Professional Documents
Culture Documents
1. Motor Specification :-
• Power : 370 KW
• Voltage : 6.6 KV
2. INSPECTION SUMMARY:
After inspection at last Thursday 28/5/2020 in your site, we found many crack
point in sleeve box insulation at slip-ring, Sleeve box included many layers of
insulation material( Bandage tape with risen and Mica) with any time possible
damage as a result of centrifugal force , So you must be take action as soon as
possible to avoid phase to phase short circuit fault between rotor winding .
JORDAN INVESTMENT & SOUTHREN DEVELOPMENT CO.( JISD) الشركة االردنية لالستثمار وتنمية الجنوب
االردن11194 عمان940521 : ب. ص+ 96232308203 : فاكس+ 96232308200 : تلفون
3. Failure Causes :
- Stripping old insulation & install new insulation layers (Bandage with resin
,mica ) or/ installation new slip-ring as we were checked in your where
house .
- Certification release.