You are on page 1of 6

2019 IEEE PES Innovative Smart Grid Technologies Asia

Research on the load model and characteristics of


inverter-fed motors for transient stability analysis
Baorong Zhou, Siyu Lu Haoqin Zhan, Fang Zhao, Zhaobin Du
Electric Power Research Institute School of Electric Power
China Southern Power Grid South China University of Technology
Guangzhou, China Guangzhou, China
zhoubr@csg.cn; lusy@csg.cn 371129902@qq.com; epduzb@scut.edu.cn

Abstract—Nowadays, the applications of inverter-fed motor voltage stability. Besides, literature [9] proposed using the
(IFM) are largely increasing. Due to load characteristics of the static equivalent model of induction motor in the PV curve
IFM different from that of the asynchronous motor (AM), if the calculation of power system. However, at present, there are
traditional load model based on AM is routinely used, it will few researches on the load model of IFM and the influence of
challenge the credibility of the analysis of system transient IFM on power system stability. In [10], according to a motor
stability. Therefore, this paper adopted both experimental and unit, they compared the differences between IFM and
digital methods to study steady-state and dynamic power common asynchronous motor (AM) in load characteristics
characteristics of IFM, and construct the dynamic model of during system voltage decline through simulation, and the
IFM. First, the widely-used IFM based on rotor-vector control is
results show that the IFM had smaller reactive power demand
established on MATLAB platform. An actual IFM is tested in a
during voltage dip. In [11], they built a mathematical model of
self-designed physical system accordingly. Finally, the steady-
state model and the multi-stage mathematical model in dynamic
IFM with PWM frequency converter, analyzed its steady-state
process are built for IFM. The simulation results show that the and dynamic load characteristics through simulation and
IFM will not produce power rush after system shocks, which is compared them with the load characteristics of traditional
more beneficial to system voltage recovery. The proposed induction motor, but they did not further analyze its
dynamic load model of IFM could help the transient stability application as a load model in transient stability analysis. In
analysis task. [7] and [12], they studied the load characteristics of IFM
online, and pointed out that the reactive power demand
Index Terms--Asynchronous motor; Inverter-fed motor; Load increased during voltage decline. In the next step of dynamic
model; Load power characteristics; Motor experiment process, [13] conducted voltage sag experiment on single-
phase AM, and found that in the state of motor stalling, when
I. INTRODUCTION the voltage recovered to normal level, it will generate
extremely high active power and reactive power demand. In
The induction motor is the most common dynamic load in [4] and [14], without considering the low-voltage protection of
power system, and it accounts for more than 90% of industrial frequency converter and the motor stall, they simulated the
load [1]. Its steady-state and dynamic load characteristics have active power and reactive power characteristics of IFM, and
significant influence on the operation of power system. pointed out that the active power and reactive power quickly
Frequency converter has high performance and outstanding declined to 0 at the moment of voltage drop and it would
energy conservation characteristics, and the energy saving rate generate short active impact after voltage recovery, and they
of motor system that uses induction motor can even reach also believed that the load of IFM is seen as constant-
40%~60% [2]. With the fast development of power electronic impedance. In [15], they believed that the IFM may be the
technology, it has become more popular for the induction parallel of induction motor and constant-power load. In
motor load to adopt frequency converter for power supply [3], summary, so far, researchers have different ideas on the model
[4]. According to optimistic estimation, in the next 10 years or of IFM, and the research space for the application of IFM
so, the capacity proportion of inverter-fed motor (IFM) will model to transient stability is large.
increase to 70% [5], [6]. Compared to the traditional induction
motor, the induction motor that adopts the PWM frequency In the future, when many IFMs are employed in the power
converter for power supply has different load characteristics grid, the main component of load characteristics will change.
[6], and it will also generate different influence on the If traditional dynamic load model based on AM is still used, it
operation and control of power system. will generate uncertain influence on the transient stability
calculation results of power system. The load characteristics of
Literatures [7] and [8] studied the influence of the load IFM involve both steady-state and dynamic characteristics.
characteristics of induction motor on the system transient The former was studied and used to build steady-state model

The work is supported by Key Science and Technology Project of China


Southern Power Grid (No.CSGTRCK163007) and the National Natural
Science Foundation of China (No.51577071).

978-1-7281-3520-5/19/$31.00 ©2019 IEEE 412


first, and the latter to build the multi-stage load model for the converter were used. The frequency converter has the rated
dynamic process of IFM and to study its influence on the power of 5.5kW, which has under-voltage and over-voltage
stability of power system. In this paper, for the AM with protection functions, and when the input voltage is lower than
PWM frequency converter, we built an experimental platform 0.75pu, the under-voltage protection of frequency converter
to analyze its steady-state and dynamic load characteristics. will activate and remove the AM from the power grid. The
While the widely-used IFM based on rotor-vector control is physical system and the structure charm of experiment are as
established on MATLAB platform, and comprehensive shown in Fig.2 and Fig.3 respectively.
simulations with and without low-voltage protection of IFM
were conducted to compare and analyze the results from the By adjusting the voltage setting value of power supply
experiment [16]. It has laid down the basis to explore the load within 0.75pu-1.2pu, we measured and recorded the static
model of power system during the transient process, and to characteristics (power-voltage curves) of the AM and IFM
supply available IFM model for transient voltage stability respectively, which will be used in the later section.
study while using direct method in future.
Dynamometer
II. STEADY-STATE CHARACTERISTICS AND LOAD MODELS
Asynchronous
In this section, we analyzed the difference between IFM Motor
and common AM in characteristics, and conducted necessary Power
simulations and experiments. In the experiment, the regular Measurement
three-phase AM and frequency converter were adopted to
represent the IFM. In MATLAB platform, we built an IFM
model with rotor flux vector control as shown in Fig.1, and the
parameters of three-phase AM in the model are as shown in
Table I.

Three-phase
TABLE I. PARAMETERS OF THREE-PHASE AM IN SIMULATION MODEL AC source Variable
Frequency
Rated voltage UN (V) 380 Stator resistance (Ω) 0.435 Drive
Rated speed nN (rpm) 1400 Rotor resistance (Ω) 0.816
Figure 2. Experimental system with AM, frequency converter,
Stator and rotor dynamometer and power measurement
Rated frequency fN (Hz) 50 2
inductance (mH)
Excitation mutual
Rotational inertia (kg·mg2) 0.19 69 Three-phase
inductance (mH)
AC source
Obtain active power/reactive
power waveforms
Breaker

Frequency converter

Three-phase Obtain torque, speed and


asynchronous motor output power waveforms

Dynamometer

Figure 1. IFM model with rotor flux vector control


Figure 3. Experimental structure charm of IFM

TABLE II. PARAMETERS OF THREE-PHASE AM ON EXPERIMENT


SYSTEM A. Static load characteristics of AM
During the experiment and simulation process, the AM
Rated power PN (kW) 2.2 Power factor cosϕ 0.85 was measured in steady-state with a frequency of 50Hz. The
Rated voltage UN (V) 380 Motor stator resistance (Ω) 1.459 voltage was regulated with the voltage regulator, and the
obtained static power-voltage curves are as shown in Fig.4 and
Rated speed nN (rpm) 2875 Motor rotor resistance (Ω) 1.589 Fig.5 respectively.
Motor stator and rotor
Rated torque TN (N⋅m) 7.3
inductance (mH)
339.8 According to Fig.4 and Fig.5, we can see that on both
experimental curve and simulation curve, when the voltage
In the experiment, the CC100KS/F dynamometer, the changed slowly, the AM kept steady-state operation, and the
YE3-90L-2 AM and the AMB100_5R5G_T3 frequency

413
active power presented small change, which was nearly
constant, and it was approximately seen as constant power
load. In comparison, the change of reactive power was more
significant, and with the voltage decline, the reactive power
presented obvious decrease.

Figure 7. Emulational power-voltage curves of inverter-fed motor

According to Fig.6 and Fig.7, we can see that when the


voltage changed slowly between 0.8pu and 1.2pu, the IFM
kept steady-state operation. Both active power and reactive
power were nearly constant, and so, they were approximately
Figure 4. Experimental power-voltage curves of AM considered as constant-power load. Noticeably, when the
voltage declined to 0.75pu, the speed had obvious change, and
the change of power is too large to use the same constant-
power pattern in higher voltage.
By comparing Fig.5 and Fig.7, we can see that when
voltage dropped and still operated in the range above 0.8pu,
the active powers of both AM and IFM increased, and this
negative characteristic will aggravate insufficiency of power at
system failure, which is not good to system recovery. When
the voltage declined from 0.8pu to the removal voltage of
frequency converter, the active power of IFM turned to
decrease. In addition, due to the effects of frequency
converter, the IFM consumes smaller reactive power. During
failure, this power characteristic of IFM is helpful to lessen the
burden of system recovery than that of AM.
Because the frequency converter has low-voltage
Figure 5. Emulational power-voltage curves of AM protection, when the voltage of power supply to frequency
converter is smaller than 0.75pu after voltage regulation, the
B. Static load characteristics of inverter-fed motor frequency converter will start low-voltage protection, and the
motor will be automatically removed.

C. Load models under steady-state operation


Under steady-state operation, motors can be expressed by
static load model such as power function. Because power
function needs less parameters, it has higher precision [17].
During the actual operation, the frequency of power grid
presents small fluctuations, so this static model only considers
the voltage characteristics. The static model expression [12] of
power functions are as follows:
p
P = PU
0 (1)

Q = Q0U q (2)
in which, P0 is the reference power of static load. Q0 is the
Figure 6. Experimental power-voltage curves of inverter-fed motor
reference reactive power of static load. U is the per-unit value
The static power-voltage curves of IFM are as shown in of load terminal voltage. p is the voltage exponent factor of
Fig.6 and Fig.7, respectively. During the experiment and active power. q is the voltage exponent factor of reactive
simulation process, the steady-state operation of IFM was also power. According to the simulation data, the parameters of
maintained. static model are given in Table III and Table IV.

414
TABLE III. STATIC LOAD MODEL OF AM the input voltage went down from 0.47pu, its active power
Voltage (pu) p q Voltage (pu) p q
quickly and monotonously declined, while the reactive power
firstly increased and gradually decreased. During the voltage
0.9 -0.0610 1.3766 1.1 -0.0388 1.5971
recovery, the active and reactive powers of motor both
0.8 -0.0859 1.1907 1.2 -0.0355 1.6631 presented exponential growth, which caused power rush.

TABLE IV. STATIC LOAD MODEL OF IFM

Voltage (pu) p q Voltage (pu) p q


0.9 -0.2289 -0.7195 1.1 -0.0380 -0.0312
0.8 -0.2213 -0.7915 1.2 -0.0298 -0.2373

According to Table III and Table IV, it can be seen when


the voltage dropped to different levels, the obtained p and q
values were also different. The p values of AM and IFM were
negative and small, which indicates that when the voltage at
power grid side declined, the active powers of both motors
increased slightly, but they can still be regarded as
approximate constant-power loads. The q of AM was positive
and higher than 1, while the q of IFM was negative and small.
This is because during voltage decline, the power factor at the
Figure 9. Reactive power-voltage characteristic curves of AM
input side of frequency converter declined accordingly, and its
power compensation was weakened. At this moment, the
reactive power demand increased, and this was different from B. Dynamic load characteristics of inverter-fed motor
the load characteristic of AM. a) Low-voltage protection action
Considering the low-voltage protection function, the
III. DYNAMIC CHARACTERISTICS AND LOAD MODEL
voltage decline at power grid side will cause tripping of
In order to further study the load characteristics of AM and frequency converter. After tripping, it generally requires
IFM, we investigated the change of active and reactive powers manually restarting the IFM, so that the power is considered
of AM and IFM during the voltage drop and recovery, and as 0 after voltage recovery. In this case, the active and reactive
discussed the difference of two models in dynamic powers of IFM under various voltages are shown in Fig.10.
characteristics.

A. Dynamic load characteristics of AM


The input voltage slowly changed from 1pu to 0, and then
recovered to the rated value, and the whole process of change
lasted for 1s. The active and reactive characteristic curves of
AM are as shown in Fig.8 and Fig.9.

Figure 10. Power characteristic curves of IFM with low-voltage protection

According to Fig.10, we find that within normal operation


scope, the active and reactive powers of IFM gradually
increased with the decline of voltage, but the change was
Figure 8. Active power-voltage characteristic curves of AM small, and the IFM could still be regarded as constant-power
load. When the voltage declined to around 0.8pu, it triggered
According to Fig.8 and Fig.9, it can be seen that the AM the low-voltage protection of frequency converter, and the
stalled under low voltage (around 0.47pu). When the input IFM was automatically turned off.
voltage was higher than 0.47pu, the changes of active power
and reactive power were not salient. In this process, the AM b) Low-voltage protection inaction
can be approximately regarded as constant-power load. When

415
When the low-voltage protection of IFM malfunctioned, or situation, the low-voltage protection of IFM does not operate,
the duration when system voltage lower than the protection and the motor fails to recover from the stall state during
setting value doesn’t reach the limit, the frequency converter voltage recovery, the IFM has obvious lower power demand
would not remove motor from the power grid. In this case, the due to the effects of frequency converter than that of AM,
active and reactive powers of IFM under various voltages are which is beneficial to the system transient stability.
shown in Fig.11 and Fig.12.
C. Dynamic load model
To sum up, the AM and IFM have different dynamic
characteristics, which have different states during processes of
voltage disturbance. According to different states of IFM, the
multi-stage mathematical model in dynamic process can be
built in segments. By observing Fig.11 and Fig.12, polynomial
function is preliminarily used for each stage.
During the initial phase of voltage recovery, both the
active and reactive powers of IFM were 0, and because the
duration was short, this phase can be ignored. Therefore,
during the voltage decline and recovery process, the model
can be approximately divided into four phases: Phase1,
Phase2, Phase3 and Phase4. In Phase1 (P1,Q1) and Phase4
(P4,Q4), power expressions are constants, while those are
linear functions in Phase2 (P2,Q2) and Phase3 (P3,Q3).
Figure 11. Active power-voltage curves of IFM without low-voltage Actually, if the better control of IFM could produce enough
protection support to load, IFM may recover successfully after voltage
recovery, then the model of Phase3 and Phase4 could be
adjustable. The phase diagram is as shown in Fig.13.

U (pu)

1 (P4,Q4)
U2 (P1,Q1)
U1
(P2,Q2) (P3,Q3)

0
t (ms)
Figure 13. Section diagram of IFM load model
Figure 12. Reactive power-voltage curves of IFM without low-voltage
protection In which, U1 represents the stall voltage of IFM, and in
According to Fig.11 and Fig.12, it can be seen that when Fig.13, U 2 is the voltage mark when the power declines to 0.
the voltage declined to 0.8pu or below, the active and reactive Each expression of phase is as shown in Formulas (3)-(6):
powers decreased and presented nearly linear relation with the
voltage. Before the voltage increased to 0.1pu, both the active  P1 = a0
 U1 ≤ U ≤ 1, U t ≤ U t −1 (3)
and reactive powers of IFM were 0. Then, with the increase of Q1 = b0
voltage, the active and reactive powers increased and then
linearly declined to 0. This reason is during the voltage  P2 = a1U + a2
recovery process, due to the constant-torque load the IFM  0 ≤ U ≤ U1 ,U t ≤ U t −1 (4)
Q2 = b1U + b2
inherited, the IFM didn’t recover from the stall state. The IFM
thus had lower active power and reactive power demands  P3 = a3U + a4
compared to the AM. As for nonconstant-torque load, further  0 ≤ U ≤ U 2 , U t > U t −1 (5)
research will be conducted in future. Q3 = b3U + b4
From the perspective of power grid, high active power and  P4 = 0
reactive power demands will be an obstacle when the system  U 2 ≤ U ≤ 1,
,U t > U t −1 (6)
has just recovered from voltage failure. If the IFM is removed Q4 = 0
at low voltages and restarts when the voltage recovers to In which, U t and U t −1 represent the voltage of t th time
nominal value, the power will gradually and smoothly
stamp and the voltage of t − 1 th time stamp.
increase, which will not generate high impact. In another

416
According to the simulation results in MATLAB Compared to AM, the IFM generated small power demand
environment, we set U1 = 0.8 , U 2 = 0.9 , and the following during the power recovery process, which was more beneficial
parameters can be obtained by MATLAB cftool: to the recovery of power grid voltage. By adopting the load
model of IFM, it could more accurately simulate the actual
operation of power grid. In this paper, we combined
TABLE V. PARAMETERS OF MULTI-STAGE MATHEMATICAL MODEL experiment and simulation to verify the reliability of
a0 10.807 b0 1.4039
simulation model, which ensured the accuracy and credibility
a1 b1
of simulation results. The built dynamic process of IFM was a
11.78 1.638
multi-phase load model, which has expanded current load
a2 0 b2 0 model, and it has laid down the basis to evaluate the stability
a3 -2.551 b3 -0.3567 of power system. In the future, more accurate dynamic load
a4 2.297 b4 0.2936 model will be built according to the load characteristics of
If the low-voltage protection action of frequency converter IFM during the transient process.
is considered, then P2 = P3 = P4 = Q2 = Q3 = Q4 = 0 .
REFERENCES
In system transient stability analysis, the analytical load [1] L. Cao, G. Li, H. Wu. Impact of induction motor model on transient
model is needed when using Lyapunov's Direct Method. The stability of East China Power Grid[J]. Power System
current proposed IFM model would be potentially employed Technology,2007(05):6-10(in Chinese).
by this kind of analysis methods although it is in terms of [2] M. Gao. Talking about Inverter Air Condition[J]. Electronics World,
piece-wise linearity. Traditional Power system plus this non- vol. 6, pp. 9-11, 2004.
[3] H. Cui, X. Jia, E. Shang. The inverter used economic type 3 filtering
continuous model could be considered as the Switched System methods of comparing[J]. Shanxi Electric Power, 2010(9): 59 -62 (in
[18] and relative work on stability analysis of such systems Chinese).
have been reported [19]. [4] S. Zhang, D. Li, J. Hu. The principle and application of energy saving
technology of variable frequency speed control technology[J]. Fan and
IV. CONCLUSION Water Pump, 2009(1): 83- -86 (in Chinese).
[5] Z. Wang, T. Wang. The Market and Load of AC Motor with Speed
In this paper, we analyzed and compared the load Regulation[J]. Electrical Technology, vol. 5, pp. 5-13, 2007.
characteristics and load model of AM and IFM. We observe [6] W. Shen, J. Zhou, Y. Tang, Q. Chen. Analysis on Influence of Variable
that with the decline of voltage, the active power presents Frequency Driving Equipment on Parameters of Load Model[J].
Guangdong Electric Power, vol. 29, no. 9, pp. 58-62, 2016.
small change, which can be seen as approximate constant- [7] M. Z. El-Sadek, F. N. Abdelbarr. Effects of induction motor load in
power load. When studying the load model during the provoking transient voltage instabilities in power systems[J]. Electric
dynamic process of IFM, we found that these two motors Power Systems Research, 1989, 17(2):119-127.
presented different dynamic characteristics, and the main [8] H. Sun, X. Zhou, R. Li. Influence of induction motor load parameters
differences include: on power system transient voltage stability[J]. Power System
Technology, 2005,29(23): 1-6 (in Chinese).
• When the voltage was lower than a certain level, e.g. [9] X. Wang, Z. Han. The PV curve and motor static characteristics
0.5pu, the AM stalled and the active power quickly analysis of power systems[J]. Automation of Electric Power Systems,
2004,28(2): 32- -36 (in Chinese).
declined, while the reactive power firstly increased [10] X. He. Study on the influence of variable frequency air conditioner on
and then gradually decreased. As for IFM, when the power grid voltage stability[D]. Zhejiang University, 2013.
voltage declined to around 0.8pu, it triggered the low- [11] Y. Li. Load characteristics of the induction motor with inverter[J].
voltage protection of frequency converter, and the Power System and Clean Energy, 2015, 31 (3) :124-128 (in Chinese).
IFM was automatically turned off, and both the active [12] Q. Gu, G. Chen, H. Wu, M. Zhu. Simulation research on grid-
connected operation of variable frequency drive equipment[J].
and reactive powers became 0. If low-voltage
Guangdong Electric Power, 2015, 28(07), pp.68-71+77.
protection is discarded, when the voltage decreased [13] NERC. Dynamic Load Modeling Tech Ref 2016-11-14 – FINAL[R].
from 0.8pu, the power presented approximately linear North American Electric Reliability Council.2016.
decline at a gentler slope compared to that of the AM. [14] Q. Wang. Load characteristics-oriented control strategy for air
conditioners during voltage sags[D]. Zhejiang University, 2018.
• After the voltage recovery, AM and IFM suffering [15] Z. Li, J. Zhou, W. Shen. Study on load model of hybrid dragging
constant-torque load failed to recover from the stall equipment[J]. Shanxi Electric Power,2016,44(01), pp.21-24.
state. Due to the effects of stall, the active power and [16] CIGRE. Working Group C4.605. Modelling and Aggregation of Loads
in Flexible Power Networks[R]. International Council on Large Electric
reactive power of AM both presented exponential Systems.2014.
growth, which would cause power rush. For IFM, due [17] L. Jiao, B. Bai, and H. Li. "The calculation of ampere force on electric
to the effects of frequency converter, the active and power transformer under the short circuit situation." in International
reactive powers increased and then linearly declined Conference on Electrical Machines & Systems IEEE, 2008.
to 0. Actually, if the better control of IFM could [18] D. Liberzon, Switching in Systems and Control. Boston, MA:
produce enough support to load, IFM may recover Birkhauser, 2003.
[19] A. A. Ahmadi and P. A. Parrilo, “Non-monotonic Lyapunov functions
successfully and the load model and characteristics for stability of discrete time nonlinear and switched systems,” in
could be obtained by the same method used in this Proceedings of the Conference on Decision and Control, 2008, pp.614–
paper. 621.

417

You might also like