Professional Documents
Culture Documents
Renewable Energy
journal homepage: www.elsevier.com/locate/renene
a r t i c l e i n f o a b s t r a c t
Article history: A small high-solidity vertical axis wind turbine, with dielectric barrier discharge plasma actuators
Received 27 April 2011 installed on the blade leading-edges, was built and tested in a low-speed wind tunnel. The main
Accepted 24 June 2011 objectives were to assess turbine performance enhancements resulting from the control of dynamic flow
Available online 22 July 2011
separation and project the viability of up-scaling the turbine. The actuators employed were configured to
control separation only on the upstream half of the turbine azimuth. Turbine power was measured using
Keywords:
a specially designed dynamometer that allowed full characterization of its performance. A parametric
Vertical axis wind turbine
study showed that actuator duty cycle dependence observed previously on static airfoils was also
Dielectric barrier discharge plasma actuator
Dynamic stall control
observed on the turbine. Optimum reduced frequencies, however, showed substantially different
dependence and this was traced to the importance of the plasma pulsation frequency relative to the
turbine rotational frequency. When considering overall performance improvements, increases in turbine
power of up to 38% were measured. Based on the data acquired, up-scaling the turbine by a factor of 5
and 10, the percentage of plasma power required to produce comparable improvements was conser-
vatively estimated at 3.3% and 1.7% respectively. Further work will address phase-locking the plasma
pulsation and turbine frequencies, assessing the performance benefits of downwind actuation,
employing combined upwind and downwind actuation and measuring the controlled flowfield using
particle image velocimetry.
Ó 2011 Elsevier Ltd. All rights reserved.
1. Introduction a partially stalled state that is exacerbated at high wind speed when
the potential for power generation is maximized. Historically, the
In recent years there has been a resurgence in vertical axis wind approach to avoiding dynamic stall was to pitch the blades using
turbine (VAWT) development for both urban-scale or off-grid mechanical levers [15,16]. Attempts are also being made presently
applications as well as off-shore alternatives to horizontal axis to improve turbine performance using circulation control [17].
wind turbines [1e7]. VAWTs have some advantages over horizontal Additionally, recent investigations have focused on performance
axis machines in that they are insensitive to wind direction, the measurements, flow visualization and PIV measurements of the
generator can be located closer to the ground and they produce dynamic stall phenomenon [8]. However, no attempts have been
lower sound emissions due to lower blade speeds [8]. A major made to directly control turbine blade dynamic stall using active
problem associated with VAWTs is the phenomenon of dynamic flow control.
stall [9e11]; namely the boundary layer separates dynamically Although dynamic stall has not been controlled on VAWTs,
from the turbine blades. Blade stall is a two-fold problem: on the airfoil dynamic stall control under incompressible conditions has
one hand it dramatically reduces turbine power through loss of lift been studied using a variety of techniques, including leading-edge
and increases in drag; on the other hand it produces large unsteady slats, deformable leading-edges, surface suction, slot blowing and
loads that compromise the structural integrity and also impact on zero mass-flux blowing (see references in [18]). The introduction of
the drive-train and generator selection [12,13]. period perturbations, in the form of zero mass-flux blowing, is
In many cases the problem is compounded in the built envi- a particularly attractive because it requires far less slot momentum
ronment or on buildings [14] where VAWTs are often required to when compared to steady blowing. Significant increases in lift and
operate at low rotational speeds and hence low blade speed to wind reductions in drag were observed when the reduced perturbation
speed ratios (l h uR/VN). This forces the turbine to operate in frequency was in the range 0.6 Fþ 1.1 [19] and this renders it
potentially viable for application on VAWTs. However, the problem
is complex because stall occurs alternately on the inboard or the
* Corresponding author. outboard surfaces of the blades depending on whether they are
E-mail address: davidg@technion.ac.il (D. Greenblatt). upwind or downwind. Hence a successful flow control strategy
0960-1481/$ e see front matter Ó 2011 Elsevier Ltd. All rights reserved.
doi:10.1016/j.renene.2011.06.040
346 D. Greenblatt et al. / Renewable Energy 37 (2012) 345e354
would require a method that can control stall alternately on both connected symmetrically on the shaft but shifted upwards to
sides of the blade. Furthermore, any technique must be energy produce a long free end, intended for future flow particle image
efficient in that annual energy yield should far exceed the energy velocimetry (PIV) measurements. The turbine was installed in
required to drive the actuators. Based on a system study conducted a low-speed blow-down wind tunnel with a 1 m 0.61 m test
by Sasson and Greenblatt [20,21], effective and energy efficient section area (2 m long) and a maximum wind speed of 55 m/s. The
control could have three important benefits: firstly, the annual maximum turbulence level in the center of the tunnel was 0.3% of
energy yield can be increased by up to a factor of three; secondly, the free-stream velocity. A schematic of the turbine is shown in
the power increases will occur in the lower l regime and hence Fig. 1a and a photograph of the turbine installed in the wind tunnel
work in favor of noise reduction and lower structural loads; and is shown in Fig. 1b.
thirdly, oscillatory aerodynamic loads imposed on the structure can A custom dynamometer was coupled to the shaft and mounted
be reduced. below the turbine outside the tunnel. The dynamometer comprised
The objective of this study was to improve performance on of a magnetic brake, used to load the turbine, and a Kistler torque/
a VAWT by controlling dynamic stall on the blades using periodic rotational speed transducer (see Fig. 2). The largest source of
perturbations. This was achieved by constructing a small, high measurement error was that associated with the torque measure-
solidity, turbine equipped with surface mounted dielectric barrier ment, namely 0.0015 N m according to the manufacturer’s spec-
discharge (DBD) plasmas actuators. The results of a parametric ification. Flexible couplings were employed to compensate for
study and a turbine performance assessment are reported here. The misalignments. The turbine dimensions were diameter D ¼ 0.5 m
application of DBD plasma actuators was demonstrated on and height H ¼ 0.6 m; these dimensions were dictated by the test
stationary and dynamically pitching airfoils by Corke et al. [22] and section dimensions. The blades employed were symmetric
Post and Corke [23]. The actuators are typically driven in the kilovolt NACA 0015 profiles of chord length c ¼ 150 mm, constructed
range at several hundred hertz to several kilohertz and these from extruded aluminum. The resulting turbine solidity, namely
produce plasma microdischarges, at time-scales O(109 s) during s ¼ Nc/R ¼ 1.25, was relatively high.
the positive- and negative-going drive signals. The net result on the DBD plasma actuators were attached to the leading-edges of the
surrounding air is a wall-jet, which is considered analogous to the blades. The actuators used were similar to those used in previous
jet blown from a two-dimensional slot. Post and Corke [23] also studies, namely the upper (exposed) and lower (encapsulated)
considered aerodynamic effects when driving the actuators in electrodes (both 70 mm thick) separated by three layers of 50 mm
a pulsed mode. Pulsing the actuator brings with it two significant thick KaptonÒ tape. These were wrapped around the leading-edge
advantages. Firstly, it has long been recognized that periodic of the blade as shown schematically in Fig. 3a. A layer of 50 mm
perturbations can achieve aerodynamic performance benefits that thick KaptonÒ tape was applied to the blade to isolate the actuator
are comparable or superior to steady blowing at one to two orders of from the wing. The actuators were driven at an ionization
magnitude less momentum input [24]. Secondly, Greenblatt et al. frequency of fion ¼ 8 kHz at V ¼ 8 kVpp (2.83 kVrms). Pulsation
[25] and Bachmann et al. [26] observed that DBD plasma duty cycles frequencies were chosen to represent the Fþ range between O(0.1)
(DC) of 1% and 50% produced comparable aerodynamic perfor- and O(5), corresponding to 10 Hz fp 500 Hz and the duty cycle
mance. Because power supplied to the actuator is proportional to range tested was 1% DC 50%. Fig. 3b is a photograph of the
duty cycle, it is possible that this plasma power input can be reduced turbine from above the wind tunnel, showing the adapters, con-
sufficiently so as to render it viable for turbine applications. Finally, necting rods and a blade. An identical actuator was calibrated
DBD plasma actuators have wide appeal because they have no independently by mounting it on sensitive load cell while recording
moving or mechanical elements and are robust and reliable. its developed thrust (Fp) as a function of power input. The thrust
developed at V ¼ 8 kVpp was 1.5 mN/m with a power consumption
2. Experimental setup of 45 W/m at 100% duty cycle.
For the purpose of conducting the high-voltage AC power
The turbine used in this investigation consisted of a vertical required to operate the DBD actuators, slip-rings were installed on
shaft rotating on two self-aligning bearings, two horizontal both turbine’s shaft ends. An end-type slip-ring was mounted at the
adapters used for the attachment of connecting rods and two top of the shaft and a through-bore-type was mounted below,
vertical blades attached to the connecting rods. The blades were above the dynamometer. In order to avoid large voltage differences
D. Greenblatt et al. / Renewable Energy 37 (2012) 345e354 347
Fig. 1. a. Schematic representation of the VAWT showing the main components. b. Photograph of the turbine mounted in the wind tunnel.
within the each slip-ring, the high-voltage and earthed connectors extend this definition by using the velocity relative to the blade
were connected via the upper and lower slip-rings respectively (see namely W, such that
Fig. 2).
fp c
Ftþ h (2)
3. Controlling parameters and experimental methods W
In all subsequent discussion we shall assume that the chord length
The reduced frequency definition Fþ appropriate to the VAWT is constant, as it is in this study, for simplicity. If we attempt to set
blades does not have a straight-forward definition as for example a constant Fþt , much like in airfoil studies, we encounter three main
its definition on stationary airfoil studies, which is: difficulties:
Fig. 3. a. Schematic of the blade leading-edge region showing attachment of the DBD plasma actuator. b. Photograph of the wind turbine shown from above the wind tunnel
transparent wall.
Thus in order to maintain a constant Fþ, the physical pulsation 4.0 m/s UN 7 m/s that are representative of commonly
frequency fp must be variable. For the sake of simplicity, in this encountered wind speeds. For all tests the wind tunnel speed was
investigation we did not attempt to change the frequency of actu- maintained constant with in 0.1 m/s. Two main types of experi-
ation as a function of q at any of the l’s tested. Instead, a constant ments were performed: (a) parametric studies; and (b) turbine
frequency was selected for each set of experiments. Apart from this performance evaluations. Parametric studies were performed by
practical simplification, the approach can also be justified on setting a particular tunnel speed and dynamometer load and
physical grounds because static thick airfoil lift coefficient data then varying the plasma control parameters systematically. The
show only a weak dependence on the reduced plasma pulsing turbine parameters were selected based on corresponding param-
frequency in the range 1 Fþ 5 [26]. Thus a constant physical eters known to control separation on static airfoils. Overall turbine
frequency can be selected such that Fþ t varies within this range. performance was assessed by fixing a particular tunnel velocity and
To distinguish between dynamic stall commencing on the
advancing and retreating blades, two nominal reduced frequencies
were defined: one for experiments conducted on the upstream half
of the turbine; and one for experiments conducted on the down-
stream half of the turbine, namely:
þ fp c fp c
Ft;u h ¼ (3)
u R þ UN ðl þ 1ÞUN
and
þ fp c fp c
Ft;d h ¼ (4)
u R UN ðl 1ÞUN
respectively (see Fig. 4). Here it is assumed that the so-called
induced velocity through the turbine and the tunnel velocity are
equal (UN ¼ Va), which is a reasonable assumption at low l.
Although these two definitions do not take into account the vari-
ability of the reduced frequency, nor the interference effect of the
turbine, they represent nominal values just prior to the blade
pitching into the post-stall regime. In a similar manner, we also
define the nominal Reynolds numbers:
ðuR þ UN Þc ðl þ 1ÞUN c
Ret:u h ¼ (5)
n n
and
ðuR UN Þc ðl 1ÞUN c
Ret:d h ¼ (6)
n n
to estimate of the range of Reynolds numbers encountered by the
blades.
Initial experiments were carried out with the plasma actuators
configured to control dynamic stall on the upwind half of the Fig. 4. Top view schematic of a three-bladed VAWT showing the velocity components
turbine. Experiments were performed at tunnel speeds in the range relative to the blade.
D. Greenblatt et al. / Renewable Energy 37 (2012) 345e354 349
then varying the load gradually from the fully unloaded condition frequency as well as wind tunnel velocity. Fig. 6a and b shows the
until the turbine stopped. The identical procedure was conducted transient turbine rotational speed when subjected to plasma
for the baseline (uncontrolled) case and controlled case with pulsations for different duty cycles. These data are typical of all
a particular parameter combination. These data were augmented parametric studies conducted here. Two groups of data are pre-
with static tests and surface flow visualization. sented: one for UN ¼ 4.9 m/s (Fig. 6a) and one for 7.0 m/s (Fig. 6b). In
all cases, data were acquired initially under baseline conditions for
4. Discussion of results t < 10 s; and at t ¼ 10 s the plasma actuators were initiated. In all
cases shown here, a frequency fe ¼ 200 Hz was selected. This corre-
4.1. Baseline turbine and the effect of slip-rings sponded to the range of reduced frequencies 1.3 Fþ t,u 2.1 observed
to increase lift on thick non-symmetric airfoils at Re 100,000
Prior to evaluating the effect of plasma actuation, baseline [25,26]. Following initiation of the actuation, the turbine rotational
turbine performance data were acquired as shown in Fig. 5a and b. speed increases and eventually settles to a higher rotational speed.
The figures show the baseline power coefficient (CP ¼ Pt/qNUNHD) With the dynamometer load constant, the measured torque remains
and torque without slip-rings as well as the effect of adding the unchanged, and hence the gross increase in turbine power is directly
upper end-type slip-ring and both the upper end-type and the proportional to the increase in rotational speed. For each data set, it
lower through-bore slip-rings. The relatively small l range shown can be seen that, although the variation with time is somewhat
in Fig. 5a is typical for a turbine with high solidity such as this different, the duty cycle does not have a significant effect on the final
(s h Nc/R ¼ 1.2). The power coefficients measured here are expec- rotational speed. This result is consistent with static airfoil data
ted to be greater than the actual turbine values due to the blockage [25,26] and is significant because it means that the same increase in
effect of the wind tunnel walls. The data were not corrected for this turbine power can be achieved with much less power to drive the
because the primary objective here was to assess the relative actuators, thereby increasing the net turbine power. The effect of this
change between baseline and controlled scenarios (see Sections 4.2 on overall performance will be discussed below.
and 4.3). The figures illustrate the significant effect of torsional slip- It can further be seen by comparing Fig. 6a and b that the “rise
rings friction: the upper slip-ring reduced the torque by approxi- time” is longer at 4.9 m/s than at 7.0 m/s: typically between
mately 0.04 N m while the combination produced almost no power 40 se80 s and 20 se40 s, respectively. This is due to the larger loads
at UN ¼ 4.3 m/s. An increase in tunnel velocity to UN ¼ 4.9 was resulting from the combination of higher tunnel speed and rota-
required to produce torque values comparable to those obtained tional speed. For each run, sufficient time was allowed for stabili-
with one slip-ring. Hence it was concluded that the total friction zation of the turbine and, following that, long time averages
associated with both slip-rings together was approximately (approximately 30 s) of the data were acquired. The turbine
0.14 N m. For these small-scale wind tunnel tests the slip-rings have response to plasma actuation exhibited substantial hysteresis. This
a significant effect. However, up-scaling the turbine markedly can be seen by comparing the difference in the initial baseline
reduces this effect as discussed in Section 4.4. speeds. Each of these “initial conditions” followed termination of
actuation from the previous experiment, followed by slowing-
4.2. Parametric study down and stabilization of the rotational speed. To account for this
hysteresis, the changes in turbine power were calculated from the
Following the baseline evaluation of the turbine, a parametric changes in turbine rotational speed, namely DPt ¼ TDu, based on
study was performed to assess turbine performance improvements the initial and final conditions for each experiment. Examples of
subject to the plasma parameters of duty cycle and pulsation turbine power coefficient changes as a function of duty cycle are
a b
Fig. 5. Baseline performance of the turbine showing the effect of slip-rings on performance: (a) power coefficient versus l; (b) turbine mean torque versus rotational speed.
350 D. Greenblatt et al. / Renewable Energy 37 (2012) 345e354
a b
Fig. 6. Transient turbine rotational speed resulting from initiation of plasma actuation for different duty cycles at two wind tunnel velocities. The reduced frequency range is:
1.3 Fþ
t,u 2.1.
shown in Fig. 7 for 4.9, 5.9 and 7.0 m/s. As expected from the Transient data were acquired as a function of frequency in the
transient data shown in Fig. 6a and b, large variations in duty cycle same manner as that acquired as a function of duty cycle described
have virtually no effect on the turbine power coefficient. If we above. Percentage changes in power coefficient for data acquired at
consider only changes to turbine power, this accounts partially for different wind speeds and l are shown in Fig. 8 as a function of Fþ
t,u.
the hysteresis phenomenon. The differences in the changes to the Three data sets represent individual experiments, while the one
power coefficient at the different speeds shown in Fig. 7 result from U ¼ 7.1 m/s set was acquired by increasing the pulsation frequency
the different l of the turbine. For example, the U ¼ 5.9 data set has fp without allowing the turbine to return to its baseline state.
an initial l ¼ 1.7, which is lower than the others, and hence the Comparing the two data sets at U ¼ 7.1 m/s shows another aspect of
blades are stalled for a greater fraction of the azimuth. Conse- the turbines hysteresis: higher power coefficients can be obtained
quently, when the plasma is initiated and the separated boundary by successively increasing the pulsation frequencies rather than
layer is controlled, the percentage increase in power is the largest. running the turbine each time from its baseline state.
Fig. 7. Effect of duty cycle on changes to the power coefficient for different wind tunnel velocities at the corresponding range of reduced frequencies 1.3 Fþ
t,u 2.1.
D. Greenblatt et al. / Renewable Energy 37 (2012) 345e354 351
Fig. 8. Effect of reduced frequency on changes to the power coefficient for different wind tunnel velocities.
One puzzling aspect of the turbine’s frequency dependence is that the flow over the static blade was separated. Data were
that its performance increases continuously with increasing acquired as function of frequency, although here the changes in
frequency. Similar observations were also made at DC ¼ 50%. This torque DT were measured and are presented in dimensionless form
observation is totally at odds with data acquired on static airfoils at DCT ¼ DT/qNcHR in Fig. 9. The higher peak values attained at lower
post-stall angles-of-attack under steady free-stream conditions speeds are due to the lower plasma force relative to the increasing
where peak lift coefficient changes are typically in the reduced wind tunnel dynamic pressure. These data show a completely
frequency range 0.5e1. It should also be noted that our convenient different dependence on reduced frequency, with peaks attained at
definition of Fþ t,u will under-predict the actual value on the blade for reduced frequencies between 1.5 and 2. The optimum frequency is
0 < q < 180 . For example, when q ¼ 90 , Fþ t ¼ fpc/uR ¼ fpc/lUN somewhat larger than that based on the lift changes to static airfoils
which is greater than Fþ t,u defined in equation (3). Hence optimum (0.5e1) and may be due to a combination of both changes in lift and
reduced frequencies observed here are much larger than those on drag, which both act to vary the torque. The changes in torque were
static airfoils. clearly due to separation control as confirmed by surface tuft flow
In an attempt to understand the phenomenon better, the visualization shown in Fig. 10aed. The photographs shown in
turbine was fixed with one blade at q ¼ 20 , namely a ¼ 20 , such Fig. 10aec were taken at arbitrarily times and illustrate the large
Fig. 9. Effect of reduced frequency on the static coefficient with one turbine blade locked at q ¼ 20 .
352 D. Greenblatt et al. / Renewable Energy 37 (2012) 345e354
Fig. 10. Tuft visualization of flow on the inboard side of the blade (turbine stationary) at q ¼ a ¼ 20 : (a)e(c) random photographs with control off (d) representative photograph at
Fþ ¼ 2.
oscillations of the tufts as they are exposed to the unsteady sepa- Consider a typical case where Fþ
t,u ¼ 2 and l ¼ 2. By substitution of
rated flow. Fig. 10d shows the tufts when the plasma actuation is dimensionless groups, we can write the ratio:
initiated at Fþ ¼ 2 and is representative of this tuft pattern
remaining time-invariant while the plasma actuator is active. The 2pfp lþ1 R þ
¼ 2p F (9)
thrust effect of the actuator on the torque when the blade was un- u l c t;u
stalled (q ¼ a ¼ 0 ) was un-measurable even at duty cycles of 50%. Under these conditions 2pfp/u ¼ 31 which would appear to
This was fully consistent with the actuator calibration which pre- fulfill the condition suggested by Greenblatt et al. [27]. However, on
dicted a value of 0.11 mN m on a single 0.6 m span blade at 50% duty the turbine this translates to one perturbation every 11.6 degrees
cycle. The differences between the turbine performance and the on the azimuth. The lack of an enforced phase relationship between
torque changes may be due to two factors. The first is the effect of the forcing and the turbine rotation means that the perturbations
dynamic pitching and the second concerns the relationship are introduced at arbitrary angles, possibly even after the flow has
between the plasma pulsation frequency and turbine rotation already begun separating from the surface. By increasing the
frequency, namely the ratio 2pfp/u. perturbation frequency the differences in the azimuthal angles are
To further understand the effect of blade pitching, consider the smaller and this causes the perturbations to be introduced closer to
conventional non-dimensional pitch-rate parameter defined for onset of dynamic stall. Hence, although the higher frequencies are
oscillating airfoils: not the optimum for performance improvements, the fact that they
are introduced more consistently closer to dynamic stall onset
khuc=2UN (7)
renders them more effective. Phase-locking the perturbations with
where unsteady effects are generally observed to manifest for the turbine rotation has the potential to overcome this limitation.
k > 0.01. By analogy with our definition for reduced pulsation Moreover, designing a turbine where the optimum reduced
frequency in equation (3), we define for the turbine frequencies correspond to 2pfp/u > O(102) would clearly also have
potential to improve performance. Effects of scaling-up the turbine
uc uc on the frequency ratio parameter are described in Section 4.4.
kt;u h ¼ (8)
2ðuR þ UN Þ 2ðl þ 1ÞUN
and based on this definition kt,u > 0.15. Even though this is rela- 4.3. Turbine performance evaluation
tively high, Greenblatt et al. [27] observed that the optimum
control frequencies are not affected on pitching airfoils providing Fig. 11 shows the overall turbine performance for two wind
that 2pfp/u [ 1. However, in that study the airfoil oscillation speeds, UN ¼ 4.9 m/s and 5.9 m/s, for both the baseline turbine as
amplitudes were small; the turbine case is significantly different. well as control in the range 4.4 Fþ
t,u 5.6. For each tunnel speed,
D. Greenblatt et al. / Renewable Energy 37 (2012) 345e354 353
Fig. 11. Overall turbine performance improvements at two wind tunnel speeds for control on the upwind side of the blades with DC ¼ 5%.
plasma produces an increase in performance over almost the entire differences in Reynolds number where significant changes in
operational range. The peak power coefficients are increased by aerodynamic performance are observed.
38% and 31% respectively. The baseline turbine performance is
strongly dependent on the tunnel speed and there are two main 4.4. Turbine scaling considerations
reasons for this. The first is the turbine torque produced relative to
the friction in the bearings and slip-rings and the second is the Based on the data acquired in this study, predictions can be
different Reynolds numbers encountered by the blades. made regarding the viability of DBD plasma actuators on full-scale
The effect of slip-ring friction on these measurements is eluci- wind turbines. The main questions considered here relate to the
dated by comparing the frictional torque versus the mean torque effectiveness and efficiency of the plasma actuation if the turbine
produced by the turbine. As discussed above in Section 4.1 (see dimensions are increased. For simplicity, we assume that the
Fig. 5a and b), addition of the upper slip-ring added 0.04 N m of turbine scales linearly, namely the turbine height to radius ratio H/R
frictional torque while the addition of both the upper and lower remains constant, but that the chord length remains constant.
slip-rings produced approximately 0.14 N m of frictional torque. For The first aspect relates to the frictional torque introduced with
baseline tests at UN ¼ 4.9 m/s and 5.9 m/s the peak net torque installation of the slip-rings. For the present turbine the maximum
values produced by the turbine are 0.067 N m and 0.15 N m which frictional torque produced by both slip-rings together was esti-
are comparable to the friction in the slip-rings. Because the mated to be 0.14 N m. At low power, typically less than 10 W (see
increased wind speed is accompanied by increases in torque, the Fig. 9), this was an appreciable fraction of the total turbine torque.
slip-ring friction effect is smaller at the higher speed. Clearly, with Consider up-scaling the turbine by a factor of 5, namely R ¼ 1.25 m
increasing scales the effects of slip-ring friction will become and H ¼ 3.0 m which is typical of many small turbines intended for
successively smaller (see Section 4.4), but for the small-scale personal off-grid use [3]. Assuming a typical power coefficient
experiments conducted here, their effect is significant. CP ¼ 0.32 at a wind speed of 5 m/s, the turbine produces 180 W. At
The second factor responsible for the differences observed here the same l as the measurements performed here, the peak turbine
is Reynolds number. For the UN ¼ 4.9 m/s and 5.9 m/s cases the torque is 22.5 N m and hence the slip-ring torque is now only 0.14/
nominal Reynolds number ranges (Ret,u to Ret,d) defined above vary 22.5 100 ¼ 0.62% of the peak torque. Up-scaling the turbine by
from 24,500 to 166,000 and from 41,300 to 212,000 respectively. a factor of 10 to a 2.5 m radius producing 0.72 kW at 5 m/s, the slip-
Carmichael [28] shows that for airfoil Reynolds numbers between ring torque percentage drops to 0.16%. Clearly, as the turbine size
30,000 and 70,000 large differences in airfoil performance are increases, so the relative frictional torque diminished dramatically.
observed. Thick airfoils, such as the NACA 0015 used here, suffer Additionally, it should be noted that in the present application,
from significant hysteresis that results from differences in laminar the end-type upper slip-ring produced only 0.04 N m of frictional
boundary separation and attachment as the airfoil pitches up and torque as compared the lower through-bore-type that produced
down. In addition, at Re < 50,000 the separated laminar shear layer more than twice as much frictional torque. The only reason for
does not transition to turbulence and reattach to the surface. These using through-bore slip-rings here was to facilitate the attachment
problems can be ameliorated using thin airfoils [29], but these are of the custom dynamometer. For an up-scaled turbine, end-type
generally not structurally viable on VAWTs due to the large slip-rings could be employed resulting in even lower friction.
centrifugal loads. For the range 70,000 Re 200,000, airfoil Assuming wind speeds and l comparable to those employed
performance generally improves markedly. Hence, even though the in the experiments, the plasma actuators power input relative
increase in tunnel speed considered here was relatively modest, the to the turbine power can be estimated. The power input to the
combined effect of this and the different l ranges produced actuators is 1.2 W per blade at DC ¼ 1% and hence the total power
354 D. Greenblatt et al. / Renewable Energy 37 (2012) 345e354