4.

LED indicators, Wires, Auxiliary Input and Output


Two-door Installation Guide Notes:

Vision: 1 . 0 . 1 1)Meaning of LED indicators: 2)Recommended use of wires:


Date: Oct. 2010
LINK indicator(green): always(green) indicates TCP/IP A Use 2-conducotor power cord
communication is proper;
B Use 6-conductor wire between wiegand reader and control panal

1.Cautions ACT indicator(yellow):its flashing indicates data is in transmitting


through TCP/IP communication.
TX indicator(yellow):its flashing indicates it is sending data through
(RVVP 6*0.5mm) (To choose the proper cord according to the
interface you connect, such as 6,8,10 cord.)

RS485 communication. C Use 4-conducotor lock power cord (RVV 4*0.75mm)


Please note the following cautions.Mis-operation may lead to personal injury or equipment failure: RX indicator(green):its flashing indicates it is receiving data through D Use 2-conducotor switch power cord(RVV 2*0.5mm)
RS485 communication.
1) Do not energize the system before installation is complete; never carry out installation activities when the system is energized. 3)The auxiliary input may be connnected to infrared body detectors,
Auxiliary output indicator(green):always(green) indicates it is in use. alam switches,etc.
2) All peripheral devices must be grounded. Lock indicator(green):always(green) indicates lock is open.
4)The auxiliary output may be connected to door bells,alarms,etc.
POWER indicator(red): always(red) indicates control panel is power
3) It is preferred that all wires run through PVC or galvanized pipes. on.
RUN indicator(green):its flashing indicates the system works normally.
4) It is strongly recommended that the length of exposed part of any connection cable should not be longer than 4 mm. Professional
CARD indicator(yellow):its flashing indicates card is punched on reader.
clamping tools may be used to avoid unintentional contact of exposed wires to avoid short-circuit or communication failure.

5) It is recommended that card readers and buttons should be installed at height of 1.4m-1.5m above ground.

6) It is recommended to use the power supply in case for control panel, and external power supply for each lock.
LINK
Description of normal working state: IN { D
SD card

AUX1
Connect the system to the power supply.If the system works properly,the POWER indicator(red) is lit constantly and the RUN indicator GND Auxiliary input1
D

LAN
Ethernet interface {

AUX2
(green) flashes. IN
GND Auxiliary input2
+12V { Extended
2.Components
GND

1 2 3 4
ACT

EXT
ON
Dip switch 485- RS485 output
485+

5 6 7 8
{ D

BUTTON1
IN
Backup battery Power supply Control panel Advanced Access Control GND
1# Door Button
TX
Key hole
PC RS485 interface
485+
485-
RX BEEP
GLED
{

PC

READER1
GND WD1
B
1#Door
TX WD0
wiegand reader
RX GND
Heat

{
NO +12V

AUXOUT1
dissipation D
hole
Thread hole
Auxiliary output1 COM
NC
BEEP { B

READER2
GLED
D

{
NO

AUXOUT2
Appearance of case WD1 1#Door
Auxiliary output2 COM WD0 wiegand reader
NC GND
+12V

{
SEN
{ D

BUTTON2
GND IN
C

1
LOCK1
NO
2# Door Button
Door1 GND
COM

3.Get through the thread hole NC BEEP


GLED
{ B

READER3
SEN
C WD1
2#Door
Thread hole GND WD0

LOCK2

1
Door2 wiegand reader
NO GND
COM +12V
NC
A
V+
BEEP
GLED
{ B

READER4
LOCK POWER
Power of lock WD1
V- 2#Door
A +12V WD0 wiegand reader
Power of Control panel POWER GND
GND RUN CARD +12V

1 2
Get through the thread hole Fixed case
5.RS485 address setting, Restore factory setting, Terminal resistance setting 7.Equipment communication
Set RS485 address through DIP switch:
1) Place 1-6 on DIP switch are for setting the number of control panel when communicating through RS485, it is adopted for binary coding, The background PC software is able to communicate with the system according to two protocols(RS485 and TCP/IP) for data exchange and
and little endian, the address represented by place 1-6 are shown as figurue(5-1). remote management. The communication cable should be away from high-voltage lines as far as possible. Do not keep the communication cable
in parallel with power cords or bind them together.
2) Before setting the address, please keep the system is power off, Jump place 1-6 to desired status, and the address number shall not be the
same as another one in the network. For example: to set the device number as 39 (39=1+2+4+32), the corresponding RS485 code is 111001,
then Jump place 1,2,3 and 6 at “ON” status.
ON
1.TCP/IP Communication

1 2 3 4 5 6 7 8
PC
3) Place 7 is for restoring factory default settings, Jump it for three times within 10 seconds and restart the system, then all information in
RAM of control panel will be cleared and the system restores factory default settings. Switch

4) Place 8 is for setting terminal resistance when communicating through RS485. Jump it at “ON” status, then it is equivalent to have a
terminal resistance of 120 ohm between 485+ and 485-.
1# control panel 2# control panel n# control panel
Diagram of places of DIP switch. LINK LINK LINK
IN IN
SD card

AUX1
IN SD card

AUX1
SD card

AUX1
GND GND GND

LAN

LAN
LAN
AUX2
IN

AUX2
IN

AUX2
IN
GND GND GND
+12V +12V +12V
GND

1 2 3 4
ACT GND

1 2 3 4
EXT
ON
GND ACT

EXT
ON
1 2 3 4
ACT

EXT
ON
485- 485- 485-

ON 485+ 485+ 485+

5 6 7 8

5 6 7 8
5 6 7 8
BUTTON1
IN
Advanced Access Control

BUTTON1
IN
LINK
Advanced Access Control

BUTTON1
IN
GND Advanced Access Control GND GND
IN
SD card TX

AUX1
TX TX
485+ RX BEEP 485+ 485+ RX BEEP
GND RX BEEP
485- GLED 485- 485- GLED

LAN

PC

READER1
GLED

PC

READER1
PC

READER1
AUX2
IN GND WD1 GND GND WD1
WD1
GND WD0
TX TX WD0 TX WD0
+12V RX GND RX GND RX GND
NO +12V +12V +12V

AUXOUT1
GND

1 2 3 4
ACT NO

AUXOUT1
EXT
ON
NO

AUXOUT1
485- COM COM COM
BEEP BEEP BEEP
485+ NC NC NC

READER2
GLED

READER2
GLED

READER2
GLED

5 6 7 8
NO

AUXOUT2
WD1 NO

BUTTON1

AUXOUT2
IN WD1
Advanced Access Control NO

AUXOUT2
WD1
COM WD0 COM COM WD0
GND WD0
TX NC GND NC NC GND

1 2 3 4
GND

5 6 7 8
485+ RX BEEP +12V +12V
SEN +12V SEN
485- GLED SEN

PC

READER1

BUTTON2
IN

BUTTON2
GND IN

BUTTON2
GND

1
LOCK1
GND IN

1
LOCK1
GND

1
LOCK1
WD1
NO GND NO NO GND
TX WD0 GND
COM COM COM
RX GND BEEP
NC NC BEEP NC BEEP
NO +12V GLED
AUXOUT1

GLED GLED

READER3

READER3
READER3
COM SEN WD1 SEN SEN WD1
WD1

32
BEEP GND
NC WD0 GND

LOCK2

1
GND WD0

LOCK2

1
WD0

LOCK2

1
READER2
GLED NO NO
GND NO GND GND
NO
AUXOUT2

WD1 COM +12V COM +12V


COM +12V
COM WD0 NC NC NC
NC GND BEEP BEEP

16
BEEP

RS485 terminal resistance +12V V+ GLED GLED

READER4
LOCK POWER
GLED V+

READER4
LOCK POWER
V+

READER4
SEN

LOCK POWER
V- WD1 WD1 V- WD1

BUTTON2
GND IN V-

1
LOCK1

+12V WD0 WD0 WD0


NO GND +12V +12V
POWER GND GND POWER GND
POWER

8
COM GND RUN CARD +12V GND GND
RUN CARD +12V RUN CARD +12V
NC BEEP
GLED

READER3
SEN WD1
GND WD0
LOCK2

4 NO
COM
NC
GND
+12V

BEEP
GLED

2
V+

READER4
LOCK POWER

Restore factory setting V-


+12V
GND POWER
WD1
WD0
GND
RUN CARD +12V

1
figure(5-1) 2.RS485 Communication
GND serial line
485- 485

6.Connection of lock
485+ Converter

5、门锁连接
1) Control panel provides lock control output interfaces. For NO lock ,it is open when power is on, and closed when power is off, so COM and
NO interfaces should be used; For NC lock, it is open when power is off, and closed when power is on, so COM and NC interfaces should be 485+ 485+ 485+
485- 485-
used.
GND
485-
GND GND
PC
2) Control panel supports “dry mode” and “wet mode” by setting the jumper, it is “wet mode” when connecting “V+ V-” Input interfaces to
1
2
3
5
4

supply power for locks, please shorten 2-3 and 4-5 . Equipment factory default setting is dry mode. For setting “dry mode” and 1# control panel
2# control panel
“wet mode”, please refer to <<C3-100/200/400 access control panel installation instructions>>. 8# control panel

1 2 3 4 5 6

ON
LINK

3) When the Electrical Lock is connected to the Access Control System, you need to parallel one FR107 diode (equipped in the package) to LINK LINK

SD card IN

AUX1
IN IN
SD card SD card

AUX1

AUX1
GND
GND GND

LAN
prevent the self-inductance EMF affecting the system, do not reverse the polarities.

LAN

LAN

AUX2
IN

AUX2

AUX2
IN IN
GND
GND GND
+12V
+12V +12V
GND

1 2 3 4
ACT

EXT
ON
GND GND

1 2 3 4

1 2 3 4
ACT ACT

EXT

EXT
ON

ON
485-
485- 485-
485+
485+ 485+

5 6 7 8
5 6 7 8

5 6 7 8

BUTTON1
IN
Advanced Access Control

BUTTON1

BUTTON1
IN IN
Advanced Access Control GND
Advanced Access Control GND
GND
TX
TX TX 485+ RX BEEP
485+ RX BEEP 485+ RX BEEP
485- GLED

PC

READER1
LINK 485- GLED 485- GLED

PC

PC
READER1

READER1
GND WD1
GND WD1 GND WD1
TX WD0
WD0 WD0
IN TX TX
SD card
AUX1

RX GND
RX GND RX GND
NO +12V

AUXOUT1
GND NO +12V NO +12V

AUXOUT1

AUXOUT1
COM
LAN

COM COM BEEP


BEEP BEEP NC
AUX2

IN NC NC

READER2
GLED

READER2

READER2
GLED GLED
NO

AUXOUT2
WD1
GND NO NO

AUXOUT2

AUXOUT2
WD1 WD1
COM WD0
COM WD0 COM WD0
NC
+12V NC GND NC GND
GND
+12V
+12V +12V SEN
FR107 GND SEN SEN

7 8
1 2 3 4

ACT
EXT

BUTTON2
ON

GND IN

1
LOCK1
BUTTON2

BUTTON2
IN IN

NO Lock
GND GND

1
LOCK1

LOCK1
NO
485- NO GND NO GND
COM
GND
COM COM
485+ NC BEEP NC BEEP NC BEEP
5 6 7 8

GLED
GLED GLED

READER3
BUTTON1

SEN

READER3

READER3
IN
Advanced Access Control SEN WD1 SEN WD1
GND
WD1
WD0

LOCK2

1
GND WD0 GND WD0

LOCK2

LOCK2
1

1
Enlarged diagram TX
GND NO
COM
GND
+12V
NO
COM
GND
+12V
NO
COM
GND
+12V
485+ RX BEEP NC NC
NC

Diode of lock ports 485- GLED


BEEP BEEP
BEEP

DIP switch
+
GLED
PC

V+

READER4
READER1

LOCK POWER
V+ GLED V+ GLED

READER4

READER4
LOCK POWER

LOCK POWER
V- WD1
GND

-
WD1 V- WD1 V- WD1
+12V WD0
+12V WD0 +12V WD0

LOCK TX WD0 GND GND GND POWER GND

SEN GND POWER GND POWER RUN CARD +12V


RX RUN CARD +12V RUN CARD +12V
GND

- + NO +12V
AUXOUT1

COM
NC
BEEP
LED
GND
READER2

GLED
NO
AUXOUT2

WD1

NO
COM
NC
WD0
GND
+12V 1 Notes:
2
SEN
BUTTON2

GND IN
1
LOCK1

3
NO GND
COM COM
1) Internationally accepted RVSP(shielded twisted-pair) wires should be used for communication to effectively avoid interference. RS485
NC BEEP
GLED 4
READER3

5
SEN WD1
Diode NC GND WD0 communication wires should be connected by means of bus cascade connection.
LOCK2

- + NO GND

LOCK
COM
NC
+12V
Jumper
- + 2)Considering stability of communication, it is recommended the length of RS485 bus is less than 600m
+
BEEP
Lock power V+ GLED terminal
READER4
LOCK POWER

WD1
input
-
V-
FR107 WD0
+12V
GND POWER GND
RUN CARD +12V 3) One RS485 BUS may hold 63 units of control panel, but it is not recommended to connect with more than 32 units access control panels..
NC Lock
4)When the bus is longer than 300m, to enhance the stability of communication, it is necessary to keep place 8 of DIP switches of
the first and the last control panel at “ON” status. As shown in the figure above, place 8 of the DIP switches of units 1# and 8#
ON
is placed at "ON " status.
“Wet mode” wiring diagram of lock connecting with external power supply. 1 2 3 4 5 6 7 8