Professional Documents
Culture Documents
Functional Specification
For
Pressure Testing of Erected Piping System
SECTION : PIPING Part IV-Vol IV
FUNCTIONAL SPECIFICATION FOR Spec.No: 04-SP-05
PRESSURE TESTING OF ERECTED PIPING Rev. No: 0
SYSTEM Sheet No: 2 of 9
1. SCOPE
These guidelines cover the requirements for pressure testing of piping systems. Part A
covers the methods to determine test pressure useful for process engineers. Part B intends
to provide guidelines for construction engineers.
c) If the test pressure as defined above would produce a stress in excess of the
yield strength at test temperature, the test pressure may be reduced to the
maximum pressure that will not exceed the yield strength at test temperature.
(See 302.3.2, Notes (2) and (3)).
a) Where the test pressure of piping attached to a vessel is the same as or less
than the test pressure for the vessel, the piping may be tested with the
vessel at the test pressure of the piping.
b) Where the test pressure of the piping exceeds the vessel test pressure, and it
is not considered practicable to isolate the piping from the vessel, the piping
and the vessel may be tested together at the test pressure of the vessel, when
approved by the Company and provided the vessel test pressure is not less
than 115% of the piping design pressure adjusted for temperature as
required by 337.4.1 (b).
b) In jacketed lines, the internal line shall be pressure tested on the basis of the
internal or external design pressure whichever is critical. This test must be
performed before completion of the jacket if necessary to provide visual
access to the joints of the internal line as required by 337.3.
If the piping is tested pneumatically, the test pressure shall be 110% of the
design pressure. Pneumatic testing involves the hazard due to possible release
of energy stored in compressed gas. Therefore, particular care must be taken to
minimize the chance of brittle failure during testing. The test temperature is
important in this regard and must be considered when the choice of material is
made in the original design. Any pneumatic test shall include a preliminary
check at not more than 25 psi (170 kPa) gauge pressure. The pressure shall be
increased gradually in steps providing sufficient time to allow the piping to
equalise strains during test and to check for leaks.
At the Company’s option, a piping system used only for Category D fluid
service (as defined in 300.2) may be tested at the operating conditions of
the system during or prior to initial operation by examining for leaks at
every joint not previously pressure tested in accordance with this code. A
preliminary check shall be made at not more than 25 psi (170 kPa) gauge
pressure when the contained fluid is a gas or vapour. The pressure shall be
increased gradually in steps providing sufficient time to allow the piping to
equalize strains during test and to check for leaks.
RS < YS
RS = Resultant Stresses due to hydrotest
PT = Hydrostatic Test Pressure.
t = Min. pipe wall thickness (i.e. excluding manufacturing
tolerances of 12.5%).
YS = Yield strength at test temperature.
(See Table A-1).
2.2.2 The provision of 337.4.2 do not replace or otherwise alter the pressure
testing requirements of the applicable vessel code.
2.2.3 Even for lines to be externally pressurised during operation, hydrostatic
pressure testing can be done by pressurising internally as the primary and
sole objective of this test is to establish leakproof joints.
2.2.4 Category D fluid Service – A fluid service in which all the following apply:
a. The fluid handled is non flammable, non-toxic, and not damaging to human
tissues;
b. The design pressure does not exceed 150 psi (1030 kPa); and
c. The design temperature is from -200F (-290C) through 3360F (1860C).
leak test (337.6) is required all joints mentioned above shall also be left
unprimed and unpainted.
If a pressure test is to be maintained for a period of time and the test liquid
in the system is subject to thermal expansion, precautions shall be taken to
avoid excessive pressure.
Records shall be made of each piping system during the testing. These
records shall include:
1) date of test;
2) identification of piping tested;
3) test fluid;
4) test pressure;
5) certification by examiner.
SECTION : PIPING Part IV-Vol IV
FUNCTIONAL SPECIFICATION FOR Spec.No: 04-SP-05
PRESSURE TESTING OF ERECTED PIPING Rev. No: 0
SYSTEM Sheet No: 9 of 9
3.2.1 Deleted
3.2.2 In services like Dry Air, Ethylene etc., small traces of water can cause
problem. Such lines should either be pneumatically tested or Hot Air
drying is to be done after Hydro-test.
3.2.3 If operating fluid in the line is much lighter than testing fluid, the additional
weight of testing fluid may render piping supports (As designed)
inadequate. This will call for additional temporary supports. The typical
examples are FLARE and vapour lines. It is preferable that hydrostatic
testing is avoided in such systems and instead pneumatic testing may be
specified.
3.2.4 Lines carrying highly hazardous/poisionous fluids must have a sensitive
leak test as per the following:
“EXTRACTS”
337.6 Sensitive Leak Test
Piping required to have a sensitive leak test shall be tested by the Gas
and Bubble Formation Testing method specified in Article 10, Section V
of the BPV code, or by another method demonstrated to have equal or
greater sensitivity. Sensitivity of the test shall be at least 10-3 atm-ml/sec
(100 Pa-ml/sec) under test conditions. If a hydrostatic pressure test is
used, it shall be done after the sensitive leak test.