GT#24
1.3.2020
Permit was issued for GT-22 and 24 heater and
panels alone. Heater of GT-24 has been inspected
and found field cables not terminated on the
heater. Measure the heater resistance and found
to be balance. Measure the heater Insulation
Resistance(IR) value was only 340 Kilo ohms. One
number of Spare element has been used in both
the stages. Field cable has been terminated.
Requested SEC to operate the heater in local
mode for IR improvement. Waited for SEC to
energize Heater-24 and run it in local mode.
Similarly Heater-22 was not shut down from
upstream side. Due to which heater tightness
check not carried out on heater side