EWFC 1000

“quick-chill and hold” cold control

GENERAL DESCRIPTION a “hold” cycle are signalled by an on-board


The EWFC 1000 is an electronic device to buzzer.
control all functions in a “quick-chill and A number of status lights indicate the sta-
WHAT IT IS
hold” freezer system. tus of the programming and of the func-
The EWFC 1000 is an electronic de- It can also be used for units designed for a tioning of the equipment.
vice to control all functions in a quick pull down of product temperature to EWFC is available in two versions: vertical
“quick-chill and hold” freezer sys- approximately 0 °C, or for blast freezing as format 72x216 mm and horizontal format
tem. dictated by prevailing legislature and regu- 216x72 mm, both for panel mount.
lations. After the initial quick-chill process,
a product-hold temperature cycle can be OPERATION
programmed for any length of time, during Operating cycle selection
HOW IT IS MADE which the system operates as a normal re- When the instrument is turned on with the
• Housing: black ABS plastic, self- frigerator. “On/Off” button, the display will flash
extinguishing Various relay outputs are available to con- “SEL”, prompting the selection of the re-
• Dimensions: front 72x215.5 mm trol the components of the system, i.e. quired operating cycle.
(2.84x8.5”), depth 110 mm (4.33”) compressor, fan, defrost cycle and cabinet The following Leds will be blinking: “Quick-
• Mounting: flush panel mount with light. chill at positive temperature”, “Quick-chill
two mounting studs provided The change-over from “quick-chill” mode at negative temperature” and “Hold, above
• Connections: Faston connectors to “hold” mode can be achieved either on or below freezing”.
6.3 mm (1/4” male spade) temperature, by using a product insert Any of the following modes may be select-
• Display: 12.5 mm LED (0.50") probe, or strictly on time, if an insert probe ed by using the respective buttons (see
• Push buttons: located on front is not used. On the contrary, temperature “front keypad” section):
panel control is achieved strictly on room probe. 1) quick-chill at positive temperature
• Relay output: one (1) SPST relay Even if an insert probe is used, the quick- (above freezing);
15(7)A 250V AC for compressor, chill will terminate on time, in the event that 2) quick-chill at negative temperature (be-
one (1) SPDT relay 8(3)A 250V AC the probe is not properly inserted into the low freezing);
for defrost, two (2) SPST relays product. 3) hold, above freezing;
8(3)A 250V AC for evaporator fan A comprehensive parameter programming 4) hold, below freezing;
control and light menu is available through which all data 5) quick-chill and hold above freezing;
• Remote alarm output: one (1) out- can be entered, such as the various oper- 6) quick-chill and hold below freezing;
put 12 Vdc/50 mA to remote alarm ating temperatures, time delays and oper- The selection of the above combinations is
buzzer or relay ating modes. done simply by pushing the corresponding
• Analog inputs: two (2) PTC probes The end of a “quick-chill” cycle and start of buttons in sequence.
for temperature control and de-
frost termination, one (1) insert
probe for product control
• Digital inputs: four (4) digital in-
puts for door switch, insert probe
in “parking”, compressor alarm
and fan alarm
• Resolution: 1 °C (°F)
• Accuracy: better than 0.5% of full
scale
• Power supply (dep. on model):
12 Vdc or 220, 110, 24 Vac,
50/60 Hz

PLUS PRODUCT

• Easy function selection by means


of keyboard guided steps
• Automatic detenction of insert
probe presence
• Product surface anti-freeze func-
tion
• Available in “horizontal” or “verti-
cal” version
Cycle change mode selection (cycles 5 FRONT KEYPAD Led means that the fan is in a delay-be-
and 6) start fore-start mode.
The change-over from the quick-chill stop Start/Stop
mode to the hold mode can be done either Starts the selected cycle if the machine is Insert probe Led
on temperature or on time. If the “Time” off or stops the cycle when it is running. If this status light is on it means that the in-
button has not been activated, then the sert probe is activated. A flashing light can
change-over point will be dictated by the Positive quick-chill (65…10) either mean that the probe is located in its
product core temperature as sensed by Pre-sets the system for a quick-chill cycle “probe holder”, or - if the flashing started
the insert probe in relation to the setpoint above or close to freezing temperature. some time after the quick-chill cycle began
as selected during the programming (see The required temperature setting is select- - that the probe is not inserted into the
“parameter programming” section). If how- ed with a programming parameter. product, thus causing the cycle to termi-
ever it is decided not to use the insert nate on time.
probe, then push the “Time” button; the Negative quick-chill (65...–22)
change-over will now take place upon Pre-sets the system for a quick-chill cycle Defrost Led
lapse of the time period as programmed below freezing. The required temperature This pushbutton is on, when a defrost cy-
with the corresponding parameter. setting is selected with a programming pa- cle is in progress.
In the event that the probe was accidental- rameter.
prg
ly not inserted in the product, then the sys- Programming Led
tem will detect such condition and cause Hold Flashes during the entire parameter pro-
the cycle change-over to take place strict- Pre-sets the system for a hold cycle. gramming procedure.
ly on time. The system will function as a normal refrig-
The same will occur in the event that the eration unit, if neither the “65...10” nor the Alarm Led
probe has been placed in its holder which “65...–22” has been activated. The hold Status light for tthe 12 Vdc/50 mA remote
will activate the “probe holder” switch. temperature can be selected within one of alarm signal.
Cycle start two ranges, i.e. 65...10 or 65...–22 by This Led stays steady during an alarm
A cycle is started with the “Start/Stop” but- pushing the appropriate button (the corre- caused by a probe or high or low temper-
ton. sponding Led will light up). ature.
During the quick chill cycle a particular On the other hand, if a quick-chill cycle is
control algorithm will eliminate “surface already selected, then activating this but- PARAMETER PROGRAMMING
chrystalisation” of the product, a phenom- ton will only light up the Led associated Programming mode can be entered by
enon harmful to hygienic principles. with the temperature relative to the prese- holding an hidden key pressed for some
Defrost management lected quick-chill cycle. seconds. Such key is located in the lower
Before a quick-chill cycle is initiated, the right (under the “Prg” Led) in the vertical
system will go through a defrost, in order Cabinet probe/Insert probe model and in the upper right (beside the
to start with a clean coil and thus make With this button the temperature display “Prg” led) in the horizontal model.
use of the full cooling capacity of the unit. can be alternated between cabinet tem- The display shows the label of the first pa-
No further defrosts will take place during perature and insert probe temperature; the rameter, and the “Prg” Led starts blinking.
this quick-chill cycle. corresponding Led indicates which is the To skip to the other parameters press
During the subsequent hold cycle however case. “Light” (which operates as “Up” key) and
the system will defrost at time intervals as On/Off (which operates as DOWN); to see
selected during the set-up programming. Time the value of the selected parameter press
Fans control Pushing this button de-activates the insert the key “room probe/core temperature
The fans remain running during the entire probe; the change-over between the two probe” placed above (vertical version) or
“quick-chill” phase, be it at positive or neg- cycles will now be determined by time, as on the right (horizontal version) of the
ative temperature (above or below freez- selected with the appropriate parameter. “Light” key.
ing). In the “hold” phase however the fans The display will switch to show the time re- To change such value press “Light” and
will operate in parallel with the compressor, maining to the end of the quick-chill cycle. “On/Off” until the required value is dis-
regardless of whether it operates at posi- During this mode the temperature can still played. By pressing “room probe/core
tive or negative temperature. be shown, simply by pushing the “Cabinet temperature probe” again the label of the
Via the parameter programming it is possi- probe/Insert probe” button; the display will parameter will be displayed - the new val-
ble to select a “fan-off” temperature, along show the temperature for a few seconds, ue has been stored.
with a corresponding switching differential. then switch back to the time read out. The instrument exit from parameters’ pro-
Status display gramming mode and stores data in case
light
Each button has a corresponding Led sta- Light no operation is performed for a few sec-
tus light. These will flash once to indicate This pushbutton activates the relay con- onds.
that this function or mode can be selected; nected to the cabinet light. Push again to
a steady Led indicates that the corre- turn the light off. DESCRIPTION OF PARAMETERS
sponding cycle is in progress, while a on Note: the letter “A“ refers to parameters
flashing Led means that the cycle is wait- off On/Off which apply to the operating cycles for
ing to be activated. Turns the instrument on or off. Power to positive temperature (cycles 1, 3 and 5),
In addition, there is a Led for each output. the EWFC 1000 is still live, even when the while the letter “C“ applies to negative tem-
The 3-digit Led display normally shows the instrument has been turned off. peratures (cycles 2, 4 and 6).
cabinet temperature; the product core diF: diFferential.
temperature can be read by pushing the Compressor Led Switching differential between on and off
appropriate button. Indicates whether the compressor is run- the compressor relay.
If a “cycle change-over on time” was se- ning; a flashing Led means that the com- LAA: Low Alarm “A”.
lected, or the insert probe is not activated, pressor is in a delay-before-start mode. Temperature deviation below box setpoint,
then the display will show the time remain- beyond which the low temperature alarm is
ing to the end of the quick-chill cycle. Fan Led activated (cycles 1, 3, 5; see the initial
Shows that the fan is running; a flashing note).

EWFC 1000 7/2000 ing 2


DEFAULT SETTINGS - STANDARD MODELS even if no evaporator probe is used.
n = no; y = yes.
Parameter Description Range Default Unit tcA: time cycle “A”.
diF diFferential 1…15 2 °C / °F This is the defrost time limit after which the
LAA Low Alarm “A” 0…60 40 °C / °F defrost is terminated; applies to cycles 1, 3
and 5 and is expressed in minutes.
LAC Low Alarm “C” 0…60 40 °C / °F
tcC: time cycle “C”.
hAA high Alarm “A” 0…60 40 °C / °F This is the defrost time limit after which the
hAC high Alarm “C” 0…60 40 °C / °F defrost is terminated; applies to cycles 2, 4
and 6 and is expressed in minutes.
AFd Alarm (and) Fan differential 0…60 2 °C / °F
diA: defrost interval “A”.
AtA Alarm time delAy 1…60 60 minutes Defrost frequency, i.e. time interval be-
EPr Evaporator Probe read-out / / °C / °F tween two consecutive defrost starts; ap-
dty defrost type selection EL / in EL flag plies to cycles 1, 3, 5 and is expressed in
hours.
dPo defrost (at) Power-on n/y n flag
diC: defrost interval “C”.
tcA time cycle “A” 0…99 5 minutes Defrost frequency, i.e. time interval be-
tcC time cycle “C” 0…99 5 minutes tween two consecutive defrost starts; ap-
plies to cycles 2, 4, 6 and is expressed in
diA defrost interval “A” 0…24 2 hours
hours.
diC defrost interval “C” 0…24 2 hours dEA: dEfrost termination “A”.
dEA dEfrost termination “A” –60…60 2 °C / °F Defrost termination temperature for cycles
dEC dEfrost termination “C” –60…60 2 °C / °F 1, 3 and 5.
dEC: dEfrost termination “C”.
ddt defrost drainage time 0…240 60 seconds
Defrost termination temperature for cycles
dct defrost count type rt / dF rt flag 2, 4 and 6.
ddl defrost display lock n / y / Lb Lb flag ddt: defrost drainage time.
Upon defrost completion, evaporator fan
FSA Fan Stop “A” –20…99 10 °C / °F
and compressor remain “OFF” for this
FSC Fan Stop “C” –20…99 10 °C / °F amount of time to allow coil drainage; ex-
Ftd Fan time delay 0…240 30 seconds pressed in seconds.
SCA Set Cabinet probe “A” –60…50 5 °C / °F dct: defrost count type.
This determines the way the defrost inter-
SSA Set inSert probe “A” –50…50 10 °C / °F
val time (“diA” and “diC”) is calculated.
i1A interval 1 “A” 24 / 240 120 minutes The choice is:
SE1 SEt 1 –60…60 2 °C / °F dF = digiFrost®; time calculation is based
on accumulative running time of the com-
SCC Set Cabinet probe “C” –60…50 –25 °C / °F
pressor;
SSC Set inSert probe “C” –50…50 –22 °C / °F rt = real time; time calculation is based on
i1C interval 1 “C” 24 / 240 120 minutes running time of the system and controller;
SE2 SEt 2 –60…60 –22 °C / °F SC = Stop Compressor; a defrost cycle is
activated each time the compressor stops.
dod disable with opened door n/y y flag
ddl: defrost disply lock.
oAo output (door) Alarm override 1…60 30 seconds Temperature display can be “locked“ in
dSd diSable (light) with open. door n/y y flag during a defrost.
n = no; the actual box temperature is dis-
tLC time light Cabinet 0…60 30 seconds
played during defrost;
cdP compressor delay Protection 1…99 1 minutes y = yes; the temperature shown at the mo-
CAL CALibration –20…20 0 °C / °F ment a defrost starts is locked in and re-
tAb tAble of parameters / / /
mains steady during the defrost;
Lb = Label; the display will show the “dEf“
label during the entire defrost cycle.
LAC: Low Alarm “C”. alarms. Note: in case of “y” or “Lb” the display will
Temperature deviation below box setpoint, AtA: Alarm time delAy. switch back to the actual temperature only
beyond which the low temperature alarm is Time delay for temperature alarm initiation, after setpoint has been reached again after
activated (cycles 2, 4, 6; see the initial in minutes. a defrost.
note). EPr: Evaporator Probe read-out. FSA: Fan Stop “A”.
hAA: high Alarm “A”. This parameter provides a read-out of the Temperature setting above which the fan
Temperature deviation above box setpoint, actual temperature of the evaporator stops in cycles 1, 3 and 5.
beyond which the high temperature alarm (sensed by the defrost termination probe) FSC: Fan Stop “C”.
is activated (cycles 1, 3, 5; see the initial even during normal operation. Temperature setting above which the fan
note). dty: defrost type selection. stops in cycles 2, 4 and 6.
hAC: high Alarm “C”. To select the defrost type. Ftd: Fan time delay.
Temperature deviation above box setpoint, EL = ELectric defrost; Fan start time delay in seconds after com-
beyond which the high temperature alarm in = hot gas (reverse cycle) defrost. pletion of a defrost, or after a defrost
is activated (cycles 2, 4, 6; see the initial dPo: defrost (at) Power-on. drainage time, if used.
note). Selects whether the system should go SCA: Set Cabinet probe “A”.
AFd: Alarm (and) Fan differential. through a defrost cycle at start-up (or after Required setting of the cabinet (box) tem-
Switching differential of the fans, in addi- a power failure). perature during cycle 1 and quick-chill
tion to the high and low box temperature If set at “y“ (yes), defrost will take place, phase of cycle 5.

3 EWFC 1000 7/2000 ing


CONNECTIONS

EWFC 1000

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

+ –

room defrost door alarm insert comp. probe fans comp. fans defrost light
probe probe switch probe alarm holder alarm
switch switch switch

POWER SUPPLY

SSA: Set inSert probe “A”. n = no; y = yes. The fans alarm input, if interrupted, cuts off
Required setting of the termination tem- tlC: time light Cabinet. the compressor output; this input should
perature of cycle 1 and of quick-chill phase Time in seconds after which the light is be shorted if not used.
of cycle 5 (if a product insert probe is turned off; if set at “0” the light is controlled
used). directly by door closure or by the light but- INSTALLATION
i1A: interval 1 “A”. ton. The EWFC 1000 is designed for flush pan-
Time setting, in minutes, which determines cdP: compressor delay Protection. el mounting. Insert the unit through a
the maximum duration of cycle 1 and of Compressor start time delay in minutes to 65.5x209.5 mm and affix with the brackets
quick-chill phase of cycle 5, if operated on avoid short-cycling. supplied.
time only (without insert probe). CAL: CALibration. The ambient temperature around the in-
SE1: SEt 1. This is an offset calibration which may be strument should be kept between –5 and
Setting of the cabinet (box) temperature re- required due to the location of the sensor. 65 °C (23…149 °F).
quired during cycle 3 and of hold phase of tAb: tAble of parameters. Select a location which will not be subject
cycle 5. This is factory set and can not be modified; to high humidity or condensation.
SCC: Set Cabinet probe “C”. it is determined by the parameter configu-
Required setting of the cabinet (box) tem- ration. ELECTRICAL WIRING
perature during cycle 2 and quick-chill The EWFC 1000 is equipped with Faston
phase of cycle 6. DIGITAL INPUTS spade connectors 6.3 mm.
SSC: Set inSert probe “C”. The EWFC 1000 can accommodate up to Make sure that the available voltage corre-
Required setting of the termination tem- four input signals, dry contact and voltage sponds to the nameplate rating of the in-
perature of cycle 2 and of quick-chill phase free. strument.
of cycle 6 (if a product insert probe is The door switch input controls the cabinet Power remains connected even if the in-
used). light: light on when input open, off when strument is turned off; a main switch
i1C: interval 1 “C”. contact is closed. should therefore be installed between the
Time setting, in minutes, which determines If the light has already been switched on instrument and the mains.
the maximum duration of cycle 2 and of with the (manual) button, then this input The three PTC-type sensors do not require
quick-chill phase of cycle 6, if operated on has no further effect (see “FRONT KEY- polarity and can be extended in the field by
time only (without insert probe). PAD” section). using common 2-lead wire. It is strongly
Note: the effective value will be 120 min- Opening of the door switch input causes recommended that the probe wiring is
utes higher than selected. the Led warning light located above the kept away from power leads.
SE2: SEt 2. “LIGHT” button to come on, and causes Also, it is good practice to install the sen-
Setting of the cabinet (box) temperature re- an audible alarm (internal buzzer) to go off sor tip facing up, in order to avoid moist
quired during cycle 4 and of hold phase of after the delay time selected through para- from entering the sensor housing. the dig-
cycle 6. meter “oAo”. The acoustic alarm can be ital inputs should be dry contacts, voltage
dod: disable with opened door (compres- turned off simply by pushing any front pan- free.
sor and fan). el button; the visual alarm remains on until The compressor output relay is voltage
A choice is given whether or not to stop the door is closed (input contact closure). free and can handle up to 1.5 HP; use a
the compressor and fan when door is The insert probe parking input enables, if suitable external contactor for larger com-
opened. shorted, the time (parameters “i1A” and pressors.
n = no; y = yes. “i1C”) to control the the maximum duration
oAo: door Alarm override. of cycle 1 and 2 and the change-over from ERROR ANNUNCIATION
Alarm time delay in seconds after the door “quick-chill” mode to “hold” mode during The EWFC 1000 will display a number of
is opened. cycles 5 and 6. temperature or probe error alarm condi-
dSd: diSable light with open door. The compressor alarm input, if interrupted, tions.
Light comes on automatically when door is cuts off the compressor output; this input In the event of an open or shorted box
opened. should be shorted if not used. probe the alarm Led status light will come

EWFC 1000 7/2000 ing 4


on, while the display will alternate between Relay outputs: one (1) SPST relay 15(7)A
code “CP” (Cabinet Probe) and the actual 250V AC for compressor, one (1) SPDT re-
box temperature. Likewise, a code “EP” lay 8(3)A 250V AC for defrost, two (2)
(Evaporator Probe) will appear to signal an SPST relays 8(3)A 250V AC for evaporator
evaporator probe alarm, “IP” (Insert Probe) fan control and light.
to signal an insert probe problem. Remote alarm output: one (1) output
If the box probe is open or shorted the cy- 12 Vdc/50 mA to remote alarm buzzer or
cle in progress is immediately interrupted, relay.
while a defrost cycle will continue and ter- Analog inputs: two (2) PTC probes for
minate normally. At this point the START temperature control and defrost termina-
function of the unit is blocked until such a tion, one (1) insert probe for product con-
time that - upon correction of the error - trol.
the system is turned OFF first (manual re- Digital inputs: four (4) digital inputs for
set). door switch, insert probe in “parking”,
In the event that the evaporator probe be- compressor alarm and fan alarm.
comes defective (open or short circuit), the Resolution: 1 °C (°F).
cycle in progress will continue and termi- Accuracy: better than 0.5% of full scale.
nate normally, while a defrost cycle is Power supply (depending on model):
stopped at once. 12 Vcc ±15%; 12, 24, 110, 220 Vca
The “START” function is again blocked, ±10%, 50/60 Hz.
however the reset is automatic. Finally, in
the event of an insert probe defect, the cy- DISCLAIMER
cle in progress will terminate on time only, This manual and its contents remain the
a defrost terminates normally and the reset sole property of Invensys Climate Controls
is automatic. s.p.a., and shall not be reproduced or dis-
If the temperature goes below the low tributed without authorization. Although
alarm temperature setting, or above the great care has been exercised in the
high alarm temperature setting; then the preparation of this document, Invensys
error codes “LI” (Low lImit), respectively Climate Controls s.p.a., its employees or
“HI” (High lImit) will be displayed; this alarm its vendors, cannot accept any liability
not have any effect on the operation of the whatsoever connected with its use.
machine. Invensys Climate Controls s.p.a. reserves
the right to make any changes or improve-
TECHNICAL DATA ments without prior notice.
Housing: black ABS plastic, self-extin-
guishing.
Dimensions: front 72x215.5 mm
(2.84x8.5”), depth 110 mm (4.33”).
Mounting: flush panel mount with two
mounting studs provided.
Connections: Faston connectors 6.3 mm
(1/4" male spade).
Display: 12.5 mm LED (0.50").
Push buttons: located on front panel.
Data storage: non-volatile EEPROM
memory.
Operating temperature: –5…65 °C
(23…149 °F).
Storage temperature: –30…75 °C
(–22…167 °F).

Invensys Climate Controls s.p.a.


via dell'Industria, 15
Zona Industriale Paludi
32010 Pieve d'Alpago (BL)
ITALY
Telephone +39 0437 986111
Facsimile +39 0437 986066
Email eliwell@invensysclimate.com
Internet http:/www.climate-eu.invensys.com

7/2000 ing
cod. 9FT41047

5 EWFC 1000 7/2000 ing

You might also like