SITE TEST REPORT 45 MVAr 33 kV Three phase Shunt Reactor MINISTRY OF ELECTRICITY & WATER CUSTOMER: ‘STATE of KUWAIT Contract No.: ME/EWIC/3485-2006/2007 ‘Substation : Kifan ‘W’ 300/132kV Substation SERIAL No. : 07MK191101 MFR'S ORDER No. : 04-MK1911 DATE OF TEST : ‘Apr.8,2009 ~ Apr.9,2009 MELCO AKO SIV Signature: Y.AKAGI Customer's Engineer Signature: we MITSUBISHI ELECTRIC CORPORATION TRANSMISSION & DISTRIBUTION SYSTEMS CENTER SITE TEST REPORT FOR 45MVAr REACTOR Date of test_18 Jun.2009 Serial No. O7MK191104 Dielectric strength of insulating oil Insulating oil was sampled from bottom of tank after oil treatment and the test was carried out in accordance with IEC standard, Sample im | 2a | ot | 4th Sth, 6th. | Average | Oil temp. Result Re | “oo | o | ~| onservaro) 88 90 | 90 90 8B 74 | BBTRV | 3B Good mi) i —_ —__| — | Re! 80 | 8 | 99 8 82 70 | B1.3kV | 38.0 Good (worToM) Criteria : More than 55 kV / 2.5 mm Gap J fre Date of test :17,Jun.2009 Tested by : 7. Forbayash! Witnessed by : Oil leakage test After the reactor compietely assembled, the test will be made by applying a pressure 0,049MPa (0.5kg/cm*) at the top of the conservator for a period of not less than 24 hours. ‘Sample Date | Time —|-—-Pressurer__| Oiltemp.| Resut | Remaks Start 17,Jun.2009 12:00 c.osmpa | 420 | Gooa Finish | 18.Jun2009 | 12:00 0.049MPa 405 CriteriaiNo ol leakage Afi Date of test: 18 Jun.2009 Tested by : 1. zumbayashi Witnessed by : Customer, Ministry of Electricity & Water Contract ME/EWIC/3485-2006/2007 Site Kifan'W' 300/132KV Substation | RE No 1 Drg No. a4 MITSUBISHI ELECTRIC CORPORATION, JAPAN Page 1 SITE TEST REPORT FOR 45MVAr REACTOR Date of test :Apr.8,2009 ‘Serial No,07MK191101 Measurement of reactance Phase | Applied current | Measured voltage | Reactance | Frequency | Oil temp. R 253.48 V (AN) 10.42 A (248.02 V) 23.80 ohm Y 254.35 V (BN) 10.42 A (248,87 V) 23.88 ohm S1AHz 30.0 °C B 251.77 V (CN) 10.42 A (246.35 V) 23.64 ohm Note; Frequency of power source under testing is 51.1 Hz. Reale > ad Then, measured values are corrected to 50Hz. Criteria : Within 5.0 % of factory data Max. Error: 23.88 / 23.69 X 100 = 0.80 % (Factory data: 23.69 ohm) Power supply R Calculation method of R phase (253.48 / (51.1 / 50.0) )/ 10.42 = 23.80 ohm Tested by : YAKAGL << dZgre Witnessed by : Customer| Ministry of Electricity & Water Contract ME/EW/C/3485-2006/2007 Site Kifan 'W' 300/132kV Substation | RE No. Drg No. MITSUBISHI ELECTRIC CORPORATION, JAPAN Page 2 Date of test_Apr.08,2009 SITE TEST REPORT FOR 45MVAr REACTOR Serial No.07MK191101 Measurement of insulation resistance of windings With 5,000 V megger 4 Ambient Oil Temp. ‘temp. Humidity, Results, | 5GQ | 300% 260°C | 41.0% ‘good 100 Insulation resistance (MQ) From 6.6kV to 22, —> 10 | Poor | 0 10 2 30 40 50 60 70 80 Transformer’s oil temperature (°C) Tested by :YAKAGI Zantac Witnessed by : T Customer Ministry of Electricity & Water Contact wt ats Site Kifan 'W' 300/132kV Substation | RE No. Drg No. MITSUBISHI ELECTRIC CORPORATION, JAPAN Page = SITE TEST REPORT FOR 45MVAr REACTOR Date of test :Apr.8,2009 Serial No.07MK191101 Test on bushing current transformer Check result Winding C1. ratio Terminal No. Insulation Result Continuity resistance Poverty Mg) N 4000/4 A St(N), S2(N) Good | 1000 | HEY Goo Hvie) | 787/49~59A | S1(B), $66) Good | >1000 | YU) Good t t — = - J — | — | | Insulation resistance: More than 2 MQ by 500 V megger Tested by : Y.AKAGI ee Witnessed by : Customer) Ministy of Electricity & Water Contract Merew/e%3486.2006/2007 T Site Kifan 'W’ 300/132kV Substation RE No. Drg No. MITSUBISHI ELECTRIC CORPORATION, JAPAN Page 4 SITE TEST REPORT FOR 45MVAr REACTOR Date of test : Apr.8,2009 Serial No.07MK191101 Check of protective devices Device or Equipment Terminal No. Operation check Result No any damage shall be Dial ol level guarge 3301, 3302. checked visually and close Good ‘contact shall be checked Operation check shall be Pressure relief devicege 9601, 9602 made with moving contact | Good switch Not | Gas | 961. 96-01 Operation check shall be _S00d Buhhotz relay Tee cae No2 | Oilflow 96-2 , 9602 made with test Good Tested by : Y.AKAGI a Witnessed by : Customer, Ministry of Electricity & Water | ara werewicngeS esr Site | Kifan'W' 300/132kV Substation | RE No. Org No. | MITSUBISHI ELECTRIC CORPORATION, JAPAN Page £ SITE TEST REPORT FOR 45MVAr REACTOR Date of test_Apr.9.2009 Serial No.07MK191101 Check of protective devices Dial type oll temperature indicator Result: Good | Alarm Trip __ Setting Measured | Setting | Measured OFF Operation test 95.0°C ON |_OFF 405°C ON | 94 87 104 99 Accuracy : - 3.0 ~ 0.0°C Differential : 5.0 ~ 9.0°C Dial type winding temperature indicator Result: Good ‘Alarm __ Trip Setting Measured Setting Measured OFF ON | OFT Operation test a ON 125°C 10497 124 | 117 Accuracy : - 3.0 ~ 0.0°C Differential : 5.0 ~ 9.0°C Tesied by : Y.AKAGL ' Witnessed by Customer Ministry of Electricity & Water Contract ME/EW/G#$485-2008/2007 site | Kifan'W' 300/132kV Substation RE No. Drg No. MITSUBISHI ELECTRIC CORPORATION, JAPAN Page & SITE TEST REPORT FOR 45MVAr REACTOR Date of test :Apr.8,2009 Serial No.07MK191101 Check of auxiliary and protection wiring 7 Insulation Device or Equipment Terminal No. Continuity resistance Result (MQ) Dialtypeol Not | 95°C 2601, 2602 Good | 74000 | Good temperature — indicator | No2 | 105°C 2003, 2604 Good ->1000- Good Dial ype winding] No.1 | 105°C | 26WgD1 , 26Wgd2 | Good | >1000 | Good temperature | indicator =«No2 | 125°C | 26WgD3 , 26WgD4 | Good >1000 | Good Good >1000 Good Dial oil level guarge gar, 330q2, Good 1000 | Good Good >1000 Good Pressure relief devicege 9eD1 9602, | Good | >1000 | Good Not | Gas | 961 , 9601 | Good | >1000 | Good Buhholz relay }———_| —_| "J No2 | Cifow | 962 , 9602 | Good >1000 Good Insulation resistance : More than 2 MQ with 500 V megger Tested by :Y.AKAGI ae Witnessed by 7 Customer Ministry of Electricity & Water Gonract ME/EW/ 2006/2007 Site | Kifan 'W' 300/132kV Substation RE No. Drg No. MITSUBISHI ELECTRIC CORPORATION, JAPAN Page 7 SITE TEST REPORT FOR 45MVAr REACTOR Date of test :6,Jun.2009 Serial No. 07MK191101 Sigunal check to control room Device or Equipment Terminal No. Criteria Result | Remarks Dial type oil No.1 95°C 26D1 , 2602 Alarm Good temperature i indicator No.2 105 °C 26D3 , 26D4 Trip Good Dialtype winding] No.1 | 105°C | 26WgD1 , 26Wgd2 | Alarm Good temperature indicator No.2 125°C 26WgD3 , 26WgD4 Trip Good Dial oil level guarge 3301 : 3302 Alarm: Good Pressure relief devicege 96D1 1 96D2 Trip Good Not | Gas 96-1 , 96-01 Alarm Good Buhholz relay | No.2 Oilflow 96-2 , 96-02 Trip Good Tested by: “7 aaa Witnessed by : Customer) Ministry of Electricity & Water Contact ME/EWICI3465-2006/2007 Site Kifan 'W' 300/132kV Substation RE No. 1 Drg No. i MITSUBISHI ELECTRIC CORPORATION, JAPAN Page SITE TEST REPORT FOR 45MVAr REACTOR Date of test: 28.Jun.2009 Serial No. __O7MK191101 Visual inspection ‘After install the reactor, construction check shall be carried outin accordance with approved drawings. No. ‘Check point Criteria Method Result 1 Fixing of anchor bolts No looseness Visual / Touch ‘Good 2. Line terminals connection Correct connection | Visual / Touch Good | "3. Tank and ground connection Correct connection Visual / Touch Good “4 Oilevel [wm ortereror Visual Good 5 [Oilleakage No leakage Visual / Touch Good 6 Painting Good condition Visual Good 7 /Allvalves Good condition Visual Good | 7-1 Oildrain valve for Reactor tank Close condition Visual Good 7-2. Exhaust valve for Reactor tank Close condition Visual Good | 78 ee ee anPIne VENETO Close condition Visual Good 7-4 [Oil drain valve for radiator Close condition Visual Good 7-6 |Oilfiter valve Close condition Visual Good | 7-6 Connection valve TR to BH Close condition ~ Visual Good 7-7. Valve for Bypass of BH Open condition Visual Good 7-8 [Radiator valve - Close condition | | Good Remarks. Outline drawing No.: SDE40150 Oillevel: 4.2 Oiltemp.: __ 44.0 ) Pe Tested by : a Witnessed by \y Customer Ministry of Electricity & Water Contract No. merypCoxes 2002007 Site Kifan 'W' 300/132kV Substation RE No. 1 Drg No. A MITSUBISHI ELECTRIC CORPORATION, JAPAN Pageq ‘Test Report Stylesheet Version: 1.15 (06-12-19) Test Device: CT-Analyzer Serial Number: DDSI6X Software Version: 2.06 (07-09-17 09:34) ardware Version: 01/00/07/05/00/11 Date/Time: 2009-04-08, 16:15:56 AM File Name: AAKIFAN 45MVA RE-1 xml Status Info: Test successfi ‘Test Settings: Identification: KIFAN 45MVA RE+1 Manufacture MELCO AKO. Type: Bs Serial Number: Us2660001 Core Number: Primary Current -pn: 1000.00 Secondary Current I-sn: 1.0004. Applied Standard: 6044-1 Core Type: Protection CT Class: P20 Frequency: S0Hz Nominal Burden: IS.00VA cos @: 0.800 Burden: 15.00VA cas : 0.800 Resistans Status Info: Test successful LDC test: 1.0008 Results: Remeas.: 3.2312 KDC: 1.0028 V-DC: 3236 ‘Temperature Compensation for Copper: Temeas.: 27.0°C Terets 750°C Reefs 3.8240. Excitation: Status Info: Test successful Overload: no Used Standard: 60044-1 Results: Knee Points: Standard VOL IEC 6044-1 421.1V 22.67mA TEC 60044-6 397.1V 24.44mA, ANSI30 395.9V 20.21ma ANSI 45. 280.0V 13.24mA Kr: 95% Lu; 66.5H 4.1mH Results with nominal Burden: Burden: 15.00VA cos @:0.800 ALF: >29.01 ALFi: 28.03 r 4.2058 Results with operating Burden: Burden: 15.00VA cos : 0.800 ALF: >2901 ALFi: 28.03 Ts: 4.2055 500 200 100 50 20 10 vw 1m 10m 400m A vA Excitation Table: Measured Data UCTrms 5163V SIL6v 494.7 489.1V ICTrms L 3.1774 193.4mH1 LLTSTA 318,1mH 508.5V 992,5mA $59, 1m 506.1V 634.7mA 869.7mHL 503.5V 410.5ma, 499.7 260.7mA 161.2mA, 100.5ma, 482.8V 65.72ma, ATA.SV 45.82mA 462.6 33.50mA 48.2V 26.57mA, 41SSV 21.81mA 358.7V 321.1V 262.1V 17,35mA 15.23mA 12.39ma 147.0V 7.322ma, 106.6V 5.713ma, 85,04V 4.839mA, 65.94 3.989mA, S1S4V 3.293ma, 40.09 2.690mA 32.54V 2.278mA, 26.24V 21.26V 20 13.96V 11.20v 8.969V 71RD 5.696V 4.456V 3.537V 2.708V 2.076 1.583V Liasv 0.998v 1911ma 1.612mA 1.360mA Liséma, 970.79A 819.5HA 694.384 589.5HA 497.2uA, 424.4UA 353.4uA, 300.7HA 255.6uA 210.98 197.94, 14H 23H 3.9H 63H 103H 16.8H 29.4H 479K BA 734H 72.7 08H 65.0H 60.7 S79H 55.0H S2.4H 49.91 479 459 44.1H 23H 40.5H 38.6H 36.4H 34.3H 32.0H 29.8H 27.3H 25.0H 28H 20.1 172 1648 Rati Status Info: Test successful Results with operating Burden: Used Burdei IS.00VA cos @: 0.800 Used 4 100,008, Delta compensation: Ratio 1 Rat 1000:0.9986 Deviation: 0.135% 0.140% 999.93 0.70min ok ‘Test Report Stylesheet Version: 1.15 (06-12-19) CT-Analyzer DDSI6X Software Version: 2.06 (07-09-17 09:34) Hardware Version: 01/00/07/05i00/11 Date/Time: 2009-04-08, 16:41:39 AM File Name: AAKIFAN 45MVA RE-1 WDG.xml Status Info: Test successful ‘Test Settings Identification: KIFAN 4SMV Ar RE-1 Manufacturer: MELCO AKO ‘Type: BCT Serial Number: 1Us2660001 Core Number: Primary Current I-pn: 787.008 Secondary Current }-sn: 5.5008 Applied Standard: 0044-1 Core Type: Protection CT Class: SP 10 Frequency: S0Hz Nominal Burden: 15.00VA cos @: 0800 Burden: 15.00VA cos @: 0.800 Resistance: Status Info: Test successful LDC test: 1.0008 Results: Remeas.: 426.4m0 LDC: 1.0014 V-Dc: 0.427V ‘Temperature Compensation for Copper: ‘T-meas.: 27.0°C Teref: 750°C Reref: 5046m2 Excitation: Status Info: Test successful Overload: Results: Knee Points: Standard Vo TEC 60044-1 59,28V 133.2mA TEC 60044-6 55,52V 194.3mA ANSI 30. $5.25V 113.6mA ANSI 4S 42.02V 80,51mA Kr: 94% Lu: 16H Ls: 415.5uH Results with nominal Burden: Burden: 15,00VA cas @: 0.800 ALF: >13.92 ALFi: >14.18 Ts: 1,728 Results with operating Burden: Burden: 15.00VA cos : 0.800 >13.92 >14.18 1.7285 70 50 30 20 vw 00H 1m 10m 100m A Excitation Table: Measured Data UCTrms 1CTrms—L. T4.18V 3.823 222mH TBSIV 2.797 31.7mH TB36V 2,023A 45.2mH T28IV 1.449A 64.3mH TLATV 1.0404 91.3mH 71,39V 742.6mA 129.4mH 70.48 $37.3mA 183.0mH 69.41 395.0mA 258,3mH 68.08 295.0mA 362.8mH 66.38V 226.9mA 506.7mH 64.09V 177.7mA 700.6mH 60.87V 143.0mA 952.8mH S621V116.8mA 13H 48.67V 94.90mA 16H 38.30V 72.82mA 7H 2432V 51.88mA SH 1742V 40.44nA 14H 13.98V 35,02mA 13H 9.807 27.11mA 1.2 7.125V 21.26mA 1.1 5320V 16.85mA 1.1 3.910V 13.18mA 10H 3.006V 10.69mA 944.2mH 2.276V 8.607mA 887.9mH LTITV 6.907mA 830.1mH L.278V 5.558mA 770.3mH 0.998V 4.708mA 71 .2mH. Rati Status Info: Test successful Results with operating Burden: Used Burden: 15.00VA cos : 0.800 Used I-p: 787.00 Delta compensation: Ratio | 787:5.6450 2.63% 2.622% 139.03 3.50min ok

You might also like