@® ae MITSUBISHI ELECTRIC CORPORATION PROJECT : MEW PREVENTIVE MAINTENANCE DATE: 30-\\.08 SUBSTATION: MINA ABDULLA ‘C' 432/44kV TEST REPORT No: LTR O ( ‘TEST REPORT FOR 250kVA LOCAL TRANSFORMER WITH OFF LOAD TAPCHANGER Transformer Name Plate Details 250KVA Three Phase Type w ‘SOHz ‘Continuous Rating Indoor Use Insulation Class F BS — 171 Type of Cooling THO00V, HV a Impedance Volt ra 433 Temperature Rise 333A Ambient Temp, Total Weight 260K, pct caceeeeecruleee L-Specification HB 42007 Serial No. 5 Lh AC Test Voltage LV 2.5K Date Feb 1985 ‘Vector Group Dyit Impulse Test Voltage No. of Taps 5 Full Wave HV 5k Present Tap Position 3 Volts 11000 Short Circuit Current Value & Duration HV Winding LV Winding Purchaser's Name Government of Kuwait, MEW VOLT ‘AMPERE ‘CONNECTION 11550 13-14 23-24 3334 ry 11280 13-15 23-25 33-35 14000 42-15 22-25 32-35 40730 12-16 22-26, 32.36 10450 11-16 21-26 31-36 Remove & Clean Filters — | Winding Temp Alarm = Clean Interior — | Winding Temp Trip ea Check All Connections 4’ Interlocking 11kV/Lt Board < ELECTRICAL CHECKS INSULATION CHECK | MEASURED | MINIMUM LV Earth FAAIISL} —_20Ma HV — Earth soooma| — 20Ma Comments :- MELCO ENGINEER: erexgetst te MEW eNoINceR ¢ ae MITSUBISH ELECTRIC CORPORATION PROJECT SUBSTATION : MEW PREVENTIVE MAINTENANCE. MINA ABDULLA ‘C' 132/11kV DATE: 01.12.08 TEST REPORT No: LTR OL. ‘TEST REPORT FOR 250kVA LOCAL TRANSFORMER WITH OFF LOAD TAPCHANGER Transformer Name Plate Details. 250KVA Three Phase [Tipe wy. soz ‘Continuous Rating Tadoor Use insulation Class F BS 171 ‘Type of Cooling HY Tiow Impedance Volt - 43: Temperature Rise 333A Ambient Temp. [Total Weight '2600kq, AC TestVollageHV : 26 L-Specification HB 42007 Serial No. 593633 ‘AC Test Voltage LV 2.5KV Pete 23262 Vector Group Dyit Impulse Test Voltage No. of Taps 5 Full Wave HV T5KV Present Tap Position: 3 Volts, 1000 ‘Short Circuit Curent Value & Duration HV Winding Q.4kA-—-3Sec, LV Winging 8.0kA—-3Sec. Purchaser's Name Government of Kuwait, MEW, VOLT ‘AMPERE CONNECTION 11550, 125, 13-14 23-24 33.34 "7 11280 12.8 13-15 23-25 33:35 11000 13.1 1215 32-35 [10730 135 12-16 22-26 32:36 10450 | 13:8 11-16 21-26, 31-38 Remove & Clean Fitters | Winding Temp Alarm = Clean Interior | Winding Temp Trip - Check All Connections - E Interlocking 1 1kV/Lt Board a“ 2 ELECTRICAL CHECKS INSULATION ; HEGRE MEASURED | — MINIMUM LV -Earth gag 1] 20Ma HV - Earth S000 M1} 20MQ Comments :- MELCO ENGINEER: acettaSAS— MEW enone

You might also like