required tap-off units shall be extendible to allow additional
components to be installed on to the internal DIN rail.
The busbar trunking system shall be the BD2A/C range from Moeller or
equal and approved.
■ Branch and junction units permit
optimum adaptation to building
structures.

14
BD2 System

Technical Data for BD2A 5 Bar, Aluminium Conductors Load Distribution Factor = 0.5

Rated Current A 160 250 315 400 500 630 800 1000
Rated Voltage VAC 690 690 690 690 690 690 690 690

Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.440 0.330 0.300 0.210 0.120 0.130 0.090 0.080
pf = 0.8 0.470 0.360 0.320 0.210 0.120 0.130 0.100 0.080
pf = 0.9 0.500 0.380 0.340 0.210 0.130 0.140 0.100 0.070
pf = 1.0 0.490 0.380 0.330 0.190 0.120 0.130 0.080 0.060
Conductor Characteristics
R mΩ/m at end temperature 0.564 0.438 0.383 0.215 0.135 0.149 0.098 0.066
X mΩ/m at end temperature 0.158 0.111 0.112 0.122 0.056 0.057 0.057 0.057
Z mΩ/m at end temperature 0.586 0.452 0.399 0.247 0.146 0.159 0.114 0.088
Protective Conductor
R0 mΩ/m 1.638 1.279 1.225 1.059 0.492 0.492 0.438 0.408
X0 mΩ/m 0.606 0.516 0.524 0.518 0.299 0.303 0.280 0.273

Weight kg/M 5.3 5.8 6.6 7.5 12.3 12.3 12.4 15.8
IP Rating Standard IP 52 IP 52 IP 52 IP 52 IP 52 IP 52 IP 52 IP 52
Optional IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP 54
Dimensions mm 167x68 167x68 167x68 167x68 167x126 167x126 167x126 167x126
Short Time Rating kA for 1 sec 5.5 10 14 16 21 26 32 34
Prospective Short Circuit Rating kA 17 32 36 40 59 64 84 90
Number of Trunkings 1 1 1 1 1 1 1 1

Technical Data for BD2C 5 Bar, Copper Conductors Load Distribution Factor = 0.5

Rated Current A 160 250 315 400 500 630 800 1000 1250
Rated Voltage VAC 690 690 690 690 690 690 690 690 690

Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.300 0.330 0.300 0.220 0.120 0.120 0.070 0.070 0.060
pf = 0.8 0.310 0.350 0.320 0.230 0.120 0.130 0.070 0.070 0.060
pf = 0.9 0.320 0.360 0.340 0.230 0.130 0.140 0.070 0.070 0.050
pf = 1.0 0.290 0.330 0.330 0.210 0.120 0.130 0.060 0.060 0.040
Conductor Characteristics
R mΩ/m at end temperature 0.333 0.383 0.383 0.239 0.136 0.151 0.065 0.068 0.041
X mΩ/m at end temperature 0.157 0.158 0.112 0.115 0.053 0.053 0.053 0.053 0.054
Z mΩ/m at end temperature 0.368 0.414 0.399 0.266 0.146 0.160 0.084 0.086 0.068
Protective Conductor
R0 mΩ/m 1.027 1.139 1.065 0.956 0.473 0.470 0.258 0.270 0.174
X0 mΩ/m 0.641 0.529 0.507 0.507 0.274 0.277 0.265 0.249 0.265

Weight kg/M 7.3 7.5 8.0 9.5 15.6 15.6 18.9 25.1 37.6
IP Rating Standard IP 52 IP 52 IP 52 IP 52 IP 52 IP 52 IP 52 IP 52 IP52
Optional IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP54
Dimensions mm 167x68 167x68 167x68 167x68 167x126 167x126 167x126 167x126 167x126
Short Time Rating kA for 1 sec 5.5 10 14 16 21 26 32 34 34
Prospective Short Circuit Rating kA 17 32 36 40 59 64 84 90 90
Number of Trunkings 1 1 1 1 1 1 1 1 1

Back-up Protection using Moulded Case Circuit Breakers


Rated current Normal Icu Icc Medium Icu Icc High Icu Icc
BD2- System Ie A Switching Capacity kA kA Switching Capacity kA kA Switching Capacity kA kA
BD2A(C)-.-160 160 NZMB2-A160 25 25 NZMN2-A160 50 50 NZMH2-A160 100 100
BD2A(C)-.-250 250 NZMB2-A250 25 25 NZMN2-A250 50 50 NZMH2-A250 100 100
BD2A/C-.-315 315 – – – NZMN3-AE400 50 50 NZMH3-AE400 100 100
BD2A/C-.-400 400 – – – NZMN3-AE400 50 50 NZMH3-AE400 100 100
BD2A/C-.-500 500 – – – NZMN3-AE630 50 50 NZMH3-AE630 100 100
BD2A/C-.-630 630 – – – NZMN3-AE630 50 50 NZMH3-AE630 100 100
BD2A/C-.-800 800 – – – NZMN4-AE800 50 50 NZMH4-AE800 100 50
BD2A(C)-.-1000 1000 – – – NZMN4-AE1000 50 50 NZMH4-AE1000 100 50
BD2C-.-1250 1250 – – – NZMN4-AE1250 50 50 NZMH4-AE1250 100 50

15
BD2 System

Dimensions Straight trunking units


c

330
centre of clamp terminal
163

167
307 (557) 220
BD2.-…-… n × 500 (1000)

L-junction units
BD2.-…-LR…(-G*), BD2.-…-LL…(-G*) BD2.-…-LV…(-G*), BD2.-…-LH…(-G*)
c

70

c
x = 360–1250

70
G* = 85°–175°
x = 360–1250

G* = 85°–175°

Rated c
current (A) (mm)
y = 360–1250
160–400 68
500–1250 126
y = 360–1250

Cabling boxes Distribution feeder unit


BD2-400-KR (BD2.-400-EE) BD2-1000-KR (BD2.-1000-EE) BD2.-400(1000)-VE

295
191
191

4 × 65 c
x12.5
108.5
9

123

223 308

247.5 332.5

223 308
307
183.5
100
100

14 × 9

163 c1

200 c2
240

285

325

370

Note These are the dimensions for


some of the more popular items in
the BD2 range. For details of the full
range please refer to Moeller’s Power
253
Distribution Catalogue (HPL 0214-2003/
338 2004 GB-INT).

16
BD2 System

End feeder units


BD2.-250-EE 270 BD2.-400-EE
14 × 9

200
143.5

64
100

105
64

74

40
40

423
x9

20
300 75

100
167

245

270

290

219
395
420
440
167

85
200 250

478
x9 14 × 9
563 200 387.5

605

687

Tap-off units
BD2-AK1/2CEE163400-EE Up to 25A
88

For M32 For M25, 32, 40 For M20


44

354
9
20

77
101
170

50

50

314 7
BD2-AK2X/F…
BD2-AK2X/GB…
BD2-AK2X/S…
BD2-AK3X/G500 Up to 63A
205

BD2-AK3X/GB1003
Up to 125A
474

440
9
20

For M25, 40, 63


101
50

50

For M32 434 7 For M20

Spacer bracket Vertical retaining elements Fixing bracket


BD2-BD BD2-BWV BD2-…-BB
15

246
33

200
c1
C

110

16
169 34
28 199
288
15
+10

135
9

250
-5
25

Rated c
48

100
208 current (A) (mm)
7.2

100 160–1250 30–82

Rated c c1
9

current (A) (mm) (mm)


91

7.2 160–400 86.5 48


28–82

14 11 500–1250 144.5 77

17
LD System

LD System 1100A–5000A
For Reliable Electrical Power

The LD system covers the current range The busbar offset ensures that the
from 1100A to 5000A. It is ideal for elements are installed with the correct
linking between transformer, main phase sequence. Installation errors are
distribution board and sub-distribution therefore reliably prevented.
boards in production units with a high
power requirement, such as for welding The tap-off units can be individually
lines in the automotive industry, or equipped, providing solutions for a
industrial furnaces. variety of different types of application.

A separate PE bar increases the Rapid mounting


High availability solutions for conductor cross-section and ensures
Advanced Micro Devices, Dresden, low impedance in the event of a fault. The compact design of the LD system
Germany – one of the most This enables longer busbar runs and a means that space is saved.
modern semiconductor factories in reliable response from the protective
the world. device even where long current paths The plug-in connections and rapid
are involved. fixing through the use of a single bolt
and hook joint ensure straightforward,
For all networks cost-efficient assembly.

The choice of a 4- or 5-conductor


system makes it suitable for a wider
range of applications. The high short-
circuit rating enables protection
using medium-voltage breakers when
transporting power between the
transformer and the main feeder unit.
Type-tested systems for wind
power. For both aluminium and copper
conductor systems, a bolt and hook
provide reliable connections, and
enable all cross-sections to be joined
with one another in a single
operation.

Safe power supply for


infrastructure and production in
the chemical industry.

18
LD System

■ Power is fed from the transformer ■ Where required, power is simply ■ Direction changes are possible in
to the LD busbar trunking system tapped via tap-off units. three axes.
via feeder units with connection
lugs prepared for transformer lug
intervals of 150 to 750 mm.

Typical Specification
All busbar trunking shall be of approved manufacture and be available
The following is intended as a guide to specifying with various degrees of ingress protection including IP34 and IP54, as
LD busbar trunking: defined in IEC/ EN 60 529.The current ratings shall be as defined on
technical data sheets, drawings and schedules.
The system shall be air insulated and metal enclosed.The trunking shall
be suitable for use up to 1000V 162/3Hz to 60 Hz supply and available in
various configurations including 3 phase and half or full PEN and 3 phase,
half or full neutral and earth (PE). It shall meet the requirements of the IEE
Wiring Regulations (BS7671) and IEC/ EN 60 439 -1 and -2.The enclosure
shall be manufactured from galvanised sheet steel, finished in RAL 7035
(pale grey), prepared to accept the manufacturer’s standard suspension
and support brackets.Phase and neutral conductors shall be nickel and tin
plated aluminium or tinned copper, all epoxy coated.
The busbar trunking shall be manufactured in different lengths up to 3.2m
either as feeder or as distribution units each complete with a single bolt
and hook joint connection, interlocked to prevent phase reversal.
Various junction units shall be supplied as standard, including elbows,
knees, T-units, U-units and Z-units. Further standard components must be
available such as expansion units, phase reversal units, cable feeder boxes,
transformer connection units and panel flange connections.
For distribution, tapping outlet positions shall be provided at different
positions with up to 3 outlets on each side of a 3.2m length. Each outlet
shall have a cover complete with sealing facility to maintain the IP rating
of the system and preventing accidental contact with the live conductors.
All plastic parts (such as tapping outlets) shall be manufactured from non-
hygroscopic, self –extinguishing halogen-free insulating material.
Tap-off Units
Tap-off units shall be plug-in type up to 800A. Incorrect mounting must
be prevented by an interlocking mechanism. The tap-off units shall be
equipped either with a load break switch or a MCCB (handoperated or
motor controlled). The short circuit capacity should be available up to
100kA at 415V 50Hz
The busbar trunking shall be the Moeller LD range or equal and approved.

19
LD System

Technical Data for LD 4 Bar, Aluminium Conductors Load Distribution Factor = 1

Size of PEN Compared to Phase Bar Full Full Full Half Full Half Full Half Full Half Full Half Full

Rated Current
Horizontal/edgewise * IP 34 A 1100 1250 1600 2000 2000 2500 2500 3000 3000 3700 3700 4000 4000
IP 54 A 900 1000 1200 1500 1500 1800 1800 2000 2000 2400 2400 2700 2700
Vertical IP 34 A 950 1100 1250 1700 1700 2100 2100 2300 2300 2800 2800 3400 3400
IP 54 A 900 1000 1200 1500 1500 1800 1800 2000 2000 2400 2400 2700 2700
Horizontal/flat IP 34 / IP 54 A 700 750 1000 1200 1200 1700 1700 1800 1800 2200 2200 2350 2350

Rated Voltage V~ 690 690 690 690 690 690 690 690 690 690 690 690 690
Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.162 0.118 0.123 0.089 0.089 0.073 0.073 0.074 0.074 0.056 0.056 0.047 0.047
pf = 0.8 0.168 0.119 0.125 0.090 0.090 0.072 0.072 0.073 0.073 0.055 0.055 0.046 0.046
pf = 0.9 0.171 0.116 0.123 0.089 0.089 0.068 0.068 0.070 0.070 0.051 0.051 0.043 0.043
pf = 1.0 0.152 0.093 0.102 0.074 0.074 0.050 0.050 0.051 0.051 0.036 0.036 0.031 0.031
Conductor Characteristics
R mΩ/m at end temperature 0.073 0.054 0.057 0.043 0.044 0.027 0.028 0.030 0.029 0.021 0.020 0.018 0.016
X mΩ/m at end temperature 0.046 0.043 0.043 0.025 0.029 0.023 0.029 0.024 0.029 0.019 0.022 0.017 0.019
Z mΩ/m at end temperature 0.098 0.069 0.072 0.049 0.053 0.036 0.041 0.038 0.041 0.029 0.030 0.025 0.025
Protective Conductor
R0 mΩ/m 0.284 0.217 0.217 0.242 0.173 0.180 0.120 0.180 0.120 0.126 0.090 0.110 0.075
X0 mΩ/m 0.232 0.200 0.200 0.154 0.174 0.154 0.154 0.154 0.153 0.097 0.119 0.086 0.087

Weight kg/m 16.7 20 20 21.7 22.9 27.4 29.4 27.4 29.4 33.7 36.6 37.2 40.6
IP Rating Standard IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34
Optional IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54
Dimensions mm 180x180 180x180 180x180 180x240 180x240 180x240 180x240 180x240 180x240 180x240 180x240 180x240 180x240
Short Time Rating
kA for 1 sec 40 55 58 80 80 110 110 116 116 116 116 116 116
(phase conductors only)
Prospective Short Circuit Rating kA 121 154 176 242 242 275 275 286 286 286 286 286 286

Technical Data for LD 4 Bar, Copper Conductors Load Distribution Factor = 1

Size of PEN Compared to Phase Bar Full Full Half Full Half Full Half Full

Rated Current
Horizontal/edgewise * IP 34 A 2000 2600 3400 3400 4400 4400 5000 5000
IP 54 A 1600 2000 2600 2600 3200 3200 3600 3600
Vertical IP 34 A 1650 2100 2700 2700 3500 3500 4250 4250
IP 54 A 1600 2000 2600 2600 3200 3200 3600 3600
Horizontal/flat IP 34 / IP 54 A 1200 1550 2000 2000 2600 2600 3000 3000

Rated Voltage V~ 690 690 690 690 690 690 690 690
Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.096 0.078 0.055 0.055 0.042 0.042 0.035 0.035
pf = 0.8 0.094 0.076 0.053 0.053 0.040 0.040 0.033 0.033
pf = 0.9 0.089 0.070 0.048 0.048 0.036 0.036 0.030 0.030
pf = 1.0 0.064 0.048 0.031 0.031 0.022 0.022 0.019 0.019
Conductor Characteristics
R mΩ/m at end temperature 0.037 0.028 0.017 0.018 0.012 0.013 0.011 0.011
X mΩ/m at end temperature 0.042 0.036 0.026 0.027 0.023 0.022 0.020 0.018
Z mΩ/m at end temperature 0.056 0.046 0.031 0.032 0.026 0.025 0.023 0.021
Protective Conductor
R0 mΩ/m 0.144 0.114 0.116 0.079 0.083 0.056 0.070 0.050
X0 mΩ/m 0.199 0.225 0.124 0.130 0.072 0.093 0.088 0.106

Weight kg/m 38.8 51.2 60.3 67.0 82.0 91.8 100.2 112.6
IP Rating Standard IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34
Optional IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54
Dimensions mm 180x180 180x180 180x240 180x240 180x240 180x240 180x240 180x240
Short Time Rating 58 58 116 116 116 116 116 116
kA for 1 sec
(phase conductors only)
Prospective Short Circuit Rating kA 176 176 286 286 286 286 286 286

* Including adjustments in height of ≤1.3 m

20
LD System

Technical Data for LD 5 Bar, Aluminium Conductors Load Distribution Factor = 1

Size of PEN Compared to Phase Bar Full Full Full Half Full Half Full Half Full Half Full Half Full

Rated Current
Horizontal/edgewise * IP 34 A 1100 1250 1600 2000 2000 2500 2500 3000 3000 3700 3700 4000 4000
IP 54 A 900 1000 1200 1500 1500 1800 1800 2000 2000 2400 2400 2700 2700
Vertical IP 34 A 950 1100 1250 1700 1700 2100 2100 2300 2300 2800 2800 3400 3400
IP 54 A 900 1000 1200 1500 1500 1800 1800 2000 2000 2400 2400 2700 2700
Horizontal/flat IP 34 / IP 54 A 700 750 1000 1200 1200 1700 1700 1800 1800 2200 2200 2350 2350

Rated Voltage V~ 690 690 690 690 690 690 690 690 690 690 690 690 690
Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.162 0.118 0.123 0.089 0.089 0.073 0.073 0.074 0.074 0.056 0.056 0.047 0.047
pf = 0.8 0.168 0.119 0.125 0.090 0.090 0.072 0.072 0.073 0.073 0.055 0.055 0.046 0.046
pf = 0.9 0.171 0.116 0.123 0.089 0.089 0.068 0.068 0.070 0.070 0.051 0.051 0.043 0.043
pf = 1.0 0.152 0.093 0.102 0.074 0.074 0.050 0.050 0.051 0.051 0.036 0.036 0.031 0.031
Conductor Characteristics
R mΩ/m at end temperature 0.088 0.054 0.059 0.042 0.043 0.028 0.029 0.029 0.030 0.020 0.021 0.017 0.018
X mΩ/m at end temperature 0.045 0.043 0.042 0.025 0.030 0.024 0.031 0.024 0.031 0.020 0.025 0.021 0.021
Z mΩ/m at end temperature 0.099 0.069 0.072 0.049 0.052 0.037 0.042 0.037 0.043 0.028 0.033 0.027 0.027
Protective Conductor
R0 mΩ/m 0.315 0.240 0.240 0.301 0.292 0.217 0.213 0.217 0.212 0.163 0.166 0.145 0.146
X0 mΩ/m 0.401 0.393 0.393 0.267 0.291 0.202 0.265 0.202 0.263 0.175 0.220 0.196 0.196

Weight kg/m 17.9 22.0 22.0 22.9 24.1 29.4 31.4 29.4 31.4 36.6 39.5 40.6 44
IP Rating Standard IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34
Optional IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54
Dimensions mm 180x180 180x180 180x180 180x240 180x240 180x240 180x240 180x240 180x240 180x240 180x240 180x240 180x240
Short Time Rating
kA for 1 sec 40 55 58 80 80 110 110 116 116 116 116 116 116
(phase conductors only)
Prospective Short Circuit Rating kA 121 154 176 242 242 275 275 286 286 286 286 286 286

Technical Data for LD 5 Bar, Copper Conductors Load Distribution Factor = 1

Size of PEN Compared to Phase Bar Full Full Half Full Half Full Half Full

Rated Current
Horizontal/edgewise * IP 34 A 2000 2600 3400 3400 4400 4400 5000 5000
IP 54 A 1600 2000 2600 2600 3200 3200 3600 3600
Vertical IP 34 A 1650 2100 2700 2700 3500 3500 4250 4250
IP 54 A 1600 2000 2600 2600 3200 3200 3600 3600
Horizontal/flat IP 34 / IP 54 A 1200 1550 2000 2000 2600 2600 3000 3000

Rated Voltage V~ 690 690 690 690 690 690 690 690
Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.096 0.078 0.055 0.055 0.042 0.042 0.035 0.035
pf = 0.8 0.094 0.076 0.053 0.053 0.040 0.040 0.033 0.033
pf = 0.9 0.089 0.070 0.048 0.048 0.036 0.036 0.030 0.030
pf = 1.0 0.064 0.048 0.031 0.031 0.022 0.022 0.019 0.019
Conductor Characteristics
R mΩ/m at end temperature 0.037 0.031 0.017 0.018 0.013 0.015 0.013 0.013
X mΩ/m at end temperature 0.043 0.038 0.028 0.028 0.024 0.022 0.020 0.020
Z mΩ/m at end temperature 0.057 0.049 0.033 0.034 0.027 0.027 0.024 0.024
Protective Conductor
R0 mΩ/m 0.179 0.134 0.149 0.149 0.116 0.100 0.103 0.103
X0 mΩ/m 0.387 0.357 0.238 0.248 0.186 0.216 0.188 0.184

Weight kg/m 45.5 61.0 67.0 73.3 91.8 101.6 112.6 125.0
IP Rating Standard IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34
Optional IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54
Dimensions mm 180x180 180x180 180x240 180x240 180x240 180x240 180x240 180x240
Short Time Rating
kA for 1 sec 58 58 116 116 116 116 116 116
(phase conductors only)
Prospective Short Circuit Rating kA 176 176 286 286 286 286 286 286

* Including adjustments in height of ≤1.3 m

21
LX System

LX System 800A–6300A
Less Weight, More Power

The LX system with its ‘sandwich’


construction is designed for
applications from 800A to 6300A. It
is used in multi-storey buildings and
wherever the flexible transportation of
large amounts of power is required.

The high degree of protection to IP55


ensures the safe distribution of power
even in extremely contaminated or
humid environments.

The tap-off units have an orientation


feature, which ensures fault-free
installation due to the design-imposed
fitting sequence. This, together with
the automatic protective mechanism Compact and light
at the tap-off points, ensures a high
degree of protection from accidental The compact, low impedance
contact for operating personnel. ‘sandwich’ construction minimises
voltage drops, so enabling the cost
Reliability in sensitive environments effective transmission of large amounts
of power, even over long distances,
The conductor configurations with whether installed horizontally or
double N conductors and clean earth vertically.
Reliability of supply was a key ensure an overload free neutral
consideration when over 1km of conductor even with imbalanced loads. Rapid connection reduces assembly
LX busbar was installed at the Susceptible loads such as computers times, as does the low weight of the
headquarters of Swiss Re in London. are not put at risk by earth faults to the LX busbar system.
With the kind permission of David Hawkins. enclosure if they are connected to the
clean earth. For full selection and technical details of
the Barduct LX Busbar Trunking System,
Flexibility in every position please request a copy of the LX Basic
Information (G3750-2209GB-INT).
The electrical load bearing capacity
of the LX system is not affected by
its installation position. This enables
optimum flexibility where busbar run
routing is concerned. The distortion
resistant aluminium enclosure is low in
weight and highly resistant to chemical
2.3 km of LX busbar trunking and atmospheric influences.
systems for the optimal supply of
exhibition hall 3 in Frankfurt Main,
Germany.

22
LX System

Typical Specification
All busbar trunking shall be of approved manufacture and comply with degree
The following is intended as a guide to specifying of ingress protection IP54 as defined in IEC/EN 60 529. The current ratings
LX busbar trunking: shall be as defined on technical data sheets, drawings and schedules.
The system shall be totally enclosed and low impedance sandwich
construction. The trunking shall be suitable for use up to 690V 50Hz supply
and available in various configurations including 3 phase and neutral, double
neutral, earth and/or clean earth (with a maximum of 6 conductors). It shall
meet the requirements of the IEE Wiring Regulations (BS7671) and IEC/
EN 60 439 -1 and -2. The enclosure shall be manufactured from aluminium,
finished in RAL 7035 (pale grey), prepared to accept the manufacturer’s
standard suspension and support brackets. Phase and neutral conductors shall
be nickel and tin plated aluminium or tinned copper, of equal cross-section,
fully insulated.
The current rating must be equal in all installation positions (flat, edge or
vertical). A derating in any position is not acceptable.
The busbar trunking shall be manufactured in different lengths up to 3m either
as feeder or as distribution unit each complete with a self-torquing single bolt
joint block.
Various junction units shall be supplied as standard, including elbows, knees,
■ Optimum matching to building
T-units, Z-units. Further standard components must be available such as cable
layouts. feeder boxes, transformer connection units, and panel flange connections.
For distribution, tapping outlet positions shall be provided at different positions
with up to 5 outlets on each side of a 3m length. Each outlet shall have a cover
complete with sealing facility to ensure IP54 rating and preventing accidental
contact with the live conductors.
All plastic parts (like tapping outlets) shall be manufactured from non-
hygroscopic, self-extinguishing halogen-free insulating material and designed
such that IP54 degree of protection is maintained.
Tap-off Units
Tap-off units shall be plug-in up to 630A and fix mounted from 800 to 1250A.
Incorrect mounting shall be prevented by an interlocking mechanism. The
tap-off units shall be equipped with either a fused switch or a MCCB. The short
circuit capacity should be 65kA at 415V 50Hz.
The busbar trunking shall be the Barduct LX range from Moeller or equal and
approved.
■ Rapid, safe mounting of structural
elements.

23
LX System

Technical Data for LX 4 Bar, Aluminium Conductors Load Distribution Factor = 1

Rated Current A 800 1000 1250 1600 2000 2500 3200 4000 4500
Rated Voltage V~ 690 690 690 690 690 690 690 690 690

Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.212 0.167 0.115 0.073 0.052 0.048 0.037 0.027 0.024
pf = 0.8 0.231 0.179 0.122 0.077 0.056 0.050 0.039 0.029 0.026
pf = 0.9 0.249 0.189 0.127 0.080 0.060 0.052 0.040 0.030 0.026
pf = 1.0 0.253 0.184 0.121 0.074 0.059 0.048 0.038 0.029 0.024
Conductor Characteristics
R mΩ/m at end temperature 0.146 0.106 0.070 0.043 0.034 0.028 0.022 0.017 0.014
X mΩ/m at end temperature 0.028 0.031 0.024 0.017 0.009 0.011 0.008 0.005 0.006
Z mΩ/m at end temperature 0.149 0.110 0.074 0.046 0.035 0.030 0.024 0.018 0.015
Protective Conductor
R0 mΩ/m 0.281 0.274 0.240 0.159 0.153 0.154 0.121 0.092 0.095
X0 mΩ/m 0.198 0.200 0.161 0.130 0.094 0.101 0.097 0.063 0.069

Weight kg/m 13.4 14.5 16.9 18.9 25.2 29.4 43.2 50.7 59.2
IP Rating Standard IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP54
Optional IP 55 IP 55 IP 55 IP 55 IP 55 IP 55 IP 55 IP 55 IP55
Dimensions mm 145x137 145x137 145x162 145x207 145x287 145x287 145x439 145x599 145x599
Short Time Rating
kA for 1 sec 25 35 50 60 75 86 100 140 150
(phase conductors only)
Prospective Short Circuit Rating kA 53 70 110 132 158 194 220 255 255

Technical Data for LX 4 Bar, Copper Conductors Load Distribution Factor = 1

Rated Current A 1000 1250 1400 1600 2000 2500 3200 4000 5000
Rated Voltage V~ 690 690 690 690 690 690 690 690 690

Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.134 0.117 0.091 0.087 0.059 0.037 0.033 0.027 0.020
pf = 0.8 0.143 0.122 0.097 0.089 0.062 0.038 0.034 0.028 0.020
pf = 0.9 0.150 0.125 0.101 0.090 0.064 0.040 0.033 0.028 0.021
pf = 1.0 0.144 0.113 0.095 0.078 0.061 0.036 0.028 0.024 0.019
Conductor Characteristics
R mΩ/m at end temperature 0.083 0.065 0.055 0.045 0.035 0.021 0.016 0.014 0.011
X mΩ/m at end temperature 0.027 0.031 0.020 0.026 0.013 0.009 0.011 0.008 0.005
Z mΩ/m at end temperature 0.087 0.072 0.059 0.051 0.037 0.022 0.019 0.016 0.012
Protective Conductor
R0 mΩ/m 0.252 0.245 0.203 0.213 0.181 0.156 0.152 0.108 0.089
X0 mΩ/m 0.192 0.191 0.161 0.157 0.132 0.096 0.096 0.079 0.067

Weight kg/m 20.7 24.0 26.4 31.5 36.6 54.7 68.8 90.1 109.8
IP Rating Standard IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP54
Optional IP 55 IP 55 IP 55 IP 55 IP 55 IP 55 IP 55 IP 55 IP55
Dimensions mm 145x137 145x137 145x162 145x162 145x207 145x287 145x287 145x439 145x599
Short Time Rating
kA for 1 sec 46 50 57 65 75 95 100 150 150
(phase conductors only)
Prospective Short Circuit Rating kA 80 110 125 132 165 189 220 255 255

Technical Data for 6300A available on request.

24
LX System

Technical Data for LX 5 Bar, Aluminium Conductors Load Distribution Factor = 1

Rated Current A 800 1000 1250 1600 2000 2500 3200 4000 4500
Rated Voltage V~ 690 690 690 690 690 690 690 690 690

Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.211 0.166 0.114 0.073 0.052 0.047 0.036 0.026 0.024
pf = 0.8 0.231 0.179 0.121 0.077 0.056 0.050 0.038 0.028 0.025
pf = 0.9 0.248 0.188 0.127 0.079 0.059 0.051 0.040 0.030 0.026
pf = 1.0 0.252 0.183 0.121 0.074 0.058 0.048 0.038 0.029 0.024
Conductor Characteristics
R mΩ/m at end temperature 0.146 0.106 0.070 0.043 0.034 0.028 0.022 0.017 0.014
X mΩ/m at end temperature 0.028 0.031 0.024 0.017 0.009 0.011 0.008 0.005 0.006
Z mΩ/m at end temperature 0.149 0.110 0.074 0.046 0.029 0.025 0.024 0.018 0.015
Protective Conductor
R0 mΩ/m 0.297 0.274 0.251 0.228 0.204 0.181 0.158 0.135 0.111
X0 mΩ/m 0.216 0.200 0.184 0.168 0.152 0.136 0.119 0.103 0.088

Weight kg/m 11.6 13.3 17.0 23.8 29.3 36.3 48.5 59.2 73.2
IP Rating Standard IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54
Optional IP55 IP55 IP55 IP55 IP55 IP55 IP55 IP55 IP55
Dimensions mm 145x137 145x137 145x162 145x207 145x287 145x287 145x439 145x599 145x599
Short Time Rating 25 35 50 60 75 86 100 140 150
kA for 1 sec
(phase conductors only)
Prospective Short Circuit Rating kA 53 70 110 132 158 194 220 255 255

Technical Data for LX 5 Bar, Copper Conductors Load Distribution Factor = 1

Rated Current A 1000 1250 1400 1600 2000 2500 3200 4000 5000
Rated Voltage V~ 690 690 690 690 690 690 690 690 690

Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.134 0.117 0.091 0.086 0.058 0.036 0.033 0.026 0.019
pf = 0.8 0.143 0.122 0.096 0.089 0.062 0.038 0.033 0.027 0.020
pf = 0.9 0.149 0.124 0.100 0.089 0.064 0.039 0.033 0.027 0.020
pf = 1.0 0.143 0.112 0.095 0.077 0.060 0.036 0.027 0.024 0.019
Conductor Characteristics
R mΩ/m at end temperature 0.083 0.065 0.055 0.045 0.035 0.021 0.016 0.014 0.011
X mΩ/m at end temperature 0.027 0.031 0.020 0.026 0.013 0.009 0.011 0.008 0.005
Z mΩ/m at end temperature 0.087 0.072 0.059 0.051 0.037 0.022 0.019 0.016 0.012
Protective Conductor
R0 mΩ/m 0.274 0.254 0.233 0.213 0.193 0.172 0.152 0.132 0.111
X0 mΩ/m 0.207 0.191 0.175 0.160 0.144 0.128 0.113 0.097 0.082

Weight kg/m 20.7 25.3 28.2 35.2 41.9 66.3 85.5 107.2 133.2
IP Rating Standard IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54
Optional IP55 IP55 IP55 IP55 IP55 IP55 IP55 IP55 IP55
Dimensions mm 145x137 145x137 145x162 145x162 145x207 145x287 145x287 145x439 145x599
Short Time Rating
kA for 1 sec 46 50 57 60 75 95 100 150 150
(phase conductors only)
Prospective Short Circuit Rating kA 80 110 125 132 165 189 220 255 255

Technical Data for 6300A available on request.

25
LX System

Technical Data for LX 6 Bar, Aluminium Conductors Load Distribution Factor = 1

Rated Current A 800 1000 1250 1600 2000 2500 3200 4000 4500
Rated Voltage V~ 690 690 690 690 690 690 690 690 690

Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.211 0.166 0.114 0.073 0.052 0.047 0.036 0.026 0.024
pf = 0.8 0.231 0.179 0.121 0.077 0.056 0.050 0.038 0.028 0.025
pf = 0.9 0.248 0.188 0.127 0.079 0.059 0.051 0.040 0.030 0.026
pf = 1.0 0.252 0.183 0.121 0.074 0.058 0.048 0.038 0.029 0.024
Conductor Characteristics
R mΩ/m at end temperature 0.146 0.106 0.070 0.043 0.034 0.028 0.022 0.017 0.014
X mΩ/m at end temperature 0.028 0.031 0.024 0.017 0.009 0.011 0.008 0.005 0.006
Z mΩ/m at end temperature 0.149 0.110 0.074 0.046 0.029 0.025 0.024 0.018 0.015
Protective Conductor
R0 mΩ/m 0.297 0.274 0.251 0.228 0.204 0.181 0.158 0.135 0.111
X0 mΩ/m 0.216 0.200 0.184 0.168 0.152 0.136 0.119 0.103 0.088

Weight kg/m 12.6 14.7 18.9 26.8 33.1 41.3 55.0 67.2 83.7
IP Rating Standard IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54
Optional IP55 IP55 IP55 IP55 IP55 IP55 IP55 IP55 IP55
Dimensions mm 145x137 145x137 145x162 145x207 145x287 145x287 145x439 145x599 145x599
Short Time Rating
kA for 1 sec 25 35 50 60 75 86 100 140 150
(phase conductors only)
Prospective Short Circuit Rating kA 53 70 110 132 158 194 220 255 255

Technical Data for LX 6 Bar, Copper Conductors Load Distribution Factor = 1

Rated Current A 1000 1250 1400 1600 2000 2500 3200 4000 5000
Rated Voltage V~ 690 690 690 690 690 690 690 690 690

Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.134 0.117 0.091 0.086 0.058 0.036 0.033 0.026 0.019
pf = 0.8 0.143 0.122 0.096 0.089 0.062 0.038 0.033 0.027 0.020
pf = 0.9 0.149 0.124 0.100 0.089 0.064 0.039 0.033 0.027 0.020
pf = 1.0 0.143 0.112 0.095 0.077 0.060 0.036 0.027 0.024 0.019
Conductor Characteristics
R mΩ/m at end temperature 0.083 0.065 0.055 0.045 0.035 0.021 0.016 0.014 0.011
X mΩ/m at end temperature 0.027 0.031 0.020 0.026 0.013 0.009 0.011 0.008 0.005
Z mΩ/m at end temperature 0.087 0.072 0.059 0.051 0.037 0.022 0.019 0.016 0.012
Protective Conductor
R0 mΩ/m 0.274 0.254 0.233 0.213 0.193 0.172 0.152 0.132 0.111
X0 mΩ/m 0.207 0.191 0.175 0.160 0.144 0.128 0.113 0.097 0.082

Weight kg/m 23.5 29.0 32.4 40.8 48.6 77.5 100.4 15.4 155.9
IP Rating Standard IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54
Optional IP55 IP55 IP55 IP55 IP55 IP55 IP55 IP55 IP55
Dimensions mm 145x137 145x137 145x162 145x162 145x207 145x287 145x287 145x439 145x599
Short Time Rating
kA for 1 sec 46 50 57 60 75 95 100 150 150
(phase conductors only)
Prospective Short Circuit Rating kA 80 110 125 132 165 189 220 255 255

Technical Data for 6300A available on request.

26
Cast Resin

Cast Resin 800A–6000A


Protection from Hostile Atmospheres
and for Use Outdoors

Cast resin busbar trunking has been Flexible and efficient


developed for the transportation and
distribution of electrical energy where This compact construction allows the
environmental factors such as humidity trunking to be positioned either flat or
and corrosive or saline atmospheres on its edge, vertically or horizontally,
may affect traditional metal-clad retaining its characteristics at all times
systems. It is designed for applications and eliminating the chimney effect.
between 800A and 6000A, although The close proximity of the conductors,
this can be increased in special cases and their layout results in low reactance
through the addition of modules with and so minimal voltage drop.
By using angles, sets and tees to the corresponding calculation.
change direction or negotiate
obstacles, cast resin busbar can It has been designed in accordance with
conform to the shape of the IEC/EN 60439 -1 and -2.
building in minimal space.
Reliability in hostile environments

Mechanical rigidity is achieved by


insulating the conductors in the centre
of the trunking, with an agglomerate
of quartz and polyester. This is highly
resistant to chemical agents and
mechanical stresses, offering IP66
protection level and high short-circuit
resistance.

Optimum reliability of the power


supply was a key factor in the
installation at the Abbey National’s
London head office.

27
Cast Resin

■ The close proximity of the ■ A universal connector enables PE ■ The busbar trunking retains its
conductors, and their layout, results Cast Resin busbar to be linked to the characteristics whether positioned
in low reactance and so minimal LX busbar system. flat or on its edge, vertically or
voltage drop. horizontally.

Typical Specification
All busbar trunking shall be of approved manufacture and comply
The following is intended as a guide to specifying with degree of ingress protection IP66 as defined in IEC/EN 60
529. The current ratings shall be as defined on technical data sheets,
PE Cast Resin busbar trunking: drawings and schedules.
The system shall be double insulated. The trunking shall be
suitable for use up to 1000V 50Hz supply and available in various
configurations, i.e. 3-, 4-, 5-bars (for IT-, TC-C, TC-S networks). It
shall meet the requirements of the IEE Wiring Regulations (BS7671)
and IEC/EN 60 439 -1 and -2. The enclosure shall be manufactured
from an agglomerate of quartz and polyester, the colour being similar
to RAL 7032 (pebble grey), and prepared to accept the manufacturer’s
standard suspension and support brackets. Phase and neutral
conductors (as well as the internal PE-conductor, where required) shall
be copper, of equal cross-section, fully insulated.
A derating in any position is not acceptable. The current rating must
be equal in all installation positions (flat, edge or vertical). The
single body system shall cover up to 3000A. By means of parallel
connections a current of 6000A must be possible.
The busbar trunking shall be manufactured in different lengths up to
3m. Joints shall be completed using bolt connection.
Various junction units shall be supplied as standard including elbows,
knees, T-units, Z-units. Further standard components must be available
such as cable feeder boxes, transformer connection units, and panel
flange connections.
All plastic parts shall be manufactured from non-hygroscopic, self-
extinguishing halogen-free insulating material and designed such that
IP66 degree of protection is maintained.
The busbar trunking shall be the PE Cast Resin range from Moeller or
equal and approved.

28
Cast Resin

Technical Data for Cast Resin Bar 4 Bar, Copper Conductors Load Distribution Factor = 1

Rated Current A 800 1000 1250 1500 1750 2000 2500 3000 3500 4000 5000 6000
Rated Voltage VAC 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

Voltage Drop, Balanced Load mV/A/m pf = 0.8 0.185 0.152 0.131 0.116 0.087 0.075 0.057 0.052 0.043 0.037 0.032 0.026
pf = 0.9 0.177 0.140 0.122 0.106 0.080 0.067 0.053 0.046 0.040 0.033 0.029 0.023
pf = 1.0 0.134 0.092 0.083 0.067 0.053 0.039 0.036 0.026 0.026 0.020 0.018 0.013
Conductor Characteristics
R mΩ/m at end temperature 0.078 0.053 0.048 0.039 0.030 0.022 0.020 0.015 0.015 0.011 0.010 0.008
X mΩ/m at end temperature 0.075 0.076 0.062 0.061 0.043 0.042 0.027 0.029 0.022 0.021 0.014 0.015
Z mΩ/m at end temperature 0.108 0.093 0.079 0.072 0.052 0.047 0.034 0.033 0.026 0.024 0.017 0.017

Weight kg/M 45.5 48.5 50.5 55.0 74.0 81.0 109.5 121.5 156.0 165.0 221.0 248.0
IP Rating Standard IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66
Optional
Dimensions mm 130x130 130x130 130x130 130x130 130x185 130x185 130x260 130x260 130x185 130x185 130x260 130x260
Short Time Rating kA for 1 sec 41 46 51 56 61 60 73 84 120 120 140 160
Prospective Short Circuit Rating kA 84 95 105 121 132 132 154 176 264 264 308 352
Number of Trunkings 1 1 1 1 1 1 1 1 2 2 2 2

Technical Data for Cast Resin Bar 5 Bar, Copper Conductors Load Distribution Factor = 1

Rated Current A 800 1000 1200 1400 1750 2000 2500 3000 3500 4000 5000 6000
Rated Voltage VAC 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

Voltage Drop, Balanced Load mV/A/m pf = 0.8 0.186 0.152 0.131 0.117 0.086 0.074 0.055 0.050 0.043 0.037 0.027 0.025
pf = 0.9 0.187 0.139 0.122 0.106 0.079 0.066 0.051 0.045 0.039 0.033 0.025 0.022
pf = 1.0 0.135 0.091 0.084 0.067 0.051 0.038 0.034 0.025 0.025 0.019 0.017 0.012
Conductor Characteristics
R mΩ/m at end temperature 0.078 0.053 0.048 0.039 0.03 0.022 0.02 0.015 0.015 0.011 0.01 0.0075
X mΩ/m at end temperature 0.075 0.076 0.062 0.061 0.043 0.042 0.027 0.029 0.0215 0.021 0.0135 0.0145
Z mΩ/m at end temperature 0.108 0.093 0.079 0.072 0.052 0.047 0.034 0.033 0.026 0.0235 0.017 0.0165

Weight kg/M 55 58.5 61 66.5 89.5 98.5 133 148 179 197 266 296
IP Rating Standard IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66
Optional
Dimensions mm 130x130 130x130 130x130 130x130 130x185 130x185 130x260 130x260 130x185 130x185 130x260 130x260
Short Time Rating kA for 1 sec 25 28 31 33 37 38 43 49 74 76 86 98
Prospective Short Circuit Rating kA 86 105 112 123 134 132 160 184 268 264 320 352
Number of Trunkings 1 1 1 1 1 1 1 1 2 2 2 2

29
Networked Busbar

Networked Busbar Trunking Systems –


Combining Economy and Flexibility

The rising demand for dynamic data The networking components


for building and industrial automation,
as well as the increasing requirement The use of networkable components
for diagnostic information has driven with the BD01, BD2, LD and LX systems,
the need for intelligent networking of and a well designed accessory package
installed applications. with a special bus duct enables the
networking of all current ranges, and
The logical next step also allows existing installations to be
upgraded.
The networking of applications in
Volvo Cars, Belgium – redundant the tap-off units of Moeller’s busbar The details of the power used can be
and flexible power distribution trunking is the logical development measured by transducers at the feeder
solution for Europe’s most modern for busbar trunking systems. Based in the tap-off unit and made available
welding lines. on standard types of tap-off units on the data bus via a bus-compatible
combined with an additional ancillary evaluation module in the device unit.
equipment unit, the network is formed This application is available both for
by laying a bus cable in a special LON and AS-Interface bus systems.
cable duct on the busbar trunking
and connecting components to this
bus. Open multi-vendor bus systems
(including EIB, AS-i and LON) with a
high level of interoperability form the
substructure of networkable tap-off/
ancillary equipment unit combinations.

Networked busbar trunking


systems for optimum reliability
and availability at Hamburg-
Mannheimer Versicherungs AG,
Germany.

Automation combined with power


distribution for flexible use in
international DIY stores.

30
Networked Busbar

Available ancillary equip-


ment units
Lighting control
■ BD01-GK-BL-EIB = EIB system
■ BD01-GK-BL-AS-i = AS-i system
■ BD2-GK-BL-EIB = EIB system
■ BD2-GK-BL-AS-i = AS-i system

Switching and signalling


■ GK-M-AS-i = Signalling function
■ Tap-off/ancillary equipment unit ■ Tap-off/ancillary equipment with ■ GK-SM-AS-i = Switching/
combination networked on a combination networked on a BD2 signalling function
BD01 system using EIB, enables the system using AS-Interface, such
switching of the phase conductors as for remote monitoring and Consumption measurement
L1 to L3 of the connected CD switching of switch-disconnectors. ■ GK-V-LON-G/-U = Consumption
system. This CD system is used Cable connection using cables with measurement with LON
for the flexible power supply and insulation displacement connections ■ GK-V-AS-i-G/-U = Consumption
fixing of luminaires. This type of maintains the flexibility of the measurement with AS-i
configuration allows the control of application. ■ GK-MV-AS-i-G/-U = Consump-
an extensive lighting system to be tion measurement and signalling
implemented simply and quickly. function with AS-i
■ GK-SMV-AS-i-G/-U = Consump-
tion measurement and switching/
signalling function with AS-i

(G=calibrated/U=uncalibrated)

Lighting control for extensive


lighting systems

Switching/signalling
Standard Remote operation/remote monitoring
tap-off units

Consumption measurement
Central data acquisition of
decentralized power consumers

Standard functions Function expansion Bus connection

31
Moeller Electric Limited

Moeller Electric Limited


PO Box 35
Gatehouse Close
Aylesbury
Buckinghamshire HP19 8DH
Tel: 01296 393322
Fax: 01296 421854
Email: marketing@moeller.co.uk
Internet: www.moeller.co.uk
© 2003 by Moeller Electric Ltd
Subject to alteration
NK 3700-259GB 09/03
Article No.: 639327

Xtra Combinations indicates that all your


automation requirements can now be met
by one company – Moeller.
We have the experience and technological
expertise to satisfy all your industrial
automation, building automation and power
distribution requirements.
From the component level up, Moeller uses
open communications standards, offers
accessibility via the Internet, and can bring
everything together into a complete solution
tailored to your requirements.
Utilise our services in any one of these specialist
areas, or in any combination, according to
your needs – Moeller’s products and services fit
together perfectly. All backed up by Moeller’s
experience and expertise over more than
100 years, in switchgear, control gear, and
PLC technology, in automation and power
distribution applications.
What other company offers so much from
a single source?
Contact us – we’d like to talk to you.

Think future. Switch to green.

You might also like