EWFC 1000
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
+ –
room defrost door alarm insert comp. probe fans comp. fans defrost light
probe probe switch probe alarm holder alarm
switch switch switch
POWER SUPPLY
SSA: Set inSert probe “A”. n = no; y = yes. The fans alarm input, if interrupted, cuts off
Required setting of the termination tem- tlC: time light Cabinet. the compressor output; this input should
perature of cycle 1 and of quick-chill phase Time in seconds after which the light is be shorted if not used.
of cycle 5 (if a product insert probe is turned off; if set at “0” the light is controlled
used). directly by door closure or by the light but- INSTALLATION
i1A: interval 1 “A”. ton. The EWFC 1000 is designed for flush pan-
Time setting, in minutes, which determines cdP: compressor delay Protection. el mounting. Insert the unit through a
the maximum duration of cycle 1 and of Compressor start time delay in minutes to 65.5x209.5 mm and affix with the brackets
quick-chill phase of cycle 5, if operated on avoid short-cycling. supplied.
time only (without insert probe). CAL: CALibration. The ambient temperature around the in-
SE1: SEt 1. This is an offset calibration which may be strument should be kept between –5 and
Setting of the cabinet (box) temperature re- required due to the location of the sensor. 65 °C (23…149 °F).
quired during cycle 3 and of hold phase of tAb: tAble of parameters. Select a location which will not be subject
cycle 5. This is factory set and can not be modified; to high humidity or condensation.
SCC: Set Cabinet probe “C”. it is determined by the parameter configu-
Required setting of the cabinet (box) tem- ration. ELECTRICAL WIRING
perature during cycle 2 and quick-chill The EWFC 1000 is equipped with Faston
phase of cycle 6. DIGITAL INPUTS spade connectors 6.3 mm.
SSC: Set inSert probe “C”. The EWFC 1000 can accommodate up to Make sure that the available voltage corre-
Required setting of the termination tem- four input signals, dry contact and voltage sponds to the nameplate rating of the in-
perature of cycle 2 and of quick-chill phase free. strument.
of cycle 6 (if a product insert probe is The door switch input controls the cabinet Power remains connected even if the in-
used). light: light on when input open, off when strument is turned off; a main switch
i1C: interval 1 “C”. contact is closed. should therefore be installed between the
Time setting, in minutes, which determines If the light has already been switched on instrument and the mains.
the maximum duration of cycle 2 and of with the (manual) button, then this input The three PTC-type sensors do not require
quick-chill phase of cycle 6, if operated on has no further effect (see “FRONT KEY- polarity and can be extended in the field by
time only (without insert probe). PAD” section). using common 2-lead wire. It is strongly
Note: the effective value will be 120 min- Opening of the door switch input causes recommended that the probe wiring is
utes higher than selected. the Led warning light located above the kept away from power leads.
SE2: SEt 2. “LIGHT” button to come on, and causes Also, it is good practice to install the sen-
Setting of the cabinet (box) temperature re- an audible alarm (internal buzzer) to go off sor tip facing up, in order to avoid moist
quired during cycle 4 and of hold phase of after the delay time selected through para- from entering the sensor housing. the dig-
cycle 6. meter “oAo”. The acoustic alarm can be ital inputs should be dry contacts, voltage
dod: disable with opened door (compres- turned off simply by pushing any front pan- free.
sor and fan). el button; the visual alarm remains on until The compressor output relay is voltage
A choice is given whether or not to stop the door is closed (input contact closure). free and can handle up to 1.5 HP; use a
the compressor and fan when door is The insert probe parking input enables, if suitable external contactor for larger com-
opened. shorted, the time (parameters “i1A” and pressors.
n = no; y = yes. “i1C”) to control the the maximum duration
oAo: door Alarm override. of cycle 1 and 2 and the change-over from ERROR ANNUNCIATION
Alarm time delay in seconds after the door “quick-chill” mode to “hold” mode during The EWFC 1000 will display a number of
is opened. cycles 5 and 6. temperature or probe error alarm condi-
dSd: diSable light with open door. The compressor alarm input, if interrupted, tions.
Light comes on automatically when door is cuts off the compressor output; this input In the event of an open or shorted box
opened. should be shorted if not used. probe the alarm Led status light will come
7/2000 ing