Energising Inrush Current Transients in Parallel-Connected Transformers
Energising Inrush Current Transients in Parallel-Connected Transformers
Paper 1189
Paper 1189
T1 T2
Paper 1189
Paper 1189
Inrush Current Impact for Increasing Number of studies show that by increasing the number of already
Already Energised Transformers energised transformers, the peak of the sympathetic
inrush appears to increase proportionally. The duration of
There are several different possible scenarios of the transient inrush is longer as well.
energisation. Simulations were carried out to study the
difference from two cases: LABORATORY EXPERIMENT VALIDATION
a) Case 1: Energise T3 with T1 and T2 already energised
b) Case 2: Energise T2 and T3 with T1 already energised
Network Topology
From both cases, the inrush currents are examined to
determine the worst case energisation.
Many previous studies have been carried out to explain
the sympathetic inrush phenomenon and its derivation of
the mathematical formulations. However, it would be of
interest to conduct laboratory experiment to observe this
phenomenon. Therefore, a small scale experiment was set
up in the laboratory to measure the transients and
compare the results to that of simulation.
-50
-100
-150
0 1 2 3 4 5 6
By referring to Figure 8 (a) and (b), the peak of Figure 11 Inrush Current Transients for energising T2 and T3
simultaneously with initially energised T1
sympathetic inrush is -81 A for two already energised
transformers whereas it is larger at -112 A for one already
Next, two transformers have been set up to observe the
energised transformer. Simulation studies were then
inrush transients occur in the system. Fig. 10 shows the
further carried out to observe the impacts of number of
sympathetic and magnetising inrush between 2 parallel-
already energised transformers on the peak of
connected transformers. The result is very similar to the
sympathetic inrush. Referring to Fig. 9, these simulation
Paper 1189
PSCAD simulation, thus it validates the transformer study," in IPEC, 2012 Conference on Power &
model. However, the PSCAD simulation result decays Energy, 2012, pp. 461-467.
faster as compared to that obtained from the experiment. [3] P. Jinsheng, A. Swee Peng, L. Haiyu, and W.
It may be due to the different damping within the system. Zhongdong, "Comparisons of normal and
sympathetic inrush and their implications toward
Subsequently, T3 is connected in parallel to T1 and T2. system voltage depression," in Universities
T2 and T3 are simultaneously energised with T1 already Power Engineering Conference (UPEC), 2010
in operation. The result is shown in Fig. 11 and it can be 45th International, 2010, pp. 1-5.
observed that the duration of the transient inrush is [4] S. Du, Z. Weilu, and Z. Wang, "Research on
longer. This verifies the PSCAD model. Principle and Countermeasures of the
Transformer Sympathetic Inrush," in Power and
Energy Engineering Conference, 2009.
CONCLUSION APPEEC 2009. Asia-Pacific, 2009, pp. 1-4.
[5] A. A. Mohd Zin, A. H. Hana, and S. P. Abdul
Through this paper, the energising inrush current Karim, "Sympathetic Inrush Phenomenon
transients in parallel-connected transformers are Analysis and Solution for a Power
presented; both in simulation modelling and laboratory Transformer," International Review on
work. It is observed that: Modelling and Simulation (IREMOS), vol. 4, pp.
601-607, April 2011 2011.
a) Sympathetic inrush will occur if the other [6] H. A. Halim, B.T. Phung, and J. Fletcher,
transformers are connected in parallel connection or "Investigation and Modelling of Sympathetic
in the same voltage-level interaction. Inrush Due to Transformer Energization,"
b) The inrush current when energising transformers presented at the International Conference on
simultaneously is more severe with initially energised Smart-Green Technology in Electrical and
transformer connected to it. Information Systems, Bali, Indonesia, 2014.
c) Increasing the number of already energised [7] M. Rioual and J. C. Reveret, "Energization of
transformers will increase the sympathetic inrush step-up transformers for wind-farms: Modeling
current transients. and its validation by tests performed on a 10
MW site," in Power & Energy Society General
In general, all the model representations and transient Meeting, 2009. PES '09. IEEE, 2009, pp. 1-7.
response waveforms show good similarity to those [8] "IEC- 60076-16 Power Transformers - part 16:
obtained from experiment. Transformer behaviours are Transformers for wind turbine applications," ed,
confirmed by experiment as well as simulation of 2011.
sympathetic phenomenon when several transformers are [9] A. Pors and N. Browne, "Modelling the
involved. The practical results also support the theoretical energisation of a generator step-up transformer
predictions. from the high voltage network," in Power
Engineering Conference, 2008. AUPEC '08.
Australasian Universities, 2008, pp. 1-5.
ACKNOWLEDGMENT [10] T. Ma and A. Cadmore, "System studies of
voltage dips resulting from energisation of MV
wind turbine transformers," in Electricity
The authors would like to acknowledge the assistance by
Distribution, 2005. CIRED 2005. 18th
Zhenyu Liu with the experimental work, the transformers
International Conference and Exhibition on,
from Ausgrid, the financial support by Postgraduate
2005, pp. 1-5.
Research Support Schemes (PRSS) UNSW and the
[11] O. Ipinnimo, S. Chowdhury, and S. P.
student sponsorship by the Malaysian Government
Chowdhury, "Voltage dip mitigation with DG
together with Universiti Malaysia Perlis.
integration: A comprehensive review," in Power
Electronics, Drives and Energy Systems
REFERENCES (PEDES) & 2010 Power India, 2010 Joint
International Conference on, 2010, pp. 1-10.
[12] C. Manitoba HVDC Research Centre Inc. (5
[1] WG C4.307, "Transformer Energization in
November). Wind Farm Transformer Inrush
Power Systems: A Study Guide," CIGRÉ
Studies: PSCAD Application Notes. Available:
Technical Brochure 568, February 2014.
https://hvdc.ca/uploads/ck/files/Application_Not
[2] L. Chengxi, C. Zhe, C. L. Bak, L. Zhou, P.
e_-
Lund, and P. Ronne-Hansen, "Transient stability
_Wind_Farm_Transformer_Inrush_Studies.pdf
assessment of power system with large amount
of wind power penetration: The Danish case