CD, BD01, BD2, LD, LX and Cast Resin busbar trunking systems,
networked busbar trunking systems
Moeller can offer single sourced the CD, BD, LD and LX busbar trunking Thanks to our many years of
automation and power distribution systems with networking capability. experience in designing, engineering,
solutions from medium voltage Moeller systems are type-tested low- manufacturing and commissioning, we
distribution boards (11kV), through voltage switchgear and controlgear can provide you with system solutions
the MODAN and PCC modular assemblies (TTA) to IEC/EN 60439-1 tailored precisely to your requirements.
power distribution systems, to final and 2, thus making it easier to certify
distribution and control, linked using your own installations.
CD system 25A–40A
Attractive and flexible,
CD is ideal for lighting
installations. See page 4.
LD system 1100A–5000A
Flexible power distribution
for high currents in industry.
See page 18.
LX system 800A–6300A
Power transmission from
the transformer to the
switchboard, and rising
mains in the building.
See page 22. Networked busbar and
trunking systems
Cast Resin busbar 800A–6000A Flexible automation on the
A totally encapsulated busbar busbar trunking system
suitable for use outdoors. using EIB, LON and AS-i
See page 27. open bus systems. See
page 30.
2
Busbar Trunking Systems
Busbar trunking systems are easier to Busbar trunking systems can reduce
design as the power distribution system on-site installation times by up to
can be planned just on the basis of the 50% compared to cable installations.
total connected load and the number A single run of busbar can replace
and type of individual loads. The linear several runs of cable, along with
network structure with tap-offs to the their associated cable trays, junction
Cable installation means higher load at regular intervals produces a boxes and fixings. No special tools are
combustive energy. clear system configuration, further required. Moeller’s busbar systems
simplifying engineering. By are simple to secure and have
using angles, sets and tees wide fixing intervals
to change direction (busbars up to every
Q
or negotiate LE U 4m, cable every
obstacles, busbar P 1.5m), further
IC
M
IB
and minimal F
A
for modification
E X
combustive energy E and expansion
FL
Busbar trunking systems Where a power
from Moeller offer clear safety distribution system has to match
With a cable installation, new loads advantages in terms of both changing requirements, busbars
have to be connected via an additional short-circuit ratings and combustive offer a fast solution. As demand
sub-distribution board, involving more energy. For example, BD2 A-250 busbar changes, tap off devices can be added
time and expense. trunking systems have a combustive or relocated with minimal disruption
energy of just 1.32kWh/m, whereas for and downtime. The installation can
comparable cable installations (NYY be expanded and modified without
4 x 95/50mm2) this is 5.19kWh/m. difficulty. Flexibility is increased still
Furthermore, Moeller busbar trunking further thanks to the wide range of
systems are halogen-free and have a tap-off units and system components
high short-circuit rating as standard. available. Cost-intensive downtimes are
The short-circuit protection close to the eliminated or kept to a minimum. At
load also simplifies trouble-shooting. all times the power distribution system
Busbar trunking systems enable tap-off Errors during assembly are practically ensures trouble-free operation with
points to be installed close to the load, eliminated thanks to safe, design- a high level of user friendliness and
providing greater transparency at the imposed connection sequences. reliability.
location concerned.
3
CD System
CD System 25A–40A
Attractive Lighting Busbar Trunking
4
CD System
■ With the CD system, the current can ■ Push-fit joints enable rapid, ■ Any commercially available lighting
be fed in at the beginning or the uncomplicated assembly of the system can be easily suspended from
end of the trunking units. trunking units without tools being any point along the trunking unit.
required.
Typical specification
All lighting trunking shall be of approved manufacture and comply with
The following is intended as a guide to specifying degree of ingress protection IP54 as defined in IEC/EN 60529. The current
CD Lighting Trunking: ratings shall be as defined on drawings and schedules.
The system shall be totally enclosed. The trunking shall be suitable for
use on a 400 volt 1, 2, 3 phase (2, 3, 4 wire; PE=housing), 50/60Hz
supply and for the installation to meet the requirements of the IEE Wiring
Regulations (BS7671) and IEC/EN 60439-1 and -2. The enclosure
shall be manufactured from zinc-coated sheet steel, finished in white
(similar to RAL 9002), rectangular in section with flanges to accept the
manufacturer’s standard suspension and luminaire support brackets. Phase
and neutral conductors shall be tinned copper, of equal cross section, fully
insulated and supported at both the tapping outlet positions and at each end
of the trunking.
The lighting trunking shall be manufactured in 2 or 3 metre lengths each
complete with a self-aligning electrical joint sleeve, interlocked to prevent
phase reversal.
Tapping outlet positions shall be provided at 0.5 and 1 metre intervals
each complete with a non-removable hinged cover complete with locking
screw to ensure IP54 rating and preventing accidental contact with the live
conductors.
All end feed units, end caps, joint sleeves and tap-off units shall be
manufactured from non-hygroscopic, self-extinguishing halogen-free
insulating material and designed such that IP54 degree of protection is
maintained.
Tap-off Units
Tap-offs shall be plug-in and designed so as to permit phase selection
on site by the insertion of prewired contact blocks into the appropriate
positions. Fused or unfused tap-off units shall be provided as required.
The lighting trunking shall be the CD range from Moeller or equal and
approved.
5
CD System
Conductors
Rated Operational Voltage Ue V~ 400 400 400 400 400 400 400
Frequency Hz 50–60 50–60 50–60 50–60 50–60 50–60 50–60
Rated Current Ie therm. Rated current at max. 40ºC and Amps 30 30 30 2 x 25 40 40 40
35ºC averaged over 24 hours
Conductor impedance at 50Hz and 20ºC busbar temperature
Resistance R20 mΩ/m 5.79 5.79 5.79 4.56 3.55 3.55 3.55
Reactance X20 mΩ/m 0.26 0.26 0.26 0.15 0.40 0.40 0.40
Impedance Z720 mΩ/m 5.80 5.80 5.80 4.56 3.57 3.57 3.57
Conductor impedance in the event of a fault
AC Resistance RF mΩ/m 8.24 8.24 8.24 7.50 5.61 5.61 5.61
Reactance XF mΩ/m 0.44 0.44 0.44 0.32 0.80 0.80 0.80
Impedance ZF mΩ/m 8.25 8.25 8.25 7.51 5.67 5.67 5.67
Zero Impedance tested to IEC 60 909, DIN VDE 0102
Resistance R0 Phase to N mΩ/m 24.24 24.24 24.24 18.59 14.85 14.85 14.85
Reactance X0 Phase to N mΩ/m 1.77 1.77 1.77 0.82 0.99 0.99 0.99
Impedance Z0 Phase to N mΩ/m 24.30 24.30 24.30 18.61 14.88 14.88 14.88
Resistance R0 Phase to PE mΩ/m 12 12 12 13.49 9.87 9.87 9.87
Reactance X0 Phase to PE mΩ/m 1.8 1.8 1.8 0.82 1.02 1.02 1.02
Impedance Z0 Phase to PE mΩ/m 12.13 12.13 12.13 13.52 9.92 9.92 9.92
Trunking Weight kg/m 0.75 0.78 0.81 1.06 0.78 0.83 0.88
Tap-off Plugs
Tap-off point Offset every 0.5 m, 1 m or 0.5 m on each side; max. 16 A
Tap-off plug 3- and 5-pole; with or without permanently attached cable; with or without fuse holders for 8.5 mm x
31.5 mm; type gG (IEC) and type gL (VDE) fast cylinder fuses.
All tap-off plugs are of utilization category AC-20B to IEC/EN 60 947-3.
The PE operates as an early-make contact during connection, and as a late-break contact during removal
of the tap-off plug.
Terminal Capacities
Designation Type L1, L2, L3 N PE
Min mm2 Max mm2 Min mm2 Max mm2 Min mm2 Max mm2
Entry Feeder Unit CD-K-…-EA 2.5 6 (f) 2.5 6 (f) 2.5 6 (f)
(Complete with end cap) 10 (st, so) 10 (st, so) 10 (st, so)
Entry Feeder Unit CD-K-…-EE 2.5 6(f) 2.5 6(f) 2.5 (6(f)
10 (st, so) 10 (st, so) 10 (st, so)
6
CD System
Feeder units
CD-K-...-EE
CD-K-...-EA
Tap-off plugs
Fixing brackets
CD-B CD-BC
7
BD01 System
8
BD01 System
■ The feeder unit can be fitted to any ■ Flexible in every direction. ■ Ancillary equipment units create
junction point. space for additional fittings along-
side tap-off units and feeder units.
Typical Specification
All busbar trunking shall be of approved manufacture, current rating as detailed
The following is intended as a guide to specifying on the drawings/schedules and complying to degree of protection IP54 defined
BD01 busbar trunking: in IEC/EN 60529 when edgewise (tap-off points at side and bottom) and IP50
when flat (tap-off points on top).
The busbar shall be designed and manufactured to comply with IEC/EN
60439-1 and -2. For use on a 400 volt, 3 phase, 4 wire (PE=housing), 50/60 Hz
supply, and capable of withstanding prospective fault level currents as detailed
on the drawings/schedules.
The busbar trunking shall be manufactured in 2 or 3 metre lengths. The
enclosure shall be manufactured from pale grey (RAL 7035) painted galvanised
sheet steel and is the protective earth conductor. The busbar trunking shall have
solid conductors with silver-plated aluminium and copper connection points
at all tap-off outlets and joint positions. Tap-off outlets shall be spaced at 0.5
or 1 metre distance and shall have automatic opening and closing shutters.
They will also ensure that correct polarity is maintained. The joint section
shall provide electrical and mechanical connection by four screws. The joint
section shall absorb any differential expansion between the trunking and the
conductors.
When a change in direction, rating or termination occurs in a busbar run,
manufacturer’s purpose-made fittings shall be used.
Where detailed on the drawings/schedules interlocking coding sets shall
be installed into the tap-off outlets and tap-off units to provide non-
interchangeability of tap-off units to non-designated tap-off outlets.
Tap-off Units
Tap-off units shall be plug-in type suitable to accept HRC fuses, MCBs, DIN
rail mounted devices and socket outlets as detailed on the drawings/schedules.
The enclosure shall be constructed from anodised aluminium and/or insulation
material, complying to degree of protection IP54, as defined in IEC/EN 60529.
The earth connection of the tap-off unit shall provide the opening of the
automatic shutter and make before and break after the live connections are
made.
Where required tap-off units shall be extendible to allow additional
components to be installed on to the internal DIN rail.
The busbar trunking system shall be the BD01 range from Moeller or equal and
approved.
9
BD01 System
Tap-off Units
Rated Operational Voltage Ue V 230 or 400
Rated Current Ie max. A 63
Switching capacity of the built-in switch-disconnector AC-20B
10
BD01 System
No of
l a tap-off points
500 4
2000
1000 2
500 6
3000
BD01-… 1000 3
BD01…R
Type l l1 l2
BD01-…-R1 500 165 316
BD01-…-R2 1000 665 –
Note These are the dimensions for some of the more popular items in the BD01 range. For details of
the full range please refer to Moeller’s Power Distribution Catalogue (HPL0214–2003/2004 GB-INT). Continued overleaf
11
BD01 System
Feeder units
BD01-E
BD01-160E
Tap-off units
BD01-AK01X/ZS BD01-AK02X/ZS3
12
BD2 System
13
BD2 System
Typical Specification
All busbar trunking shall be of approved manufacture, current rating as
The following is intended as a guide to specifying detailed on the drawings/schedules and complying to degree of ingress
BD2 busbar trunking: protection IP52 defined in IEC/EN 60529 and IP54 with accessories.
The busbar shall be designed and manufactured to comply with IEC/EN
60439-1 and -2. For use on a 690 volt, 3 phase, 5 wire (3L, N or 1⁄2 N, PE or
1⁄2 PE), 50/60 Hz supply, and capable of withstanding prospective fault level
currents as detailed on the drawings/schedules.
The busbar trunking shall be manufactured in 1.25, 2.25 or 3.25 metre
lengths or optional lengths from 0.5 up to 3.24 metres. The enclosure shall
be manufactured from pale grey (RAL 7035) painted galvanised sheet steel.
The busbar trunking shall have solid conductors, nickel-plated and tinned
aluminium or copper, with insulated tap-off outlets and busbar supports.
Tap-off outlets shall be spaced at 0.5 or 1 metre distance and shall have
automatic opening and closing shutters. They will also ensure that correct
polarity is maintained. The joint section shall provide electrical and
mechanical connection by four screws. The joint section shall absorb any
differential expansion between the trunking and the conductors.
When a change in direction, rating or termination occurs in a busbar run,
manufacturer’s purpose-made fittings shall be used.
Tap-off Units
■ Compact feeder units are available Tap-off units shall be plug-in type suitable to accept HRC and BS fuses,
for the incoming supply. MCBs, MCCBs, switch disconnectors, DIN rail mounted devices and socket
outlets as detailed on the drawings/schedules.
The enclosure shall be constructed from painted steel and/or insulation
material, complying to degree of protection IP54, as defined in IEC/EN
60529.
The earth connection of the tap-off unit shall provide the opening of the
automatic shutter and make before and break after the live connections are
made.
Where required tap-off units shall be extendible to allow additional
components to be installed on to the internal DIN rail.
The busbar trunking system shall be the BD2A/C range from Moeller or
equal and approved.
■ Branch and junction units permit
optimum adaptation to building
structures.
14
BD2 System
Technical Data for BD2A 5 Bar, Aluminium Conductors Load Distribution Factor = 0.5
Rated Current A 160 250 315 400 500 630 800 1000
Rated Voltage VAC 690 690 690 690 690 690 690 690
Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.440 0.330 0.300 0.210 0.120 0.130 0.090 0.080
pf = 0.8 0.470 0.360 0.320 0.210 0.120 0.130 0.100 0.080
pf = 0.9 0.500 0.380 0.340 0.210 0.130 0.140 0.100 0.070
pf = 1.0 0.490 0.380 0.330 0.190 0.120 0.130 0.080 0.060
Conductor Characteristics
R mΩ/m at end temperature 0.564 0.438 0.383 0.215 0.135 0.149 0.098 0.066
X mΩ/m at end temperature 0.158 0.111 0.112 0.122 0.056 0.057 0.057 0.057
Z mΩ/m at end temperature 0.586 0.452 0.399 0.247 0.146 0.159 0.114 0.088
Protective Conductor
R0 mΩ/m 1.638 1.279 1.225 1.059 0.492 0.492 0.438 0.408
X0 mΩ/m 0.606 0.516 0.524 0.518 0.299 0.303 0.280 0.273
Weight kg/M 5.3 5.8 6.6 7.5 12.3 12.3 12.4 15.8
IP Rating Standard IP 52 IP 52 IP 52 IP 52 IP 52 IP 52 IP 52 IP 52
Optional IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP 54
Dimensions mm 167x68 167x68 167x68 167x68 167x126 167x126 167x126 167x126
Short Time Rating kA for 1 sec 5.5 10 14 16 21 26 32 34
Prospective Short Circuit Rating kA 17 32 36 40 59 64 84 90
Number of Trunkings 1 1 1 1 1 1 1 1
Technical Data for BD2C 5 Bar, Copper Conductors Load Distribution Factor = 0.5
Rated Current A 160 250 315 400 500 630 800 1000 1250
Rated Voltage VAC 690 690 690 690 690 690 690 690 690
Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.300 0.330 0.300 0.220 0.120 0.120 0.070 0.070 0.060
pf = 0.8 0.310 0.350 0.320 0.230 0.120 0.130 0.070 0.070 0.060
pf = 0.9 0.320 0.360 0.340 0.230 0.130 0.140 0.070 0.070 0.050
pf = 1.0 0.290 0.330 0.330 0.210 0.120 0.130 0.060 0.060 0.040
Conductor Characteristics
R mΩ/m at end temperature 0.333 0.383 0.383 0.239 0.136 0.151 0.065 0.068 0.041
X mΩ/m at end temperature 0.157 0.158 0.112 0.115 0.053 0.053 0.053 0.053 0.054
Z mΩ/m at end temperature 0.368 0.414 0.399 0.266 0.146 0.160 0.084 0.086 0.068
Protective Conductor
R0 mΩ/m 1.027 1.139 1.065 0.956 0.473 0.470 0.258 0.270 0.174
X0 mΩ/m 0.641 0.529 0.507 0.507 0.274 0.277 0.265 0.249 0.265
Weight kg/M 7.3 7.5 8.0 9.5 15.6 15.6 18.9 25.1 37.6
IP Rating Standard IP 52 IP 52 IP 52 IP 52 IP 52 IP 52 IP 52 IP 52 IP52
Optional IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP54
Dimensions mm 167x68 167x68 167x68 167x68 167x126 167x126 167x126 167x126 167x126
Short Time Rating kA for 1 sec 5.5 10 14 16 21 26 32 34 34
Prospective Short Circuit Rating kA 17 32 36 40 59 64 84 90 90
Number of Trunkings 1 1 1 1 1 1 1 1 1
15
BD2 System
330
centre of clamp terminal
163
167
307 (557) 220
BD2.-…-… n × 500 (1000)
L-junction units
BD2.-…-LR…(-G*), BD2.-…-LL…(-G*) BD2.-…-LV…(-G*), BD2.-…-LH…(-G*)
c
70
c
x = 360–1250
70
G* = 85°–175°
x = 360–1250
G* = 85°–175°
Rated c
current (A) (mm)
y = 360–1250
160–400 68
500–1250 126
y = 360–1250
295
191
191
4 × 65 c
x12.5
108.5
9
123
223 308
247.5 332.5
223 308
307
183.5
100
100
14 × 9
163 c1
200 c2
240
285
325
370
16
BD2 System
200
143.5
64
100
105
64
74
40
40
423
x9
20
300 75
100
167
245
270
290
219
395
420
440
167
85
200 250
478
x9 14 × 9
563 200 387.5
605
687
Tap-off units
BD2-AK1/2CEE163400-EE Up to 25A
88
354
9
20
77
101
170
50
50
314 7
BD2-AK2X/F…
BD2-AK2X/GB…
BD2-AK2X/S…
BD2-AK3X/G500 Up to 63A
205
BD2-AK3X/GB1003
Up to 125A
474
440
9
20
50
246
33
200
c1
C
110
16
169 34
28 199
288
15
+10
135
9
250
-5
25
Rated c
48
100
208 current (A) (mm)
7.2
Rated c c1
9
14 11 500–1250 144.5 77
17
LD System
LD System 1100A–5000A
For Reliable Electrical Power
The LD system covers the current range The busbar offset ensures that the
from 1100A to 5000A. It is ideal for elements are installed with the correct
linking between transformer, main phase sequence. Installation errors are
distribution board and sub-distribution therefore reliably prevented.
boards in production units with a high
power requirement, such as for welding The tap-off units can be individually
lines in the automotive industry, or equipped, providing solutions for a
industrial furnaces. variety of different types of application.
18
LD System
■ Power is fed from the transformer ■ Where required, power is simply ■ Direction changes are possible in
to the LD busbar trunking system tapped via tap-off units. three axes.
via feeder units with connection
lugs prepared for transformer lug
intervals of 150 to 750 mm.
Typical Specification
All busbar trunking shall be of approved manufacture and be available
The following is intended as a guide to specifying with various degrees of ingress protection including IP34 and IP54, as
LD busbar trunking: defined in IEC/ EN 60 529.The current ratings shall be as defined on
technical data sheets, drawings and schedules.
The system shall be air insulated and metal enclosed.The trunking shall
be suitable for use up to 1000V 162/3Hz to 60 Hz supply and available in
various configurations including 3 phase and half or full PEN and 3 phase,
half or full neutral and earth (PE). It shall meet the requirements of the IEE
Wiring Regulations (BS7671) and IEC/ EN 60 439 -1 and -2.The enclosure
shall be manufactured from galvanised sheet steel, finished in RAL 7035
(pale grey), prepared to accept the manufacturer’s standard suspension
and support brackets.Phase and neutral conductors shall be nickel and tin
plated aluminium or tinned copper, all epoxy coated.
The busbar trunking shall be manufactured in different lengths up to 3.2m
either as feeder or as distribution units each complete with a single bolt
and hook joint connection, interlocked to prevent phase reversal.
Various junction units shall be supplied as standard, including elbows,
knees, T-units, U-units and Z-units. Further standard components must be
available such as expansion units, phase reversal units, cable feeder boxes,
transformer connection units and panel flange connections.
For distribution, tapping outlet positions shall be provided at different
positions with up to 3 outlets on each side of a 3.2m length. Each outlet
shall have a cover complete with sealing facility to maintain the IP rating
of the system and preventing accidental contact with the live conductors.
All plastic parts (such as tapping outlets) shall be manufactured from non-
hygroscopic, self –extinguishing halogen-free insulating material.
Tap-off Units
Tap-off units shall be plug-in type up to 800A. Incorrect mounting must
be prevented by an interlocking mechanism. The tap-off units shall be
equipped either with a load break switch or a MCCB (handoperated or
motor controlled). The short circuit capacity should be available up to
100kA at 415V 50Hz
The busbar trunking shall be the Moeller LD range or equal and approved.
19
LD System
Size of PEN Compared to Phase Bar Full Full Full Half Full Half Full Half Full Half Full Half Full
Rated Current
Horizontal/edgewise * IP 34 A 1100 1250 1600 2000 2000 2500 2500 3000 3000 3700 3700 4000 4000
IP 54 A 900 1000 1200 1500 1500 1800 1800 2000 2000 2400 2400 2700 2700
Vertical IP 34 A 950 1100 1250 1700 1700 2100 2100 2300 2300 2800 2800 3400 3400
IP 54 A 900 1000 1200 1500 1500 1800 1800 2000 2000 2400 2400 2700 2700
Horizontal/flat IP 34 / IP 54 A 700 750 1000 1200 1200 1700 1700 1800 1800 2200 2200 2350 2350
Rated Voltage V~ 690 690 690 690 690 690 690 690 690 690 690 690 690
Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.162 0.118 0.123 0.089 0.089 0.073 0.073 0.074 0.074 0.056 0.056 0.047 0.047
pf = 0.8 0.168 0.119 0.125 0.090 0.090 0.072 0.072 0.073 0.073 0.055 0.055 0.046 0.046
pf = 0.9 0.171 0.116 0.123 0.089 0.089 0.068 0.068 0.070 0.070 0.051 0.051 0.043 0.043
pf = 1.0 0.152 0.093 0.102 0.074 0.074 0.050 0.050 0.051 0.051 0.036 0.036 0.031 0.031
Conductor Characteristics
R mΩ/m at end temperature 0.073 0.054 0.057 0.043 0.044 0.027 0.028 0.030 0.029 0.021 0.020 0.018 0.016
X mΩ/m at end temperature 0.046 0.043 0.043 0.025 0.029 0.023 0.029 0.024 0.029 0.019 0.022 0.017 0.019
Z mΩ/m at end temperature 0.098 0.069 0.072 0.049 0.053 0.036 0.041 0.038 0.041 0.029 0.030 0.025 0.025
Protective Conductor
R0 mΩ/m 0.284 0.217 0.217 0.242 0.173 0.180 0.120 0.180 0.120 0.126 0.090 0.110 0.075
X0 mΩ/m 0.232 0.200 0.200 0.154 0.174 0.154 0.154 0.154 0.153 0.097 0.119 0.086 0.087
Weight kg/m 16.7 20 20 21.7 22.9 27.4 29.4 27.4 29.4 33.7 36.6 37.2 40.6
IP Rating Standard IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34
Optional IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54
Dimensions mm 180x180 180x180 180x180 180x240 180x240 180x240 180x240 180x240 180x240 180x240 180x240 180x240 180x240
Short Time Rating
kA for 1 sec 40 55 58 80 80 110 110 116 116 116 116 116 116
(phase conductors only)
Prospective Short Circuit Rating kA 121 154 176 242 242 275 275 286 286 286 286 286 286
Size of PEN Compared to Phase Bar Full Full Half Full Half Full Half Full
Rated Current
Horizontal/edgewise * IP 34 A 2000 2600 3400 3400 4400 4400 5000 5000
IP 54 A 1600 2000 2600 2600 3200 3200 3600 3600
Vertical IP 34 A 1650 2100 2700 2700 3500 3500 4250 4250
IP 54 A 1600 2000 2600 2600 3200 3200 3600 3600
Horizontal/flat IP 34 / IP 54 A 1200 1550 2000 2000 2600 2600 3000 3000
Rated Voltage V~ 690 690 690 690 690 690 690 690
Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.096 0.078 0.055 0.055 0.042 0.042 0.035 0.035
pf = 0.8 0.094 0.076 0.053 0.053 0.040 0.040 0.033 0.033
pf = 0.9 0.089 0.070 0.048 0.048 0.036 0.036 0.030 0.030
pf = 1.0 0.064 0.048 0.031 0.031 0.022 0.022 0.019 0.019
Conductor Characteristics
R mΩ/m at end temperature 0.037 0.028 0.017 0.018 0.012 0.013 0.011 0.011
X mΩ/m at end temperature 0.042 0.036 0.026 0.027 0.023 0.022 0.020 0.018
Z mΩ/m at end temperature 0.056 0.046 0.031 0.032 0.026 0.025 0.023 0.021
Protective Conductor
R0 mΩ/m 0.144 0.114 0.116 0.079 0.083 0.056 0.070 0.050
X0 mΩ/m 0.199 0.225 0.124 0.130 0.072 0.093 0.088 0.106
Weight kg/m 38.8 51.2 60.3 67.0 82.0 91.8 100.2 112.6
IP Rating Standard IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34
Optional IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54
Dimensions mm 180x180 180x180 180x240 180x240 180x240 180x240 180x240 180x240
Short Time Rating 58 58 116 116 116 116 116 116
kA for 1 sec
(phase conductors only)
Prospective Short Circuit Rating kA 176 176 286 286 286 286 286 286
20
LD System
Size of PEN Compared to Phase Bar Full Full Full Half Full Half Full Half Full Half Full Half Full
Rated Current
Horizontal/edgewise * IP 34 A 1100 1250 1600 2000 2000 2500 2500 3000 3000 3700 3700 4000 4000
IP 54 A 900 1000 1200 1500 1500 1800 1800 2000 2000 2400 2400 2700 2700
Vertical IP 34 A 950 1100 1250 1700 1700 2100 2100 2300 2300 2800 2800 3400 3400
IP 54 A 900 1000 1200 1500 1500 1800 1800 2000 2000 2400 2400 2700 2700
Horizontal/flat IP 34 / IP 54 A 700 750 1000 1200 1200 1700 1700 1800 1800 2200 2200 2350 2350
Rated Voltage V~ 690 690 690 690 690 690 690 690 690 690 690 690 690
Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.162 0.118 0.123 0.089 0.089 0.073 0.073 0.074 0.074 0.056 0.056 0.047 0.047
pf = 0.8 0.168 0.119 0.125 0.090 0.090 0.072 0.072 0.073 0.073 0.055 0.055 0.046 0.046
pf = 0.9 0.171 0.116 0.123 0.089 0.089 0.068 0.068 0.070 0.070 0.051 0.051 0.043 0.043
pf = 1.0 0.152 0.093 0.102 0.074 0.074 0.050 0.050 0.051 0.051 0.036 0.036 0.031 0.031
Conductor Characteristics
R mΩ/m at end temperature 0.088 0.054 0.059 0.042 0.043 0.028 0.029 0.029 0.030 0.020 0.021 0.017 0.018
X mΩ/m at end temperature 0.045 0.043 0.042 0.025 0.030 0.024 0.031 0.024 0.031 0.020 0.025 0.021 0.021
Z mΩ/m at end temperature 0.099 0.069 0.072 0.049 0.052 0.037 0.042 0.037 0.043 0.028 0.033 0.027 0.027
Protective Conductor
R0 mΩ/m 0.315 0.240 0.240 0.301 0.292 0.217 0.213 0.217 0.212 0.163 0.166 0.145 0.146
X0 mΩ/m 0.401 0.393 0.393 0.267 0.291 0.202 0.265 0.202 0.263 0.175 0.220 0.196 0.196
Weight kg/m 17.9 22.0 22.0 22.9 24.1 29.4 31.4 29.4 31.4 36.6 39.5 40.6 44
IP Rating Standard IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34
Optional IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54
Dimensions mm 180x180 180x180 180x180 180x240 180x240 180x240 180x240 180x240 180x240 180x240 180x240 180x240 180x240
Short Time Rating
kA for 1 sec 40 55 58 80 80 110 110 116 116 116 116 116 116
(phase conductors only)
Prospective Short Circuit Rating kA 121 154 176 242 242 275 275 286 286 286 286 286 286
Size of PEN Compared to Phase Bar Full Full Half Full Half Full Half Full
Rated Current
Horizontal/edgewise * IP 34 A 2000 2600 3400 3400 4400 4400 5000 5000
IP 54 A 1600 2000 2600 2600 3200 3200 3600 3600
Vertical IP 34 A 1650 2100 2700 2700 3500 3500 4250 4250
IP 54 A 1600 2000 2600 2600 3200 3200 3600 3600
Horizontal/flat IP 34 / IP 54 A 1200 1550 2000 2000 2600 2600 3000 3000
Rated Voltage V~ 690 690 690 690 690 690 690 690
Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.096 0.078 0.055 0.055 0.042 0.042 0.035 0.035
pf = 0.8 0.094 0.076 0.053 0.053 0.040 0.040 0.033 0.033
pf = 0.9 0.089 0.070 0.048 0.048 0.036 0.036 0.030 0.030
pf = 1.0 0.064 0.048 0.031 0.031 0.022 0.022 0.019 0.019
Conductor Characteristics
R mΩ/m at end temperature 0.037 0.031 0.017 0.018 0.013 0.015 0.013 0.013
X mΩ/m at end temperature 0.043 0.038 0.028 0.028 0.024 0.022 0.020 0.020
Z mΩ/m at end temperature 0.057 0.049 0.033 0.034 0.027 0.027 0.024 0.024
Protective Conductor
R0 mΩ/m 0.179 0.134 0.149 0.149 0.116 0.100 0.103 0.103
X0 mΩ/m 0.387 0.357 0.238 0.248 0.186 0.216 0.188 0.184
Weight kg/m 45.5 61.0 67.0 73.3 91.8 101.6 112.6 125.0
IP Rating Standard IP34 IP34 IP34 IP34 IP34 IP34 IP34 IP34
Optional IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54
Dimensions mm 180x180 180x180 180x240 180x240 180x240 180x240 180x240 180x240
Short Time Rating
kA for 1 sec 58 58 116 116 116 116 116 116
(phase conductors only)
Prospective Short Circuit Rating kA 176 176 286 286 286 286 286 286
21
LX System
LX System 800A–6300A
Less Weight, More Power
22
LX System
Typical Specification
All busbar trunking shall be of approved manufacture and comply with degree
The following is intended as a guide to specifying of ingress protection IP54 as defined in IEC/EN 60 529. The current ratings
LX busbar trunking: shall be as defined on technical data sheets, drawings and schedules.
The system shall be totally enclosed and low impedance sandwich
construction. The trunking shall be suitable for use up to 690V 50Hz supply
and available in various configurations including 3 phase and neutral, double
neutral, earth and/or clean earth (with a maximum of 6 conductors). It shall
meet the requirements of the IEE Wiring Regulations (BS7671) and IEC/
EN 60 439 -1 and -2. The enclosure shall be manufactured from aluminium,
finished in RAL 7035 (pale grey), prepared to accept the manufacturer’s
standard suspension and support brackets. Phase and neutral conductors shall
be nickel and tin plated aluminium or tinned copper, of equal cross-section,
fully insulated.
The current rating must be equal in all installation positions (flat, edge or
vertical). A derating in any position is not acceptable.
The busbar trunking shall be manufactured in different lengths up to 3m either
as feeder or as distribution unit each complete with a self-torquing single bolt
joint block.
Various junction units shall be supplied as standard, including elbows, knees,
■ Optimum matching to building
T-units, Z-units. Further standard components must be available such as cable
layouts. feeder boxes, transformer connection units, and panel flange connections.
For distribution, tapping outlet positions shall be provided at different positions
with up to 5 outlets on each side of a 3m length. Each outlet shall have a cover
complete with sealing facility to ensure IP54 rating and preventing accidental
contact with the live conductors.
All plastic parts (like tapping outlets) shall be manufactured from non-
hygroscopic, self-extinguishing halogen-free insulating material and designed
such that IP54 degree of protection is maintained.
Tap-off Units
Tap-off units shall be plug-in up to 630A and fix mounted from 800 to 1250A.
Incorrect mounting shall be prevented by an interlocking mechanism. The
tap-off units shall be equipped with either a fused switch or a MCCB. The short
circuit capacity should be 65kA at 415V 50Hz.
The busbar trunking shall be the Barduct LX range from Moeller or equal and
approved.
■ Rapid, safe mounting of structural
elements.
23
LX System
Rated Current A 800 1000 1250 1600 2000 2500 3200 4000 4500
Rated Voltage V~ 690 690 690 690 690 690 690 690 690
Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.212 0.167 0.115 0.073 0.052 0.048 0.037 0.027 0.024
pf = 0.8 0.231 0.179 0.122 0.077 0.056 0.050 0.039 0.029 0.026
pf = 0.9 0.249 0.189 0.127 0.080 0.060 0.052 0.040 0.030 0.026
pf = 1.0 0.253 0.184 0.121 0.074 0.059 0.048 0.038 0.029 0.024
Conductor Characteristics
R mΩ/m at end temperature 0.146 0.106 0.070 0.043 0.034 0.028 0.022 0.017 0.014
X mΩ/m at end temperature 0.028 0.031 0.024 0.017 0.009 0.011 0.008 0.005 0.006
Z mΩ/m at end temperature 0.149 0.110 0.074 0.046 0.035 0.030 0.024 0.018 0.015
Protective Conductor
R0 mΩ/m 0.281 0.274 0.240 0.159 0.153 0.154 0.121 0.092 0.095
X0 mΩ/m 0.198 0.200 0.161 0.130 0.094 0.101 0.097 0.063 0.069
Weight kg/m 13.4 14.5 16.9 18.9 25.2 29.4 43.2 50.7 59.2
IP Rating Standard IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP54
Optional IP 55 IP 55 IP 55 IP 55 IP 55 IP 55 IP 55 IP 55 IP55
Dimensions mm 145x137 145x137 145x162 145x207 145x287 145x287 145x439 145x599 145x599
Short Time Rating
kA for 1 sec 25 35 50 60 75 86 100 140 150
(phase conductors only)
Prospective Short Circuit Rating kA 53 70 110 132 158 194 220 255 255
Rated Current A 1000 1250 1400 1600 2000 2500 3200 4000 5000
Rated Voltage V~ 690 690 690 690 690 690 690 690 690
Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.134 0.117 0.091 0.087 0.059 0.037 0.033 0.027 0.020
pf = 0.8 0.143 0.122 0.097 0.089 0.062 0.038 0.034 0.028 0.020
pf = 0.9 0.150 0.125 0.101 0.090 0.064 0.040 0.033 0.028 0.021
pf = 1.0 0.144 0.113 0.095 0.078 0.061 0.036 0.028 0.024 0.019
Conductor Characteristics
R mΩ/m at end temperature 0.083 0.065 0.055 0.045 0.035 0.021 0.016 0.014 0.011
X mΩ/m at end temperature 0.027 0.031 0.020 0.026 0.013 0.009 0.011 0.008 0.005
Z mΩ/m at end temperature 0.087 0.072 0.059 0.051 0.037 0.022 0.019 0.016 0.012
Protective Conductor
R0 mΩ/m 0.252 0.245 0.203 0.213 0.181 0.156 0.152 0.108 0.089
X0 mΩ/m 0.192 0.191 0.161 0.157 0.132 0.096 0.096 0.079 0.067
Weight kg/m 20.7 24.0 26.4 31.5 36.6 54.7 68.8 90.1 109.8
IP Rating Standard IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP 54 IP54
Optional IP 55 IP 55 IP 55 IP 55 IP 55 IP 55 IP 55 IP 55 IP55
Dimensions mm 145x137 145x137 145x162 145x162 145x207 145x287 145x287 145x439 145x599
Short Time Rating
kA for 1 sec 46 50 57 65 75 95 100 150 150
(phase conductors only)
Prospective Short Circuit Rating kA 80 110 125 132 165 189 220 255 255
24
LX System
Rated Current A 800 1000 1250 1600 2000 2500 3200 4000 4500
Rated Voltage V~ 690 690 690 690 690 690 690 690 690
Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.211 0.166 0.114 0.073 0.052 0.047 0.036 0.026 0.024
pf = 0.8 0.231 0.179 0.121 0.077 0.056 0.050 0.038 0.028 0.025
pf = 0.9 0.248 0.188 0.127 0.079 0.059 0.051 0.040 0.030 0.026
pf = 1.0 0.252 0.183 0.121 0.074 0.058 0.048 0.038 0.029 0.024
Conductor Characteristics
R mΩ/m at end temperature 0.146 0.106 0.070 0.043 0.034 0.028 0.022 0.017 0.014
X mΩ/m at end temperature 0.028 0.031 0.024 0.017 0.009 0.011 0.008 0.005 0.006
Z mΩ/m at end temperature 0.149 0.110 0.074 0.046 0.029 0.025 0.024 0.018 0.015
Protective Conductor
R0 mΩ/m 0.297 0.274 0.251 0.228 0.204 0.181 0.158 0.135 0.111
X0 mΩ/m 0.216 0.200 0.184 0.168 0.152 0.136 0.119 0.103 0.088
Weight kg/m 11.6 13.3 17.0 23.8 29.3 36.3 48.5 59.2 73.2
IP Rating Standard IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54
Optional IP55 IP55 IP55 IP55 IP55 IP55 IP55 IP55 IP55
Dimensions mm 145x137 145x137 145x162 145x207 145x287 145x287 145x439 145x599 145x599
Short Time Rating 25 35 50 60 75 86 100 140 150
kA for 1 sec
(phase conductors only)
Prospective Short Circuit Rating kA 53 70 110 132 158 194 220 255 255
Rated Current A 1000 1250 1400 1600 2000 2500 3200 4000 5000
Rated Voltage V~ 690 690 690 690 690 690 690 690 690
Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.134 0.117 0.091 0.086 0.058 0.036 0.033 0.026 0.019
pf = 0.8 0.143 0.122 0.096 0.089 0.062 0.038 0.033 0.027 0.020
pf = 0.9 0.149 0.124 0.100 0.089 0.064 0.039 0.033 0.027 0.020
pf = 1.0 0.143 0.112 0.095 0.077 0.060 0.036 0.027 0.024 0.019
Conductor Characteristics
R mΩ/m at end temperature 0.083 0.065 0.055 0.045 0.035 0.021 0.016 0.014 0.011
X mΩ/m at end temperature 0.027 0.031 0.020 0.026 0.013 0.009 0.011 0.008 0.005
Z mΩ/m at end temperature 0.087 0.072 0.059 0.051 0.037 0.022 0.019 0.016 0.012
Protective Conductor
R0 mΩ/m 0.274 0.254 0.233 0.213 0.193 0.172 0.152 0.132 0.111
X0 mΩ/m 0.207 0.191 0.175 0.160 0.144 0.128 0.113 0.097 0.082
Weight kg/m 20.7 25.3 28.2 35.2 41.9 66.3 85.5 107.2 133.2
IP Rating Standard IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54
Optional IP55 IP55 IP55 IP55 IP55 IP55 IP55 IP55 IP55
Dimensions mm 145x137 145x137 145x162 145x162 145x207 145x287 145x287 145x439 145x599
Short Time Rating
kA for 1 sec 46 50 57 60 75 95 100 150 150
(phase conductors only)
Prospective Short Circuit Rating kA 80 110 125 132 165 189 220 255 255
25
LX System
Rated Current A 800 1000 1250 1600 2000 2500 3200 4000 4500
Rated Voltage V~ 690 690 690 690 690 690 690 690 690
Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.211 0.166 0.114 0.073 0.052 0.047 0.036 0.026 0.024
pf = 0.8 0.231 0.179 0.121 0.077 0.056 0.050 0.038 0.028 0.025
pf = 0.9 0.248 0.188 0.127 0.079 0.059 0.051 0.040 0.030 0.026
pf = 1.0 0.252 0.183 0.121 0.074 0.058 0.048 0.038 0.029 0.024
Conductor Characteristics
R mΩ/m at end temperature 0.146 0.106 0.070 0.043 0.034 0.028 0.022 0.017 0.014
X mΩ/m at end temperature 0.028 0.031 0.024 0.017 0.009 0.011 0.008 0.005 0.006
Z mΩ/m at end temperature 0.149 0.110 0.074 0.046 0.029 0.025 0.024 0.018 0.015
Protective Conductor
R0 mΩ/m 0.297 0.274 0.251 0.228 0.204 0.181 0.158 0.135 0.111
X0 mΩ/m 0.216 0.200 0.184 0.168 0.152 0.136 0.119 0.103 0.088
Weight kg/m 12.6 14.7 18.9 26.8 33.1 41.3 55.0 67.2 83.7
IP Rating Standard IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54
Optional IP55 IP55 IP55 IP55 IP55 IP55 IP55 IP55 IP55
Dimensions mm 145x137 145x137 145x162 145x207 145x287 145x287 145x439 145x599 145x599
Short Time Rating
kA for 1 sec 25 35 50 60 75 86 100 140 150
(phase conductors only)
Prospective Short Circuit Rating kA 53 70 110 132 158 194 220 255 255
Rated Current A 1000 1250 1400 1600 2000 2500 3200 4000 5000
Rated Voltage V~ 690 690 690 690 690 690 690 690 690
Voltage Drop, Balanced Load mV/A/m pf = 0.7 0.134 0.117 0.091 0.086 0.058 0.036 0.033 0.026 0.019
pf = 0.8 0.143 0.122 0.096 0.089 0.062 0.038 0.033 0.027 0.020
pf = 0.9 0.149 0.124 0.100 0.089 0.064 0.039 0.033 0.027 0.020
pf = 1.0 0.143 0.112 0.095 0.077 0.060 0.036 0.027 0.024 0.019
Conductor Characteristics
R mΩ/m at end temperature 0.083 0.065 0.055 0.045 0.035 0.021 0.016 0.014 0.011
X mΩ/m at end temperature 0.027 0.031 0.020 0.026 0.013 0.009 0.011 0.008 0.005
Z mΩ/m at end temperature 0.087 0.072 0.059 0.051 0.037 0.022 0.019 0.016 0.012
Protective Conductor
R0 mΩ/m 0.274 0.254 0.233 0.213 0.193 0.172 0.152 0.132 0.111
X0 mΩ/m 0.207 0.191 0.175 0.160 0.144 0.128 0.113 0.097 0.082
Weight kg/m 23.5 29.0 32.4 40.8 48.6 77.5 100.4 15.4 155.9
IP Rating Standard IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54 IP54
Optional IP55 IP55 IP55 IP55 IP55 IP55 IP55 IP55 IP55
Dimensions mm 145x137 145x137 145x162 145x162 145x207 145x287 145x287 145x439 145x599
Short Time Rating
kA for 1 sec 46 50 57 60 75 95 100 150 150
(phase conductors only)
Prospective Short Circuit Rating kA 80 110 125 132 165 189 220 255 255
26
Cast Resin
27
Cast Resin
■ The close proximity of the ■ A universal connector enables PE ■ The busbar trunking retains its
conductors, and their layout, results Cast Resin busbar to be linked to the characteristics whether positioned
in low reactance and so minimal LX busbar system. flat or on its edge, vertically or
voltage drop. horizontally.
Typical Specification
All busbar trunking shall be of approved manufacture and comply
The following is intended as a guide to specifying with degree of ingress protection IP66 as defined in IEC/EN 60
529. The current ratings shall be as defined on technical data sheets,
PE Cast Resin busbar trunking: drawings and schedules.
The system shall be double insulated. The trunking shall be
suitable for use up to 1000V 50Hz supply and available in various
configurations, i.e. 3-, 4-, 5-bars (for IT-, TC-C, TC-S networks). It
shall meet the requirements of the IEE Wiring Regulations (BS7671)
and IEC/EN 60 439 -1 and -2. The enclosure shall be manufactured
from an agglomerate of quartz and polyester, the colour being similar
to RAL 7032 (pebble grey), and prepared to accept the manufacturer’s
standard suspension and support brackets. Phase and neutral
conductors (as well as the internal PE-conductor, where required) shall
be copper, of equal cross-section, fully insulated.
A derating in any position is not acceptable. The current rating must
be equal in all installation positions (flat, edge or vertical). The
single body system shall cover up to 3000A. By means of parallel
connections a current of 6000A must be possible.
The busbar trunking shall be manufactured in different lengths up to
3m. Joints shall be completed using bolt connection.
Various junction units shall be supplied as standard including elbows,
knees, T-units, Z-units. Further standard components must be available
such as cable feeder boxes, transformer connection units, and panel
flange connections.
All plastic parts shall be manufactured from non-hygroscopic, self-
extinguishing halogen-free insulating material and designed such that
IP66 degree of protection is maintained.
The busbar trunking shall be the PE Cast Resin range from Moeller or
equal and approved.
28
Cast Resin
Technical Data for Cast Resin Bar 4 Bar, Copper Conductors Load Distribution Factor = 1
Rated Current A 800 1000 1250 1500 1750 2000 2500 3000 3500 4000 5000 6000
Rated Voltage VAC 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Voltage Drop, Balanced Load mV/A/m pf = 0.8 0.185 0.152 0.131 0.116 0.087 0.075 0.057 0.052 0.043 0.037 0.032 0.026
pf = 0.9 0.177 0.140 0.122 0.106 0.080 0.067 0.053 0.046 0.040 0.033 0.029 0.023
pf = 1.0 0.134 0.092 0.083 0.067 0.053 0.039 0.036 0.026 0.026 0.020 0.018 0.013
Conductor Characteristics
R mΩ/m at end temperature 0.078 0.053 0.048 0.039 0.030 0.022 0.020 0.015 0.015 0.011 0.010 0.008
X mΩ/m at end temperature 0.075 0.076 0.062 0.061 0.043 0.042 0.027 0.029 0.022 0.021 0.014 0.015
Z mΩ/m at end temperature 0.108 0.093 0.079 0.072 0.052 0.047 0.034 0.033 0.026 0.024 0.017 0.017
Weight kg/M 45.5 48.5 50.5 55.0 74.0 81.0 109.5 121.5 156.0 165.0 221.0 248.0
IP Rating Standard IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66
Optional
Dimensions mm 130x130 130x130 130x130 130x130 130x185 130x185 130x260 130x260 130x185 130x185 130x260 130x260
Short Time Rating kA for 1 sec 41 46 51 56 61 60 73 84 120 120 140 160
Prospective Short Circuit Rating kA 84 95 105 121 132 132 154 176 264 264 308 352
Number of Trunkings 1 1 1 1 1 1 1 1 2 2 2 2
Technical Data for Cast Resin Bar 5 Bar, Copper Conductors Load Distribution Factor = 1
Rated Current A 800 1000 1200 1400 1750 2000 2500 3000 3500 4000 5000 6000
Rated Voltage VAC 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Voltage Drop, Balanced Load mV/A/m pf = 0.8 0.186 0.152 0.131 0.117 0.086 0.074 0.055 0.050 0.043 0.037 0.027 0.025
pf = 0.9 0.187 0.139 0.122 0.106 0.079 0.066 0.051 0.045 0.039 0.033 0.025 0.022
pf = 1.0 0.135 0.091 0.084 0.067 0.051 0.038 0.034 0.025 0.025 0.019 0.017 0.012
Conductor Characteristics
R mΩ/m at end temperature 0.078 0.053 0.048 0.039 0.03 0.022 0.02 0.015 0.015 0.011 0.01 0.0075
X mΩ/m at end temperature 0.075 0.076 0.062 0.061 0.043 0.042 0.027 0.029 0.0215 0.021 0.0135 0.0145
Z mΩ/m at end temperature 0.108 0.093 0.079 0.072 0.052 0.047 0.034 0.033 0.026 0.0235 0.017 0.0165
Weight kg/M 55 58.5 61 66.5 89.5 98.5 133 148 179 197 266 296
IP Rating Standard IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66 IP 66
Optional
Dimensions mm 130x130 130x130 130x130 130x130 130x185 130x185 130x260 130x260 130x185 130x185 130x260 130x260
Short Time Rating kA for 1 sec 25 28 31 33 37 38 43 49 74 76 86 98
Prospective Short Circuit Rating kA 86 105 112 123 134 132 160 184 268 264 320 352
Number of Trunkings 1 1 1 1 1 1 1 1 2 2 2 2
29
Networked Busbar
30
Networked Busbar
(G=calibrated/U=uncalibrated)
Switching/signalling
Standard Remote operation/remote monitoring
tap-off units
Consumption measurement
Central data acquisition of
decentralized power consumers
31