Professional Documents
Culture Documents
0K4287-D SG 070-6.8G FORD INDUSTRIAL H-100 27 Nov 2017 PDF
0K4287-D SG 070-6.8G FORD INDUSTRIAL H-100 27 Nov 2017 PDF
8L | 70 kW
INDUSTRIAL SPARK-IGNITED GENERATOR SET
EPA Certified Stationary Emergency
*EPA Certified Prime ratings are not available in the US or its Territories
Digital H Control Panel—Dual 4x20 Display • 0.2 msec High Speed Remote Trending • Battery Voltage
• Alarm Information Automatically Annunciated • Alarms and Warnings Time and Date Stamped
Program Functions on the Display • Snap Shots of Key Operation Parameters During
• Programmable Crank Limiter Alarms and Warnings
Full System Status Display •
• 7-Day Programmable Exerciser Alarms and Warnings Spelled Out (No Alarm Codes)
• Special Applications Programmable Logic Controller
• Power Output (kW)
• RS-232/485 Communications
• Power Factor
• kW Hours, Total, and Last Run
SPEC SHEET
• Waterproof/Sealed Connectors
• Oil Pressure
○ 10A UL Battery Charger ○ GenLink® Communications Software (English Only) ○ Remote Communication - Modem
○ 2.5A UL Battery Charger ○ Extended Factory Testing (3-Phase Only) ○ 10A Run Relay
○ Battery Warmer ○ 8 Position Load Center ○ Ground Fault Indication and Protection Functions
○ Permanent Magnet Excitation ○ Level 2 with Motorized Dampers ○ 7 Year Extended Limited Warranty
○ Aluminum Enclosure
○ Up to 200 MPH Wind Kit (Contact Factory
for Availability)
○ AC/DC Enclosure Lighting Kit
○ Door Open Alarm Switch
ENGINEERED OPTIONS
CONTROL SYSTEM
○ Spare Inputs (x4) / Outputs (x4)
○ Battery Disconnect Switch SPEC SHEET
3 of 6
SG070 | 6.8L | 70 kW
INDUSTRIAL SPARK-IGNITED GENERATOR SET
EPA Certified Stationary Emergency
ENGINE SPECIFICATIONS
Engine Governing
Governor Electronic
Frequency Regulation (Steady State) ±0.25%
Lubrication System
Oil Pump Type Gear
Oil Filter Type Full-Flow Spin-On Cartridge
Crankcase Capacity - qt (L) 6 (5.7)
ALTERNATOR SPECIFICATIONS
4 of 6
SG070 | 6.8L | 70 kW
INDUSTRIAL SPARK-IGNITED GENERATOR SET
EPA Certified Stationary Emergency
COOLING
Standby
Air Flow (Inlet Air Combustion and Radiator) ft3/min (m3/min) 5,813 (164.6)
Coolant Flow gpm (lpm) 38 (144)
Coolant System Capacity gal (L) 6.3 (23.9)
Heat Rejection to Coolant BTU/hr (kW) 275,800 (80.8)
Maximum Operating Ambient Temperature °F (°C) 122 (50)
Maximum Operating Ambient Temperature (Before Derate) See Bulletin No. 0199270SSD
Maximum Radiator Backpressure in H2O (kPa) 0.5 (0.12)
ENGINE EXHAUST
Standby Standby
Rated Engine Speed rpm 1,800 Exhaust Flow (Rated Output) cfm (m3/min) 680 (19.2)
Horsepower at Rated kW** hp 107 Maximum Exhaust Backpressure inHg (kPa) 1.5 (5.1)
SPEC SHEET
Piston Speed ft/min (m/min) 1,251 (381) Exhaust Temp (Rated Output - Post Silencer) °F (°C) 1,250 (676.7)
BMEP psi (kPa) 119 (820)
** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.
Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions.
Please contact a Generac Power Systems Industrial Dealer for additional details. All performance ratings in accordance with ISO3046, BS5514, ISO8528, and DIN6271 standards.
Standby - See Bulletin 0187500SSB
Demand Response - See Bulletin 10000018250
Prime - See Bulletin 0187510SSB 5 of 6
SG070 | 6.8L | 70 kW
INDUSTRIAL SPARK-IGNITED GENERATOR SET
EPA Certified Stationary Emergency
STANDARD ENCLOSURE
L x W x H - in (mm) 111.8 (2,840) x 40.5 (1,028) x 56.2 (1,427)
Steel: 2,370 (1,075)
Weight - lbs (kg)
Aluminum: 2,075 (941)
Specification characteristics may change without notice. Please contact a Generac Power Systems Industrial Dealer for detailed installation drawings.
6 of 6
Generac Power Systems, Inc. | P.O. Box 8 | Waukesha, WI 53189 Part No. 0K4287
P: (262) 544-4811 ©2017 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Rev. D 11/27/17