Features
Accessories include:
• Kit for future unknown utility C/T (provision for • Pull box 24” height
window or bar-type current transformers) • Entry plate (fiber or aluminum)
• Padlock and key interlock attachments • Wooden cable support
• I-Line plug-on modules • Surge protection devices and surge arrestors
for QOTM circuit breakers
• Rodent barriers
• Fire pump circuit breakers
• Seismic certificate qualification
• Ethernet communication cards
on customer metering • Multiple distribution sections can be added
Structures
MDS switchboards are totally enclosed conveniently front accessible with
ASA49 grey finish. All sections are complete with a 1.5 in. H (38 mm. H)
base channel that adds to the 90 in. H (2,286 mm. H) shown below.
Main Section:
• 90 in. H x 14 in. D x 30 in. W (2,286 mm. H x 356 mm. D x 762 mm. W)
for indoor use NEMA Type 1 OR drip protected Type 2
OR sprinkler protected
• 90 in. H x 14 in. D x 38 in. W (2,286 mm. H x 356 mm. D x 965 mm. W)
for indoor use NEMA Type 1 OR drip protected Type 2
OR sprinkler protected enclosures
Distribution Section:
• 90 in. H x 14 in. D x 36 in. W (2,286 mm. H x 356 mm. D x 914 mm. W)
for indoor use NEMA Type 1 OR drip protected Type 2
OR sprinkler protected
• 90 in. H x 14 in. D x 42 in. W (2,286 mm. H x 356 mm. D x 1,066 mm. W)
for indoor use NEMA Type 1 OR drip protected Type 2
OR sprinkler protected
Bussing
The main circuit breaker version of the MDS switchboard comes standard with tin
plated aluminum bus. Silver plated copper bus is optional for any ampacity.
System Voltage
• 208Y/120V 3Ph 4W 60Hz • 120/240 V 1Ph 3W 60Hz
• 480Y/277V 3Ph 4W 60Hz • 480V 3Ph 3W 60Hz
• 600Y/347V 3Ph 4W 60Hz • 600V 3Ph 3W 60Hz
Mains
Source Description Max. System Voltage System Amps Max. Available Fault
(Vac) (A) Current (KA)
Single Main 240 400 & 600 200
800 to 1200 125
480 400 & 600 200
Special louvers on sprinkler 800 to 1200 100
protected switchboard 600 400 & 600 100
800 to 1200 50
Main is Remote 240 All 200
480 All 200
600 All 100
Customer Metering
The new design of customer metering 6 in. H (152 mm. H) allows access to splice
links and cable connections by swinging out. Access to line bus with main and
utility compartment door in place is prevented by considering flanges at the top
and bottom of the box.
The swing out compartment is trapped closed when the main and utility door is
closed and sealed. Serviceable components inside the metering compartment
is gained through a vented access cover.
Utility Metering
Staggered Utility C/T’s, provision is designed to meet any Canadian Hydro
requirement.
• R6MC
• R6L (38W only)
• MV-7 (2 wire)
• MV-7 (3 wire-max 400A)
• JAK-0
• JAD-0
Feeder Compartment
Distribution Section
MDS Switchboards offer as many distribution sections connected by
through bus as required. single row interior has 54in. H (1372 mm. H)space
for mounting circuit breakers in 36in. W(914 mm. W), 14in. D (356 mm. D).
This interior has 27 in. H (686 mm. H) space available above the centre tap
and 27in. H (686 mm. H) space below which can accommodate breakers
up to 800 A
Double row interior in 42 in. W (1067 mm. W), 14in. D (356 mm. D) has a
full 63 in. H (1600 mm. H) of branch height on the right side (narrow side) in
which F, Q, H and J frame breakers up to 250 A can be mounted.
The left side (wide side) has 27 in. (686 mm.) of branch height above and
27 in. (686 mm.) of branch height below center tap of the interior and can
accommodate any I-Line circuit breaker up to 600 A.
*Fire pump Breaker Selection: From 60A up to 250A (Requires bussed auxiliary section)
Optional aluminum or fiber entry plates for cables entering the top of the main enclosure or cables
entering the bottom of an incoming auxiliary section are optional.
Wooden cable support is supplied to meet BC Hydro requirements.
P-frame molded case circuit breakers are available with either a basic ET
1.0I electronic trip system or with a Micrologic trip system.
Breaker Type Ampere Rating Frame Type Interrupting Rating (KA) Max UL/CSA Available Trip
240Vac 480Vac 600Vac Values
300 300-600
350 MG 65 35 18
400 700-800
M-Frame Basic 450
Electronic 500 300-600
600 MJ 100 65 25
700
800 700-800
600-800
PG 65 35 18
1000-1200
P-Frame Basic 600-800
Electronic 600-1200 PK 65 50 50
1000-1200
600-800
PJ 100 65 25
1000-1200
600-800
PL 125 100 –
1000-1200
PG 65 35 18
P-Frame
Micrologic trip PK 65 50 50
circuit breaker 400-1200A 160-1200A
PJ 100 65 25
80% or 100%
Rated PL 125 100 –
LD 25 18 14
L- Frame 80% LG 65 35 18 125, 150, 175,
Micrologic trip 400A or 600A 200, 225, 250,
LJ 100 65 25
circuit breaker 300, 350, 400,
LL 125 100 50 450, 500, 600
LR 200 200 100
LD 25 18 14
L- Frame 100% LG 65 35 18 125, 150, 175,
Micrologic trip 400A 200, 225, 250,
LJ 100 65 25
circuit breaker 300, 350, 400
LL 125 100 50
LR 200 200 100
Basic Electronic
A Fixed Handle Pad-Lock Attachment Default on service entrance switchboard main device. Optional on non service
entrance switchboard
Kirk key interlock Optional for P or M frame
Shunt Trip Optional: 250Vdc, 125Vdc, 48Vdc, 24Vdc, 12Vdc 480Vac, 380Vac, 277Vac,
120Vac, 48Vac, 24Vac
Alarm Switch 1A/1B Form C
Auxiliary Contact 1A/1B Form C, 2A/2B Form C, 3A/3B Form C
*Kirk key interlock and a pad-lock attachment can be installed together on a P frame circuit breaker.
System Amps Lug Type CU Wire Range Wire Qty/ Phase or Neut
400A Al Mechanical 3/0 – 750 kcmil 3
Optional: 350-1000 kcmil
2
1
1 Hole Al Compression 500 – 750 kcmil 2
1
1 Hole Cu Compression 400 – 750 kcmil 2
1
600A Al Mechanical 3/0 – 750 kcmil 3
Optional: 350-1000 kcmil
2
1 Hole Al Compression 500 – 750 kcmil 2
1
1 Hole Cu Compression 400 – 750 kcmil 2
1
800A Al Mechanical 3/0 – 750 kcmil 3
Optional: 350-1000 kcmil
2
1 Hole Al Compression 500 – 750 kcmil 3
2
1 Hole Cu Compression 400 – 750 kcmil 3
2
1000A Al Mechanical 3/0 – 750 kcmil 4
Optional: 350-1000 kcmil
3
2
1 Hole Al Compression 500 – 750 kcmil 4
3
1 Hole Cu Compression 400 – 750 kcmil 4
3
2
1200A Al Mechanical 3/0 – 750 kcmil 4
Optional: 350-1000 kcmil
3
All lugs for use with AI or Cu wire 1 Hole Al Compression 500 – 750 kcmil 4
Cu lugs for use with Cu wire only 3
1 Hole Cu Compression 400 – 750 kcmil 4
3
The PM8000 series meters are compliant with stringent international standards that
guarantee their metering accuracy and power quality measurements. Ideal for
industrial and critical power installations that are responsible for maintaining the
operation and profitability of a facility.
Note: For PM8000 product features please refer to DE13, or Technical Data Sheet PLSED310058EN
Device Mounting Breaker Frame ID Pole Trip Amps (A) Device Mounting Breaker Frame ID Pole Trip Amps (A)
Bolt-on QOB 1 15-60 Plug-on QO 1 15-60
70 70
QOB-VH 1 15-30 QO-VH 1 15-30
QH 1 15-30
40-60
QO 2 15-60
70
70
QHB 1 15-30
80-100
QOB 2 15-60
110-125
70
QO-VH 2 15-60
80-100
70
110-125
80-100
QOB-VH 2 15-60
110-125
70
QH 2 15-30
80-100
QO 3 15-60
110-125
70
QHB 2 15-30
80-100
QOB 3 15-60
QO-VH 3 15-60
70
70
80-100
80-100
QOB-VH 3 15-60
QH 3 15-30
70
80-100
QHB 3 15-30
NQ Accessories:
Note: Total number of QO breakers with ampacity greater than 60A that requires a neutral connection is 12.
EGB 1 15-60
70
Max Volts Breaker Frame ID Pole Qty Trip Amps (A)
EJB 1 15-60
600Y/347 Max. EDB 1 15-60
70
70
EDB 2 15-60
EGB 1 15-60
70-100
70
110-125
EJB 1 15- 60
EGB 2 15-60
70
70-100
EDB 2 15-60
110
70-100
125
EGB 2 15-60
EJB 2 15-60
70 -100
70-100
480Y/277 Max. EJB 2 15-60
110
70-100
125
EDB 3 15-60
EDB 3 15-60
70-100
70-100
EGB 3 15-60
110
70-100
125
EJB 3 15-60
EGB 3 15-60
70-100
70-100
110
125 NF Breaker Accessories:
EJB 3 15-60
70-100 Description
Note: The maximum combined amperage of circuit breakers mounted opposite each other is 170 Amps.
Total number of circuit breakers mounted on NF panel with ampacity greater than 60 A that requires a neutral connection is 12.
The compact size and small footprint of the P-frame circuit breaker permits
high density installations in switchboards. These circuit breakers are available
in 100% rated construction for all unit-mount circuit breakers and up to 800 A
in I-Line circuit breakers to meet a broad range of commercial and industrial
application needs.
For information on other Square D brand PowerPact molded case circuit breakers,
see the Class 611 AND 612 catalogs.
I-Line Double Row distribution section
Note: Not optional for 2 -P H, J and L or L frame breakers that have 250 A sensors.