Professional Documents
Culture Documents
Domestic and Treated water Pumps Head - Lifting Stage 1 (From B3 To S1) Approved by:
Pipe Friction
Accessories Friction
Static Head
Estimated Power = g x Q x H
pump h x motor h
= 3.3 Hp
VALVE LOSSES IN EQUIVALENT FEET OF PIPE
Y-Type Y-Type
Swing
Nominal Globe 60º-Y 45º-Y Angle Gate Strainer Strainer
Check Flanged End Screwed End
Pipe Size
(mm)
3/8 17 8 6 6 0.6 5 - -
1/2 18 9 7 7 0.7 6 - 3
3/4 22 11 9 9 0.9 8 - 4
1 29 15 12 12 1 10 - 5
1 1/4 38 20 15 15 1.5 14 - 9
1 1/2 43 24 18 18 1.8 16 - 10
2 55 30 24 24 2.3 20 27 14
2 1/2 69 35 29 29 2.8 25 28 20
3 84 43 35 35 3.2 30 42 40
3 1/2 100 50 41 41 4 35 48 -
4 120 58 47 47 4.5 40 60 -
5 140 71 58 58 6 50 80 -
6 170 88 70 70 7 60 110 -
8 220 115 85 85 9 80 150 -
10 280 145 105 105 12 100 190 -
12 320 165 130 130 13 120 250 -
14 360 185 155 155 15 135 - -
16 410 210 180 180 17 150 - -
18 460 240 200 200 19 165 - -
20 520 275 235 235 22 200 - -
24 610 320 265 265 25 240 - -
Approved by: