AIR CONDITIONING SYSTEMS

MODEL

PUCY-P200-1500Y(S)KD (-BS)
PUCY-EP400-1100YSKD (-BS)
body1.fm 1 ページ 2018年11月12日 月曜日 午前10時49分

GENERAL LINE-UP GENERAL LINE-UP

I.GENERAL LINE-UP

Line-up of Outdoor Units of R410A CITY MULTI


es
Cooling-only Y-Series

PUCY-P200YKD(-BS) PUCY-P250YKD(-BS) PUCY-P350YKD(-BS)


D( BS) PUCY-P400YKD(-BS)
PUCY
C
PUCY-P300YKD(-BS) PUCY-P450YKD(-BS)

8, 10, 12HP 14, 16, 18HP

PUCY-P500YKD(-BS) PUCY-P550YSKD(-BS)

20HP 22HP

PUCY-P600YSKD(-BS) PUCY-P650YSKD(-BS) PUCY-P800YSKD(-BS) PUCY-P850YSKD(-BS)


PUCY-P700YSKD(-BS) PUCY-P750YSKD(-BS) PUCY-P900YSKD(-BS)

24, 26, 28, 30HP 32, 34, 36HP

PUCY-P950YSKD(-BS) PUCY-P1000YSKD(-BS)

38HP 40HP

PUCY-P1050YSKD(-BS) PUCY-P1100YSKD(-BS)

42HP 44HP

MEES18K047 1
body1.fm 2 ページ 2018年11月12日 月曜日 午前10時49分

GENERAL LINE-UP GENERAL LINE-UP

PUCY-P1150YSKD(-BS) PUCY-P1200YSKD(-BS)
PUCY-P1250YSKD(-BS) PUCY-P1300YSKD(-BS)
PUCY-P1350YSKD(-BS) PUCY-P1400YSKD(-BS)

46, 48, 50, 52, 54HP 56HP

PUCY-P1450YSKD(-BS) PUCY-P1500YSKD(-BS)

58HP 60HP

PUCY-EP400YSKD(-BS) PUCY-EP450YSKD(-BS)
PUCY-EP500YSKD(-BS) PUCY-EP650YSKD(-BS)

16, 18, 20HP 26HP

PUCY-EP750YSKD(-BS) PUCY-EP800YSKD(-BS)
PUCY-EP850YSKD(-BS) PUCY-EP900YSKD(-BS)
PUCY-EP700YSKD(-BS) PUCY-EP950YSKD(-BS)

28HP 30, 32, 34, 36, 38HP

PUCY-EP1000YSKD(-BS) PUCY-EP1050YSKD(-BS) PUCY-EP1100YSKD(-BS)

40HP 42, 44HP

MEES18K047 2
0000005024.BOOK 1 ページ 2018年11月12日 月曜日 午後6時54分

CONTENTS Y-Series (Cooling-only)

PUCY-P-Y(S)KD, PUCY-EP-YSKD
I.Y-Series (Cooling-only)

1. SPECIFICATIONS .................................................................................................................................... 2
2. EXTERNAL DIMENSIONS ....................................................................................................................... 42
3. CENTER OF GRAVITY ............................................................................................................................ 59
4. ELECTRICAL WIRING DIAGRAMS ......................................................................................................... 60
5. SOUND LEVELS ...................................................................................................................................... 62
6. VIBRATION LEVEL .................................................................................................................................. 76
7. OPERATION TEMPERATURE RANGE................................................................................................... 77
8. CAPACITY TABLES ................................................................................................................................. 78
8-1. Selection of Cooling Units................................................................................................................ 78
8-2. Correction by temperature ............................................................................................................... 82
8-3. Correction by total indoor................................................................................................................. 107
8-4. Correction by part load ratio ............................................................................................................ 127
8-5. Correction by refrigerant piping length............................................................................................. 147
9. OPTIONAL PARTS................................................................................................................................... 152
9-1. JOINT .............................................................................................................................................. 152
9-2. HEADER.......................................................................................................................................... 153
9-3. OUTDOOR TWINNING KIT............................................................................................................. 154
10.ELECTRICAL WORK ............................................................................................................................... 155
10-1.General cautions ............................................................................................................................. 155
10-2.Power supply for Outdoor unit ......................................................................................................... 156
10-3.Power cable specifications .............................................................................................................. 158
10-4.Power supply examples................................................................................................................... 159
11.M-NET CONTROL ................................................................................................................................... 162
11-1.Transmission cable length limitation................................................................................................ 162
11-2.Transmission cable specifications ................................................................................................... 163
11-3.System configuration restrictions..................................................................................................... 164
11-4.Address setting................................................................................................................................ 168
12.PIPING DESIGN ...................................................................................................................................... 180
12-1.R410A Piping material..................................................................................................................... 180
12-2.Piping Design .................................................................................................................................. 182
12-3.Refrigerant charging calculation ...................................................................................................... 186
13.OUTDOOR INSTALLATION .................................................................................................................... 188
13-1.Requirement on installation site ...................................................................................................... 188
13-2.Spacing............................................................................................................................................ 189
13-3.Piping direction ................................................................................................................................ 191

MEES18K047 1
0000005024.BOOK 2 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

I.Y-Series
1. SPECIFICATIONS
(Cooling-only)

Model PUCY-P200YKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 22.4
(Nominal) kcal/h 20,000
BTU/h 76,400
Power input kW 4.66
PUCY-P-Y(S)KD, EP-YSKD

Current input A 7.8-7.4-7.2


EER kW/kW 4.80
Cooling capacity *3 kW 22.7
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P250/1~17
Sound pressure level (measured in anechoic room) dB <A> 57
Refrigerant Liquid pipe mm (in.) 9.52 (3/8) Brazed
piping diameter Gas pipe mm (in.) 22.2 (7/8) Brazed
FAN Type x Quantity Propeller fan x 1
Air flow rate m3/min 175
L/s 2,917
cfm 6,179
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor
Starting method Inverter
Motor output kW 5.5
Case heater kW -
Lubricant MEL32
External finish Pre-coated galvanized steel sheets (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740
in. 65 x 36-1/4 x 29-3/16
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Refrigerant Type x original charge R410A x 5.5 kg (13 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 174 (384)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure
Drawing External WKL94T411
Wiring WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Joint: CMY-Y102SS/LS-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 2
0000005024.BOOK 3 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P250YKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 28.0
(Nominal) kcal/h 25,000
BTU/h 95,500
Power input kW 5.95

PUCY-P-Y(S)KD, EP-YSKD
Current input A 10.0-9.5-9.1
EER kW/kW 4.70
Cooling capacity *3 kW 28.4
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P250/1~21
Sound pressure level (measured in anechoic room) dB <A> 58
Refrigerant Liquid pipe mm (in.) 9.52 (3/8) Brazed (12.7 (1/2) Brazed, farthest length >= 90 m)
piping diameter Gas pipe mm (in.) 22.2 (7/8) Brazed
FAN Type x Quantity Propeller fan x 1
Air flow rate m3/min 175
L/s 2,917
cfm 6,179
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor
Starting method Inverter
Motor output kW 6.9
Case heater kW -
Lubricant MEL32
External finish Pre-coated galvanized steel sheets (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740
in. 65 x 36-1/4 x 29-3/16
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Refrigerant Type x original charge R410A x 6.5 kg (15 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 183 (404)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure
Drawing External WKL94T411
Wiring WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Joint: CMY-Y102SS/LS-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 3
0000005024.BOOK 4 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P300YKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 33.5
(Nominal) kcal/h 30,000
BTU/h 114,300
Power input kW 7.82
PUCY-P-Y(S)KD, EP-YSKD

Current input A 13.2-12.5-12.0


EER kW/kW 4.28
Cooling capacity *3 kW 34.0
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P250/1~26
Sound pressure level (measured in anechoic room) dB <A> 61
Refrigerant Liquid pipe mm (in.) 9.52 (3/8) Brazed (12.7 (1/2) Brazed, farthest length >= 40 m)
piping diameter Gas pipe mm (in.) 22.2 (7/8) Brazed
FAN Type x Quantity Propeller fan x 1
Air flow rate m3/min 175
L/s 2,917
cfm 6,179
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor
Starting method Inverter
Motor output kW 8.1
Case heater kW -
Lubricant MEL32
External finish Pre-coated galvanized steel sheets (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740
in. 65 x 36-1/4 x 29-3/16
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Refrigerant Type x original charge R410A x 6.5 kg (15 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 200 (441)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure
Drawing External WKL94T411
Wiring WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Joint: CMY-Y102SS/LS-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 4
0000005024.BOOK 5 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P350YKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 40.0
(Nominal) kcal/h 35,000
BTU/h 136,500
Power input kW 9.66

PUCY-P-Y(S)KD, EP-YSKD
Current input A 16.3-15.4-14.9
EER kW/kW 4.14
Cooling capacity *3 kW 40.6
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P400/1~30
Sound pressure level (measured in anechoic room) dB <A> 61
Refrigerant Liquid pipe mm (in.) 12.7 (1/2) Brazed
piping diameter Gas pipe mm (in.) 28.58 (1-1/8) Brazed
FAN Type x Quantity Propeller fan x 1
Air flow rate m3/min 210
L/s 3,500
cfm 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor
Starting method Inverter
Motor output kW 10.4
Case heater kW -
Lubricant MEL32
External finish Pre-coated galvanized steel sheets (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,220 x 740
in. 65 x 48-1/16 x 29-3/16
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Refrigerant Type x original charge R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure
Drawing External WKL94T412
Wiring WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Joint: CMY-Y102SS/LS-G2,CMY-Y202S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 5
0000005024.BOOK 6 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P400YKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 44.0
(Nominal) kcal/h 39,000
BTU/h 150,100
Power input kW 12.42
PUCY-P-Y(S)KD, EP-YSKD

Current input A 20.9-19.9-19.1


EER kW/kW 3.54
Cooling capacity *3 kW 44.7
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~34
Sound pressure level (measured in anechoic room) dB <A> 63
Refrigerant Liquid pipe mm (in.) 12.7 (1/2) Brazed
piping diameter Gas pipe mm (in.) 28.58 (1-1/8) Brazed
FAN Type x Quantity Propeller fan x 1
Air flow rate m3/min 210
L/s 3,500
cfm 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor
Starting method Inverter
Motor output kW 10.8
Case heater kW -
Lubricant MEL32
External finish Pre-coated galvanized steel sheets (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,220 x 740
in. 65 x 48-1/16 x 29-3/16
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Refrigerant Type x original charge R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure
Drawing External WKL94T412
Wiring WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Joint: CMY-Y102SS/LS-G2,CMY-Y202S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 6
0000005024.BOOK 7 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P450YKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 48.0
(Nominal) kcal/h 43,000
BTU/h 163,800
Power input kW 14.32

PUCY-P-Y(S)KD, EP-YSKD
Current input A 24.1-22.9-22.1
EER kW/kW 3.35
Cooling capacity *3 kW 48.8
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~39
Sound pressure level (measured in anechoic room) dB <A> 63
Refrigerant Liquid pipe mm (in.) 15.88 (5/8) Brazed
piping diameter Gas pipe mm (in.) 28.58 (1-1/8) Brazed
FAN Type x Quantity Propeller fan x 1
Air flow rate m3/min 210
L/s 3,500
cfm 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor
Starting method Inverter
Motor output kW 12.4
Case heater kW -
Lubricant MEL32
External finish Pre-coated galvanized steel sheets (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,220 x 740
in. 65 x 48-1/16 x 29-3/16
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Refrigerant Type x original charge R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure
Drawing External WKL94T412
Wiring WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Joint: CMY-Y102SS/LS-G2,CMY-Y202S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 7
0000005024.BOOK 8 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P500YKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 56.0
(Nominal) kcal/h 50,000
BTU/h 191,100
Power input kW 16.51
PUCY-P-Y(S)KD, EP-YSKD

Current input A 27.8-26.4-25.5


EER kW/kW 3.39
Cooling capacity *3 kW 56.9
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~43
Sound pressure level (measured in anechoic room) dB <A> 65
Refrigerant Liquid pipe mm (in.) 15.88 (5/8) Brazed
piping diameter Gas pipe mm (in.) 28.58 (1-1/8) Brazed
FAN Type x Quantity Propeller fan x 2
Air flow rate m3/min 320
L/s 5,333
cfm 11,299
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 2
*2 External static press. 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor
Starting method Inverter
Motor output kW 13.3
Case heater kW -
Lubricant MEL32
External finish Pre-coated galvanized steel sheets (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,750 x 740
in. 65 x 68-15/16 x 29-3/16
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Refrigerant Type x original charge R410A x 11.8 kg (27 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 304 (671)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure
Drawing External WKL94T413
Wiring WKE94G900
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Joint: CMY-Y102SS/LS-G2,CMY-Y202S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 8
0000005024.BOOK 9 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P550YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 61.5
(Nominal) kcal/h 52,900
BTU/h 209,800
Power input kW 14.04

PUCY-P-Y(S)KD, EP-YSKD
Current input A 23.7-22.5-21.7
EER kW/kW 4.38
Cooling capacity *3 kW 62.5
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~47
Sound pressure level (measured in anechoic room) dB <A> 63
Refrigerant Liquid pipe mm (in.) 15.88 (5/8) Brazed
piping diameter Gas pipe mm (in.) 28.58 (1-1/8) Brazed
Set Model
Model PUCY-P250YKD (-BS) PUCY-P300YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 175 175
L/s 2,917 2,917
cfm 6,179 6,179
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter
Motor output kW 6.9 8.1
Case heater kW - -
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740 1,650 x 920 x 740
in. 65 x 36-1/4 x 29-3/16 65 x 36-1/4 x 29-3/16
High pressure sensor, High pressure switch at 4.15 MPa (601 High pressure sensor, High pressure switch at 4.15 MPa (601
Protection devices High pressure protection
psi) psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor - -
Fan motor - -
Refrigerant Type x original charge R410A x 6.5 kg (15 lbs) R410A x 6.5 kg (15 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 183 (404) 200 (441)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52 (3/8) Brazed 12.7 (1/2) Brazed
distributor Gas pipe mm (in.) 22.2 (7/8) Brazed 22.2 (7/8) Brazed
Drawing External WKL94T414
Wiring WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y100VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 9
0000005024.BOOK 10 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P600YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 68.0
(Nominal) kcal/h 58,500
BTU/h 232,000
Power input kW 15.34
PUCY-P-Y(S)KD, EP-YSKD

Current input A 25.8-24.6-23.7


EER kW/kW 4.43
Cooling capacity *3 kW 69.1
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~50
Sound pressure level (measured in anechoic room) dB <A> 63
Refrigerant Liquid pipe mm (in.) 15.88 (5/8) Brazed
piping diameter Gas pipe mm (in.) 28.58 (1-1/8) Brazed
Set Model
Model PUCY-P250YKD (-BS) PUCY-P350YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 175 210
L/s 2,917 3,500
cfm 6,179 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter
Motor output kW 6.9 10.4
Case heater kW - -
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740 1,650 x 1,220 x 740
in. 65 x 36-1/4 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure switch at 4.15 MPa (601 High pressure sensor, High pressure switch at 4.15 MPa (601
Protection devices High pressure protection
psi) psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor - -
Fan motor - -
Refrigerant Type x original charge R410A x 6.5 kg (15 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 183 (404) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52 (3/8) Brazed 12.7 (1/2) Brazed
distributor Gas pipe mm (in.) 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T415
Wiring WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y100VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 10
0000005024.BOOK 11 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P650YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 72.0
(Nominal) kcal/h 61,900
BTU/h 245,700
Power input kW 17.73

PUCY-P-Y(S)KD, EP-YSKD
Current input A 29.9-28.4-27.4
EER kW/kW 4.06
Cooling capacity *3 kW 73.2
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~50
Sound pressure level (measured in anechoic room) dB <A> 64.5
Refrigerant Liquid pipe mm (in.) 15.88 (5/8) Brazed
piping diameter Gas pipe mm (in.) 28.58 (1-1/8) Brazed
Set Model
Model PUCY-P250YKD (-BS) PUCY-P400YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 175 210
L/s 2,917 3,500
cfm 6,179 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter
Motor output kW 6.9 10.8
Case heater kW - -
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740 1,650 x 1,220 x 740
in. 65 x 36-1/4 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure switch at 4.15 MPa (601 High pressure sensor, High pressure switch at 4.15 MPa (601
Protection devices High pressure protection
psi) psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor - -
Fan motor - -
Refrigerant Type x original charge R410A x 6.5 kg (15 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 183 (404) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52 (3/8) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T415
Wiring WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y100VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 11
0000005024.BOOK 12 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P700YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 76.0
(Nominal) kcal/h 65,400
BTU/h 259,300
Power input kW 19.24
PUCY-P-Y(S)KD, EP-YSKD

Current input A 32.4-30.8-29.7


EER kW/kW 3.95
Cooling capacity *3 kW 77.2
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~50
Sound pressure level (measured in anechoic room) dB <A> 64.5
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 34.93 (1-3/8) Brazed
Set Model
Model PUCY-P250YKD (-BS) PUCY-P450YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 175 210
L/s 2,917 3,500
cfm 6,179 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter
Motor output kW 6.9 12.4
Case heater kW - -
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740 1,650 x 1,220 x 740
in. 65 x 36-1/4 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure switch at 4.15 MPa (601 High pressure sensor, High pressure switch at 4.15 MPa (601
Protection devices High pressure protection
psi) psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor - -
Fan motor - -
Refrigerant Type x original charge R410A x 6.5 kg (15 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 183 (404) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52 (3/8) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T415
Wiring WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y200VBK2
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 12
0000005024.BOOK 13 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P750YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 81.5
(Nominal) kcal/h 70,100
BTU/h 278,100
Power input kW 21.79

PUCY-P-Y(S)KD, EP-YSKD
Current input A 36.7-34.9-33.6
EER kW/kW 3.74
Cooling capacity *3 kW 82.8
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~50
Sound pressure level (measured in anechoic room) dB <A> 65.5
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 34.93 (1-3/8) Brazed
Set Model
Model PUCY-P300YKD (-BS) PUCY-P450YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 175 210
L/s 2,917 3,500
cfm 6,179 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter
Motor output kW 8.1 12.4
Case heater kW - -
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740 1,650 x 1,220 x 740
in. 65 x 36-1/4 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure switch at 4.15 MPa (601 High pressure sensor, High pressure switch at 4.15 MPa (601
Protection devices High pressure protection
psi) psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor - -
Fan motor - -
Refrigerant Type x original charge R410A x 6.5 kg (15 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 200 (441) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7 (1/2) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T415
Wiring WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y200VBK2
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 13
0000005024.BOOK 14 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P800YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 88.0
(Nominal) kcal/h 75,700
BTU/h 300,300
Power input kW 25.00
PUCY-P-Y(S)KD, EP-YSKD

Current input A 42.2-40.0-38.6


EER kW/kW 3.52
Cooling capacity *3 kW 89.4
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~50
Sound pressure level (measured in anechoic room) dB <A> 66
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 34.93 (1-3/8) Brazed
Set Model
Model PUCY-P400YKD (-BS) PUCY-P400YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 210 210
L/s 3,500 3,500
cfm 7,415 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter
Motor output kW 10.8 10.8
Case heater kW - -
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,220 x 740 1,650 x 1,220 x 740
in. 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure switch at 4.15 MPa (601 High pressure sensor, High pressure switch at 4.15 MPa (601
Protection devices High pressure protection
psi) psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor - -
Fan motor - -
Refrigerant Type x original charge R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 236 (521) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 15.88 (5/8) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T416
Wiring WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y200VBK2
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 14
0000005024.BOOK 15 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P850YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 92.0
(Nominal) kcal/h 79,100
BTU/h 313,900
Power input kW 26.97

PUCY-P-Y(S)KD, EP-YSKD
Current input A 45.5-43.2-41.6
EER kW/kW 3.41
Cooling capacity *3 kW 93.5
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~50
Sound pressure level (measured in anechoic room) dB <A> 66
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P400YKD (-BS) PUCY-P450YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 210 210
L/s 3,500 3,500
cfm 7,415 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter
Motor output kW 10.8 12.4
Case heater kW - -
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,220 x 740 1,650 x 1,220 x 740
in. 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure switch at 4.15 MPa (601 High pressure sensor, High pressure switch at 4.15 MPa (601
Protection devices High pressure protection
psi) psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor - -
Fan motor - -
Refrigerant Type x original charge R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 236 (521) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 15.88 (5/8) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T416
Wiring WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y200VBK2
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 15
0000005024.BOOK 16 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P900YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 96.0
(Nominal) kcal/h 82,600
BTU/h 327,600
Power input kW 29.00
PUCY-P-Y(S)KD, EP-YSKD

Current input A 48.9-46.5-44.8


EER kW/kW 3.31
Cooling capacity *3 kW 97.6
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~50
Sound pressure level (measured in anechoic room) dB <A> 66
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P450YKD (-BS) PUCY-P450YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 210 210
L/s 3,500 3,500
cfm 7,415 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter
Motor output kW 12.4 12.4
Case heater kW - -
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,220 x 740 1,650 x 1,220 x 740
in. 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure switch at 4.15 MPa (601 High pressure sensor, High pressure switch at 4.15 MPa (601
Protection devices High pressure protection
psi) psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor - -
Fan motor - -
Refrigerant Type x original charge R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 236 (521) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 15.88 (5/8) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T416
Wiring WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y200VBK2
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 16
0000005024.BOOK 17 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P950YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 104.0
(Nominal) kcal/h 89,400
BTU/h 354,800
Power input kW 31.51

PUCY-P-Y(S)KD, EP-YSKD
Current input A 53.1-50.5-48.7
EER kW/kW 3.30
Cooling capacity *3 kW 105.7
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~50
Sound pressure level (measured in anechoic room) dB <A> 67.5
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P450YKD (-BS) PUCY-P500YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 2
Air flow rate m3/min 210 320
L/s 3,500 5,333
cfm 7,415 11,299
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 2
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter
Motor output kW 12.4 13.3
Case heater kW - -
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,220 x 740 1,650 x 1,750 x 740
in. 65 x 48-1/16 x 29-3/16 65 x 68-15/16 x 29-3/16
High pressure sensor, High pressure switch at 4.15 MPa (601 High pressure sensor, High pressure switch at 4.15 MPa (601
Protection devices High pressure protection
psi) psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor - -
Fan motor - -
Refrigerant Type x original charge R410A x 11.5 kg (26 lbs) R410A x 11.8 kg (27 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 236 (521) 304 (671)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 15.88 (5/8) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T417
Wiring WKE94G899 WKE94G900
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y200VBK2
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 17
0000005024.BOOK 18 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P1000YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 112.0
(Nominal) kcal/h 96,300
BTU/h 382,100
Power input kW 34.04
PUCY-P-Y(S)KD, EP-YSKD

Current input A 57.4-54.5-52.6


EER kW/kW 3.29
Cooling capacity *3 kW 113.9
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~50
Sound pressure level (measured in anechoic room) dB <A> 68
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P500YKD (-BS) PUCY-P500YKD (-BS)
FAN Type x Quantity Propeller fan x 2 Propeller fan x 2
Air flow rate m3/min 320 320
L/s 5,333 5,333
cfm 11,299 11,299
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 2 0.92 x 2
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter
Motor output kW 13.3 13.3
Case heater kW - -
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,750 x 740 1,650 x 1,750 x 740
in. 65 x 68-15/16 x 29-3/16 65 x 68-15/16 x 29-3/16
High pressure sensor, High pressure switch at 4.15 MPa (601 High pressure sensor, High pressure switch at 4.15 MPa (601
Protection devices High pressure protection
psi) psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor - -
Fan motor - -
Refrigerant Type x original charge R410A x 11.8 kg (27 lbs) R410A x 11.8 kg (27 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 304 (671) 304 (671)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 15.88 (5/8) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T418
Wiring WKE94G900 WKE94G900
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y200VBK2
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 18
0000005024.BOOK 19 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P1050YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 115.0
(Nominal) kcal/h 98,900
BTU/h 392,400
Power input kW 29.63

PUCY-P-Y(S)KD, EP-YSKD
Current input A 50.0-47.5-45.8
EER kW/kW 3.88
Cooling capacity *3 kW 116.9
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/2~50
Sound pressure level (measured in anechoic room) dB <A> 66.5
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P300YKD (-BS) PUCY-P300YKD (-BS) PUCY-P450YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 175 175 210
L/s 2,917 2,917 3,500
cfm 6,179 6,179 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 8.1 8.1 12.4
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740 1,650 x 920 x 740 1,650 x 1,220 x 740
in. 65 x 36-1/4 x 29-3/16 65 x 36-1/4 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 6.5 kg (15 lbs) R410A x 6.5 kg (15 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 200 (441) 200 (441) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7 (1/2) Brazed 12.7 (1/2) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 22.2 (7/8) Brazed 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T419
Wiring WKE94G899 WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 19
0000005024.BOOK 20 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P1100YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 121.5
(Nominal) kcal/h 104,500
BTU/h 414,600
Power input kW 30.99
PUCY-P-Y(S)KD, EP-YSKD

Current input A 52.3-49.7-47.9


EER kW/kW 3.92
Cooling capacity *3 kW 123.5
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/2~50
Sound pressure level (measured in anechoic room) dB <A> 66.5
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P300YKD (-BS) PUCY-P350YKD (-BS) PUCY-P450YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 175 210 210
L/s 2,917 3,500 3,500
cfm 6,179 7,415 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 8.1 10.4 12.4
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740 1,650 x 1,220 x 740 1,650 x 1,220 x 740
in. 65 x 36-1/4 x 29-3/16 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 6.5 kg (15 lbs) R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 200 (441) 236 (521) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7 (1/2) Brazed 12.7 (1/2) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T420
Wiring WKE94G899 WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 20
0000005024.BOOK 21 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P1150YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 128.0
(Nominal) kcal/h 110,100
BTU/h 436,700
Power input kW 33.95

PUCY-P-Y(S)KD, EP-YSKD
Current input A 57.3-54.4-52.4
EER kW/kW 3.77
Cooling capacity *3 kW 130.1
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/2~50
Sound pressure level (measured in anechoic room) dB <A> 67.5
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P350YKD (-BS) PUCY-P400YKD (-BS) PUCY-P400YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 210 210 210
L/s 3,500 3,500 3,500
cfm 7,415 7,415 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 10.4 10.8 10.8
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,220 x 740 1,650 x 1,220 x 740 1,650 x 1,220 x 740
in. 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 236 (521) 236 (521) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7 (1/2) Brazed 15.88 (5/8) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T421
Wiring WKE94G899 WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 21
0000005024.BOOK 22 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P1200YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 132.0
(Nominal) kcal/h 113,500
BTU/h 450,400
Power input kW 37.50
PUCY-P-Y(S)KD, EP-YSKD

Current input A 63.3-60.1-57.9


EER kW/kW 3.52
Cooling capacity *3 kW 134.2
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/2~50
Sound pressure level (measured in anechoic room) dB <A> 68
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P400YKD (-BS) PUCY-P400YKD (-BS) PUCY-P400YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 210 210 210
L/s 3,500 3,500 3,500
cfm 7,415 7,415 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 10.8 10.8 10.8
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,220 x 740 1,650 x 1,220 x 740 1,650 x 1,220 x 740
in. 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 236 (521) 236 (521) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 15.88 (5/8) Brazed 15.88 (5/8) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T421
Wiring WKE94G899 WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 22
0000005024.BOOK 23 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P1250YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 136.0
(Nominal) kcal/h 117,000
BTU/h 464,000
Power input kW 39.42

PUCY-P-Y(S)KD, EP-YSKD
Current input A 66.5-63.2-60.9
EER kW/kW 3.45
Cooling capacity *3 kW 138.3
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/2~50
Sound pressure level (measured in anechoic room) dB <A> 68
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P400YKD (-BS) PUCY-P400YKD (-BS) PUCY-P450YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 210 210 210
L/s 3,500 3,500 3,500
cfm 7,415 7,415 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 10.8 10.8 12.4
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,220 x 740 1,650 x 1,220 x 740 1,650 x 1,220 x 740
in. 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 236 (521) 236 (521) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 15.88 (5/8) Brazed 15.88 (5/8) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T421
Wiring WKE94G899 WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 23
0000005024.BOOK 24 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P1300YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 140.0
(Nominal) kcal/h 120,400
BTU/h 477,700
Power input kW 41.54
PUCY-P-Y(S)KD, EP-YSKD

Current input A 70.1-66.6-64.2


EER kW/kW 3.37
Cooling capacity *3 kW 142.3
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/2~50
Sound pressure level (measured in anechoic room) dB <A> 68
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P400YKD (-BS) PUCY-P450YKD (-BS) PUCY-P450YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 210 210 210
L/s 3,500 3,500 3,500
cfm 7,415 7,415 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 10.8 12.4 12.4
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,220 x 740 1,650 x 1,220 x 740 1,650 x 1,220 x 740
in. 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 236 (521) 236 (521) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 15.88 (5/8) Brazed 15.88 (5/8) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T421
Wiring WKE94G899 WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 24
0000005024.BOOK 25 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P1350YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 144.0
(Nominal) kcal/h 123,800
BTU/h 491,300
Power input kW 43.63

PUCY-P-Y(S)KD, EP-YSKD
Current input A 73.6-69.9-67.4
EER kW/kW 3.30
Cooling capacity *3 kW 146.4
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/2~50
Sound pressure level (measured in anechoic room) dB <A> 68
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P450YKD (-BS) PUCY-P450YKD (-BS) PUCY-P450YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 210 210 210
L/s 3,500 3,500 3,500
cfm 7,415 7,415 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 12.4 12.4 12.4
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,220 x 740 1,650 x 1,220 x 740 1,650 x 1,220 x 740
in. 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 236 (521) 236 (521) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 15.88 (5/8) Brazed 15.88 (5/8) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T421
Wiring WKE94G899 WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 25
0000005024.BOOK 26 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P1400YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 152.0
(Nominal) kcal/h 130,700
BTU/h 518,600
Power input kW 46.06
PUCY-P-Y(S)KD, EP-YSKD

Current input A 77.7-73.8-71.1


EER kW/kW 3.30
Cooling capacity *3 kW 154.5
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/2~50
Sound pressure level (measured in anechoic room) dB <A> 68.5
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P450YKD (-BS) PUCY-P450YKD (-BS) PUCY-P500YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 2
Air flow rate m3/min 210 210 320
L/s 3,500 3,500 5,333
cfm 7,415 7,415 11,299
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 2
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 12.4 12.4 13.3
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,220 x 740 1,650 x 1,220 x 740 1,650 x 1,750 x 740
in. 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16 65 x 68-15/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs) R410A x 11.8 kg (27 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 236 (521) 236 (521) 304 (671)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 15.88 (5/8) Brazed 15.88 (5/8) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T422
Wiring WKE94G899 WKE94G899 WKE94G900
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 26
0000005024.BOOK 27 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P1450YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 160.0
(Nominal) kcal/h 137,600
BTU/h 545,900
Power input kW 48.63

PUCY-P-Y(S)KD, EP-YSKD
Current input A 82.0-77.9-75.1
EER kW/kW 3.29
Cooling capacity *3 kW 162.7
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/2~50
Sound pressure level (measured in anechoic room) dB <A> 69.5
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P450YKD (-BS) PUCY-P500YKD (-BS) PUCY-P500YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 2 Propeller fan x 2
Air flow rate m3/min 210 320 320
L/s 3,500 5,333 5,333
cfm 7,415 11,299 11,299
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 2 0.92 x 2
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 12.4 13.3 13.3
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,220 x 740 1,650 x 1,750 x 740 1,650 x 1,750 x 740
in. 65 x 48-1/16 x 29-3/16 65 x 68-15/16 x 29-3/16 65 x 68-15/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 11.5 kg (26 lbs) R410A x 11.8 kg (27 lbs) R410A x 11.8 kg (27 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 236 (521) 304 (671) 304 (671)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 15.88 (5/8) Brazed 15.88 (5/8) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T423
Wiring WKE94G899 WKE94G900 WKE94G900
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 27
0000005024.BOOK 28 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-P1500YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 168.0
(Nominal) kcal/h 144,500
BTU/h 573,200
Power input kW 51.06
PUCY-P-Y(S)KD, EP-YSKD

Current input A 86.1-81.8-78.9


EER kW/kW 3.29
Cooling capacity *3 kW 170.8
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/2~50
Sound pressure level (measured in anechoic room) dB <A> 70
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P500YKD (-BS) PUCY-P500YKD (-BS) PUCY-P500YKD (-BS)
FAN Type x Quantity Propeller fan x 2 Propeller fan x 2 Propeller fan x 2
Air flow rate m3/min 320 320 320
L/s 5,333 5,333 5,333
cfm 11,299 11,299 11,299
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 2 0.92 x 2 0.92 x 2
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 13.3 13.3 13.3
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,750 x 740 1,650 x 1,750 x 740 1,650 x 1,750 x 740
in. 65 x 68-15/16 x 29-3/16 65 x 68-15/16 x 29-3/16 65 x 68-15/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 11.8 kg (27 lbs) R410A x 11.8 kg (27 lbs) R410A x 11.8 kg (27 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 304 (671) 304 (671) 304 (671)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 15.88 (5/8) Brazed 15.88 (5/8) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T424
Wiring WKE94G900 WKE94G900 WKE94G900
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 28
0000005024.BOOK 29 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-EP400YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 44.8
(Nominal) kcal/h 38,500
BTU/h 152,900
Power input kW 9.93

PUCY-P-Y(S)KD, EP-YSKD
Current input A 16.7-15.9-15.3
EER kW/kW 4.51
Cooling capacity *3 kW 45.5
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~34
Sound pressure level (measured in anechoic room) dB <A> 60
Refrigerant Liquid pipe mm (in.) 12.7 (1/2) Brazed
piping diameter Gas pipe mm (in.) 28.58 (1-1/8) Brazed
Set Model
Model PUCY-P200YKD (-BS) PUCY-P200YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 175 175
L/s 2,917 2,917
cfm 6,179 6,179
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter
Motor output kW 5.5 5.5
Case heater kW - -
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740 1,650 x 920 x 740
in. 65 x 36-1/4 x 29-3/16 65 x 36-1/4 x 29-3/16
High pressure sensor, High pressure switch at 4.15 MPa (601 High pressure sensor, High pressure switch at 4.15 MPa (601
Protection devices High pressure protection
psi) psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor - -
Fan motor - -
Refrigerant Type x original charge R410A x 5.5 kg (13 lbs) R410A x 5.5 kg (13 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 174 (384) 174 (384)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52 (3/8) Brazed 9.52 (3/8) Brazed
distributor Gas pipe mm (in.) 22.2 (7/8) Brazed 22.2 (7/8) Brazed
Drawing External WKL94T414
Wiring WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y100VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 29
0000005024.BOOK 30 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-EP450YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 50.4
(Nominal) kcal/h 43,300
BTU/h 172,000
Power input kW 11.37
PUCY-P-Y(S)KD, EP-YSKD

Current input A 19.1-18.2-17.5


EER kW/kW 4.43
Cooling capacity *3 kW 51.2
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~39
Sound pressure level (measured in anechoic room) dB <A> 60.5
Refrigerant Liquid pipe mm (in.) 15.88 (5/8) Brazed
piping diameter Gas pipe mm (in.) 28.58 (1-1/8) Brazed
Set Model
Model PUCY-P200YKD (-BS) PUCY-P250YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 175 175
L/s 2,917 2,917
cfm 6,179 6,179
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter
Motor output kW 5.5 6.9
Case heater kW - -
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740 1,650 x 920 x 740
in. 65 x 36-1/4 x 29-3/16 65 x 36-1/4 x 29-3/16
High pressure sensor, High pressure switch at 4.15 MPa (601 High pressure sensor, High pressure switch at 4.15 MPa (601
Protection devices High pressure protection
psi) psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor - -
Fan motor - -
Refrigerant Type x original charge R410A x 5.5 kg (13 lbs) R410A x 6.5 kg (15 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 174 (384) 183 (404)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52 (3/8) Brazed 9.52 (3/8) Brazed
distributor Gas pipe mm (in.) 22.2 (7/8) Brazed 22.2 (7/8) Brazed
Drawing External WKL94T414
Wiring WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y100VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 30
0000005024.BOOK 31 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-EP500YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 56.0
(Nominal) kcal/h 48,200
BTU/h 191,100
Power input kW 12.84

PUCY-P-Y(S)KD, EP-YSKD
Current input A 21.6-20.5-19.8
EER kW/kW 4.36
Cooling capacity *3 kW 56.9
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~43
Sound pressure level (measured in anechoic room) dB <A> 61
Refrigerant Liquid pipe mm (in.) 15.88 (5/8) Brazed
piping diameter Gas pipe mm (in.) 28.58 (1-1/8) Brazed
Set Model
Model PUCY-P250YKD (-BS) PUCY-P250YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 175 175
L/s 2,917 2,917
cfm 6,179 6,179
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter
Motor output kW 6.9 6.9
Case heater kW - -
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740 1,650 x 920 x 740
in. 65 x 36-1/4 x 29-3/16 65 x 36-1/4 x 29-3/16
High pressure sensor, High pressure switch at 4.15 MPa (601 High pressure sensor, High pressure switch at 4.15 MPa (601
Protection devices High pressure protection
psi) psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor - -
Fan motor - -
Refrigerant Type x original charge R410A x 6.5 kg (15 lbs) R410A x 6.5 kg (15 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 183 (404) 183 (404)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52 (3/8) Brazed 9.52 (3/8) Brazed
distributor Gas pipe mm (in.) 22.2 (7/8) Brazed 22.2 (7/8) Brazed
Drawing External WKL94T414
Wiring WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y100VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 31
0000005024.BOOK 32 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-EP650YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 73.5
(Nominal) kcal/h 63,200
BTU/h 250,800
Power input kW 18.32
PUCY-P-Y(S)KD, EP-YSKD

Current input A 30.9-29.3-28.3


EER kW/kW 4.01
Cooling capacity *3 kW 74.7
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~50
Sound pressure level (measured in anechoic room) dB <A> 64
Refrigerant Liquid pipe mm (in.) 15.88 (5/8) Brazed
piping diameter Gas pipe mm (in.) 28.58 (1-1/8) Brazed
Set Model
Model PUCY-P300YKD (-BS) PUCY-P350YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 175 210
L/s 2,917 3,500
cfm 6,179 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter
Motor output kW 8.1 10.4
Case heater kW - -
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740 1,650 x 1,220 x 740
in. 65 x 36-1/4 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure switch at 4.15 MPa (601 High pressure sensor, High pressure switch at 4.15 MPa (601
Protection devices High pressure protection
psi) psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor - -
Fan motor - -
Refrigerant Type x original charge R410A x 6.5 kg (15 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 200 (441) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7 (1/2) Brazed 12.7 (1/2) Brazed
distributor Gas pipe mm (in.) 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T415
Wiring WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y100VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 32
0000005024.BOOK 33 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-EP700YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 80.0
(Nominal) kcal/h 68,800
BTU/h 273,000
Power input kW 19.75

PUCY-P-Y(S)KD, EP-YSKD
Current input A 33.3-31.6-30.5
EER kW/kW 4.05
Cooling capacity *3 kW 81.3
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~50
Sound pressure level (measured in anechoic room) dB <A> 64
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 34.93 (1-3/8) Brazed
Set Model
Model PUCY-P350YKD (-BS) PUCY-P350YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 210 210
L/s 3,500 3,500
cfm 7,415 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter
Motor output kW 10.4 10.4
Case heater kW - -
Lubricant MEL32 MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS Pre-coated galvanized steel sheets (+powder coating for -BS
External finish
type) type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,220 x 740 1,650 x 1,220 x 740
in. 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure switch at 4.15 MPa (601 High pressure sensor, High pressure switch at 4.15 MPa (601
Protection devices High pressure protection
psi) psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Compressor - -
Fan motor - -
Refrigerant Type x original charge R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 236 (521) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7 (1/2) Brazed 12.7 (1/2) Brazed
distributor Gas pipe mm (in.) 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T416
Wiring WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y200VBK2
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 33
0000005024.BOOK 34 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-EP750YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 84.8
(Nominal) kcal/h 72,900
BTU/h 289,300
Power input kW 19.44
PUCY-P-Y(S)KD, EP-YSKD

Current input A 32.8-31.1-30.0


EER kW/kW 4.36
Cooling capacity *3 kW 86.2
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~50
Sound pressure level (measured in anechoic room) dB <A> 64
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 34.93 (1-3/8) Brazed
Set Model
Model PUCY-P200YKD (-BS) PUCY-P200YKD (-BS) PUCY-P350YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 175 175 210
L/s 2,917 2,917 3,500
cfm 6,179 6,179 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 5.5 5.5 10.4
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740 1,650 x 920 x 740 1,650 x 1,220 x 740
in. 65 x 36-1/4 x 29-3/16 65 x 36-1/4 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 5.5 kg (13 lbs) R410A x 5.5 kg (13 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 174 (384) 174 (384) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52 (3/8) Brazed 9.52 (3/8) Brazed 12.7 (1/2) Brazed
distributor Gas pipe mm (in.) 22.2 (7/8) Brazed 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T419
Wiring WKE94G899 WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 34
0000005024.BOOK 35 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-EP800YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 90.4
(Nominal) kcal/h 77,700
BTU/h 308,400
Power input kW 20.97

PUCY-P-Y(S)KD, EP-YSKD
Current input A 35.4-33.6-32.4
EER kW/kW 4.31
Cooling capacity *3 kW 91.9
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~50
Sound pressure level (measured in anechoic room) dB <A> 64
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 34.93 (1-3/8) Brazed
Set Model
Model PUCY-P200YKD (-BS) PUCY-P250YKD (-BS) PUCY-P350YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 175 175 210
L/s 2,917 2,917 3,500
cfm 6,179 6,179 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 5.5 6.9 10.4
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740 1,650 x 920 x 740 1,650 x 1,220 x 740
in. 65 x 36-1/4 x 29-3/16 65 x 36-1/4 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 5.5 kg (13 lbs) R410A x 6.5 kg (15 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 174 (384) 183 (404) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52 (3/8) Brazed 9.52 (3/8) Brazed 12.7 (1/2) Brazed
distributor Gas pipe mm (in.) 22.2 (7/8) Brazed 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T419
Wiring WKE94G899 WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 35
0000005024.BOOK 36 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-EP850YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 96.0
(Nominal) kcal/h 82,600
BTU/h 327,600
Power input kW 22.53
PUCY-P-Y(S)KD, EP-YSKD

Current input A 38.0-36.1-34.8


EER kW/kW 4.26
Cooling capacity *3 kW 97.6
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~50
Sound pressure level (measured in anechoic room) dB <A> 64
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P250YKD (-BS) PUCY-P250YKD (-BS) PUCY-P350YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 175 175 210
L/s 2,917 2,917 3,500
cfm 6,179 6,179 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 6.9 6.9 10.4
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740 1,650 x 920 x 740 1,650 x 1,220 x 740
in. 65 x 36-1/4 x 29-3/16 65 x 36-1/4 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 6.5 kg (15 lbs) R410A x 6.5 kg (15 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 183 (404) 183 (404) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52 (3/8) Brazed 9.52 (3/8) Brazed 12.7 (1/2) Brazed
distributor Gas pipe mm (in.) 22.2 (7/8) Brazed 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T419
Wiring WKE94G899 WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 36
0000005024.BOOK 37 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-EP900YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 101.5
(Nominal) kcal/h 87,300
BTU/h 346,300
Power input kW 24.57

PUCY-P-Y(S)KD, EP-YSKD
Current input A 41.4-39.4-37.9
EER kW/kW 4.13
Cooling capacity *3 kW 103.2
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~50
Sound pressure level (measured in anechoic room) dB <A> 65
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P250YKD (-BS) PUCY-P300YKD (-BS) PUCY-P350YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 175 175 210
L/s 2,917 2,917 3,500
cfm 6,179 6,179 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 6.9 8.1 10.4
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740 1,650 x 920 x 740 1,650 x 1,220 x 740
in. 65 x 36-1/4 x 29-3/16 65 x 36-1/4 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 6.5 kg (15 lbs) R410A x 6.5 kg (15 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 183 (404) 200 (441) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 9.52 (3/8) Brazed 12.7 (1/2) Brazed 12.7 (1/2) Brazed
distributor Gas pipe mm (in.) 22.2 (7/8) Brazed 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T419
Wiring WKE94G899 WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 37
0000005024.BOOK 38 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-EP950YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 107.0
(Nominal) kcal/h 92,000
BTU/h 365,100
Power input kW 26.81
PUCY-P-Y(S)KD, EP-YSKD

Current input A 45.2-42.9-41.4


EER kW/kW 3.99
Cooling capacity *3 kW 108.8
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~50
Sound pressure level (measured in anechoic room) dB <A> 66
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P300YKD (-BS) PUCY-P300YKD (-BS) PUCY-P350YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 175 175 210
L/s 2,917 2,917 3,500
cfm 6,179 6,179 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 8.1 8.1 10.4
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740 1,650 x 920 x 740 1,650 x 1,220 x 740
in. 65 x 36-1/4 x 29-3/16 65 x 36-1/4 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 6.5 kg (15 lbs) R410A x 6.5 kg (15 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 200 (441) 200 (441) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7 (1/2) Brazed 12.7 (1/2) Brazed 12.7 (1/2) Brazed
distributor Gas pipe mm (in.) 22.2 (7/8) Brazed 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T419
Wiring WKE94G899 WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 38
0000005024.BOOK 39 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-EP1000YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 113.5
(Nominal) kcal/h 97,600
BTU/h 387,300
Power input kW 28.80

PUCY-P-Y(S)KD, EP-YSKD
Current input A 48.6-46.1-44.5
EER kW/kW 3.94
Cooling capacity *3 kW 115.4
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/1~50
Sound pressure level (measured in anechoic room) dB <A> 66
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P300YKD (-BS) PUCY-P350YKD (-BS) PUCY-P350YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 175 210 210
L/s 2,917 3,500 3,500
cfm 6,179 7,415 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 8.1 10.4 10.4
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 920 x 740 1,650 x 1,220 x 740 1,650 x 1,220 x 740
in. 65 x 36-1/4 x 29-3/16 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 6.5 kg (15 lbs) R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 200 (441) 236 (521) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7 (1/2) Brazed 12.7 (1/2) Brazed 12.7 (1/2) Brazed
distributor Gas pipe mm (in.) 22.2 (7/8) Brazed 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T420
Wiring WKE94G899 WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 39
0000005024.BOOK 40 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-EP1050YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 120.0
(Nominal) kcal/h 103,200
BTU/h 409,400
Power input kW 29.62
PUCY-P-Y(S)KD, EP-YSKD

Current input A 50.0-47.5-45.7


EER kW/kW 4.05
Cooling capacity *3 kW 122.0
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/2~50
Sound pressure level (measured in anechoic room) dB <A> 66
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P350YKD (-BS) PUCY-P350YKD (-BS) PUCY-P350YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 210 210 210
L/s 3,500 3,500 3,500
cfm 7,415 7,415 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 10.4 10.4 10.4
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,220 x 740 1,650 x 1,220 x 740 1,650 x 1,220 x 740
in. 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 236 (521) 236 (521) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7 (1/2) Brazed 12.7 (1/2) Brazed 12.7 (1/2) Brazed
distributor Gas pipe mm (in.) 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T421
Wiring WKE94G899 WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 40
0000005024.BOOK 41 ページ 2018年11月12日 月曜日 午後6時54分

1. SPECIFICATIONS Y-Series (Cooling-only)

Model PUCY-EP1100YSKD (-BS)


Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 124.0
(Nominal) kcal/h 106,600
BTU/h 423,100
Power input kW 32.37

PUCY-P-Y(S)KD, EP-YSKD
Current input A 54.6-51.9-50.0
EER kW/kW 3.83
Cooling capacity *3 kW 126.1
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. 10.0~52.0°C (50~126°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable Model/Quantity P15~P500/2~50
Sound pressure level (measured in anechoic room) dB <A> 67
Refrigerant Liquid pipe mm (in.) 19.05 (3/4) Brazed
piping diameter Gas pipe mm (in.) 41.28 (1-5/8) Brazed
Set Model
Model PUCY-P350YKD (-BS) PUCY-P350YKD (-BS) PUCY-P400YKD (-BS)
FAN Type x Quantity Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air flow rate m3/min 210 210 210
L/s 3,500 3,500 3,500
cfm 7,415 7,415 7,415
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1 0.92 x 1 0.92 x 1
*2 External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Starting method Inverter Inverter Inverter
Motor output kW 10.4 10.4 10.8
Case heater kW - - -
Lubricant MEL32 MEL32 MEL32
Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets Pre-coated galvanized steel sheets
External finish
(+powder coating for -BS type) (+powder coating for -BS type) (+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar> <MUNSELL 3Y 7.8/1.1 or similar>
External dimension H x W x D mm 1,650 x 1,220 x 740 1,650 x 1,220 x 740 1,650 x 1,220 x 740
in. 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16 65 x 48-1/16 x 29-3/16
High pressure sensor, High pressure High pressure sensor, High pressure High pressure sensor, High pressure
Protection devices High pressure protection
switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi) switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current pro- Over-heat protection, Over-current pro- Over-heat protection, Over-current pro-
Inverter circuit (COMP./FAN)
tection tection tection
Compressor - - -
Fan motor - - -
Refrigerant Type x original charge R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs) R410A x 11.5 kg (26 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 236 (521) 236 (521) 236 (521)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure Copper pipe, tube-in-tube structure
Pipe between unit and Liquid pipe mm (in.) 12.7 (1/2) Brazed 12.7 (1/2) Brazed 15.88 (5/8) Brazed
distributor Gas pipe mm (in.) 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed 28.58 (1-1/8) Brazed
Drawing External WKL94T421
Wiring WKE94G899 WKE94G899 WKE94G899
Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe
Optional parts Outdoor Twinning kit: CMY-Y300VBK3
Joint: CMY-Y102SS/LS-G2, CMY-Y202/302S-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.

Notes: Unit converter


1.Nominal cooling conditions (subject to JIS B8615-2) BTU/h =kW x 3,412
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.) cfm =m3/min x 35.31
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.External static pressure option is available (30Pa, 60Pa/3.1mmH2O, 6.1mmH2O). lbs =kg/0.4536
3.Reference data under condition of Indoor: 27°CD.B./19.5°CW.B. (81°FD.B./67°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)

*Above specification data is


subject to rounding variation.

MEES18K047 41
PUCY-P-Y(S)KD, EP-YSKD

<Accessories>

2. EXTERNAL DIMENSIONS
●Connecting pipe

MEES18K047
<Gas> •Pipe (ID19.05×OD22.2) • • • • P200 1pc.
•Pipe (ID25.4×OD22.2) • • • • P250,P300 1pc.
0000005024.BOOK

740
<Liquid> •Pipe (ID9.52×OD9.52) • • • • P200,P250 1pc.
•Pipe reducer (ID9.52×OD12.7) • • • • P250 1pc.
•Pipe (ID12.7×OD12.7) • • • • P300 1pc.
•Pipe reducer (ID12.7×OD9.52) • • • • P300 1pc.
Note1.Please refer to the next page for information
regarding necessary spacing around the
920 unit and foundation work.
2.At brazing of pipes,wrap the refrigerant service valve
Discharge air
Top view with wet cloth and keep the temperature of
refrigerant service valve under 120˚C.
2. EXTERNAL DIMENSIONS

Connecting pipe specifications

303
Control box Diameter
PUCY-P200, 250, 300YKD(-BS)

Model Refrigerant pipe *1 Service valve


Liquid Gas Liquid Gas

Intake Intake
air PUCY-P200YKD(-BS) ø9.52 Brazed ø19.05
Intake air
air ø9.52
ø9.52 Brazed
PUCY-P250YKD(-BS) (ø12.7 Brazed)

1650
ø22.2 Brazed
*2
Service ø25.4

1347
Refrigerant service valve panel ø9.52 Brazed
<gas> PUCY-P300YKD(-BS) (ø12.7 Brazed) ø12.7
42 ページ 2018年11月12日 月曜日 午後6時54分

4 *3,*4
Refrigerant service valve 7 1
*1 Connect by using the connecting pipes (for bottom piping and front piping)

88
<liquid>
that are supplied.

72
*2 Furthest piping length (OU from IU)≥90m

54
*3 Furthest piping length (OU from IU)≥40m

262
222
131
*4 Indicates dimensions and connection specifications in the case the unit is
used in combination with other outdoor units.
3 204 98

89
57 20 20 57 2×2-80×35 Oval hole
586 251 102 <Sling hole> Usage Specifications
NO.
Front view 1 Front through hole 102 × 72 Knockout hole
Left side view
For pipes
2×2-14×20 Oval hole
222 150 2 Bottom through hole 150 × 94 Knockout hole
251 83 3 Front through hole ø65 or ø40 Knockout hole

84
177

137
29.5
4 Front through hole ø52 or ø27 Knockout hole

121
For wires

147
196
5 Bottom through hole ø65 Knockout hole

94
5 6 Bottom through hole ø52 Knockout hole
2

681
6 (740) 7 For transmission cables Front through hole ø34 Knockout hole
Refrigerant service Refrigerant service (Mounting pitch)
valve <liquid> valve <gas>

80 760 80
29.5

(Mounting pitch)
Bottom view
Unit: mm

42
Y-Series (Cooling-only)
0000005024.BOOK

1.Required space around the unit ●In case of collective installation


1 When multiple units are installed adjacent to each other, secure enough space to allow

MEES18K047
●In case of single installation for air circulation and walkway between groups of units as shown in the figures below.
1 Secure enough space around the unit as shown in the figure below. 2 At least two sides must be left open.
· With a space of at least · With a space of at least 3 As with the single installation, add the height that exceeds the height limit<h>
300mm to the wall on 100mm to the wall on to the figures that are marked with an asterisk.
the back of the unit the back of the unit 4 If there is a wall at both the front and the rear of the unit, install up to six units
consecutively in the side direction and provide a space of 1000mm or more as inlet space/
passage space for each six units.
<To be left open>

100 min.*

300 min.*
450 min.*
Wall <H> Wall <H> 450 min.

300 min.*
100 min.*
2. EXTERNAL DIMENSIONS

Front
Front

Front
Front
Front
50 min.* 50 min.* Front Front
450 min.

450 min.*
Wall <H>

Wall<H>
15 min.* 15 min.*

<To be left open>


<To be left open>

<To be left open>

450 min.*
<To be left open>
Wall <H> Wall <H> 100 min.*
PUCY-P200, 250, 300YKD(-BS)

450 min.*
<Top view> <Top view> 30 min. 100 min.

450 min.*
<Unit:mm> <To be left open>

2 When the height of the walls on the front,back or on the sides<H>


exceeds the wall height limit as defined below Wall <H>
Wall <H>
43 ページ 2018年11月12日 月曜日 午後6時54分

300 min.*
add the height that exceeds the height limit <h> to the figures that
300 min.*

are marked with an asterisk.


Wall <H>
<Wall height limit> Front: Up to the unit height

h
Back: Up to 500mm from
the unit bottom

H
Front
Front
Front
Front Front

15 min.*

h
900 min.

900 min.

Side: Up to the unit height

Front

Unit height
450 min. 450 min.
<To be left open>

<To be left open>

500
<To be left open>

<Side view> <To be left open>


Wall<H> 1000 min.*
<Unit:mm>
300 min.*

2.Foundation work
1 Take into consideration the surface strength,water drainage route,
piping route,and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
2 Build the foundation in such way that the corner of the installation leg is
30mm max.

securely supported as shown in the right figure.(Fig.A)


When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
3 The protrusion length of the anchor bolt must not exceed 30mm.(Fig.A) M10 anchor bolt Fixing plate
4 Use four fixing plates as shown in the right figure <field supply required> <field supply required> <field supply required>
when using post-installed anchor bolts.(Fig.B) Fig.A Fig.B
5 To prevent small animals and water and snow from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
6 When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
7 Refer to the Installation Manual when installing units on an installation base.
Unit: mm
Y-Series (Cooling-only)

43
PUCY-P-Y(S)KD, EP-YSKD
PUCY-P-Y(S)KD, EP-YSKD

<Accessories>
●Connecting pipe

MEES18K047
<Gas> · Elbow (ID28.58XOD28.58)····P350,P400,P450 1pc.
0000005024.BOOK

<Liquid> · Pipe (ID15.88XOD15.88)····P350,P400,P450 1pc.


4X5-ø4.6 Hole · Pipe reducer(ID15.88XOD12.7)····P350,P400 1pc.

740
(Make hole at the plastic fan guard Note1. Please refer to the next page for information

600=150x4
for snow hood attachment) regarding necessary spacing around the

150
<Snow hood attachment hole> unit and foundation work.
2. At brazing of pipes,wrap the refrigerant service valve

70
19.5 1181 19.5 with wet cloth and keep the temperature of
1220 refrigerant service valve under 120°C.
Discharge air Top view
Connecting pipe specifications
2. EXTERNAL DIMENSIONS

Diameter

303
Model Refrigerant pipe*1 Service valve
Control box Liquid Gas Liquid Gas
ø12.7 Brazed
PUCY-P350, 400, 450YKD(-BS)

PUCY-P350YKD(-BS)
ø12.7 Brazed
Intake Intake PUCY-P400YKD(-BS) (ø15.88 Brazed) ø28.58 Brazed ø15.88 ø28.58
Intake air
air *2
air PUCY-P450YKD(-BS) ø15.88 Brazed
*1 Connect by using the connecting pipes (for bottom piping and front piping)

1650
Service

1347
Refrigerant service valve that are supplied.
<liquid> panel *2 Indicates dimensions and connection specifications in the case the unit is
used in combination with other outdoor units.
Refrigerant service valve
1
44 ページ 2018年11月12日 月曜日 午後6時54分

<gas> 4 NO. Usage Specifications


7

88
1 Front through hole 102 × 72 Knockout hole

72
For pipes

54
2 Bottom through hole 150 × 94 Knockout hole

238
172
131
3 Front through hole ø65 or ø40 Knockout hole
3

89
57 20 20 57 254 98 2X2-80X35 Oval hole 4 Front through hole ø52 or ø27 Knockout hole
586 301 102 <Sling hole> For wires
5 Bottom through hole ø65 Knockout hole
Left side view Front view
6 Bottom through hole ø52 Knockout hole
272 150 2X2-14X20 Oval hole
301 83 7 For transmission cables Front through hole ø34 Knockout hole
227

84
29.5

145

121
144
196
94
5

681
2 Refrigerant service
(740)
6 valve <gas>
Refrigerant service
(Mounting pitch)

valve <liquid>
80 1060 80
(Mounting pitch)
29.5

Bottom view
Unit: mm

44
Y-Series (Cooling-only)
0000005024.BOOK

1. Required space around the unit ● In case of collective installation


1 When multiple units are installed adjacent to each other, secure enough space to allow

MEES18K047
● In case of single installation for air circulation and walkway between groups of units as shown in the figures below.
1 Secure enough space around the unit as shown in the figure below. 2 At least two sides must be left open.
3 As with the single installation, add the height that exceeds the height limit<h>
· With a space of at least · With a space of at least
300mm to the wall on to the figures that are marked with an asterisk.
100mm to the wall on
4 If there is a wall at both the front and the rear of the unit, install up to six units
the back of the unit the back of the unit
consecutively in the side direction and provide a space of 1000mm or more as inlet space/
passage space for each six units. <To be left open>

100 min.*

300 min.*
450 min.*
Wall <H> 450 min.

300 min.*
Wall <H>

100 min.*
2. EXTERNAL DIMENSIONS

Front
Front

Front
Front
Front
Front Front
450 min.

450 min.*
Wall <H>

Wall <H>

<To be left open>


<To be left open>
<To be left open>
<To be left open>

450 min.*
15 min.* 15 min.* 50 min.* 50 min.* Wall <H>
PUCY-P350, 400, 450YKD(-BS)

Wall <H> 100 min.*


<Top view>

450 min.*
<Top view> 30 min. 100 min.

450 min.*
<Unit:mm>
<To be left open>

2 When the height of the walls on the front,back or on the sides<H>


exceeds the wall height limit as defined below Wall <H>
45 ページ 2018年11月12日 月曜日 午後6時54分

Wall <H>

300 min.*
300 min.*

add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk. Wall <H>
<Wall height limit> Front : Up to the unit height

h
Back : Up to 500mm from
the unit bottom

H
Front

Front
Front
Front
Front

15 min.*

h
900 min.

Side : Up to the unit height


900 min.

Front
450 min. 450 min.

Unit height
<To be left open>

<To be left open>

500
<To be left open>

<Side view> 1000 min.* <To be left open>


Wall <H>
<Unit:mm>
300 min.*

2. Foundation work
1 Take into consideration the surface strength,water drainage route,
piping route,and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
2 Build the foundation in such way that the corner of the installation leg is
30mm max.

securely supported as shown in the right figure.(Fig.A)


When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs. M10 anchor bolt Fixing plate
3 The protrusion length of the anchor bolt must not exceed 30mm.(Fig.A) <field supply required>
4 Use four fixing plates as shown in the right figure <field supply required> <field supply required>
when using post-installed anchor bolts.(Fig.B) Fig.A Fig.B
5 To prevent small animals and water and snow from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
6 When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
Unit: mm

7 Refer to the Installation Manual when installing units on an installation base.


Y-Series (Cooling-only)

45
PUCY-P-Y(S)KD, EP-YSKD
PUCY-P-Y(S)KD, EP-YSKD

MEES18K047
<Accessories>
0000005024.BOOK

●Connecting pipe
<Gas> · Elbow (ID28.58XOD28.58)····P500 1pc.
2X7-ø4.6 Hole <Liquid> · Pipe (ID15.88XOD15.88)····P500 1pc.

740
(Make hole at he plastic fan guard

600=150X4
for snow hood attachment) Note1. Please refer to the next page for information

150
<Snow hood attachment hole> regarding necessary spacing around the
49 unit and foundation work.

70
19.5 831 831 19.5 2. At brazing of pipes, wrap the refrigerant service valve
PUCY-P500YKD(-BS)

1750 with wet cloth and keep the temperature of


refrigerant service valve under 120°C.
2. EXTERNAL DIMENSIONS

Discharge air Top view

303
Connecting pipe specifications
Control box
Diameter
Model Refrigerant pipe*1 Service valve
Intake Intake Liquid Gas Liquid Gas
Intake air air PUCY-P500YKD(-BS) ø15.88 Brazed ø28.58 Brazed ø15.88 ø28.58
air
*1 Connect by using the connecting pipes (for bottom piping and front piping)
Service panel Service

1650
that are supplied.
panel
Refrigerant service valve

1347
46 ページ 2018年11月12日 月曜日 午後6時54分

<liquid> Usage
NO. Specifications
Refrigerant service valve 3 4 7
<gas> 1 Front through hole 102 × 72 Knockout hole
1

88
Fan box
150 × 94 Knockout hole

72
2 For pipes Bottom through hole

54
3 Front through hole ø65 or ø40 Knockout hole

238
172
131
4 Front through hole ø52 or ø27 Knockout hole
544 98

89
57 20 20 57 591 102 2X2-80X35 Oval hole
5 For wires Bottom through hole ø65 Knockout hole
586 <Sling hole>
Front view 6 Bottom through hole ø52 Knockout hole
Left side view 2X3-14X20 Oval hole
561 150
590 83 7 For transmission cables Front through hole ø34 Knockout hole
516

84
29.5

145

121
144
196
94
5 6
2
681
(740)

Refrigerant service Refrigerant service


(Mounting pitch)

valve <liquid> valve <gas>

80 795 795 80
29.5

(Mounting pitch) (Mounting pitch)


Bottom view
Unit: mm

46
Y-Series (Cooling-only)
0000005024.BOOK

1. Required space around the unit ●In case of collective installation


1 When multiple units are installed adjacent to each other, secure enough space to allow

MEES18K047
● In case of single installation for air circulation and walkway between groups of units as shown in the figures below.
1 Secure enough space around the unit as shown in the figure below. 2 At least two sides must be left open.
3 As with the single installation, add the height that exceeds the height limit<h>
·With a space of at least ·With a space of at least to the figures that are marked with an asterisk.
300mm to the wall on 100mm to the wall on 4 If there is a wall at both the front and the rear of the unit, install up to three units
the back of the unit the back of the unit consecutively in the side direction and provide a space of 1000mm or more as inlet space/
passage space for each three units.
<To be left open>
450 min.*

100 min.*

300 min.*
450 min.
PUCY-P500YKD(-BS)

Wall <H> Wall <H>

300 min.*
100 min.*
2. EXTERNAL DIMENSIONS

Front
Front

Front
Front
Front

Wall <H>
Wall <H>

Front Front

450 min.*

450 min.*
15 min.* 15 min.* 50 min.* 50 min.* 450 min.

<To be left open>


<To be left open>
<To be left open>
<To be left open>
Wall <H> Wall <H>
<Top view> <Top view> 100 min. 100 min.*

450 min.*
30 min.

450 min.*
<Unit:mm> <To be left open>

2 When the height of the walls on the front,back or on the sides<H>


exceeds the wall height limit as defined below
47 ページ 2018年11月12日 月曜日 午後6時54分

Wall <H> Wall <H>


300 min.*

300 min.*
add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk.
Wall <H>

h
<Wall height limit> Front: Up to the unit height
Back: Up to 500mm from

H
the unit bottom Front Front

15 min.*

h
900 min.
900 min.

Front
Front
Front

H
Side: Up to the unit height

Front

Unit height
500
<To be left open>

<To be left open>


<To be left open>

450 min. 450 min.


<Side view> <To be left open>
Wall <H> 1000 min.*
300 min.*

2. Foundation work <Unit:mm>

1 Take into consideration the surface strength,water drainage route,


piping route,and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
30mm max.

2 Build the foundation in such way that the corner of the installation leg is
securely supported as shown in the right figure.(Fig.A)
When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs. Fixing plate
M10 anchor bolt
3 The protrusion length of the anchor bolt must not exceed 30mm.(Fig.A) <field supply required>
<field supply required>
4 Use four fixing plates as shown in the right figure <field supply required>
Fig.A Fig.B
when using post-installed anchor bolts.(Fig.B)
5 To prevent small animals and water and snow from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
6 When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
7 Refer to the Installation Manual when installing units on an installation base.
Unit: mm
Y-Series (Cooling-only)

47
PUCY-P-Y(S)KD, EP-YSKD
PUCY-P-Y(S)KD, EP-YSKD

740 920 30 920

MEES18K047
Discharge air Outdoor unit 1 Outdoor unit 2
0000005024.BOOK

PUCY-P550YSKD(-BS)
2. EXTERNAL DIMENSIONS

PUCY-EP400, 450, 500YSKD(-BS)

1650
Intake Intake Intake
air air air
48 ページ 2018年11月12日 月曜日 午後6時54分

e a
Left view c To indoor unit
Liquid Twinning pipe<optional parts>
Twinning pipe connection size f
d b To indoor unit
Package unit name PUCY-EP400YSKD(-BS) PUCY-EP450YSKD(-BS) PUCY-EP500YSKD(-BS) PUCY-P550YSKD(-BS)
Gas Twinning pipe<optional parts>
PUCY-P200YKD(-BS) PUCY-P250YKD(-BS) PUCY-P250YKD(-BS) PUCY-P300YKD(-BS) Front view
Component unit name Outdoor unit 1
Outdoor unit 2 PUCY-P200YKD(-BS) PUCY-P200YKD(-BS) PUCY-P250YKD(-BS) PUCY-P250YKD(-BS)
Outdoor Twinning Kit(optional parts) CMY-Y100VBK3 Liquid Gas
Liquid a Unit model c or e d or f
Indoor unit~Twinning pipe ø12.7 ø15.88
Gas b ø28.58 P200 ø9.52 ø22.2
Twinning pipe~Outdoor unit P250 ø9.52 ø22.2
Note1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size. P300 ø12.7 ø22.2
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a" and "b" in the figure)
must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).
Unit: mm

48
Y-Series (Cooling-only)
0000005024.BOOK

740 1220 30 920

MEES18K047
Discharge air Outdoor unit 1 Outdoor unit 2
PUCY-EP650YSKD(-BS)
2. EXTERNAL DIMENSIONS

1650
PUCY-P600, 650, 700, 750YSKD(-BS)

Intake Intake Intake


49 ページ 2018年11月12日 月曜日 午後6時54分

air air air

e
Left view c a To indoor unit
Liquid Twinning pipe<optional parts>
f
d b To indoor unit
Gas Twinning pipe<optional parts>
Front view
Twinning pipe connection size
Package unit name PUCY-EP650YSKD(-BS) PUCY-P600YSKD(-BS) PUCY-P650YSKD(-BS) PUCY-P700YSKD(-BS) PUCY-P750YSKD(-BS) Liquid Gas
Unit model
Outdoor unit 1 PUCY-P350YKD(-BS) PUCY-P350YKD(-BS) PUCY-P400YKD(-BS) PUCY-P450YKD(-BS) PUCY-P450YKD(-BS) c or e d or f
Component unit name ø9.52 ø22.2
Outdoor unit 2 PUCY-P300YKD(-BS) PUCY-P250YKD(-BS) PUCY-P250YKD(-BS) PUCY-P250YKD(-BS) PUCY-P300YKD(-BS) P250
Outdoor Twinning Kit(optional parts) CMY-Y100VBK3 CMY-Y200VBK2 P300 ø12.7 ø22.2
Liquid a ø15.88 ø19.05 Twinning pipe~Outdoor unit P350 ø12.7 ø28.58
Indoor unit~Twinning pipe
Gas b ø28.58 ø34.93 P400 ø15.88 ø28.58
P450 ø15.88 ø28.58
Note1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).
Unit: mm
Y-Series (Cooling-only)

49
PUCY-P-Y(S)KD, EP-YSKD
PUCY-P-Y(S)KD, EP-YSKD

740 1220 30 1220

MEES18K047
0000005024.BOOK

Discharge air Outdoor unit 1 Outdoor unit 2

PUCY-EP700YSKD(-BS)
2. EXTERNAL DIMENSIONS

PUCY-P800, 850, 900YSKD(-BS)

1650
Intake Intake Intake
air air air
50 ページ 2018年11月12日 月曜日 午後6時54分

e a
Left view c To indoor unit
Liquid Twinning pipe<optional parts>
f b
d To indoor unit
Gas Twinning pipe<optional parts>
Front view
Twinning pipe connection size
Package unit name PUCY-EP700YSKD(-BS) PUCY-P800YSKD(-BS) PUCY-P850YSKD(-BS) PUCY-P900YSKD(-BS) Liquid Gas
Outdoor unit 1 PUCY-P350YKD(-BS) PUCY-P400YKD(-BS) PUCY-P450YKD(-BS) PUCY-P450YKD(-BS) Unit model c or e d or f
Component unit name
Outdoor unit 2 PUCY-P350YKD(-BS) PUCY-P400YKD(-BS) PUCY-P400YKD(-BS) PUCY-P450YKD(-BS) P350 ø12.7 ø28.58
Outdoor Twinning Kit(optional parts) CMY-Y200VBK2 Twinning pipe~Outdoor unit P400 ø15.88 ø28.58
Liquid a ø19.05 P450 ø15.88 ø28.58
Indoor unit~Twinning pipe
Gas b ø34.93 ø41.28

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).
Unit: mm

50
Y-Series (Cooling-only)
0000005024.BOOK

740 1750 30 1220

MEES18K047
Discharge air Outdoor unit 1 Outdoor unit 2
PUCY-P950YSKD(-BS)
2. EXTERNAL DIMENSIONS

1650
Intake Intake
air air Intake
51 ページ 2018年11月12日 月曜日 午後6時54分

air

Left view e a
c To indoor unit
Liquid Twinning pipe<optional parts>
f b
d To indoor unit
Twinning pipe connection size Gas Twinning pipe<optional parts>
Package unit name
Front view
PUCY-P950YSKD(-BS)
Outdoor unit 1 PUCY-P500YKD(-BS)
Component unit name
Outdoor unit 2 PUCY-P450YKD(-BS) Liquid Gas
Outdoor Twinning Kit(optional parts) CMY-Y200VBK2 Unit model
c or e d or f
Liquid a ø19.05 P450 ø15.88 ø28.58
Indoor unit~Twinning pipe Twinning pipe~Outdoor unit
Gas b ø41.28 P500 ø15.88 ø28.58
Note1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).
Unit: mm
Y-Series (Cooling-only)

51
PUCY-P-Y(S)KD, EP-YSKD
PUCY-P-Y(S)KD, EP-YSKD

MEES18K047
740 1750 30 1750
0000005024.BOOK

Discharge air Outdoor unit 1 Outdoor unit 2

PUCY-P1000YSKD(-BS)
2. EXTERNAL DIMENSIONS

1650
Intake Intake Intake
air air air
52 ページ 2018年11月12日 月曜日 午後6時54分

Left view e a
c To indoor unit
Liquid Twinning pipe<optional parts>
f b
d To indoor unit
Gas Twinning pipe<optional parts>
Front view
Twinning pipe connection size
Package unit name PUCY-P1000YSKD(-BS)
Outdoor unit 1 PUCY-P500YKD(-BS)
Component unit name
Outdoor unit 2 PUCY-P500YKD(-BS)
Outdoor Twinning Kit(optional parts) CMY-Y200VBK2
Liquid Gas
ø19.05 Unit model
Indoor unit~Twinning pipe Liquid a c or e d or f
Gas b ø41.28
Twinning pipe~Outdoor unit P500 ø15.88 ø28.58
Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).
Unit: mm

52
Y-Series (Cooling-only)
0000005024.BOOK

MEES18K047
740 1220 30 920 30 920
Discharge air Outdoor unit 1 Outdoor unit 2 Outdoor unit 3

PUCY-P1050YSKD(-BS)
2. EXTERNAL DIMENSIONS

1650
Intake Intake Intake
air air air
53 ページ 2018年11月12日 月曜日 午後6時54分

PUCY-EP750, 800, 850, 900, 950YSKD(-BS)

e g i a
Left view c To indoor unit
Liquid Twinning pipe 1<optional parts> Liquid Twinning pipe 2<optional parts>
j
f h d b To indoor unit
Front view Gas Twinning pipe 1<optional parts> Gas Twinning pipe 2 <optional parts>
Twinning pipe connection size
Package unit name PUCY-EP750YSKD(-BS)
PUCY-EP800YSKD(-BS) PUCY-EP850YSKD(-BS) PUCY-EP900YSKD(-BS) PUCY-EP950YSKD(-BS) PUCY-P1050YSKD(-BS)
Outdoor unit 1 PUCY-P350YKD(-BS) PUCY-P350YKD(-BS) PUCY-P350YKD(-BS) PUCY-P350YKD(-BS) PUCY-P350YKD(-BS) PUCY-P450YKD(-BS) Liquid Gas
Unit model
Component unit name Outdoor unit 2 PUCY-P200YKD(-BS) PUCY-P250YKD(-BS) PUCY-P250YKD(-BS) PUCY-P300YKD(-BS) PUCY-P300YKD(-BS) PUCY-P300YKD(-BS) e or g or i f or h or j
Outdoor unit 3 PUCY-P200YKD(-BS) PUCY-P200YKD(-BS) PUCY-P250YKD(-BS) PUCY-P250YKD(-BS) PUCY-P300YKD(-BS) PUCY-P300YKD(-BS) P200 ø9.52 ø22.2
Outdoor Twinning Kit(optional parts) CMY-Y300VBK3 P250 ø9.52 ø22.2
Liquid a ø19.05 ø12.7 ø22.2
Indoor unit~Twinning pipe 2 Twinning pipe~Outdoor unit P300
Gas b ø34.93 ø41.28 P350 ø12.7 ø28.58
Liquid c ø19.05 P400 ø15.88 ø28.58
Twinning pipe 1~Twinning pipe 2 Gas d ø15.88 ø28.58
ø34.93 P450
Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).
Unit: mm
Y-Series (Cooling-only)

53
PUCY-P-Y(S)KD, EP-YSKD
PUCY-P-Y(S)KD, EP-YSKD

740 1220 30 1220 30 920

MEES18K047
0000005024.BOOK

Discharge air Outdoor unit 1 Outdoor unit 2 Outdoor unit3

PUCY-P1100YSKD(-BS)
2. EXTERNAL DIMENSIONS

PUCY-EP1000YSKD(-BS)

1650
Intake Intake Intake
air air air
54 ページ 2018年11月12日 月曜日 午後6時54分

Left view g i a
e c To indoor unit
Liquid Twinning pipe 2 <optional parts>
Liquid Twinning pipe 1 <optional parts>
h j
d b To indoor unit
f
Twinning pipe connection size Gas Twinning pipe 2 <optional parts>
Front view Gas Twinning pipe 1 <optional parts>
Package unit name PUCY-EP1000YSKD(-BS) PUCY-P1100YSKD(-BS)
Outdoor unit 1 PUCY-P350YKD(-BS) PUCY-P450YKD(-BS)
Component unit name Outdoor unit 2 PUCY-P350YKD(-BS) PUCY-P350YKD(-BS)
Outdoor unit 3 PUCY-P300YKD(-BS) PUCY-P300YKD(-BS)
Outdoor Twinning Kit(optional parts) CMY-Y300VBK3 Liquid Gas
Liquid a Unit model e or g or i f or h or j
Indoor unit~Twinning pipe 2 ø19.05
Gas b ø41.28 P300 ø12.7 ø22.2
Liquid c ø19.05 Twinning pipe~Outdoor unit P350 ø12.7 ø28.58
Twinning pipe 1~Twinning pipe2
Gas d ø34.93 P450 ø15.88 ø28.58

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).
Unit: mm

54
Y-Series (Cooling-only)
0000005024.BOOK

740 1220 30 1220 30 1220

MEES18K047
Discharge air Outdoor unit 1 Outdoor unit 2 Outdoor unit 3
2. EXTERNAL DIMENSIONS

1650
Intake Intake Intake
PUCY-EP1050, 1100YSKD(-BS)

air air air


55 ページ 2018年11月12日 月曜日 午後6時54分

i
PUCY-P1150, 1200, 1250, 1300, 1350YSKD(-BS)

Left view g a
e c To indoor unit
Liquid Twinning pipe 1 <optional parts> Liquid Twinning pipe2 <optional parts>
h j b
f d To indoor unit
Gas Twinning pipe 1<optional parts> Gas Twinning pipe 2 <optional parts>
Front view
Twinning pipe connection size
Package unit name PUCY-EP1050YSKD(-BS) PUCY-EP1100YSKD(-BS) PUCY-P1150YSKD(-BS) PUCY-P1200YSKD(-BS) PUCY-P1250YSKD(-BS) PUCY-P1300YSKD(-BS) PUCY-P1350YSKD(-BS)
Outdoor unit 1 PUCY-P350YKD(-BS) PUCY-P400YKD(-BS) PUCY-P400YKD(-BS) PUCY-P400YKD(-BS) PUCY-P450YKD(-BS) PUCY-P450YKD(-BS) PUCY-P450YKD(-BS)
Component unit name Outdoor unit 2 PUCY-P350YKD(-BS) PUCY-P350YKD(-BS) PUCY-P400YKD(-BS) PUCY-P400YKD(-BS) PUCY-P400YKD(-BS) PUCY-P450YKD(-BS) PUCY-P450YKD(-BS)
Outdoor unit 3 PUCY-P350YKD(-BS) PUCY-P350YKD(-BS) PUCY-P350YKD(-BS) PUCY-P400YKD(-BS) PUCY-P400YKD(-BS) PUCY-P400YKD(-BS) PUCY-P450YKD(-BS)
Outdoor Twinning Kit(optional parts) CMY-Y300VBK3
Liquid a ø19.05
Indoor unit~Twinning pipe 2
Gas b ø41.28
Liquid c ø19.05
Twinning pipe 1~Twinning pipe 2
Gas d ø34.93
Liquid Gas
Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size. Unit model
e or g or i f or h or j
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
P350 ø12.7 ø28.58
Be sure to see the Installation Manual for details of Twinning pipe installation. Twinning pipe~Outdoor unit P400 ø15.88 ø28.58
3. The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure) must have at least 500mm of straight section P450 ø15.88 ø28.58
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).
Unit: mm
Y-Series (Cooling-only)

55
PUCY-P-Y(S)KD, EP-YSKD
PUCY-P-Y(S)KD, EP-YSKD

MEES18K047
0000005024.BOOK

740 1750 30 1220 30 1220

Discharge air Outdoor unit 1 Outdoor unit 2 Outdoor unit 3


PUCY-P1400YSKD(-BS)
2. EXTERNAL DIMENSIONS

1650
Intake Intake Intake
air air air
56 ページ 2018年11月12日 月曜日 午後6時54分

Left view g i a
e c To indoor unit
Liquid Twinning pipe 1 <optional parts> Liquid Twinning pipe 2 <optional parts>
h j b
f d To indoor unit

Front view Gas Twinning pipe 1 <optional parts> Gas Twinning pipe 2 <optional parts>
Twinning pipe connection size
Package unit name PUCY-P1400YSKD(-BS)
Outdoor unit 1 PUCY-P500YKD(-BS)
Component unit name Outdoor unit 2 PUCY-P450YKD(-BS)
Outdoor unit 3 PUCY-P450YKD(-BS)
Outdoor Twinning Kit(optional parts) CMY-Y300VBK3 Liquid Gas
Unit model
Liquid a ø19.05 e or g or i f or h or j
Indoor unit~Twinning pipe 2
Gas b ø41.28 P450
Twinning pipe~Outdoor unit ø15.88 ø28.58
Liquid c ø19.05 P500
Twinning pipe 1~Twinning pipe 2
Gas d ø34.93

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure)
must have at least 500mm of straight section (*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).
Unit: mm

56
Y-Series (Cooling-only)
0000005024.BOOK

MEES18K047
740 1750 30 1750 30 1220

Discharge air Outdoor unit 1 Outdoor unit 2 Outdoor unit 3


PUCY-P1450YSKD(-BS)
2. EXTERNAL DIMENSIONS

1650
Intake
Intake Intake air
air air
57 ページ 2018年11月12日 月曜日 午後6時54分

g i a
e c To indoor unit
Left view
Liquid Twinning pipe 1 <optional parts> Liquid Twinning pipe 2 <optional parts>
h j b
f d To indoor unit
Gas Twinning pipe 2 <optional parts>
Gas Twinning pipe 1 <optional parts>

Front view
Twinning pipe connection size
Package unit name PUCY-P1450YSKD(-BS)
Outdoor unit 1 PUCY-P500YKD(-BS)
Component unit name Outdoor unit 2 PUCY-P500YKD(-BS)
Outdoor unit 3 PUCY-P450YKD(-BS)
Outdoor Twinning Kit (optional parts) CMY-Y300VBK3
Liquid a ø19.05 Liquid Gas
Indoor unit~Twinning pipe 2 Unit model
Gas b ø41.28 e or g or i f or h or j
Liquid c ø19.05 P450
Twinning pipe 1~Twinning pipe 2 Twinning pipe~Outdoor unit ø15.88 ø28.58
Gas d ø34.93 P500

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).
Unit: mm
Y-Series (Cooling-only)

57
PUCY-P-Y(S)KD, EP-YSKD
PUCY-P-Y(S)KD, EP-YSKD

MEES18K047
0000005024.BOOK

740 1750 30 1750 30 1750


Discharge air
Outdoor unit 1 Outdoor unit 2 Outdoor unit 3 PUCY-P1500YSKD(-BS)
2. EXTERNAL DIMENSIONS

Intake Intake

1650
air air Intake
air
58 ページ 2018年11月12日 月曜日 午後6時54分

g i a
e c To indoor unit
Left view
Liquid Twinning pipe 1 <optional parts> Liquid Twinning pipe 2 <optional parts>
h j
f d b To indoor unit
Gas Twinning pipe 1<optional parts> Gas Twinning pipe 2 <optional parts>

Twinning pipe connection size Front view


Package unit name PUCY-P1500YSKD(-BS)
Outdoor unit 1 PUCY-P500YKD(-BS)
Component unit name Outdoor unit 2 PUCY-P500YKD(-BS)
Outdoor unit 3 PUCY-P500YKD(-BS)
Outdoor Twinning Kit(optional parts) CMY-Y300VBK3
Liquid a ø19.05 Liquid Gas
Indoor unit~Twinning pipe 2 Unit model
Gas b ø41.28 e or g or i f or h or j
Liquid c ø19.05
Twinning pipe 1~Twinning pipe 2 Twinning pipe~Outdoor unit P500 ø15.88 ø28.58
Gas d ø34.93

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure) must have at least 500mm of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).
Unit: mm

58
Y-Series (Cooling-only)
0000005024.BOOK 59 ページ 2018年11月12日 月曜日 午後6時54分

3. CENTER OF GRAVITY Y-Series (Cooling-only)

3. CENTER OF GRAVITY

PUCY-P200, 250, 300YKD (-BS)

920 740

PUCY-P-Y(S)KD, EP-YSKD
Unit: mm
Model X Y Z
PUCY-P200YKD(-BS) 316 286 617
1347

PUCY-P250YKD(-BS) 317 296 634


PUCY-P300YKD(-BS) 309 282 610
Z

X Y
760 80 681

PUCY-P350, 400, 450YKD (-BS)

1220 740

Unit: mm
Model X Y Z
PUCY-P350YKD(-BS) 436 305 587
1347

PUCY-P400YKD(-BS) 436 305 587


PUCY-P450YKD(-BS) 436 305 587
Z

X Y
1060 80 681

PUCY-P500YKD (-BS)

1750 740

Unit: mm
Model X Y Z
1347

PUCY-P500YKD(-BS) 678 326 645


Z

X Y
795 795 80 681

MEES18K047 59
PUCY-P-Y(S)KD, EP-YSKD

4. ELECTRICAL WIRING DIAGRAMS

MEES18K047
*1. Single-dotted lines indicate wiring not supplied with the unit.
0000005024.BOOK

*2. Dot-dash lines indicate the control box boundaries.


*3. Refer to the Data book for connecting input/output 63H1
signal connectors.
P
*4. Daisy-chain terminals (TB3) on the outdoor units in the
same refrigerant system together.
*5. Faston terminals have a locking function. 1 CNSNR 1 2 4 56 6
2 FAN Board 5
3 CN81
Make sure the terminals are securely locked in place 4 F121 green CN80 4
3
after insertion. Press the tab on the terminals to 5 DC700V 2
4A T C151,C152 1
4 CNDC
removed them. 1 1 3 red 12 6 5 4 21 321 4321 6
1 CN82 2 5
*6. Control box houses high-voltage parts. IPM 1 ON blue 3 CN801 CN61 CN2 CN4
4 green 4 M
CNVDC RSH01/02 CPU power red black CNLVA 3
Before inspecting the inside of the control box,turn off 7 6 CN83 1 supply circuit 2
U black 2 1 LEV1
the power,keep the unit off for at least 10 minutes, and SW001
Fan motor MS V 4 LED1:Normal operation(Lit) 6
5 ZNR400
confirm that the voltage between FT-P and FT-N on (Heat exchanger) 3~ /Error(Blink) 72C 2 CNLVB 4 M
1 CNINV U
INV Board has dropped to DC20V or less. W LED4:CPU in operation 6 1 CN72 Power failure Control Board red 3
detection circuit 2
C100 1 LEV2
DCL
R1,R5 *5 LED1 3
black 6 LED3
red 1 2 1
3 72C 4 SV1a CNTYP2
3 CN505 LED2:Normaloperation(Lit) black
red black CN43 2 Z25
6 CN5 21 yellow 1 X06 SWU2 SWU1 / Error(Blink) CNTYP5 3
CN4 1 3 1 10's 1's 1 ON 1 ON 1 ON
5 1 3 blue red SC-P2 SC-P1 CN6 digit digit green 1
7 Z24
4. ELECTRICAL WIRING DIAGRAMS

CN2 R5 D1 R4 6
3 LED1:Normal operation(Lit) SWP01 CNTYP4 2
*6 5 green 1
+ CN1
1 R6 P FT-P /Error(Blink) CN2 Unit address
10 10 10 SET UP(SW6-10)
4 setting CN213 2
C11 Z5 1 N FT-N C1 1 SW4 SW5 SW6 green t° TH6
Surge 1
absorber + U - C30,C32, C31,C33, ZNR1 CNTYP 3 LED1
Noise C34,C36 RSH1 4
DB1 C35,C37 black Display Function CN212 t° TH7
U 1 3
Filter + + setting/ setting red 2 t° TH3
IPM 1
R30,R32, R31,R33, t° Function
F4 R34 R35 THHS setting CN990 2
green t° TH15
AC250V 1
Noise filter DC12V CN51
PUCY-P200, 250, 300, 350, 400, 450YKD

6.3A T SC-V
SC-L1 1 3 1
red red SC-U SC-W *3 CN202 2 2 63LS
3 red 1 3
white white 4 Compressor ON/OFF output
Noise filter 5 Error detection output
black 3 1
black TB7 Power CN201 2 2 63HS1
SC-L2
selecting 1 3
60 ページ 2018年11月12日 月曜日 午後6時54分

1
CT3 SC-L3 connector
3 4 t° TH4
L1 L2 L3 N CN211 3
CN1A CN3 F01 CN40 green
CT12 CT22 2 t° TH2
green INV Board AC250V 1 234 ON 1
3 1 4 1 CN1B red white black 3.15A T yellow yellow green
TB21 TB22 TB23 TB24 blue red red
CNPOW CN3K CN3N CN3S CN3D CN62 CN41 CNPS
L CNAC 3 1 2 1 black 12 3 21 3 21 3 21 3 21 1 2 3 4 56 1 234 OFF 1 2345
CNAC2

*3
<Symbol explanation>
Symbol Explanation TB1
63H1 Pressure High pressure protection for the L1 L2 L3 N CN04 CNIT
1 3 red 21 1 2 3 4 CN102 red 54321
switch outdoor unit
red white black CNS2 LED1:Power supply to
63HS1 Pressure Discharge pressure V yellow Indoor/Outdoor
63LS sensor Low pressure U M-NET power transmission line
MS W supply circuit
72C Magnetic relay(inverter main circuit) 3~ TB3 TB7
C30~C37 Capacitor (inverter main circuit) M1 M2 M1 M2 S
Current sensor(AC) L1 L2 L3 N Motor TP1 TP2
CT12,22,3 (Compressor)
DCL DC reactor Power Source
L Choke coil (for high frequency noise reduction) 3N~ M-NET Board
50/60Hz
LEV1 Linear HIC bypass,Controls refrigerant 380/400/415V
expansion flow in HIC circuit
valve
LEV2 Pressure control, Refrigerant flow
rate control *4
R1,5 Resistor For inrush current prevention Indoor/Outdoor Central control
RSH01/02, For current detection transmission transmission
RSH1 cable cable
SV1a Solenoid For opening/closing the bypass
valve circuit under the O/S
TB1 Terminal Power supply
TB3 block Indoor/Outdoor transmission cable
TB7 Central control transmission cable
TH2 Thermistor Subcool bypass outlet
temperature
TH3 Pipe temperature
TH4 Discharge pipe temperature
TH6 Subcooled liquid refrigerant
temperature
TH7 OA temperature
TH15 Compressor shell bottom temperature
THHS IPM temperature
Z24,25 Function setting connector

60
Y-Series (Cooling-only)
0000005024.BOOK

MEES18K047
1 CNSNR 6
2 5
3 FAN Board CN80 4
4 F121 3
5 DC700V 2
4A T C151,C152 1
4 63H1
1 ON 1
IPM 2 P
1 CN81
CNVDC 6 green
RSH01/02
7 SW001
U 6
MS V 4 LED1:Normal operation(Lit)
PUCY-P500YKD

3~ /Error(Blink)
1 CNINV
Fan motor W LED4:CPU in operation
(Heat exchanger) 1 CNSNR
FAN Board 1 2 456 6
2 5
3 CN81 CN80 4 CNDC
4 F121 green 3 1 3 red 21 12 6 5 4 21 3 21 3 21 4 3 21 4 3 21 6
CN104 4 1 CONNECT Board 1 3 5 DC700V 2 5
1 CN332 CN801 CN61 CN2 CN2A CN4 CN4A 4
FT2-P FT2-N CN202 4A T C151,C152 blue red green black black CNLVA M
green 4 CPUpower 3
1 2
F101 C102 IPM CN82 2 supply circuit 1 LEV1
DC700V
C101 + + 1 1 ON ZNR400
blue 3 5
4A T CNVDC RSH01/02 4 6
CN201 3 72C 2 U
black R101~R103 R104~R106 7 CN83 1 Power failure
4 1 blue 1 6 6 1 CN72 CNLVB 4 M
CN103 U black 2 detection circuit red 3
SW001 2
MS V 4 LED1:Normal operation(Lit) 6 Control Board 1 LEV2
Fan motor 3~ CNINV /Error(Blink)
1 SV1a 3
*1. Single-dotted lines indicate wiring not supplied (Heat exchanger) W LED4:CPU in operation 3 CN505 LED1
with the unit. C100 X06 LED3 1
1 CNTYP2
R1,R5 *5 black
*2. Dot-dash lines indicate the control box boundaries. DCL black
6
LED2:Normal operation(Lit) Z25
4. ELECTRICAL WIRING DIAGRAMS

*3. Refer to the Data book for connecting input/output red 1 2 5 SWU2 SWU1 /Error(Blink) CNTYP5 3
10's 1's 1 ON 1 ON 1 ON green
3 72C 4
SV5b CN506 digit digit 1
signal connectors. 3 red Z24
red black CN43 2 CNTYP4 2
6 CN5 21 yellow 1 21S4b X08 SWP01 green 1
*4. Daisy-chain terminals (TB3) on the outdoor units in 5 CN4 red 1 3 SC-P2 1
1 3 blue SC-P1 CN6 Unit address
black red 7 10 10 10 SET UP(SW6-10)
the same refrigerant system together. CN2 R5 D1 R4 6 X07 setting
3 *6 LED1:Normal operation(Lit) 5 SW4 SW5 SW6
*5. Faston terminals have a locking function. + CN1 CN213 2
R6 P FT-P /Error(Blink) CN2 t° TH6
1 LED1 green 1
Make sure the terminals are securely locked in place 4 Display Function
Surge C11 Z5 N FT-N C1 1 4 t° TH7
1 setting/ setting CN212 3
after insertion. Press the tab on the terminals to absorber + U - ZNR1 red
61 ページ 2018年11月12日 月曜日 午後6時54分

C30,C32, C31,C33, RSH1 2 t° TH3


Noise C34,C36 CNTYP 3 Function 1
removed them. DB1 C35,C37 U black
+ + 1 setting
Filter IPM CN990 2 t° TH15
*6. Control box houses high-voltage parts. Before t°
green 1
R30,R32, R31,R33, DC12V CN51
F4 R35 THHS
inspecting the inside of the control box,turn off R34 1
Noise filter AC250V SC-V *3 3 1
the power, keep the unit off for at least 10 minutes, 6.3A T 3 CN202 2 2 63LS
4 Compressor ON/OFF output red 1 3
SC-L1 SC-U SC-W
and confirm that the voltage between FT-P and FT-N on 5 Error detection output
red red 3 1
INV Board has dropped to DC20V or less. CN201 2 2 63HS1
Noise filter white white 1 3
black black
TB7 Power
SC-L2 selecting 4
CN211 t° TH4
1 connector 3
CT3 SC-L3 green 2 TH2
F01 t°
<Symbol explanation> 3 AC250V CN40 1
L1 L2 L3 N CT12 CT22 3.15A T
CN1A CN3 INV Board 1 234 ON
Symbol Explanation green red white black black yellow yellow blue red green red
3 1 4 1 CN1B
TB21 TB22 TB23 TB24 CNAC2 CNPOW CN3K CN3N CN3S CN3D CN62 CN41 CNPS
21S4b 4-way valve(Heat exchanger capacity control)
CNAC 3 1 21 12 3 21 3 21 3 21 3 21 12 3 4 56 1 234 OFF 1 2345
63H1 Pressure High pressure protection for the L
switch outdoor unit
*3
63HS1 Pressure Discharge pressure
63LS sensor Low pressure
72C Magnetic relay (inverter main circuit)
C30~C37 Capacitor (inverter main circuit) TB1
L1 L2 L3 N CN04 CNIT
CT12,22,3 Current sensor(AC) 1 3 red 2 1 1 2 3 4 CN102 5 4 3 2 1 red
DCL DC reactor red white black CNS2 LED1:Power supply to
Choke coil (for high frequency noise reduction) V yellow
L Indoor/Outdoor
U MS W M-NET power transmission line
LEV1 Linear HIC bypass,Controls refrigerant supply circuit
expansion flow in HIC circuit 3~ TB3 TB7
valve L1 L2 L3 N M1 M2 M1 M2 S
LEV2 Pressure control, Refrigerant flow Motor TP1 TP2
rate control Power Source (Compressor)
R1,5 For inrush current prevention 3N~
Resistor 50/60Hz M-NET Board
RSH01/02, For current detection 380/400/415V
RSH1
SV1a Solenoid For opening/closing the bypass
valve circuit under the O/S
SV5b Outdoor unit heat exchanger *4
capacity control Indoor/Outdoor Central control
TB1 Power supply transmission transmission
Terminal
block Indoor/Outdoor transmission cable
cable cable
TB3
TB7 Central control transmission cable
TH2 Thermistor Subcool bypass outlet temperature
TH3 Pipe temperature
TH4 Discharge pipe temperature
TH6 Subcooled liquid refrigerant
temperature
TH7 OA temperature
TH15 Compressor shell bottom temperature
THHS IPM temperature
Z24,25 Functionࠉsettingࠉconnector
Y-Series (Cooling-only)

61
PUCY-P-Y(S)KD, EP-YSKD
0000005024.BOOK 62 ページ 2018年11月12日 月曜日 午後6時54分

5. SOUND LEVELS Y-Series (Cooling-only)

5. SOUND LEVELS

Measurement condition Sound level of PUCY-P300YKD(-BS)


90
PUCY-P200, 250, 300YKD(-BS) Stand 50/60Hz

80 Low 50/60Hz

Octave band sound level (dB)


70
NC-70
PUCY-P-Y(S)KD, EP-YSKD

1m 60
NC-60

50
NC-50

40
Measurement NC-40
1m

location 30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 73.5 67.5 63.0 58.5 53.0 47.5 46.5 38.5 61.0
Low noise mode 50/60Hz 54.5 58.0 48.0 47.5 43.0 40.5 35.5 37.0 50.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUCY-P200YKD(-BS)


90
Stand 50/60Hz

80 Low 50/60Hz
Octave band sound level (dB)

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 73.0 64.5 58.5 54.5 48.5 44.0 39.5 33.5 57.0
Low noise mode 50/60Hz 51.0 49.5 45.5 39.0 34.0 38.0 27.0 29.0 44.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUCY-P250YKD(-BS)


90
Stand 50/60Hz

80 Low 50/60Hz
Octave band sound level (dB)

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 68.5 63.5 59.5 56.5 50.0 45.0 44.0 38.0 58.0
Low noise mode 50/60Hz 52.0 56.0 45.5 47.5 40.0 35.5 31.5 30.0 48.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.

MEES18K047 62
0000005024.BOOK 63 ページ 2018年11月12日 月曜日 午後6時54分

5. SOUND LEVELS Y-Series (Cooling-only)

Measurement condition Sound level of PUCY-P450YKD(-BS)


90
PUCY-P350, 400, 450YKD(-BS) Stand 50/60Hz

80 Low 50/60Hz

Octave band sound level (dB)


70
NC-70

PUCY-P-Y(S)KD, EP-YSKD
1m 60
NC-60

50
NC-50

40
Measurement NC-40
1m

location 30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 80.5 68.0 64.5 60.0 55.5 51.0 51.0 42.5 63.0
Low noise mode 50/60Hz 67.0 61.5 54.5 50.0 45.0 45.5 41.0 35.5 54.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUCY-P350YKD(-BS)


90
Stand 50/60Hz

80 Low 50/60Hz
Octave band sound level (dB)

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 78.5 66.0 62.5 58.0 53.5 49.0 49.0 40.5 61.0
Low noise mode 50/60Hz 65.0 59.5 52.5 48.0 43.0 43.5 39.0 33.5 52.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUCY-P400YKD(-BS)


90
Stand 50/60Hz

80 Low 50/60Hz
Octave band sound level (dB)

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 80.5 68.0 64.5 60.0 55.5 51.0 51.0 42.5 63.0
Low noise mode 50/60Hz 66.0 60.5 53.5 49.0 44.0 44.5 40.0 34.5 53.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.

MEES18K047 63
0000005024.BOOK 64 ページ 2018年11月12日 月曜日 午後6時54分

5. SOUND LEVELS Y-Series (Cooling-only)

Measurement condition Measurement condition


PUCY-P500YKD(-BS) PUCY-P550YSKD(-BS)
PUCY-P-Y(S)KD, EP-YSKD

1m 1m

Measurement Measurement
location location

1m
1m

Sound level of PUCY-P500YKD(-BS) Sound level of PUCY-P550YSKD(-BS)


90 90
Stand 50/60Hz Stand 50/60Hz

80 Low 50/60Hz 80 Low 50/60Hz


Octave band sound level (dB)

Octave band sound level (dB)

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 Approximate minimum 20 Approximate minimum


audible limit on NC-20 audible limit on NC-20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz) Octave band central frequency (Hz)
63 125 250 500 1k 2k 4k 8k dB(A) 63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 78.5 74.0 67.0 63.0 56.5 52.5 46.5 44.0 65.0 Standard 50/60Hz 75.0 69.5 65.0 61.0 55.5 50.0 49.0 42.0 63.0
Low noise mode 50/60Hz 68.0 62.5 55.5 51.0 46.0 46.5 42.0 36.5 55.0 Low noise mode 50/60Hz 57.0 60.5 50.5 51.0 45.5 42.0 37.5 38.5 52.5
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe. from Low noise mode automatically in the case that the operation condition is severe.

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.

MEES18K047 64
0000005024.BOOK 65 ページ 2018年11月12日 月曜日 午後6時54分

5. SOUND LEVELS Y-Series (Cooling-only)

Measurement condition Sound level of PUCY-P700YSKD(-BS)


90
PUCY-P600, 650, 700, 750YSKD(-BS) Stand 50/60Hz

80 Low 50/60Hz

Octave band sound level (dB)


70
NC-70

PUCY-P-Y(S)KD, EP-YSKD
1m 60
NC-60

50
NC-50

40
Measurement 1m NC-40
location
30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 81.0 69.5 65.5 61.5 56.5 52.0 52.0 44.0 64.5
Low noise mode 50/60Hz 67.0 62.5 55.0 52.0 46.0 46.0 41.5 36.5 55.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUCY-P600YSKD(-BS) Sound level of PUCY-P750YSKD(-BS)


90 90
Stand 50/60Hz Stand 50/60Hz

80 Low 50/60Hz 80 Low 50/60Hz


Octave band sound level (dB)

Octave band sound level (dB)

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 Approximate minimum 20 Approximate minimum


audible limit on NC-20 audible limit on NC-20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz) Octave band central frequency (Hz)
63 125 250 500 1k 2k 4k 8k dB(A) 63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 79.0 68.0 64.5 60.5 55.0 50.5 50.0 42.5 63.0 Standard 50/60Hz 81.5 71.0 67.0 62.5 57.5 52.5 52.5 44.0 65.5
Low noise mode 50/60Hz 65.0 60.5 53.0 50.5 44.5 43.5 39.5 34.5 53.0 Low noise mode 50/60Hz 67.5 63.0 55.5 52.0 47.0 46.5 42.0 39.5 55.5
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe. from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUCY-P650YSKD(-BS)


90
Stand 50/60Hz

80 Low 50/60Hz
Octave band sound level (dB)

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 81.0 69.5 65.5 61.5 56.5 52.0 52.0 44.0 64.5
Low noise mode 50/60Hz 66.5 62.5 54.5 52.0 46.0 45.5 41.0 36.5 54.5
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.

MEES18K047 65
0000005024.BOOK 66 ページ 2018年11月12日 月曜日 午後6時54分

5. SOUND LEVELS Y-Series (Cooling-only)

Measurement condition Sound level of PUCY-P900YSKD(-BS)


90
PUCY-P800, 850, 900YSKD(-BS) Stand 50/60Hz

80 Low 50/60Hz

Octave band sound level (dB)


70
NC-70
PUCY-P-Y(S)KD, EP-YSKD

60
NC-60
1m
50
NC-50

40
NC-40
Measurement
1m

location 30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 83.5 71.0 67.5 63.0 58.5 54.0 54.0 45.5 66.0
Low noise mode 50/60Hz 70.0 64.5 57.5 53.0 48.0 48.5 44.0 38.5 57.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUCY-P800YSKD(-BS)


90
Stand 50/60Hz

80 Low 50/60Hz
Octave band sound level (dB)

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 83.5 71.0 67.5 63.0 58.5 54.0 54.0 45.5 66.0
Low noise mode 50/60Hz 69.0 63.5 56.5 52.0 47.0 47.5 43.0 37.5 56.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUCY-P850YSKD(-BS)


90
Stand 50/60Hz

80 Low 50/60Hz
Octave band sound level (dB)

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 83.5 71.0 67.5 63.0 58.5 54.0 54.0 45.5 66.0
Low noise mode 50/60Hz 70.0 64.5 57.5 53.0 48.0 48.5 44.0 38.5 57.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.

MEES18K047 66
0000005024.BOOK 67 ページ 2018年11月12日 月曜日 午後6時54分

5. SOUND LEVELS Y-Series (Cooling-only)

Measurement condition Measurement condition


PUCY-P950YSKD(-BS) PUCY-P1000YSKD(-BS)

PUCY-P-Y(S)KD, EP-YSKD
1m 1m

Measurement Measurement
1m
location

1m
location

Sound level of PUCY-P950YSKD(-BS) Sound level of PUCY-P1000YSKD(-BS)


90 90
Stand 50/60Hz Stand 50/60Hz

80 Low 50/60Hz 80 Low 50/60Hz


Octave band sound level (dB)

Octave band sound level (dB)

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 Approximate minimum 20 Approximate minimum


audible limit on NC-20 audible limit on NC-20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz) Octave band central frequency (Hz)
63 125 250 500 1k 2k 4k 8k dB(A) 63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 82.5 75.0 69.0 65.0 59.0 55.0 52.5 46.5 67.5 Standard 50/60Hz 81.5 77.0 70.0 66.0 59.5 55.5 49.5 47.0 68.0
Low noise mode 50/60Hz 71.0 65.5 58.5 54.0 49.0 49.5 45.0 39.5 58.0 Low noise mode 50/60Hz 71.0 65.5 58.5 54.0 49.0 49.5 45.0 39.5 58.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe. from Low noise mode automatically in the case that the operation condition is severe.

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.

MEES18K047 67
0000005024.BOOK 68 ページ 2018年11月12日 月曜日 午後6時54分

5. SOUND LEVELS Y-Series (Cooling-only)

Measurement condition Measurement condition


PUCY-P1050YSKD(-BS) PUCY-P1100YSKD(-BS)
PUCY-P-Y(S)KD, EP-YSKD

1m 1m

Measurement Measurement

1m
location
1m

location

Sound level of PUCY-P1050YSKD(-BS) Sound level of PUCY-P1100YSKD(-BS)


90 90
Stand 50/60Hz Stand 50/60Hz

80 Low 50/60Hz 80 Low 50/60Hz


Octave band sound level (dB)

Octave band sound level (dB)

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 Approximate minimum 20 Approximate minimum


audible limit on NC-20 audible limit on NC-20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz) Octave band central frequency (Hz)
63 125 250 500 1k 2k 4k 8k dB(A) 63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 82.0 72.5 68.5 64.0 59.0 54.0 53.5 45.0 66.5 Standard 50/60Hz 83.0 72.0 68.0 63.5 59.0 54.0 54.0 45.5 66.5
Low noise mode 50/60Hz 68.0 65.0 56.5 54.0 49.0 48.0 43.5 42.0 57.0 Low noise mode 50/60Hz 69.5 64.5 57.0 53.5 48.5 48.5 44.0 40.5 57.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe. from Low noise mode automatically in the case that the operation condition is severe.

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.

MEES18K047 68
0000005024.BOOK 69 ページ 2018年11月12日 月曜日 午後6時54分

5. SOUND LEVELS Y-Series (Cooling-only)

Measurement condition Sound level of PUCY-P1250YSKD(-BS)


90
PUCY-P1150, 1200, 1250, 1300, 1350YSKD(-BS) Stand 50/60Hz

80 Low 50/60Hz

Octave band sound level (dB)


70
NC-70

PUCY-P-Y(S)KD, EP-YSKD
60
NC-60
1m
50
NC-50

40
NC-40
Measurement

1m
location 30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 85.5 73.0 69.5 65.0 60.5 56.0 56.0 47.5 68.0
Low noise mode 50/60Hz 71.5 66.0 59.0 54.5 49.5 50.0 45.5 40.0 58.5
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUCY-P1150YSKD(-BS) Sound level of PUCY-P1300YSKD(-BS)


90 90
Stand 50/60Hz Stand 50/60Hz

80 Low 50/60Hz 80 Low 50/60Hz


Octave band sound level (dB)

Octave band sound level (dB)

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 Approximate minimum 20 Approximate minimum


audible limit on NC-20 audible limit on NC-20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz) Octave band central frequency (Hz)
63 125 250 500 1k 2k 4k 8k dB(A) 63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 85.0 72.5 69.0 64.5 60.0 55.5 55.5 47.0 67.5 Standard 50/60Hz 85.5 73.0 69.5 65.0 60.5 56.0 56.0 47.5 68.0
Low noise mode 50/60Hz 70.5 65.0 58.0 53.5 48.5 49.0 44.5 39.0 57.5 Low noise mode 50/60Hz 71.5 66.0 59.0 54.5 49.5 50.0 45.5 40.0 58.5
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe. from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUCY-P1200YSKD(-BS) Sound level of PUCY-P1350YSKD(-BS)


90 90
Stand 50/60Hz Stand 50/60Hz

80 Low 50/60Hz 80 Low 50/60Hz


Octave band sound level (dB)

Octave band sound level (dB)

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 Approximate minimum 20 Approximate minimum


audible limit on NC-20 audible limit on NC-20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz) Octave band central frequency (Hz)
63 125 250 500 1k 2k 4k 8k dB(A) 63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 85.5 73.0 69.5 65.0 60.5 56.0 56.0 47.5 68.0 Standard 50/60Hz 85.5 73.0 69.5 65.0 60.5 56.0 56.0 47.5 68.0
Low noise mode 50/60Hz 71.0 65.5 58.5 54.0 49.0 49.5 45.0 39.5 58.0 Low noise mode 50/60Hz 72.0 66.5 59.5 55.0 50.0 50.5 46.0 40.5 59.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe. from Low noise mode automatically in the case that the operation condition is severe.

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.

MEES18K047 69
0000005024.BOOK 70 ページ 2018年11月12日 月曜日 午後6時54分

5. SOUND LEVELS Y-Series (Cooling-only)

Measurement condition Measurement condition


PUCY-P1400YSKD(-BS) PUCY-P1450YSKD(-BS)
PUCY-P-Y(S)KD, EP-YSKD

1m 1m

Measurement
1m Measurement
location location

1m
Sound level of PUCY-P1400YSKD(-BS) Sound level of PUCY-P1450YSKD(-BS)
90 90
Stand 50/60Hz Stand 50/60Hz
Low 50/60Hz 80 Low 50/60Hz
80

70
Octave band sound level (dB)

70
Octave band sound level (dB)

NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 Approximate minimum 20 Approximate minimum


audible limit on NC-20
audible limit on NC-20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz) Octave band central frequency (Hz)

63 125 250 500 1k 2k 4k 8k dB(A) 63 125 250 500 1k 2k 4k 8k dB(A)


Standard 50/60Hz 85.0 76.0 70.5 66.0 60.5 56.5 55.0 48.0 68.5 Standard 50/60Hz 84.0 77.5 71.0 67.0 61.0 57.0 53.5 48.5 69.5
Low noise mode 50/60Hz 72.0 66.5 59.5 55.0 50.0 50.5 46.0 40.5 59.5 Low noise mode 50/60Hz 72.5 67.0 60.0 55.5 50.5 51.0 46.5 41.0 59.5
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe. from Low noise mode automatically in the case that the operation condition is severe.

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.

MEES18K047 70
0000005024.BOOK 71 ページ 2018年11月12日 月曜日 午後6時54分

5. SOUND LEVELS Y-Series (Cooling-only)

Measurement condition
PUCY-P1500YSKD(-BS)

PUCY-P-Y(S)KD, EP-YSKD
1m

Measurement
location

1m

Sound level of PUCY-P1500YSKD(-BS)


90
Stand 50/60Hz

80 Low 50/60Hz

70
Octave band sound level (dB)

NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)

63 125 250 500 1k 2k 4k 8k dB(A)


Standard 50/60Hz 83.5 79.0 72.0 68.0 61.5 57.5 51.5 49.0 70.0
Low noise mode 50/60Hz 73.0 67.5 60.5 56.0 51.0 51.5 47.0 41.5 60.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.

MEES18K047 71
0000005024.BOOK 72 ページ 2018年11月12日 月曜日 午後6時54分

5. SOUND LEVELS Y-Series (Cooling-only)

Measurement condition Sound level of PUCY-EP500YSKD(-BS)


90
PUCY-EP400, 450, 500YSKD(-BS) Stand 50/60Hz

80 Low 50/60Hz

Octave band sound level (dB)


70
NC-70
PUCY-P-Y(S)KD, EP-YSKD

60
1m NC-60

50
NC-50

40
Measurement NC-40
location
1m

30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 71.5 66.5 62.5 59.5 53.0 48.0 47.0 41.0 61.0
Low noise mode 50/60Hz 55.0 59.0 48.5 50.5 43.0 38.5 34.5 33.0 51.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUCY-EP400YSKD(-BS)


90
Stand 50/60Hz

80 Low 50/60Hz
Octave band sound level (dB)

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 76.0 67.5 61.5 57.5 51.5 47.0 42.5 36.5 60.0
Low noise mode 50/60Hz 54.0 52.5 48.5 42.0 37.0 41.0 30.0 32.0 47.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUCY-EP450YSKD(-BS)


90
Stand 50/60Hz

80 Low 50/60Hz
Octave band sound level (dB)

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 74.5 67.0 62.0 58.5 52.5 47.5 45.5 39.5 60.5
Low noise mode 50/60Hz 54.5 57.0 48.5 48.0 41.0 40.0 33.0 32.5 49.5
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.

MEES18K047 72
0000005024.BOOK 73 ページ 2018年11月12日 月曜日 午後6時54分

5. SOUND LEVELS Y-Series (Cooling-only)

Measurement condition Measurement condition


PUCY-EP650YSKD(-BS) PUCY-EP700YSKD(-BS)

PUCY-P-Y(S)KD, EP-YSKD
1m
1m

Measurement Measurement

1m
1m
location location

Sound level of PUCY-EP650YSKD(-BS) Sound level of PUCY-EP700YSKD(-BS)


90 90
Stand 50/60Hz Stand 50/60Hz

80 Low 50/60Hz 80 Low 50/60Hz


Octave band sound level (dB)

Octave band sound level (dB)

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 Approximate minimum 20 Approximate minimum


audible limit on NC-20 audible limit on NC-20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz) Octave band central frequency (Hz)
63 125 250 500 1k 2k 4k 8k dB(A) 63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 79.5 70.0 66.0 61.5 56.5 51.5 51.0 42.5 64.0 Standard 50/60Hz 81.5 69.0 65.5 61.0 56.5 52.0 52.0 43.5 64.0
Low noise mode 50/60Hz 65.0 61.5 53.5 50.5 45.5 45.0 40.0 38.0 54.0 Low noise mode 50/60Hz 67.0 61.5 54.5 50.0 45.0 45.5 41.0 35.5 54.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe. from Low noise mode automatically in the case that the operation condition is severe.

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.

MEES18K047 73
0000005024.BOOK 74 ページ 2018年11月12日 月曜日 午後6時54分

5. SOUND LEVELS Y-Series (Cooling-only)

Measurement condition Sound level of PUCY-EP850YSKD(-BS)


90
PUCY-EP750, 800, 850, 900, 950YSKD(-BS) Stand 50/60Hz

80 Low 50/60Hz

Octave band sound level (dB)


70
PUCY-P-Y(S)KD, EP-YSKD

NC-70

60
1m NC-60

50
NC-50

40
Measurement NC-40
location
1m

30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 79.5 69.5 65.5 62.0 56.5 51.5 51.0 44.0 64.0
Low noise mode 50/60Hz 65.0 62.0 53.5 52.0 45.5 44.0 40.0 36.0 54.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUCY-EP750YSKD(-BS) Sound level of PUCY-EP900YSKD(-BS)


90 90
Stand 50/60Hz Stand 50/60Hz

80 Low 50/60Hz 80 Low 50/60Hz


Octave band sound level (dB)

Octave band sound level (dB)

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 Approximate minimum 20 Approximate minimum


audible limit on NC-20 audible limit on NC-20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz) Octave band central frequency (Hz)
63 125 250 500 1k 2k 4k 8k dB(A) 63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 81.0 70.5 65.5 61.5 56.0 51.5 50.5 42.5 64.0 Standard 50/60Hz 80.0 71.0 66.5 62.5 57.0 52.5 52.0 44.0 65.0
Low noise mode 50/60Hz 65.0 60.0 53.5 48.5 43.5 45.0 39.0 35.5 52.5 Low noise mode 50/60Hz 65.5 63.0 54.5 52.5 47.0 46.0 41.0 39.0 55.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe. from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUCY-EP800YSKD(-BS) Sound level of PUCY-EP950YSKD(-BS)


90 90
Stand 50/60Hz Stand 50/60Hz

80 Low 50/60Hz 80 Low 50/60Hz


Octave band sound level (dB)

Octave band sound level (dB)

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 Approximate minimum 20 Approximate minimum


audible limit on NC-20 audible limit on NC-20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz) Octave band central frequency (Hz)
63 125 250 500 1k 2k 4k 8k dB(A) 63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 80.0 69.5 65.5 61.5 56.0 51.5 50.5 43.0 64.0 Standard 50/60Hz 81.0 72.5 68.0 63.5 58.5 53.5 53.0 44.5 66.0
Low noise mode 50/60Hz 65.0 61.0 53.5 50.5 44.5 44.5 39.5 35.5 53.5 Low noise mode 50/60Hz 66.0 63.5 55.0 52.5 48.0 46.5 42.0 41.0 55.5
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe. from Low noise mode automatically in the case that the operation condition is severe.

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.

MEES18K047 74
0000005024.BOOK 75 ページ 2018年11月12日 月曜日 午後6時54分

5. SOUND LEVELS Y-Series (Cooling-only)

Measurement condition Measurement condition


PUCY-EP1000YSKD(-BS) PUCY-EP1050, 1100YSKD(-BS)

PUCY-P-Y(S)KD, EP-YSKD
1m 1m

Measurement Measurement

1m

1m
location location

Sound level of PUCY-EP1000YSKD(-BS) Sound level of PUCY-EP1050YSKD(-BS)


90 90
Stand 50/60Hz Stand 50/60Hz

80 Low 50/60Hz 80 Low 50/60Hz


Octave band sound level (dB)

Octave band sound level (dB)

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 Approximate minimum 20 Approximate minimum


audible limit on NC-20 audible limit on NC-20
continuous noise continuous noise
10 10
63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz) Octave band central frequency (Hz)
63 125 250 500 1k 2k 4k 8k dB(A) 63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 82.0 71.5 67.5 63.0 58.0 53.5 53.0 45.0 66.0 Standard 50/60Hz 83.5 71.0 67.5 63.0 58.5 54.0 54.0 45.5 66.0
Low noise mode 50/60Hz 67.5 63.5 56.0 52.0 47.5 47.0 42.5 39.5 55.5 Low noise mode 50/60Hz 69.0 63.5 56.5 52.0 47.0 47.5 43.0 37.5 56.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe. from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUCY-EP1100YSKD(-BS)


90
Stand 50/60Hz

80 Low 50/60Hz
Octave band sound level (dB)

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20 Approximate minimum
audible limit on NC-20
continuous noise
10
63 125 250 500 1k 2k 4k 8k

Octave band central frequency (Hz)


63 125 250 500 1k 2k 4k 8k dB(A)
Standard 50/60Hz 84.5 72.0 68.5 64.0 59.5 55.0 55.0 46.5 67.0
Low noise mode 50/60Hz 70.0 64.5 57.5 53.0 48.0 48.5 44.0 38.5 57.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.

MEES18K047 75
0000005024.BOOK 76 ページ 2018年11月12日 月曜日 午後6時54分

6. VIBRATION LEVEL Y-Series (Cooling-only)

[PUCY-P200-500YKD, PUCY-(E)P400-1500YSKD]
6. VIBRATION LEVEL

Measurement condition

Measurement frequency: 1 Hz-80 Hz


Measurement point: Ground surface 20 cm away from the unit leg
PUCY-P-Y(S)KD, EP-YSKD

Installation condition: Direct installation on the concrete floor


Power source: 3-phase 4-wire 380-400-415 V 50/60 Hz
Operation condition: JIS condition (cooling, heating)
Measurement device: Vibration level meter for vibration pollution VM-1220C (JIS-compliant product)

Service panel side

Concrete

Measurement point

10cm
20cm

Vibration level
Model Vibration level (dB)
PUCY-P200YKD (-BS) 45
PUCY-P250, 300YKD (-BS) 46
PUCY-P350, 400YKD (-BS) 47
PUCY-P450, 500YKD (-BS) 48
PUCY-P550YSKD (-BS) 49
PUCY-P600, 650YSKD (-BS) 49.5
PUCY-P700, 750YSKD (-BS) 50.5
PUCY-P800YSKD (-BS) 50
PUCY-P850YSKD (-BS) 50.5
PUCY-P900, 950, 1000YSKD (-BS) 51
PUCY-P1050YSKD (-BS) 51.5
PUCY-P1100, 1150, 1200YSKD (-BS) 52
PUCY-P1250, 1300YSKD (-BS) 52.5
PUCY-P1350, 1400, 1450, 1500YSKD (-BS) 53
PUCY-EP400YSKD (-BS) 48
PUCY-EP450YSKD (-BS) 48.5
PUCY-EP500YSKD (-BS) 49
PUCY-EP650YSKD (-BS) 49.5
PUCY-EP700YSKD (-BS) 50.0
PUCY-EP750YSKD (-BS) 50.5
PUCY-EP800YSKD (-BS) 51
PUCY-EP850, 900, 950, 1000YSKD (-BS) 51.5
PUCY-EP1050YSKD (-BS) 52
PUCY-EP1100YSKD (-BS) 52
* Vibration level varies depending on the conditions of actual installation site.

MEES18K047 76
0000005024.BOOK 77 ページ 2018年11月12日 月曜日 午後6時54分

7. OPERATION TEMPERATURE RANGE Y-Series (Cooling-only)

7. OPERATION TEMPERATURE RANGE

• Cooling

86 30

77 25
Indoor temperature

PUCY-P-Y(S)KD, EP-YSKD
68 20
Range for continuous operation

59 15

50 10

41 5

32 0
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
-4 5 14 23 32 41 50 59 68 77 86 95 104 113 122
Outdoor temperature

MEES18K047 77
0000005024.BOOK 78 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

8-1. Selection of Cooling Units


8. CAPACITY TABLES

How to determine the capacity when less than or equal 100% indoor model size units are connected in total:
The purpose of this flow chart is to select the indoor and outdoor units. For other purposes, this flow chart is intended only for reference.

Determine the load (L) and


PUCY-P-Y(S)KD, EP-YSKD

the Indoor/Outdoor Temperature

Temporarily select the Indoor/Outdoor Units

Reselect the indoor units Reselect the indoor units

Reselect the outdoor units Reselect the outdoor units

Indoor Unit n
Total Indoor Units Capacity (CTi) = ∑ (Individual Rated Indoor Unit Capacity CTik ×
k=1 n: Total Number of Indoor Units
Individual Indoor Temperature Correction Coef. αk) (Fig.1) k: Indoor Unit Number

Outdoor Unit *1
Outdoor Unit Capacity (CTo) = Rated Outdoor Unit Capacity × Outdoor (If indoor to outdoor connectable
capacity ratio is less than 100%, the
Temperature Correction Coef. (Fig.2-1) × Piping Length
capacity correction is set as 100% )
Correction Coef. (Fig.4) × Defrost Correction Coef. (in heating operation)

Capacity No
Determination CTo ≤ CTi Maximum Capacity(CTx) = CTi

Yes
No
Maximum Capacity(CTx) = CTo L ≤ CTi

Yes
No
L ≤ CTo
Yes
Need to select smaller
Yes outdoor unit?

Yes No
Want to change to smaller
indoor units? No
Does it fulfill the load of
No each room?

CTik × αk
Individual Indoor Unit Capacity: CT'ik= CTx × n
∑ (CTim × αm)
m=1 Yes

No
Does it fulfill the load of
each room? Completed Selecting Units

Yes

Completed Selecting Units

*ck: Outdoor unit power input coefficient of k indoor unit room temp. (Fig.2-2)
*Mk: Number part of the k indoor unit model (e.g. P80 → 80)

Average Indoor temp. power input Coef. (cave) Average Indoor temp. power input Coef. (cave)
n n n n
cave = ∑ {ck × (Mk/ ∑ Mk)} cave = ∑ {ck × (Mk/ ∑ Mk)}
Input k=1 k=1 k=1 k=1
Calculation

Outdoor Unit Input = Rated Outdoor Unit Input × cave


Outdoor Unit Input = Rated Outdoor Unit Input × cave
× (CTi /CTo) (Fig.3)

(x) is the approximate correction function when less than or equal


100% model size units are input as connected.

1.3 Indoor Temperature


1.2
1.1 24°CW.B.
1.2 1.2 1.0 75°FW.B.
22°CW.B.
0.9
Ratio of power input

1.1 72°FW.B.
Ratio of cooling capacity

Ratio of cooling capacity

1.0 0.8 20°CW.B.


1.1 68°FW.B.
0.9 0.7 19°CW.B.
66°FW.B.
0.6
0.8 18°CW.B.
1.0 0.5 64°FW.B.
0.7 16°CW.B.
0.4 61°FW.B.
0.6 0.3 15°CW.B.
0.9 59°FW.B.
0.5 0.2
0.4 0.1
0.8 0.3 0.0
15 16 17 18 19 20 21 22 23 24 -5 0 5 10 15 20 25 30 35 40 45 50 °CD.B. -5 0 5 10 15 20 25 30 35 40 45 50 °CD.B.
23 32 41 50 59 68 77 86 95 104 113 122 °FD.B. 23 32 41 50 59 68 77 86 95 104 113 122 °FD.B.
Indoor Temperature [°CW.B.]
Outdoor Temperature Outdoor Temperature

Fig.1 Indoor unit temperature correction Fig.2-1 Outdoor unit temperature correction (capacity) Fig.2-2 Outdoor unit temperature correction (power input)
*1 When the indoor unit sizes from P100 to P140 or total capacity indoor units from P81 to P140 are connected to only 1 port on the BC controller in the R2 system, the cooling
capacity of the indoor unit should be multiplied by a correction factor of 0.97.

MEES18K047 78
0000005024.BOOK 79 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

How to determine the capacity when greater than 100% indoor model size units are connected in total:
The purpose of this flow chart is to select the indoor and outdoor units. For other purposes, this flow chart is intended only for reference.

Determine the load (L) and


the Indoor/Outdoor Temperature

PUCY-P-Y(S)KD, EP-YSKD
Temporarily select the indoor/outdoor units

Reselect the indoor units Reselect the indoor units

Reselect the outdoor units Reselect the outdoor units

Indoor Unit n
Total Indoor Units Capacity (CTi) = ∑ (Individual Rated Indoor Unit Capacity CTik ×
k=1 n: Total Number of Indoor Units
Individual Indoor Temperature Correction Coef. αk) (Fig.1) k: Indoor Unit Number

Outdoor Unit *1
Outdoor Unit Capacity (CTo) = Rated Outdoor Unit Capacity × (Model Size Ratio)
× Outdoor Temperature Correction Coef. (Fig.2-1) (x) is the approximate correction function when greater
× Piping Length Correction Coef. (Fig.4) × Defrost Correction Coef. (in heating) than 100% model size units are connected (Fig.3)

No
CTo ≤ CTi Maximum Capacity(CTx) = CTi

Yes
No
Maximum Capacity(CTx) = CTo L ≤ CTi

Yes
No
L ≤ CTo
Need to select smaller Yes
outdoor unit?
Yes

Yes No
Want to change to smaller
indoor units? No
Does it fulfill the load of
No each room?

CTik × αk
Individual Indoor Unit Capacity: CT'ik= CTx × n Yes
∑ (CTim × αm)
m=1
Completed Selecting Units

No
Does it fulfill the load of
Outdoor Unit Input
each room? = Rated Outdoor Unit Input ×
Rated Outdoor Unit Capacity No
Outdoor Temperature
Yes < Total Indoor Units Capacity Correction Coef. (Fig.2-2)
× (CTi / Rated Outdoor Capacity)
Completed Selecting Units (Fig.3)
(x) is the approximate correction function when less than or equal
*ck: Outdoor unit power input coefficient of k indoor unit room temp. (Fig.2-2) Yes 100% model size units are input as connected.
*Mk: Number part of the k indoor unit model (e.g. P80 → 80)

Average Indoor temp. power input Coef. (cave) Average Indoor temp. power input Coef. (cave)
n n n n
cave = ∑ {ck × (Mk/ ∑ Mk)} = ∑ {ck × (Mk/ ∑ Mk)}
k=1 k=1 k=1 k=1

Outdoor Unit Input =Rated Outdoor Unit Input × cave Outdoor Unit Input = Rated Outdoor Unit Input × cave
× (Model Size Ratio) (Fig.3) × (CTi /Rated Outdoor Capacity) (Fig.3)

(x) is the approximate correction function when greater than 100%


model size units are input as connected.
1.2 (x) Total capacity of indoor unit
1 100
1.0
Ratio of capacity

0.8 0.95

0.6
Cooling capacity correction factor

0.90
150
0.4
0.85
0.2
1.2 200
0.80
(x) 260
Ratio of power input

1.0
0.75
0.8
(x) 0.70
0.6

0.4 0.65
Cooling
Heating 0 20 40 60 80 100 120 140 160 180
0.2
50 100 150 200 250 300 Piping equivalent length (m)
Total capacity of indoor units

Fig.3 Correction by total indoor Fig.4 Correction of refrigerant piping length


*1 When the indoor unit sizes from P100 to P140 or total capacity indoor units from P81 to P140 are connected to only 1 port on the BC controller in the R2 system, the cooling
capacity of the indoor unit should be multiplied by a correction factor of 0.97.

MEES18K047 79
0000005024.BOOK 80 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

<Cooling>
Design Condition
Outdoor Design Dry Bulb Temperature 37 ºC
Total Cooling Load 19.0 kW
PUCY-P-Y(S)KD, EP-YSKD

Room1
Indoor Design Dry Bulb Temperature 27 ºC
Indoor Design Wet Bulb Temperature 20 ºC
Cooling Load 9.0 kW
Room2
Indoor Design Dry Bulb Temperature 24 ºC
Indoor Design Wet Bulb Temperature 18 ºC
Cooling Load 10.0 kW
<Other>
Indoor/Outdoor Equivalent Piping Length 50 m

1. Cooling Calculation

Ratio of cooling capacity


(1) Temporary Selection of Indoor Units 1.03
Room1 0.98

PLFY-P100 11.2 kW (Rated)


Room2
PEFY-P100 11.2 kW (Rated) 18 20

Indoor Temperature [°CW.B.]


(2) Total Indoor Units Capacity
P100 + P100 = P200 Fig.1 Indoor unit temperature correction
To be used to correct indoor unit only
(3) Selection of Outdoor Unit
The P200 outdoor unit is selected as total indoor units capacity is P200
Ratio of cooling capacity

0.99
PUHY-EP200 22.4 kW
(4) Total Indoor Units Capacity Correction Calculation
Room1
Indoor Design Wet Bulb Temperature Correction (20ºC) 1.03 (Refer to Fig.1) 37
Outdoor Temperature [°CD.B.]
Room2
Indoor Design Wet Bulb Temperature Correction (18ºC) 0.98 (Refer to Fig.1) Fig.2 Outdoor unit temperature correction
To be used to correct outdoor unit only
Total Indoor Units Capacity (CTi)
Total capacity of indoor unit
CTi = Σ (Indoor Unit Rating × Indoor Design Temperature Correction) V=Capacity of outdoor unit
V× 0.5
= 11.2 × 1.03 + 11.2 × 0.98
Cooling capacity correction factor

0.95
= 22.5 kW
V× 0.75
(5) Outdoor Unit Correction Calculation
Outdoor Design Dry Bulb Temperature Correction (37ºC) 0.99 (Refer to Fig.2)
V× 1.0
Piping Length Correction (50 m) 0.95 (Refer to Fig.3) V× 1.3

Total Outdoor Unit Capacity (CTo)


CTo = Outdoor Rating × Outdoor Design Temperature Correction × Piping Length Correction 50
= 22.4 × 0.99 × 0.95 Piping equivalent length (m)

= 21.0 kW
Fig.3 Correction of refrigerant piping length
(6) Determination of Maximum System Capacity (CTx)
Comparison of Capacity between Total Indoor Units Capacity (CTi) and Total Outdoor Unit Capacity (CTo)
CTi = 22.5 > CTo = 21.0, thus, select CTo.
CTx = CTo = 21.0 kW

(7) Comparison with Essential Load


Against the essential load 19.0kW, the maximum system capacity is 21.0kW: Proper outdoor units have been selected.

(8) Calculation of Maximum Indoor Unit Capacity of Each Room


CTx = CTo, thus, calculate by the calculation below
Room1
Maximum Capacity × Room1 Capacity after the Temperature Correction/(Room1,2 Total Capacity after the Temperature Correction)
= 21.0 × (11.2 × 1.03)/(11.2 × 1.03 + 11.2 × 0.98)
= 10.8 kW OK: fulfills the load 9.0kW
Room2
Maximum Capacity × Room2 Capacity after the Temperature Correction/(Room1,2Total Capacity after the Temperature Correction)
= 21.0 × (11.2 × 0.98)/(11.2 × 1.03 + 11.2 × 0.98)
= 10.2 kW OK: fulfills the load 10.0kW
Go on to the heating trial calculation since the selected units fulfill the cooling loads of Room 1, 2.

MEES18K047 80
0000005024.BOOK 81 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

3. Power input of outdoor unit


<Cooling>

PUCY-P-Y(S)KD, EP-YSKD
(1) Rated power input of outdoor unit 5.19 kW

(2) Calculation of the average indoor temperature power input coefficient


Coefficient of the outdoor unit for indoor unit 1 (Outdoor temp. 37 °CD.B., Indoor temp. 20 °CW.B.)
1.07
Coefficient of the outdoor unit for indoor unit 2 (Outdoor temp. 37 °CD.B., Indoor temp. 18 °CW.B.)
1.00

n n
Average indoor temp. power input coefficient (cave) = ∑ {ck × (Mk/ ∑ Mk)}
k=1 k=1

n: Total number of the indoor units


k: Number of the indoor unit
ck: Outdoor unit power input coefficient of k indoor unit room temp.
Mk: Number part of the k indoor unit model (e.g. P80 → 80)

= 1.07 × 100/(100 + 100) + 1 × 100/(100 + 100)


= 1.04

(3) No need to consider Coefficient of the partial load (CTi/CTo) -

(4) Outdoor power input (PIo)

Maximum System Capacity (CTx) = Total Outdoor unit Capacity (CTo), so use the following formula
PIo = Outdoor unit Cooling Rated Power Input × Correction Coefficient of Indoor temperature
= 5.19 × 1.04
= 5.4 kW

MEES18K047 81
0000005024.BOOK 82 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

8-2. Correction by temperature


CITY MULTI could have varied capacity at different designing temperature. Using the nominal cooling/heating capacity value and
the ratio below, the capacity can be observed at various temperature.

PUCY- P200YKD P250YKD Indoor unit temperature correction


PUCY-P-Y(S)KD, EP-YSKD

Nominal kW 22.4 28.0 To be used to correct indoor unit capacity only


Cooling
Capacity BTU/h 76,400 95,500
Input kW 4.66 5.95 1.2

PUCY- EP400YSKD

Ratio of cooling capacity


Nominal kW 44.8 1.1
Cooling
Capacity BTU/h 152,900
Input kW 9.93
1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.3 Indoor Temperature

1.2

1.1
24°CW.B.
75°FW.B.
1.0
22°CW.B.
0.9 72°FW.B.
Ratio of power input

0.8 20°CW.B.
68°FW.B.
0.7 19°CW.B.
66°FW.B.
0.6
18°CW.B.
0.5 64°FW.B.
16°CW.B.
0.4
61°FW.B.
0.3 15°CW.B.
59°FW.B.
0.2

0.1

0.0
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 82
0000005024.BOOK 83 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY- P300YKD Indoor unit temperature correction


Nominal kW 33.5 To be used to correct indoor unit capacity only
Cooling
Capacity BTU/h 114,300
Input kW 7.82 1.2

PUCY-P-Y(S)KD, EP-YSKD
Ratio of cooling capacity
1.1

1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.3 Indoor Temperature

1.2

1.1
24°CW.B.
75°FW.B.
1.0
22°CW.B.
0.9 72°FW.B.
Ratio of power input

0.8 20°CW.B.
68°FW.B.
0.7 19°CW.B.
66°FW.B.
0.6
18°CW.B.
0.5 64°FW.B.
16°CW.B.
0.4
61°FW.B.
0.3 15°CW.B.
59°FW.B.
0.2

0.1

0.0
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 83
0000005024.BOOK 84 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY- P350YKD Indoor unit temperature correction


Nominal kW 44.0 To be used to correct indoor unit capacity only
Cooling
Capacity BTU/h 136,500
Input kW 9.66 1.2
PUCY-P-Y(S)KD, EP-YSKD

Ratio of cooling capacity


1.1

1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.4 Indoor Temperature

1.3

1.2
24°CW.B.
75°FW.B.
1.1
22°CW.B.
1.0 72°FW.B.
Ratio of power input

0.9 20°CW.B.
68°FW.B.
0.8 19°CW.B.
66°FW.B.
0.7
18°CW.B.
0.6 64°FW.B.
16°CW.B.
0.5
61°FW.B.
0.4 15°CW.B.
59°FW.B.
0.3

0.2

0.1
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 84
0000005024.BOOK 85 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY- P400YKD Indoor unit temperature correction


Nominal kW 44.0 To be used to correct indoor unit capacity only
Cooling
Capacity BTU/h 150,100
Input kW 12.42 1.2

PUCY-P-Y(S)KD, EP-YSKD
Ratio of cooling capacity
1.1

1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.3 Indoor Temperature

1.2

1.1
24°CW.B.
75°FW.B.
1.0
22°CW.B.
0.9 72°FW.B.
Ratio of power input

0.8 20°CW.B.
68°FW.B.
0.7 19°CW.B.
66°FW.B.
0.6
18°CW.B.
0.5 64°FW.B.
16°CW.B.
0.4
61°FW.B.
0.3 15°CW.B.
59°FW.B.
0.2

0.1

0.0
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 85
0000005024.BOOK 86 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY- P450YKD Indoor unit temperature correction


Nominal kW 48.0 To be used to correct indoor unit capacity only
Cooling
Capacity BTU/h 163,800
Input kW 14.32 1.2
PUCY-P-Y(S)KD, EP-YSKD

Ratio of cooling capacity


1.1

1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.3 Indoor Temperature

1.2

1.1
24°CW.B.
75°FW.B.
1.0
22°CW.B.
0.9 72°FW.B.
Ratio of power input

0.8 20°CW.B.
68°FW.B.
0.7 19°CW.B.
66°FW.B.
0.6
18°CW.B.
0.5 64°FW.B.
16°CW.B.
0.4
61°FW.B.
0.3 15°CW.B.
59°FW.B.
0.2

0.1

0.0
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 86
0000005024.BOOK 87 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY- P500YKD Indoor unit temperature correction


Nominal kW 56.0 To be used to correct indoor unit capacity only
Cooling
Capacity BTU/h 191,100
Input kW 16.51 1.2

PUCY-P-Y(S)KD, EP-YSKD
Ratio of cooling capacity
1.1

1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.3 Indoor Temperature

1.2

1.1
24°CW.B.
75°FW.B.
1.0
22°CW.B.
0.9 72°FW.B.
Ratio of power input

0.8 20°CW.B.
68°FW.B.
0.7 19°CW.B.
66°FW.B.
0.6
18°CW.B.
0.5 64°FW.B.
16°CW.B.
0.4
61°FW.B.
0.3 15°CW.B.
59°FW.B.
0.2

0.1

0.0
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 87
0000005024.BOOK 88 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY- P550YSKD P600YSKD P650YSKD Indoor unit temperature correction


Nominal kW 61.5 68.0 72.0 To be used to correct indoor unit capacity only
Cooling
Capacity BTU/h 209,800 232,000 245,700
Input kW 14.04 15.34 17.73 1.2

PUCY- EP450YSKD EP500YSKD EP650YSKD


PUCY-P-Y(S)KD, EP-YSKD

Ratio of cooling capacity


Nominal kW 50.4 56.0 73.5 1.1
Cooling
Capacity BTU/h 172,000 191,100 250,800
Input kW 11.37 12.84 18.32
1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.3 Indoor Temperature

1.2

1.1
24°CW.B.
75°FW.B.
1.0
22°CW.B.
0.9 72°FW.B.
Ratio of power input

0.8 20°CW.B.
68°FW.B.
0.7 19°CW.B.
66°FW.B.
0.6
18°CW.B.
0.5 64°FW.B.
16°CW.B.
0.4
61°FW.B.
0.3 15°CW.B.
59°FW.B.
0.2

0.1

0.0
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 88
0000005024.BOOK 89 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY- EP700YSKD Indoor unit temperature correction


Nominal kW 80.0 To be used to correct indoor unit capacity only
Cooling
Capacity BTU/h 273,000
Input kW 19.75 1.2

PUCY-P-Y(S)KD, EP-YSKD
Ratio of cooling capacity
1.1

1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.3 Indoor Temperature

1.2

1.1
24°CW.B.
75°FW.B.
1.0
22°CW.B.
0.9 72°FW.B.
Ratio of power input

0.8 20°CW.B.
68°FW.B.
0.7 19°CW.B.
66°FW.B.
0.6
18°CW.B.
0.5 64°FW.B.
16°CW.B.
0.4
61°FW.B.
0.3 15°CW.B.
59°FW.B.
0.2

0.1

0.0
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 89
0000005024.BOOK 90 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY- P700YSKD P750YSKD P800YSKD Indoor unit temperature correction


Nominal kW 76.0 81.5 88.0 To be used to correct indoor unit capacity only
Cooling
Capacity BTU/h 259,300 278,100 300,300
Input kW 19.24 21.79 25.00 1.2

PUCY- EP750YSKD EP800YSKD


PUCY-P-Y(S)KD, EP-YSKD

Ratio of cooling capacity


Nominal kW 84.8 90.4 1.1
Cooling
Capacity BTU/h 289,300 308,400
Input kW 19.44 20.97
1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.3 Indoor Temperature

1.2

1.1
24°CW.B.
75°FW.B.
1.0
22°CW.B.
0.9 72°FW.B.
Ratio of power input

0.8 20°CW.B.
68°FW.B.
0.7 19°CW.B.
66°FW.B.
0.6
18°CW.B.
0.5 64°FW.B.
16°CW.B.
0.4
61°FW.B.
0.3 15°CW.B.
59°FW.B.
0.2

0.1

0.0
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 90
0000005024.BOOK 91 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY- P850YSKD P900YSKD P950YSKD Indoor unit temperature correction


Nominal kW 92.0 96.0 104.0 To be used to correct indoor unit capacity only
Cooling
Capacity BTU/h 313,900 327,600 354,800
Input kW 26.97 29.00 31.51 1.2

PUCY- P1000YSKD P1050YSKD

PUCY-P-Y(S)KD, EP-YSKD
Nominal kW

Ratio of cooling capacity


112.0 115.0 1.1
Cooling
Capacity BTU/h 382,100 392,400
Input kW 34.04 29.63
1.0
PUCY- EP850YSKD EP900YSKD EP950YSKD
Nominal kW 96.0 101.5 107.0
Cooling
Capacity BTU/h 327,600 346,300 365,100 0.9
Input kW 22.53 24.57 26.81
PUCY- EP1000YSKD 0.8
Nominal kW 113.5
Cooling 15 16 17 18 19 20 21 22 23 24
Capacity BTU/h 387,300
Indoor Temperature[°CW.B.]
Input kW 28.80

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.3 Indoor Temperature

1.2

1.1
24°CW.B.
75°FW.B.
1.0
22°CW.B.
0.9 72°FW.B.
Ratio of power input

0.8 20°CW.B.
68°FW.B.
0.7 19°CW.B.
66°FW.B.
0.6
18°CW.B.
0.5 64°FW.B.
16°CW.B.
0.4
61°FW.B.
0.3 15°CW.B.
59°FW.B.
0.2

0.1

0.0
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 91
0000005024.BOOK 92 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY- EP1050YSKD Indoor unit temperature correction


Nominal kW 120.0 To be used to correct indoor unit capacity only
Cooling
Capacity BTU/h 409,400
Input kW 29.62 1.2
PUCY-P-Y(S)KD, EP-YSKD

Ratio of cooling capacity


1.1

1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.3 Indoor Temperature

1.2

1.1
24°CW.B.
75°FW.B.
1.0
22°CW.B.
0.9 72°FW.B.
Ratio of power input

0.8 20°CW.B.
68°FW.B.
0.7 19°CW.B.
66°FW.B.
0.6
18°CW.B.
0.5 64°FW.B.
16°CW.B.
0.4
61°FW.B.
0.3 15°CW.B.
59°FW.B.
0.2

0.1

0.0
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 92
0000005024.BOOK 93 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY- P1100YSKD P1150YSKD P1200YSKD Indoor unit temperature correction


Nominal kW 121.5 128.0 132.0 To be used to correct indoor unit capacity only
Cooling
Capacity BTU/h 414,600 436,700 450,400
Input kW 30.99 33.95 37.50 1.2

PUCY- P1250YSKD P1300YSKD P1350YSKD

PUCY-P-Y(S)KD, EP-YSKD
Nominal kW 136.0 140.0 144.0

Ratio of cooling capacity


Cooling 1.1
Capacity BTU/h 464,000 477,700 491,300
Input kW 39.42 41.54 43.63
1.0
PUCY- P1400YSKD P1450YSKD P1500YSKD
Nominal kW 152.0 160.0 168.0
Cooling
Capacity BTU/h 518,600 545,900 573,200 0.9
Input kW 46.06 48.63 51.06
PUCY- EP1100YSKD
0.8
Nominal kW 124.0
Cooling 15 16 17 18 19 20 21 22 23 24
Capacity BTU/h 423,100
Indoor Temperature[°CW.B.]
Input kW 32.37

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.3 Indoor Temperature

1.2

1.1
24°CW.B.
75°FW.B.
1.0
22°CW.B.
0.9 72°FW.B.
Ratio of power input

0.8 20°CW.B.
68°FW.B.
0.7 19°CW.B.
66°FW.B.
0.6
18°CW.B.
0.5 64°FW.B.
16°CW.B.
0.4
61°FW.B.
0.3 15°CW.B.
59°FW.B.
0.2

0.1

0.0
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 93
0000005024.BOOK 94 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

Correction by temperature (Capacity Assist Mode)


Increases the outdoor unit fan speed upon temperature rise. This function will be disabled when the unit is set to the outdoor
high static pressure setting or to the night mode setting. The outdoor unit will make more noise due to an increased airflow.
Refrain from using this function where quiet is required. To select capacity assist mode, SW4 (904) must be set to ON.
Capacity Assist Mode
Indoor unit temperature correction
PUCY-P-Y(S)KD, EP-YSKD

PUCY- P200YKD To be used to correct indoor unit capacity only


Nominal kW 22.4
Cooling
Capacity BTU/h 76,400 1.2
Input kW 4.66

Ratio of cooling capacity


PUCY- EP400YSKD 1.1
Nominal kW 44.8
Cooling
Capacity BTU/h 152,900
Input kW 9.93 1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.6 Indoor Temperature

1.5

1.4
24°CW.B.
75°FW.B.
1.3
22°CW.B.
1.2 72°FW.B.
Ratio of power input

1.1 20°CW.B.
68°FW.B.
1.0 19°CW.B.
66°FW.B.
0.9
18°CW.B.
0.8 64°FW.B.
16°CW.B.
0.7
61°FW.B.
0.6 15°CW.B.
59°FW.B.
0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 94
0000005024.BOOK 95 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

Capacity Assist Mode


Indoor unit temperature correction
PUCY- P250YKD To be used to correct indoor unit capacity only
Nominal kW 28.0
Cooling
Capacity BTU/h 95,500 1.2
Input kW 5.95

PUCY-P-Y(S)KD, EP-YSKD
Ratio of cooling capacity
1.1

1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.6 Indoor Temperature

1.5

1.4
24°CW.B.
75°FW.B.
1.3
22°CW.B.
1.2 72°FW.B.
Ratio of power input

1.1 20°CW.B.
68°FW.B.
1.0 19°CW.B.
66°FW.B.
0.9
18°CW.B.
0.8 64°FW.B.
16°CW.B.
0.7
61°FW.B.
0.6 15°CW.B.
59°FW.B.
0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 95
0000005024.BOOK 96 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

Capacity Assist Mode


Indoor unit temperature correction
PUCY- P300YKD To be used to correct indoor unit capacity only
Nominal kW 33.5
Cooling
Capacity BTU/h 114,300 1.2
Input kW 7.82
PUCY-P-Y(S)KD, EP-YSKD

Ratio of cooling capacity


1.1

1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.6 Indoor Temperature

1.5

1.4
24°CW.B.
75°FW.B.
1.3
22°CW.B.
1.2 72°FW.B.
Ratio of power input

1.1 20°CW.B.
68°FW.B.
1.0 19°CW.B.
66°FW.B.
0.9
18°CW.B.
0.8 64°FW.B.
16°CW.B.
0.7
61°FW.B.
0.6 15°CW.B.
59°FW.B.
0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 96
0000005024.BOOK 97 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

Capacity Assist Mode


Indoor unit temperature correction
PUCY- P350YKD To be used to correct indoor unit capacity only
Nominal kW 40.0
Cooling
Capacity BTU/h 136,500 1.2
Input kW 9.66

PUCY-P-Y(S)KD, EP-YSKD
Ratio of cooling capacity
1.1

1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.6 Indoor Temperature

1.5

1.4
24°CW.B.
75°FW.B.
1.3
22°CW.B.
1.2 72°FW.B.
Ratio of power input

1.1 20°CW.B.
68°FW.B.
1.0 19°CW.B.
66°FW.B.
0.9
18°CW.B.
0.8 64°FW.B.
16°CW.B.
0.7
61°FW.B.
0.6 15°CW.B.
59°FW.B.
0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 97
0000005024.BOOK 98 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

Capacity Assist Mode


Indoor unit temperature correction
PUCY- P400YKD To be used to correct indoor unit capacity only
Nominal kW 44.0
Cooling
Capacity BTU/h 150,100 1.2
Input kW 12.42
PUCY-P-Y(S)KD, EP-YSKD

Ratio of cooling capacity


1.1

1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.6 Indoor Temperature

1.5

1.4
24°CW.B.
75°FW.B.
1.3
22°CW.B.
1.2 72°FW.B.
Ratio of power input

1.1 20°CW.B.
68°FW.B.
1.0 19°CW.B.
66°FW.B.
0.9
18°CW.B.
0.8 64°FW.B.
16°CW.B.
0.7
61°FW.B.
0.6 15°CW.B.
59°FW.B.
0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 98
0000005024.BOOK 99 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

Capacity Assist Mode


Indoor unit temperature correction
PUCY- P450YKD To be used to correct indoor unit capacity only
Nominal kW 48.0
Cooling
Capacity BTU/h 163,800 1.2
Input kW 14.32

PUCY-P-Y(S)KD, EP-YSKD
Ratio of cooling capacity
1.1

1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.6 Indoor Temperature

1.5

1.4
24°CW.B.
75°FW.B.
1.3
22°CW.B.
1.2 72°FW.B.
Ratio of power input

1.1 20°CW.B.
68°FW.B.
1.0 19°CW.B.
66°FW.B.
0.9
18°CW.B.
0.8 64°FW.B.
16°CW.B.
0.7
61°FW.B.
0.6 15°CW.B.
59°FW.B.
0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 99
0000005024.BOOK 100 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

Capacity Assist Mode


Indoor unit temperature correction
PUCY- P500YKD To be used to correct indoor unit capacity only
Nominal kW 56.0
Cooling
Capacity BTU/h 191,100 1.2
Input kW 16.51
PUCY-P-Y(S)KD, EP-YSKD

Ratio of cooling capacity


1.1

1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.6 Indoor Temperature

1.5

1.4
24°CW.B.
75°FW.B.
1.3
22°CW.B.
1.2 72°FW.B.
Ratio of power input

1.1 20°CW.B.
68°FW.B.
1.0 19°CW.B.
66°FW.B.
0.9
18°CW.B.
0.8 64°FW.B.
16°CW.B.
0.7
61°FW.B.
0.6 15°CW.B.
59°FW.B.
0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 100
0000005024.BOOK 101 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

Capacity Assist Mode


Indoor unit temperature correction
PUCY- P550YSKD P600YSKD P650YSKD To be used to correct indoor unit capacity only
Nominal kW 61.5 68.0 72.0
Cooling
Capacity BTU/h 209,800 232,000 245,700 1.2
Input kW 14.04 15.34 17.73

PUCY-P-Y(S)KD, EP-YSKD
Ratio of cooling capacity
PUCY- EP450YSKD EP500YSKD EP650YSKD 1.1
Nominal kW 50.4 56.0 73.5
Cooling
Capacity BTU/h 172,000 191,100 250,800
Input kW 11.37 12.84 18.32 1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.6 Indoor Temperature

1.5

1.4
24°CW.B.
75°FW.B.
1.3
22°CW.B.
1.2 72°FW.B.
Ratio of power input

1.1 20°CW.B.
68°FW.B.
1.0 19°CW.B.
66°FW.B.
0.9
18°CW.B.
0.8 64°FW.B.
16°CW.B.
0.7
61°FW.B.
0.6 15°CW.B.
59°FW.B.
0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 101
0000005024.BOOK 102 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

Capacity Assist Mode


Indoor unit temperature correction
PUCY- EP700YSKD To be used to correct indoor unit capacity only
Nominal kW 80.0
Cooling
Capacity BTU/h 273,000 1.2
Input kW 19.75
PUCY-P-Y(S)KD, EP-YSKD

Ratio of cooling capacity


1.1

1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.6 Indoor Temperature

1.5

1.4
24°CW.B.
75°FW.B.
1.3
22°CW.B.
1.2 72°FW.B.
Ratio of power input

1.1 20°CW.B.
68°FW.B.
1.0 19°CW.B.
66°FW.B.
0.9
18°CW.B.
0.8 64°FW.B.
16°CW.B.
0.7
61°FW.B.
0.6 15°CW.B.
59°FW.B.
0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 102
0000005024.BOOK 103 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

Capacity Assist Mode


Indoor unit temperature correction
PUCY- P700YSKD P750YSKD P800YSKD To be used to correct indoor unit capacity only
Nominal kW 76.0 81.5 88.0
Cooling
Capacity BTU/h 259,300 278,100 300,300 1.2
Input kW 19.24 21.79 25.00

PUCY-P-Y(S)KD, EP-YSKD
Ratio of cooling capacity
PUCY- EP750YSKD EP800YSKD 1.1
Nominal kW 84.8 90.4
Cooling
Capacity BTU/h 289,300 308,400
Input kW 19.44 20.97 1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.6 Indoor Temperature

1.5

1.4
24°CW.B.
75°FW.B.
1.3
22°CW.B.
1.2 72°FW.B.
Ratio of power input

1.1 20°CW.B.
68°FW.B.
1.0 19°CW.B.
66°FW.B.
0.9
18°CW.B.
0.8 64°FW.B.
16°CW.B.
0.7
61°FW.B.
0.6 15°CW.B.
59°FW.B.
0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 103
0000005024.BOOK 104 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

Capacity Assist Mode


Indoor unit temperature correction
PUCY- P850YSKD P900YSKD P950YSKD To be used to correct indoor unit capacity only
Nominal kW 92.0 96.0 104.0
Cooling
Capacity BTU/h 313,900 327,600 354,800 1.2
Input kW 26.97 29.00 31.51
PUCY-P-Y(S)KD, EP-YSKD

PUCY- P1000YSKD P1050YSKD

Ratio of cooling capacity


Nominal kW 1.1
112.0 115.0
Cooling
Capacity BTU/h 382,100 392,400
Input kW 34.04 29.63 1.0
PUCY- EP850YSKD EP900YSKD EP950YSKD
Nominal kW 96.0 101.5 107.0
Cooling 0.9
Capacity BTU/h 327,600 346,300 365,100
Input kW 22.53 24.57 26.81
PUCY- EP1000YSKD 0.8
Nominal kW 15 16 17 18 19 20 21 22 23 24
113.5
Cooling
Capacity BTU/h 387,300 Indoor Temperature[°CW.B.]
Input kW 28.80
Outdoor unit temperature correction
To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.6 Indoor Temperature

1.5

1.4
24°CW.B.
75°FW.B.
1.3
22°CW.B.
1.2 72°FW.B.
Ratio of power input

1.1 20°CW.B.
68°FW.B.
1.0 19°CW.B.
66°FW.B.
0.9
18°CW.B.
0.8 64°FW.B.
16°CW.B.
0.7
61°FW.B.
0.6 15°CW.B.
59°FW.B.
0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 104
0000005024.BOOK 105 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

Capacity Assist Mode


Indoor unit temperature correction
EP1050YSKD PUCY- To be used to correct indoor unit capacity only
Nominal kW 120.0
Cooling
Capacity BTU/h 409,400 1.2
Input kW 29.62

PUCY-P-Y(S)KD, EP-YSKD
Ratio of cooling capacity
1.1

1.0

0.9

0.8
15 16 17 18 19 20 21 22 23 24

Indoor Temperature[°CW.B.]

Outdoor unit temperature correction


To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.6 Indoor Temperature

1.5

1.4
24°CW.B.
75°FW.B.
1.3
22°CW.B.
1.2 72°FW.B.
Ratio of power input

1.1 20°CW.B.
68°FW.B.
1.0 19°CW.B.
66°FW.B.
0.9
18°CW.B.
0.8 64°FW.B.
16°CW.B.
0.7
61°FW.B.
0.6 15°CW.B.
59°FW.B.
0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 105
0000005024.BOOK 106 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

Capacity Assist Mode


Indoor unit temperature correction
PUCY- P1100YSKD P1150YSKD P1200YSKD
To be used to correct indoor unit capacity only
Nominal kW 121.5 128.0 132.0
Cooling
Capacity BTU/h 414,600 436,700 450,400
1.2
Input kW 30.99 33.95 37.50
PUCY-P-Y(S)KD, EP-YSKD

PUCY- P1250YSKD P1300YSKD P1350YSKD

Ratio of cooling capacity


Nominal kW 1.1
136.0 140.0 144.0
Cooling
Capacity BTU/h 464,000 477,700 491,300
Input kW 39.42 41.54 43.63 1.0
PUCY- P1400YSKD P1450YSKD P1500YSKD
Nominal kW 152.0 160.0 168.0
Cooling 0.9
Capacity BTU/h 518,600 545,900 573,200
Input kW 46.06 48.63 51.06
PUCY- EP1100YSKD 0.8
Nominal kW 15 16 17 18 19 20 21 22 23 24
124.0
Cooling
Capacity BTU/h 423,100 Indoor Temperature[°CW.B.]
Input kW 32.37
Outdoor unit temperature correction
To be used to correct outdoor unit only
Outdoor unit capacity is NOT affected by the indoor temperature.
Outdoor unit power input is affected by the indoor and outdoor temperatures. Please consult the sales office for details.

1.2

1.1

1.0
Ratio of cooling capacity

0.9

0.8

0.7

0.6

0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

1.6 Indoor Temperature

1.5

1.4
24°CW.B.
75°FW.B.
1.3
22°CW.B.
1.2 72°FW.B.
Ratio of power input

1.1 20°CW.B.
68°FW.B.
1.0 19°CW.B.
66°FW.B.
0.9
18°CW.B.
0.8 64°FW.B.
16°CW.B.
0.7
61°FW.B.
0.6 15°CW.B.
59°FW.B.
0.5

0.4

0.3
10 15 20 25 30 35 40 45 50 °CD.B.
50 59 68 77 86 95 104 113 122 °FD.B.
Outdoor Temperature

MEES18K047 106
0000005024.BOOK 107 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

8-3. Correction by total indoor


CITY MULTI system has different capacities and inputs when many combinations of indoor units with different total capacities are
connected. Using following tables, the maximum capacity can be found to ensure the system is installed with enough capacity for
a particular application.

PUCY-P200YKD PUCY-P200YKD

PUCY-P-Y(S)KD, EP-YSKD
Nominal kW 22.4
Cooling
Capacity BTU/h 76,400 1.2
Input kW 4.66

1.0

Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
50 100 150 200 250 300
Total capacity of indoor units

PUCY-P250YKD PUCY-P250YKD
Nominal kW 28.0
Cooling
Capacity BTU/h 95,500 1.2
Input kW 5.95

1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
100 150 200 250 300 350
Total capacity of indoor units

MEES18K047 107
0000005024.BOOK 108 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P300YKD PUCY-P300YKD
Nominal kW 33.5
Cooling
Capacity BTU/h 114,300 1.2
Input kW 7.82
1.0
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
100 150 200 250 300 350 400 450
Total capacity of indoor units

PUCY-P350YKD PUCY-P350YKD
Nominal kW 40.0
Cooling
Capacity BTU/h 136,500 1.2
Input kW 9.66
1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
150 200 250 300 350 400 450 500
Total capacity of indoor units

MEES18K047 108
0000005024.BOOK 109 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P400YKD PUCY-P400YKD
Nominal kW 44.0
Cooling
Capacity BTU/h 150,100 1.2
Input kW 12.42

1.0

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
100 200 300 400 500 600
Total capacity of indoor units

PUCY-P450YKD PUCY-P450YKD
Nominal kW 48.0
Cooling
Capacity BTU/h 163,800 1.2
Input kW 14.32

1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
200 300 400 500 600 700
Total capacity of indoor units

MEES18K047 109
0000005024.BOOK 110 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P500YKD PUCY-P500YKD
Nominal kW 56.0
Cooling
Capacity BTU/h 191,100 1.2
Input kW 16.51

1.0
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
200 300 400 500 600 700
Total capacity of indoor units

PUCY-P550YSKD PUCY-P550YSKD
Nominal kW 61.5
Cooling
Capacity BTU/h 209,800 1.2
Input kW 14.04

1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
200 300 400 500 600 700 800
Total capacity of indoor units

MEES18K047 110
0000005024.BOOK 111 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P600YSKD PUCY-P600YSKD
Nominal kW 68.0
Cooling
Capacity BTU/h 232,000 1.2
Input kW 15.34

1.0

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
200 300 400 500 600 700 800
Total capacity of indoor units

PUCY-P650YSKD PUCY-P650YSKD
Nominal kW 72.0
Cooling
Capacity BTU/h 245,700 1.2
Input kW 17.73
1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
300 400 500 600 700 800 900 1000
Total capacity of indoor units

MEES18K047 111
0000005024.BOOK 112 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P700YSKD PUCY-P700YSKD
Nominal kW 76.0
Cooling
Capacity BTU/h 259,300 1.2
Input kW 19.24
1.0
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
300 400 500 600 700 800 900 1000
Total capacity of indoor units

PUCY-P750YSKD PUCY-P750YSKD
Nominal kW 81.5
Cooling
Capacity BTU/h 278,100 1.2
Input kW 21.79

1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
300 400 500 600 700 800 900 1000
Total capacity of indoor units

MEES18K047 112
0000005024.BOOK 113 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P800YSKD PUCY-P800YSKD
Nominal kW 88.0
Cooling
Capacity BTU/h 300,300 1.2
Input kW 25.00

1.0

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
200 400 600 800 1000 1200
Total capacity of indoor units

PUCY-P850YSKD PUCY-P850YSKD
Nominal kW 92.0
Cooling
Capacity BTU/h 313,900 1.2
Input kW 26.97

1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
200 400 600 800 1000 1200
Total capacity of indoor units

MEES18K047 113
0000005024.BOOK 114 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P900YSKD PUCY-P900YSKD
Nominal kW 96.0
Cooling
Capacity BTU/h 327,600 1.2
Input kW 29.00

1.0
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
200 400 600 800 1000 1200
Total capacity of indoor units

PUCY-P950YSKD PUCY-P950YSKD
Nominal kW 104.0
Cooling
Capacity BTU/h 354,800 1.2
Input kW 31.51

1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
400 600 800 1000 1200 1400
Total capacity of indoor units

MEES18K047 114
0000005024.BOOK 115 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P1000YSKD PUCY-P1000YSKD
Nominal kW 112.0
Cooling
Capacity BTU/h 382,100 1.2
Input kW 34.04

1.0

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
400 600 800 1000 1200 1400
Total capacity of indoor units

PUCY-P1050YSKD PUCY-P1050YSKD
Nominal kW 115.0
Cooling
Capacity BTU/h 392,400 1.2
Input kW 29.63

1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
400 600 800 1000 1200 1400 1600
Total capacity of indoor units

MEES18K047 115
0000005024.BOOK 116 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P1100YSKD PUCY-P1100YSKD
Nominal kW 121.5
Cooling
Capacity BTU/h 414,600 1.2
Input kW 30.99

1.0
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
400 600 800 1000 1200 1400 1600
Total capacity of indoor units

PUCY-P1150YSKD PUCY-P1150YSKD
Nominal kW 128.0
Cooling
Capacity BTU/h 436,700 1.2
Input kW 33.95

1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
400 600 800 1000 1200 1400 1600
Total capacity of indoor units

MEES18K047 116
0000005024.BOOK 117 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P1200YSKD PUCY-P1200YSKD
Nominal kW 132.0
Cooling
Capacity BTU/h 450,400 1.2
Input kW 37.50

1.0

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
400 600 800 1000 1200 1400 1600
Total capacity of indoor units

PUCY-P1250YSKD PUCY-P1250YSKD
Nominal kW 136.0
Cooling
Capacity BTU/h 464,000 1.2
Input kW 39.42

1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
600 800 1000 1200 1400 1600 1800
Total capacity of indoor units

MEES18K047 117
0000005024.BOOK 118 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P1300YSKD PUCY-P1300YSKD
Nominal kW 140.0
Cooling
Capacity BTU/h 477,700 1.2
Input kW 41.54

1.0
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
600 800 1000 1200 1400 1600 1800
Total capacity of indoor units

PUCY-P1350YSKD PUCY-P1350YSKD
Nominal kW 144.0
Cooling
Capacity BTU/h 491,300 1.2
Input kW 43.63

1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
600 800 1000 1200 1400 1600 1800
Total capacity of indoor units

MEES18K047 118
0000005024.BOOK 119 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P1400YSKD PUCY-P1400YSKD
Nominal kW 152.0
Cooling
Capacity BTU/h 518,600 1.2
Input kW 46.06

1.0

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
600 800 1000 1200 1400 1600 1800 2000
Total capacity of indoor units

PUCY-P1450YSKD PUCY-P1450YSKD
Nominal kW 160.0
Cooling
Capacity BTU/h 545,900 1.2
Input kW 48.63

1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
600 800 1000 1200 1400 1600 1800 2000
Total capacity of indoor units

MEES18K047 119
0000005024.BOOK 120 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P1500YSKD PUCY-P1500YSKD
Nominal kW 168.0
Cooling
Capacity BTU/h 573,200 1.2
Input kW 51.06

1.0
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
600 800 1000 1200 1400 1600 1800 2000
Total capacity of indoor units

PUCY-EP400YSKD PUCY-EP400YSKD
Nominal kW 44.8
Cooling
Capacity BTU/h 152,900 1.2
Input kW 9.93

1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
100 200 300 400 500 600
Total capacity of indoor units

MEES18K047 120
0000005024.BOOK 121 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-EP450YSKD PUCY-EP450YSKD
Nominal kW 50.4
Cooling
Capacity BTU/h 172,000 1.2
Input kW 11.37

1.0

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
200 300 400 500 600 700
Total capacity of indoor units

PUCY-EP500YSKD PUCY-EP500YSKD
Nominal kW 56.0
Cooling
Capacity BTU/h 191,100 1.2
Input kW 12.84

1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
200 300 400 500 600 700
Total capacity of indoor units

MEES18K047 121
0000005024.BOOK 122 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-EP650YSKD PUCY-EP650YSKD
Nominal kW 73.5
Cooling
Capacity BTU/h 250,800 1.2
Input kW 18.32
1.0
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
300 400 500 600 700 800 900 1000
Total capacity of indoor units

PUCY-EP700YSKD PUCY-EP700YSKD
Nominal kW 80.0
Cooling
Capacity BTU/h 273,000 1.2
Input kW 19.75
1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
300 400 500 600 700 800 900 1000
Total capacity of indoor units

MEES18K047 122
0000005024.BOOK 123 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-EP750YSKD PUCY-EP750YSKD
Nominal kW 84.8
Cooling
Capacity BTU/h 289,300 1.2
Input kW 19.44
1.0

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
300 400 500 600 700 800 900 1000
Total capacity of indoor units

PUCY-EP800YSKD PUCY-EP800YSKD
Nominal kW 90.4
Cooling
Capacity BTU/h 308,400 1.2
Input kW 20.97

1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
200 400 600 800 1000 1200
Total capacity of indoor units

MEES18K047 123
0000005024.BOOK 124 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-EP850YSKD PUCY-EP850YSKD
Nominal kW 96.0
Cooling
Capacity BTU/h 327,600 1.2
Input kW 22.53

1.0
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
200 400 600 800 1000 1200
Total capacity of indoor units

PUCY-EP900YSKD PUCY-EP900YSKD
Nominal kW 101.5
Cooling
Capacity BTU/h 346,300 1.2
Input kW 24.57

1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
200 400 600 800 1000 1200
Total capacity of indoor units

MEES18K047 124
0000005024.BOOK 125 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-EP950YSKD PUCY-EP950YSKD
Nominal kW 107.0
Cooling
Capacity BTU/h 365,100 1.2
Input kW 26.81

1.0

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
400 600 800 1000 1200 1400
Total capacity of indoor units

PUCY-EP1000YSKD PUCY-EP1000YSKD
Nominal kW 113.5
Cooling
Capacity BTU/h 387,300 1.2
Input kW 28.80

1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
400 600 800 1000 1200 1400
Total capacity of indoor units

MEES18K047 125
0000005024.BOOK 126 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-EP1050YSKD PUCY-EP1050YSKD
Nominal kW 120.0
Cooling
Capacity BTU/h 409,400 1.2
Input kW 29.62

1.0
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
400 600 800 1000 1200 1400 1600
Total capacity of indoor units

PUCY-EP1100YSKD PUCY-EP1100YSKD
Nominal kW 124.0
Cooling
Capacity BTU/h 423,100 1.2
Input kW 32.37

1.0
Ratio of capacity

0.8

0.6

0.4

0.2

1.2

1.0
Ratio of power input

0.8

0.6

0.4
Cooling
0.2
400 600 800 1000 1200 1400 1600
Total capacity of indoor units

MEES18K047 126
0000005024.BOOK 127 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

8-4. Correction by part load ratio


CITY MULTI system has different capacities and inputs depending on the operation load. Using following tables, the maximum
capacity can be found to ensure the system is installed with enough capacity for a particular application.

PUCY-P200YKD PUCY-P200YKD
Nominal kW 22.4

PUCY-P-Y(S)KD, EP-YSKD
Cooling
Capacity BTU/h 76,400 1.0
Input kW 4.66

0.8

Ratio of capacity 0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-P250YKD PUCY-P250YKD
Nominal kW 28.0
Cooling
Capacity BTU/h 95,500 1.0
Input kW 5.95

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 127
0000005024.BOOK 128 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P300YKD PUCY-P300YKD
Nominal kW 33.5
Cooling
Capacity BTU/h 114,300 1.0
Input kW 7.82

0.8
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-P350YKD PUCY-P350YKD
Nominal kW 40.0
Cooling
Capacity BTU/h 136,500 1.0
Input kW 9.66

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 128
0000005024.BOOK 129 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P400YKD PUCY-P400YKD
Nominal kW 44.0
Cooling
Capacity BTU/h 150,100 1.0
Input kW 12.42

0.8

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-P450YKD PUCY-P450YKD
Nominal kW 48.0
Cooling
Capacity BTU/h 163,800 1.0
Input kW 14.32

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 129
0000005024.BOOK 130 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P500YKD PUCY-P500YKD
Nominal kW 56.0
Cooling
Capacity BTU/h 191,100 1.0
Input kW 16.51

0.8
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-P550YSKD PUCY-P550YSKD
Nominal kW 61.5
Cooling
Capacity BTU/h 209,800 1.0
Input kW 14.04

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 130
0000005024.BOOK 131 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P600YSKD PUCY-P600YSKD
Nominal kW 68.0
Cooling
Capacity BTU/h 232,000 1.0
Input kW 15.34

0.8

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-P650YSKD PUCY-P650YSKD
Nominal kW 72.0
Cooling
Capacity BTU/h 245,700 1.0
Input kW 17.73

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 131
0000005024.BOOK 132 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P700YSKD PUCY-P700YSKD
Nominal kW 76.0
Cooling
Capacity BTU/h 259,300 1.0
Input kW 19.24

0.8
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-P750YSKD PUCY-P750YSKD
Nominal kW 81.5
Cooling
Capacity BTU/h 278,100 1.0
Input kW 21.79

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 132
0000005024.BOOK 133 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P800YSKD PUCY-P800YSKD
Nominal kW 88.0
Cooling
Capacity BTU/h 300,300 1.0
Input kW 25.00

0.8

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-P850YSKD PUCY-P850YSKD
Nominal kW 92.0
Cooling
Capacity BTU/h 313,900 1.0
Input kW 26.97

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 133
0000005024.BOOK 134 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P900YSKD PUCY-P900YSKD
Nominal kW 96.0
Cooling
Capacity BTU/h 327,600 1.0
Input kW 29.00

0.8
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-P950YSKD PUCY-P950YSKD
Nominal kW 104.0
Cooling
Capacity BTU/h 354,800 1.0
Input kW 31.51

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 134
0000005024.BOOK 135 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P1000YSKD PUCY-P1000YSKD
Nominal kW 112.0
Cooling
Capacity BTU/h 382,100 1.0
Input kW 34.04

0.8

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-P1050YSKD PUCY-P1050YSKD
Nominal kW 115.0
Cooling
Capacity BTU/h 392,400 1.0
Input kW 29.63

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 135
0000005024.BOOK 136 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P1100YSKD PUCY-P1100YSKD
Nominal kW 121.5
Cooling
Capacity BTU/h 414,600 1.0
Input kW 30.99

0.8
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-P1150YSKD PUCY-P1150YSKD
Nominal kW 128.0
Cooling
Capacity BTU/h 436,700 1.0
Input kW 33.95

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 136
0000005024.BOOK 137 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P1200YSKD PUCY-P1200YSKD
Nominal kW 132.0
Cooling
Capacity BTU/h 450,400 1.0
Input kW 37.50

0.8

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-P1250YSKD PUCY-P1250YSKD
Nominal kW 136.0
Cooling
Capacity BTU/h 464,000 1.0
Input kW 39.42

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 137
0000005024.BOOK 138 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P1300YSKD PUCY-P1300YSKD
Nominal kW 140.0
Cooling
Capacity BTU/h 477,700 1.0
Input kW 41.54

0.8
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-P1350YSKD PUCY-P1350YSKD
Nominal kW 144.0
Cooling
Capacity BTU/h 491,300 1.0
Input kW 43.63

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 138
0000005024.BOOK 139 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P1400YSKD PUCY-P1400YSKD
Nominal kW 152.0
Cooling
Capacity BTU/h 518,600 1.0
Input kW 46.06

0.8

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-P1450YSKD PUCY-P1450YSKD
Nominal kW 160.0
Cooling
Capacity BTU/h 545,900 1.0
Input kW 48.63

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 139
0000005024.BOOK 140 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P1500YSKD PUCY-P1500YSKD
Nominal kW 168.0
Cooling
Capacity BTU/h 573,200 1.0
Input kW 51.06

0.8
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-EP400YSKD PUCY-EP450YSKD
Nominal kW 44.8
Cooling
Capacity BTU/h 152,900 1.0
Input kW 9.93

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 140
0000005024.BOOK 141 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-EP450YSKD PUCY-EP450YSKD
Nominal kW 50.4
Cooling
Capacity BTU/h 172,000 1.0
Input kW 11.37

0.8

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-EP500YSKD PUCY-EP500YSKD
Nominal kW 56.0
Cooling
Capacity BTU/h 191,100 1.0
Input kW 12.84

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 141
0000005024.BOOK 142 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-EP650YSKD PUCY-EP650YSKD
Nominal kW 73.5
Cooling
Capacity BTU/h 250,800 1.0
Input kW 18.32

0.8
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-EP700YSKD PUCY-EP700YSKD
Nominal kW 80.0
Cooling
Capacity BTU/h 273,000 1.0
Input kW 19.75

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 142
0000005024.BOOK 143 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-EP750YSKD PUCY-EP750YSKD
Nominal kW 84.8
Cooling
Capacity BTU/h 289,300 1.0
Input kW 19.44

0.8

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-EP800YSKD PUCY-EP800YSKD
Nominal kW 90.4
Cooling
Capacity BTU/h 308,400 1.0
Input kW 20.97

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 143
0000005024.BOOK 144 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-EP850YSKD PUCY-EP850YSKD
Nominal kW 96.0
Cooling
Capacity BTU/h 327,600 1.0
Input kW 22.53

0.8
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-EP900YSKD PUCY-EP900YSKD
Nominal kW 101.5
Cooling
Capacity BTU/h 346,300 1.0
Input kW 24.57

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 144
0000005024.BOOK 145 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-EP950YSKD PUCY-EP950YSKD
Nominal kW 107.0
Cooling
Capacity BTU/h 365,100 1.0
Input kW 26.81

0.8

PUCY-P-Y(S)KD, EP-YSKD
Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-EP1000YSKD PUCY-EP1000YSKD
Nominal kW 113.5
Cooling
Capacity BTU/h 387,300 1.0
Input kW 28.80

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 145
0000005024.BOOK 146 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-EP1050YSKD PUCY-EP1050YSKD
Nominal kW 120.0
Cooling
Capacity BTU/h 409,400 1.0
Input kW 29.62

0.8
PUCY-P-Y(S)KD, EP-YSKD

Ratio of capacity
0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

PUCY-EP1100YSKD PUCY-EP1100YSKD
Nominal kW 124.0
Cooling
Capacity BTU/h 423,100 1.0
Input kW 32.37

0.8
Ratio of capacity

0.6

0.4

0.2

0.0

1.0

0.8
Ratio of power input

0.6

0.4

0.2
Cooling
0.0
30 40 50 60 70 80 90 100
Part load ratio (%)

MEES18K047 146
0000005024.BOOK 147 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

8-5. Correction by refrigerant piping length


CITY MULTI system can extend the piping flexibly within its limitation for the actual situation. However, a decrease of cooling
capacity could happen correspondently. Using following correction factor according to the equivalent length of the piping shown at
8-5-1, the capacity can be observed. 8-5-2 shows how to obtain the equivalent length of piping.

8-5-1. Cooling capacity correction

PUCY-P-Y(S)KD, EP-YSKD
PUCY-P200YKD(-BS) Total capacity of indoor unit
PUCY-(E)P400Y(S)KD(-BS) Total capacity of indoor unit
1 100 1 200
Cooling capacity correction factor

Cooling capacity correction factor


0.95 0.95

0.90 0.90
150
0.85 0.85
300
0.80 200 0.80
260
400
0.75 0.75 520
0.70 0.70

0.65 0.65
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m) Piping equivalent length (m)

PUCY-P250YKD(-BS) Total capacity of indoor unit


PUCY-(E)P450Y(S)KD(-BS) Total capacity of indoor unit
1 125 1 225
Cooling capacity correction factor

Cooling capacity correction factor

0.95 0.95

0.90 0.90

0.85 0.85
338
0.80 188 0.80

0.75 0.75
250 450
325 585
0.70 0.70

0.65 0.65
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m) Piping equivalent length (m)

PUCY-P300Y(S)KD(-BS) Total capacity of indoor unit


PUCY-(E)P500Y(S)KD(-BS) Total capacity of indoor unit
1 150 1 250
Cooling capacity correction factor

Cooling capacity correction factor

0.95 0.95

0.90 0.90

0.85 0.85

0.80 0.80 375


225
0.75 0.75
500
650
0.70 0.70
300
0.65 390 0.65
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m) Piping equivalent length (m)

PUCY-P350Y(S)KD(-BS) Total capacity of indoor unit


PUCY-P550YSKD(-BS) Total capacity of indoor unit
1 175 1 275
Cooling capacity correction factor

Cooling capacity correction factor

0.95 0.95

0.90 0.90
263
0.85 0.85

0.80 350 0.80 413


455
0.75 0.75
550
0.70 0.70 715

0.65 0.65
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m) Piping equivalent length (m)

MEES18K047 147
0000005024.BOOK 148 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P600YSKD(-BS) Total capacity of indoor unit


PUCY-(E)P800YSKD(-BS) Total capacity of indoor unit
1 300 1 400
Cooling capacity correction factor

Cooling capacity correction factor


0.95 0.95

0.90 0.90
PUCY-P-Y(S)KD, EP-YSKD

0.85 0.85

0.80 0.80 600


450
0.75 0.75
800
0.70 0.70 1040
600
0.65 780 0.65
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m) Piping equivalent length (m)

PUCY-(E)P650YSKD(-BS) Total capacity of indoor unit


PUCY-(E)P850YSKD(-BS) Total capacity of indoor unit
1 325 1 425
Cooling capacity correction factor

Cooling capacity correction factor

0.95 0.95

0.90 0.90

0.85 0.85
638
0.80 0.80
488 850
0.75 0.75 1105

0.70 0.70
650
0.65 845 0.65
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m) Piping equivalent length (m)

PUCY-(E)P700YSKD(-BS) Total capacity of indoor unit


PUCY-(E)P900YSKD(-BS) Total capacity of indoor unit
1 350 1 450
Cooling capacity correction factor

Cooling capacity correction factor

0.95 0.95

0.90 0.90

0.85 0.85
525 675
0.80 0.80

0.75 0.75
700 900
910 1170
0.70 0.70

0.65 0.65
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m) Piping equivalent length (m)

PUCY-(E)P750YSKD(-BS) Total capacity of indoor unit


PUCY-(E)P950YSKD(-BS) Total capacity of indoor unit
1 375 1 475
Cooling capacity correction factor

Cooling capacity correction factor

0.95 0.95

0.90 0.90

0.85 0.85
713
0.80 563 0.80

0.75 0.75
750 950
975 1235
0.70 0.70

0.65 0.65
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m) Piping equivalent length (m)

MEES18K047 148
0000005024.BOOK 149 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-(E)P1000YSKD(-BS) Total capacity of indoor unit


PUCY-P1200YSKD(-BS) Total capacity of indoor unit
1 500 1 600
Cooling capacity correction factor

Cooling capacity correction factor


0.95 0.95

0.90 0.90

PUCY-P-Y(S)KD, EP-YSKD
0.85 0.85
750
0.80 0.80 900
1000
0.75 1300 0.75
1200
1560
0.70 0.70

0.65 0.65
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m) Piping equivalent length (m)

PUCY-(E)P1050YSKD(-BS) Total capacity of indoor unit


PUCY-P1250YSKD(-BS) Total capacity of indoor unit
1 525 1 625
Cooling capacity correction factor

Cooling capacity correction factor


0.95 0.95

0.90 0.90

0.85 0.85
788
0.80 0.80 938

0.75 0.75
1050 1250
1365 1625
0.70 0.70

0.65 0.65
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m) Piping equivalent length (m)

PUCY-(E)P1100YSKD(-BS) Total capacity of indoor unit


PUCY-P1300YSKD(-BS) Total capacity of indoor unit
1 550 1 650
Cooling capacity correction factor

Cooling capacity correction factor

0.95 0.95

0.90 0.90

0.85 0.85
825
0.80 0.80
975
0.75 0.75
1100
1430 1300
0.70 0.70 1690

0.65 0.65
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m) Piping equivalent length (m)

PUCY-P1150YSKD(-BS) Total capacity of indoor unit


PUCY-P1350YSKD(-BS) Total capacity of indoor unit
1 575 1 675
Cooling capacity correction factor

Cooling capacity correction factor

0.95 0.95

0.90 0.90

0.85 0.85
863
0.80 0.80
1013
0.75 0.75
1150
1495
0.70 0.70 1350
1755
0.65 0.65
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m) Piping equivalent length (m)

MEES18K047 149
0000005024.BOOK 150 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

PUCY-P1400YSKD(-BS) Total capacity of indoor unit


1 700
Cooling capacity correction factor

0.95

0.90
PUCY-P-Y(S)KD, EP-YSKD

0.85

0.80
1050
0.75
1400
0.70
1820
0.65
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)

PUCY-P1450YSKD(-BS) Total capacity of indoor unit


1 725
Cooling capacity correction factor

0.95

0.90

0.85

0.80

0.75 1088

0.70
1450
1885
0.65
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)

PUCY-P1500YSKD(-BS) Total capacity of indoor unit


1 750
Cooling capacity correction factor

0.95

0.90

0.85

0.80

0.75
1125
0.70
1500
0.65 1950
0 20 40 60 80 100 120 140 160 180
Piping equivalent length (m)

MEES18K047 150
0000005024.BOOK 151 ページ 2018年11月12日 月曜日 午後6時54分

8. CAPACITY TABLES Y-Series (Cooling-only)

8-5-2. How to obtain the equivalent piping length


1 PUCY-P200, 250, 300YKD(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.42 x number of bends in the piping) m
2 PUCY-P350YKD(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.47 x number of bends in the piping) m

PUCY-P-Y(S)KD, EP-YSKD
3 PUCY-(E)P400, 450, 500, 550, 600, 650Y(S)KD(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 x number of bends in the piping) m
4 PUCY-(E)P700, 750, 800YSKD(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.70 x number of bends in the piping) m
5 PUCY-(E)P850, 900, 950, 1000, 1050, 1100, 1150, 1200, 1250, 1300, 1350, 1400, 1450, 1500YSKD(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.80 x number of bends in the piping) m

MEES18K047 151
0000005024.BOOK 152 ページ 2018年11月12日 月曜日 午後6時54分

9. OPTIONAL PARTS Y-Series (Cooling-only)

9-1. JOINT
9. OPTIONAL PARTS

CITY MULTI units can be easily connected by using Joint sets and Header sets provided by Mitsubishi Electric. Four kinds of Joint
sets are available for use. Refer to section "Piping Design" or the Installation Manual that comes with the Joint set for how to install
the Joint set.

CMY-Y102SS-G2
PUCY-P-Y(S)KD, EP-YSKD

mm
For Gas pipe: <Deformed pipe(Accessory)> For Liquid pipe:
ø15.88 ø12.7
(Outside diameter) <Deformed pipe(Accessory)>

28
ø15.88
ø19.05 ø15.88 ø9.52
ø19.05 (Outside diameter) ø9.52 ø6.35
ø19.05 ø9.52
30

ø9.52 (Outside diameter)

18
30
20
(2 Pcs.) 36
58 (2 Pcs.)
ø19.05 ø12.7
(Outside diameter)

*Pipe diameter is indicated by inside diameter. 37

CMY-Y102LS-G2 <Deformed pipe(Accessory)> mm


ø28.58
For Gas pipe: ø19.05 ø12.7
ø25.4
(Outside diameter)
For Liquid pipe:
(Outside diameter)

<Deformed pipe(Accessory)>
37 54
ø19.05 ø15.88 (2 Pcs.)
ø25.4 ø19.05
(Outside diameter) (Outside diameter) ø9.52
ø6.35
(Outside diameter)
ø19.05
30 ø9.52 20
ø25.4 41
ø25.4 ø19.05 ø22.2 (2 Pcs.) ø12.7
ø12.7
39

20

(Outside diameter) ø25.4 ø15.88 ø12.7 ø9.52


(Outside diameter) (Outside diameter)
40
54
76 23
ø25.4 ø22.2 45
(Outside diameter) (2 Pcs.)

42
*Pipe diameter is indicated by inside diameter. (2 Pcs.)

CMY-Y202S-G2 <Deformed pipe(Accessory)> mm


For Gas pipe: ø19.05 ø12.7
ø25.4 ø28.58 For Liquid pipe:
(Outside diameter) (Outside diameter)

<Deformed pipe(Accessory)>
37 54
(3 Pcs.) ø15.88 ø12.7
ø19.05 ø15.88 ø19.05 ø25.4
(Outside diameter) (Outside diameter)
(Outside diameter)
ø19.05 28
ø12.7
ø25.4 30 ø15.88 ø12.7 ø9.52
ø25.4 54 ø15.88 (Outside diameter)
23
39

ø19.05 ø22.2
(Outside diameter) 23
49 ø12.7 ø6.35
76 (Outside diameter)
54
23
ø25.4 ø22.2 ø15.88 ø9.52
(Outside diameter) (Outside diameter)
28
*Pipe diameter is indicated by inside diameter. 42

CMY-Y302S-G2 <Deformed pipe(Accessory)> mm


For Gas pipe: ø25.4 ø19.05 For Liquid pipe:
(Outside diameter) <Deformed pipe(Accessory)>
ø25.4 ø22.2
(Outside diameter)
41
ø25.4
42 ø15.88
(Outside diameter) ø15.88 ø12.7
ø25.4 ø15.88 ø9.52
ø12.7 (Outside diameter)
(Outside diameter) (Outside diameter)
45 28
ø25.4 ø31.75 28
ø34.93 ø15.88
ø31.75 45 (Outside diameter) ø19.05 ø12.7
ø31.75 ø19.05 ø19.05 ø15.88 ø6.35
46

30

ø25.4 (Outside diameter)


ø28.58 (Outside diameter)
(Outside diameter)
37 28
69 58
100 (2 Pcs.) ø19.05 ø15.88
54 ø31.75 ø41.28 (Outside diameter)
(Outside diameter)
ø31.75 ø28.58 30
(Outside diameter)

69
*Pipe diameter is indicated by inside diameter. 46 (2 Pcs.)

MEES18K047 152
0000005024.BOOK 153 ページ 2018年11月12日 月曜日 午後6時54分

9. OPTIONAL PARTS Y-Series (Cooling-only)

9-2. HEADER
CITY MULTI units can be easily connected by using Joint sets and Header sets provided by Mitsubishi Electric. Three kinds of
Header sets are available for use. Refer to section "Piping Design" or the Installation Manual that comes with the Header set for
how to install the Header set.

PUCY-P-Y(S)KD, EP-YSKD
mm
CMY-Y104-G
For Gas pipe:
<Deformed pipe(Accessory)>

For Liquid pipe: <Deformed pipe(Accessory)>

CMY-Y108-G mm

For Gas pipe:


<Deformed pipe(Accessory)>

For Liquid pipe: <Deformed pipe(Accessory)>

mm
CMY-Y1010-G
For Gas pipe:
<Deformed pipe(Accessory)>

For Liquid pipe:


<Deformed pipe(Accessory)>

MEES18K047 153
0000005024.BOOK 154 ページ 2018年11月12日 月曜日 午後6時54分

9. OPTIONAL PARTS Y-Series (Cooling-only)

9-3. OUTDOOR TWINNING KIT


The following optional Outdoor Twinning Kit is needed to use to combine multiple refrigerant pipes. Refer to section "Piping Design"
for the details of selecting a proper twinning kit.

mm
CMY-Y100VBK3
PUCY-P-Y(S)KD, EP-YSKD

For Gas pipe: For Liquid pipe: <Deformed pipe(Accessory)>

505 183 12.7


25.4 12.7
22.2
Pipe cover 12.7 15.88
15.88 Local brazing 9.52 12.7
(Dot-dashed part)
Local brazing 12.7

98
28.58 49 49
160

(2 pcs.)
22.2 22.2 28.58 22.2 19.05
15.88
Note 2 Pipe cover
28.58 83 12.7
(Dot-dashed part) 62 62
Note 2 342 Distributer 25.4 (2 pcs.)
Distributer (2 pcs.)
588
241

ID: Inner Diameter OD: Outer Diameter

CMY-Y200VBK2 mm
For Gas pipe: For Liquid pipe: <Deformed pipe(Accessory)>

503 191 15.88


28.58 15.88
28.58
Pipe cover 19.05 15.88 12.7
Local brazing
(Dot-dashed part)
15.88
115

Local brazing
31.75 49
162

(2 pcs.)
28.58 34.93 41.28
19.05 Pipe cover
Note 2 (Dot-dashed part)
34.93 85 15.88
Note 2 337 Distributer 69
Distributer 28.58
244
585

ID: Inner Diameter OD: Outer Diameter

CMY-Y300VBK3 mm
For Gas pipe: For Liquid pipe: <Deformed pipe(Accessory)>

505
28.58
38.1 41.28
28.58 15.88 12.7
Pipe cover 191 15.88
(Dot-dashed part)
15.88
Local brazing 49
31.75 19.05 Local brazing 69
162

19.05 28.58 22.2


115

34.93 15.88 9.52

38.1 62 49
Note 2 19.05 (3 pcs.)
339 28.58 Note 2 Pipe cover
85 (Dot-dashed part) 15.88
Distributer
582 Distributer
246 38.1
12.7 9.52 34.93
185
500 12.7
25.4 12.7
28.58 49
Pipe cover 15.88 Local brazing
(2 pcs.) 69
(Dot-dashed part)
12.7 12.7 15.88 28.58 19.05
98

Local brazing
28.58
162

28.58 49
19.05 62
Pipe cover (2 pcs.)
Note 2 (2 pcs.)
(Dot-dashed part) 12.7
34.93 85
Note 2 Distributer
337 25.4 243

Distributer
585

ID: Inner Diameter OD: Outer Diameter

Note 1. Refer to the figure below for the installation position of the twinning pipe.

Twinning pipe
15

Slope of the twinning pipes are at an angle within 15 to the horizontal plane.
2. Use the attached pipe to braze the port-opening of the twinning pipe.
3. Pipe diameter is indicated by inside diameter.
4. Only use the twinning pipe by Mitsubishi (optional parts).

MEES18K047 154
0000005024.BOOK 155 ページ 2018年11月12日 月曜日 午後6時54分

10. ELECTRICAL WORK Y-Series (Cooling-only)

10-1. General cautions


10. ELECTRICAL WORK

Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring
regulations, and guidance of each electric power company.
Wiring for control (hereinafter referred to as transmission cable) shall be (50mm[1-5/8in.] or more) apart from power source
wiring so that it is not influenced by electric noise from power source wiring. (Do not insert transmission cable and power

PUCY-P-Y(S)KD, EP-YSKD
source wire in the same conduit.)
Be sure to provide designated grounding work to outdoor unit.
Give some allowance to wiring for electrical part box of indoor and outdoor units, because the box is sometimes removed
at the time of service work.
Never connect 380~415V(220~240V) power source to terminal block of transmission cable. If connected,electrical parts
will be damaged.
Use 2-core shield cable for transmission cable. If transmission cables of different systems are wired with the same
multiple-core cable, the resultant poor transmitting and receiving will cause erroneous operations.
When extending the transmission line, make sure to extend the shield cable as well.

Indoor unit Indoor unit


Outdoor Outdoor
unit unit

OK NO
2-core shield cable
Multiple-
core cable Remote
Remote controller
controller
BC controller BC controller

2-core shield cable

MEES18K047 155
0000005024.BOOK 156 ページ 2018年11月12日 月曜日 午後6時54分

10. ELECTRICAL WORK Y-Series (Cooling-only)

10-2. Power supply for Outdoor unit


10-2-1. Electrical characteristics of Outdoor unit
Symbols: MCA: Max Circuit Amps
RLA: Rated Load Amps SC: Starting Current
PUCY-P-Y(S)KD, EP-YSKD

Units Power supply Compressor FAN RLA (A) (50 / 60Hz)


PUCY-P-YKD Unit Combination
Hz Volts Voltage range MCA(A) Output (kW) SC (A) Output (kW) Cooling
PUCY-P200YKD(-BS) - 18.0 5.5 0.92 7.8/7.4/7.2
PUCY-P250YKD(-BS) - 22.4 6.9 0.92 10.0/9.5/9.1
PUCY-P300YKD(-BS) - 27.6 8.1 0.92 13.2/12.5/12.0
PUCY-P350YKD(-BS) - 28.7 10.4 0.92 16.3/15.4/14.9
PUCY-P400YKD(-BS) - 34.9 10.8 0.92 20.9/19.9/19.1
PUCY-P450YKD(-BS) - 35.3 12.4 0.92 24.1/22.9/22.1
PUCY-P500YKD(-BS) - 37.6 13.3 0.92+0.92 27.8/26.4/25.5
PUCY-P300YKD(-BS) 27.6 8.1 0.92
PUCY-P550YSKD(-BS) 23.7/22.5/21.7
PUCY-P250YKD(-BS) 22.4 6.9 0.92
PUCY-P350YKD(-BS) 28.7 10.4 0.92
PUCY-P600YSKD(-BS) 25.8/24.6/23.7
PUCY-P250YKD(-BS) 22.4 6.9 0.92
PUCY-P400YKD(-BS) 34.9 10.8 0.92
PUCY-P650YSKD(-BS) 29.9/28.4/27.4
PUCY-P250YKD(-BS) 22.4 6.9 0.92
PUCY-P450YKD(-BS) 35.3 12.4 0.92
PUCY-P700YSKD(-BS) 32.4/30.8/29.7
PUCY-P250YKD(-BS) 22.4 6.9 0.92
PUCY-P450YKD(-BS) 35.3 12.4 0.92
PUCY-P750YSKD(-BS) 36.7/34.9/33.6
PUCY-P300YKD(-BS) 27.6 8.1 0.92
PUCY-P400YKD(-BS) 34.9 10.8 0.92
PUCY-P800YSKD(-BS) 42.2/40.0/38.6
PUCY-P400YKD(-BS) 34.9 10.8 0.92
PUCY-P450YKD(-BS) 35.3 12.4 0.92
PUCY-P850YSKD(-BS) 45.5/43.2/41.6
PUCY-P400YKD(-BS) 34.9 10.8 0.92
PUCY-P450YKD(-BS) 35.3 12.4 0.92
PUCY-P900YSKD(-BS) 48.9/46.5/44.8
PUCY-P450YKD(-BS) 35.3 12.4 0.92
PUCY-P500YKD(-BS) 37.6 13.3 0.92+0.92
PUCY-P950YSKD(-BS) 53.1/50.5/48.7
PUCY-P450YKD(-BS) 35.3 12.4 0.92
PUCY-P500YKD(-BS) 37.6 13.3 0.92+0.92
PUCY-P1000YSKD(-BS) 57.4/54.5/52.6
PUCY-P500YKD(-BS) 37.6 13.3 0.92+0.92
PUCY-P450YKD(-BS) 35.3 12.4 0.92
380
Max: 456V
PUCY-P1050YSKD(-BS) PUCY-P300YKD(-BS) 50/60 400 27.6 8.1 8 0.92 50.0/47.5/45.8
Min: 342V
415
PUCY-P300YKD(-BS) 27.6 8.1 0.92
PUCY-P450YKD(-BS) 35.3 12.4 0.92
PUCY-P1100YSKD(-BS) PUCY-P350YKD(-BS) 28.7 10.4 0.92 52.3/49.7/47.9
PUCY-P300YKD(-BS) 27.6 8.1 0.92
PUCY-P400YKD(-BS) 34.9 10.8 0.92
PUCY-P1150YSKD(-BS) PUCY-P400YKD(-BS) 34.9 10.8 0.92 57.3/54.4/52.4
PUCY-P350YKD(-BS) 28.7 10.4 0.92
PUCY-P400YKD(-BS) 34.9 10.8 0.92
PUCY-P1200YSKD(-BS) PUCY-P400YKD(-BS) 34.9 10.8 0.92 63.3/60.1/57.9
PUCY-P400YKD(-BS) 34.9 10.8 0.92
PUCY-P450YKD(-BS) 35.3 12.4 0.92
PUCY-P1250YSKD(-BS) PUCY-P400YKD(-BS) 34.9 10.8 0.92 66.5/63.2/60.9
PUCY-P400YKD(-BS) 34.9 10.8 0.92
PUCY-P450YKD(-BS) 35.3 12.4 0.92
PUCY-P1300YSKD(-BS) PUCY-P450YKD(-BS) 35.3 12.4 0.92 70.1/66.6/64.2
PUCY-P400YKD(-BS) 34.9 10.8 0.92
PUCY-P450YKD(-BS) 35.3 12.4 0.92
PUCY-P1350YSKD(-BS) PUCY-P450YKD(-BS) 35.3 12.4 0.92 73.6/69.9/67.4
PUCY-P450YKD(-BS) 35.3 12.4 0.92
PUCY-P500YKD(-BS) 37.6 13.3 0.92+0.92
PUCY-P1400YSKD(-BS) PUCY-P450YKD(-BS) 35.3 12.4 0.92 77.7/73.8/71.1
PUCY-P450YKD(-BS) 35.3 12.4 0.92
PUCY-P500YKD(-BS) 37.6 13.3 0.92+0.92
PUCY-P1450YSKD(-BS) PUCY-P500YKD(-BS) 37.6 13.3 0.92+0.92 82.0/77.9/75.1
PUCY-P450YKD(-BS) 35.3 12.4 0.92
PUCY-P500YKD(-BS) 37.6 13.3 0.92+0.92
PUCY-P1500YSKD(-BS) PUCY-P500YKD(-BS) 37.6 13.3 0.92+0.92 86.1/81.8/78.9
PUCY-P500YKD(-BS) 37.6 13.3 0.92+0.92

MEES18K047 156
0000005024.BOOK 157 ページ 2018年11月12日 月曜日 午後6時54分

10. ELECTRICAL WORK Y-Series (Cooling-only)

Symbols: MCA: Max Circuit Amps


RLA: Rated Load Amps SC: Starting Current

Units Power supply Compressor FAN RLA(A)(50/60Hz)


PUCY-EP-YKD Unit Combination Output
Hz Volts Voltage range MCA(A) Output (kW) SC(A) Cooling
(kW)

PUCY-P-Y(S)KD, EP-YSKD
PUCY-P200YKD(-BS) 18.0 5.5 0.92
PUCY-EP400YSKD(-BS) 16.7/15.9/15.3
PUCY-P200YKD(-BS) 18.0 5.5 0.92
PUCY-P250YKD(-BS) 22.4 6.9 0.92
PUCY-EP450YSKD(-BS) 19.1/18.2/17.5
PUCY-P200YKD(-BS) 18.0 5.5 0.92
PUCY-P250YKD(-BS) 22.4 6.9 0.92
PUCY-EP500YSKD(-BS) 21.6/20.5/19.8
PUCY-P250YKD(-BS) 22.4 6.9 0.92
PUCY-P350YKD(-BS) 28.7 10.4 0.92
PUCY-EP650YSKD(-BS) 30.9/29.3/28.3
PUCY-P300YKD(-BS) 27.6 8.1 0.92
PUCY-P350YKD(-BS) 28.7 10.4 0.92
PUCY-EP700YSKD(-BS) 33.3/31.6/30.5
PUCY-P350YKD(-BS) 28.7 10.4 0.92
PUCY-P350YKD(-BS) 28.7 10.4 0.92
PUCY-EP750YSKD(-BS) PUCY-P200YKD(-BS) 18.0 5.5 0.92 32.8/31.1/30.0
PUCY-P200YKD(-BS) 18.0 5.5 0.92
PUCY-P350YKD(-BS) 28.7 10.4 0.92
PUCY-EP800YSKD(-BS) PUCY-P250YKD(-BS) 22.4 6.9 0.92 35.4/33.6/32.4
PUCY-P200YKD(-BS) 18.0 5.5 0.92
PUCY-P350YKD(-BS) 380 28.7 10.4 0.92
Max:456V
50/60 400 8
PUCY-EP850YSKD(-BS) PUCY-P250YKD(-BS) Min:342V 22.4 6.9 0.92 38.0/36.1/34.8
415
PUCY-P250YKD(-BS) 22.4 6.9 0.92
PUCY-P350YKD(-BS) 28.7 10.4 0.92
PUCY-EP900YSKD(-BS) PUCY-P300YKD(-BS) 27.6 8.1 0.92 41.4/39.4/37.9
PUCY-P250YKD(-BS) 22.4 6.9 0.92
PUCY-P350YKD(-BS) 28.7 10.4 0.92
PUCY-EP950YSKD(-BS) PUCY-P300YKD(-BS) 27.6 8.1 0.92 45.2/42.9/41.4
PUCY-P300YKD(-BS) 27.6 8.1 0.92
PUCY-P350YKD(-BS) 28.7 10.4 0.92
PUCY-EP1000YSKD(-BS) PUCY-P350YKD(-BS) 28.7 10.4 0.92 48.6/46.1/44.5
PUCY-P300YKD(-BS) 27.6 8.1 0.92
PUCY-P350YKD(-BS) 28.7 10.4 0.92
PUCY-EP1050YSKD(-BS) PUCY-P350YKD(-BS) 28.7 10.4 0.92 50.0/47.5/45.7
PUCY-P350YKD(-BS) 28.7 10.4 0.92
PUCY-P400YKD(-BS) 34.9 10.8 0.92
PUCY-EP1100YSKD(-BS) PUCY-P350YKD(-BS) 28.7 10.4 0.92 54.6/51.9/50.0
PUCY-P350YKD(-BS) 28.7 10.4 0.92

MEES18K047 157
0000005024.BOOK 158 ページ 2018年11月12日 月曜日 午後6時54分

10. ELECTRICAL WORK Y-Series (Cooling-only)

10-3. Power cable specifications


Thickness of wire for main power supply, capacities of the switch and system impedance
Minimum wire thickness (mm2) Local switch (A) Breaker for wiring (A) Max.Permissive
Model Ground-fault interrupter *1
Main cable Branch Ground Capacity Fuse (Non-fuse breaker) System Impedance
PUCY-P200YKD 4.0 - 4.0 20A 100mA 0.1sec. or less 20 20 20 *2
PUCY-P-Y(S)KD, EP-YSKD

PUCY-P250YKD 4.0 - 4.0 30A 100mA 0.1sec. or less 25 25 30 *2


PUCY-P300YKD 4.0 - 4.0 30A 100mA 0.1sec. or less 32 32 30 0.26Ω
Outdoor unit PUCY-P350YKD 4.0 - 4.0 30A 100mA 0.1sec. or less 32 32 30 0.25Ω
PUCY-P400YKD 6.0 - 6.0 40A 100mA 0.1sec. or less 40 40 40 0.20Ω
PUCY-P450YKD 6.0 - 6.0 40A 100mA 0.1sec. or less 40 40 40 0.20Ω
PUCY-P500YKD 6.0 - 6.0 40A 100mA 0.1sec. or less 40 40 40 0.19Ω
Total operating F0 = 16A or less *3 1.5 1.5 1.5 20A current sensitivity *4 16 16 20 (apply to IEC61000-3-3)
current of F0 = 25A or less *3 2.5 2.5 2.5 30A current sensitivity *4 25 25 30 (apply to IEC61000-3-3)
the indoor unit F0 = 32A or less *3 4.0 4.0 4.0 40A current sensitivity *4 32 32 40 (apply to IEC61000-3-3)

*1 The Ground-fault interrupter should support Inverter circuit.


The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Meet technical requirements of IEC61000-3-3

*3 Please take the larger of F1 or F2 as the value for F0.


F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type1)/C} + {V1 × (Quantity of Type2)/C} + {V1 × (Quantity of Type3)/C} + {V1 × (Quantity of Type4)/C} + {V1 × (Quantity of Type5)/C} +
{V1 × (Quantity of Type6)/C} + {V1 × (Quantity of Type7)/C} + {V1 × (Quantity of Others)/C}

Indoor unit V1 V2
6000
Type1 PEFY-VMS, PFFY-VKM, PFFY-VLRMM 18.6 2.4
Type2 PEFY-VMA 38 1.6
Type3 PEFY-P200, 250VMHS 13.8 4.8 600 SAMPLE
Type4 PEFY-P40-140VMHS 26.8 1.6
Type5 PLFY-VBM, PCFY-VKM 19.8 2.4

Tripping Time [s]


60
Type6 PMFY-VBM, PKFY-VKM, PKFY-VHM 9.9 2.4
Type7 PLFY-VEM, PLFY-VFM 17.1 2.4 10
Others Other indoor unit 0 0
C: Multiple of tripping current at tripping time 0.01s
1
Please pick up "C" from the tripping characteristic of the breaker.
<Example of "F2" calculation>
*Condition PEFY-VMS × 4 + PEFY-VMA × 1, C = 8 (refer to right sample chart) 0.1
F2 = 18.6 × 4/8 + 38 × 1/8
= 14.05 0.01
→16 A breaker (Tripping current = 8 × 16 A at 0.01s) 1 2 3 4 6 8 10 20

C
Rated Tripping current (x)
*4 Current sensitivity is calculated using the following formula. Sample chart
G1 = (V2 × Quantity of Type1) + (V2 × Quantity of Type2) + (V2 × Quantity of Type3) + (V2 × Quantity of Type4) + (V2 × Quantity of Type5) +
(V2 × Quantity of Type6) + (V2 × Quantity of Type7) + (V2 × Quantity of Others) + (V3 × Wire length [km])

G1 Current sensitivity Wire thickness V3


30 or less 30 mA 0.1sec or less 1.5 mm2 48
100 or less 100 mA 0.1sec or less 2.5 mm2 56
4.0 mm2 66

1. Use dedicated power supplies for the outdoor unit and indoor unit. Ensure OC and OS are wired individually.
2. Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water, etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one rank thicker in diameter. Make sure the power-supply voltage does not drop more
than 10%. Make sure that the voltage imbalance between the phases is 2% or less.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For example, use wiring such as YZW.
6. A switch with at least 3 mm contact separation in each pole shall be provided by the Air Conditioner installer.

 Be sure to use specified wires for connections and ensure no external force is imparted to terminal connections. If connections are not fixed firmly, heating or fire may result.
 Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.

 The breakers for current leakage should support Inverter circuit. (e.g. Mitsubishi Electric's NV-S series or equivalent). If no earth leakage breaker is installed, it may cause an electric shock.
 Breakers for current leakage should combine using of switch.
 Do not use anything other than a breaker with the correct capacity. Using a breaker of too large capacity may cause malfunction or fire.
 If a large electric current flows due to malfunction or faulty wiring, earth-leakage breakers on the unit side and on the upstream side of the power supply system may both operate.
Depending on the importance of the system, separate the power supply system or take protective coordination of breakers.

 This device is intended for the connection to a power supply system with a maximum permissible system impedance shown in the above table at the interface point (power service box) of
the user's supply.

 The user must ensure that this device is connected only to a power supply system which fulfils the requirement above.
If necessary, the user can ask the public power supply company for the system impedance at the interface point.

 This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc(*2) at the interface point between the user's supply and the public
system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to
a supply with a short-circuit power Ssc greater than or equal to Ssc(*2).

Ssc(*2)
Model PUCY-P200YKD PUCY-P250YKD PUCY-P300YKD PUCY-P350YKD PUCY-P400YKD PUCY-P450YKD PUCY-P500YKD
Ssc(MVA) 1.40 1.74 2.14 2.23 2.71 2.74 2.92

MEES18K047 158
0000005024.BOOK 159 ページ 2018年11月12日 月曜日 午後6時54分

10. ELECTRICAL WORK Y-Series (Cooling-only)

10-4. Power supply examples

The local standards and/or regulations is applicable at a higher priority.


10-4-1. PUCY-P200-500YKD
Note:
<In the case a system controller is connected.> 1 The transmission cable is not-polarity double-wire.

PUCY-P-Y(S)KD, EP-YSKD
Centralized control 2 Symbol means a screw terminal for wiring.
transmission cable 3 The shield wire of transmission cable should be connected to the grounding terminal at
Note11 >=1.25mm2 Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be
SC Shield cable connected to the S terminal at Indoor unit or all shield wire should be connected together.
(CVVS, CPEVS The broken line at the scheme means shield wire.
MVVS) 4 When the Outdoor unit connected with system controller, power-supply to TB7 of the
outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the
OU outdoor units will enable the outdoor unit to supply power to TB7, or an extra power
Connector supplying unit PAC-SC51KUA should be used. The transmission cable (above 1.25mm2,
CN41 CN40 Note4 shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is called
Note4 centralized control transmission cable. The shield wire of the centralized control
transmission cable must be grounded at the Outdoor unit whose CN41 is changed to
To other OU CN40. When the power supplying unit PAC-SC51KUA is used, connect the shielded
cable to the ground terminal on the PAC-SC51KUA.
5 MA R/C transmission cable (0.3-1.25mm2) must be less than 200m in length, while ME
LW TB1 TB3 TB7 R/C transmission cable (0.3-1.25mm2) must be less than 10m in length. But transmission
GFI WB (L1,L2,L3,N) (M1,M2) (M1,M2) cable to the ME R/C can be extend using a M-NET cable (>=1.25mm2) when the length
is counted in the M-Net length.
TB7 6 MA remote controller and ME remote controller should not be grouped together.
Power supply (S) When a PAR-CT01MA or PAR-3X MA-Series (X indicates 1, 2…) is connected to a
3-phase 4-wire
380-400-415V 50/60Hz group, no other MA remote controllers can be connected to the same group.
Note10,12 7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
transmission cable to connect all the TB15 terminals of the Indoor units. It is called
"Grouping".
If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set
Note3 address to Indoor unit and ME remote controller. For the method, refer to 11-4. "Address
Setting".
8 Indoor board consumes power from TB3. The power balance should be considered
according to System Design 11-3 "System configuration restrictions".
To *1 or *2 9 If Transmission booster is needed, be sure to connect the shield wires to the both sides
to the booster.
*1 10 The critical current for choosing power source equipment is approximate
1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).
(Using MA remote controller) 11 When System controller (SC) is connected to the system, turn the SW5-1 on.
Connecting TB5 terminal. 12 The phases of electricity power must be confirmed to be right used. Phase-reverse, or
phase-missing could break the controllers.

LW >=dia.1.6mm Pull box


GFI WB >=dia.1.6mm

Note7 LW
Power supply GFI WB
1-phase
220-240V 50/60Hz TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15
Note10 (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) Power supply TB1 (M1,M2) (L,N) (1,2)
S S S 1-phase (R,S) E S
* Power supply GFI, LW, WB IU (Shield) (Shield) (Shield) 220-240V 50/60Hz
TB2 TB3 (Shield)
specifications vary with the MA R/C cable
model of connected indoor S S 0.3-1.25mm2
units (Shield) (Shield)
<=200m
Indoor-outdoor Transmission Note5
transmission cable booster
>=1.25mm2 Note6 Note8
Shield cable Note7 Note9
MA R/C MA R/C MA R/C

*2
(Using ME remote controller)
Connecting TB5 terminal.

LW >=dia.1.6mm Pull box


GFI WB >=dia.1.6mm

Note7 LW
Power supply GFI WB
1-phase
220-240V 50/60Hz TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15
Note10 (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) Power supply
TB1 (M1,M2) (L,N) (1,2)
S S S 1-phase S
220-240V 50/60Hz (R,S) E
* Power supply, GFI, LW, WB IU (Shield) (Shield) (Shield) TB2 TB3 (Shield)
specifications vary with the
model of connected indoor S S ME R/C cable
units (Shield) (Shield) 0.3~1.25mm2
<=10m
Indoor-outdoor Transmission Note5
transmission cable booster
>=1.25mm2 Note8
Shield cable Note6 Note9
Note7
ME R/C ME R/C ME R/C

Symbol Model Ground-fault interrupter Local switch Wiring breaker*4 Minimum Wire thickness
*1, *2, *4 BKC OCP*3, *4 (NFB) Power wire Earth wire
<A> <A> <A> <mm2> <mm2>

GFI Ground-fault interrupter PUCY-P200YKD 20A 100mA 0.1sec. or less 20 20 20 4 4


LW Local switch PUCY-P250YKD 30A 100mA 0.1sec. or less 25 25 30 4 4
BKC Breaker capacity PUCY-P300YKD 30A 100mA 0.1sec. or less 32 32 30 4 4
OCP Over-current protector PUCY-P350YKD 30A 100mA 0.1sec. or less 32 32 30 4 4
WB Wiring breaker PUCY-P400YKD 40A 100mA 0.1sec. or less 40 40 40 6 6
NFB Non-fuse breaker PUCY-P450YKD 40A 100mA 0.1sec. or less 40 40 40 6 6
OU Outdoor unit PUCY-P500YKD 40A 100mA 0.1sec. or less 40 40 40 6 6
IU Indoor unit
SC System controller *1 The Ground-fault interrupter should support Inverter circuit. (e.g. Mitsubishi Electric's NV-S-Series or equivalent).
*2 Ground-fault interrupter should combine using of local switch or wiring breaker.
MA R/C MA remote controller
*3 It shows data for B-type fuse of the breaker for current leakage.
ME R/C ME remote controller *4 If a large electric current flows due to malfunction or faulty wiring, earth-leakage breakers on the unit side and on the centralized controller side
may both operate.
Depending on the importance of the system, separate the power supply system or take protective coordination of breakers.

MEES18K047 159
0000005024.BOOK 160 ページ 2018年11月12日 月曜日 午後6時54分

10. ELECTRICAL WORK Y-Series (Cooling-only)

The local standards and/or regulations is applicable at a higher priority.


10-4-2. PUCY-P550-1000YSKD, PUCY-EP400-700YSKD
<In the case a system controller is connected.> Note:
Centralized control 1 The transmission cable is not-polarity double-wire.
transmission cable 2 Symbol means a screw terminal for wiring.
Note11 >=1.25mm2 3 The shield wire of transmission cable should be connected to the grounding terminal at
SC Shield cable Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be
PUCY-P-Y(S)KD, EP-YSKD

(CVVS, CPEVS connected to the S terminal at Indoor unit or all shield wire should be connected together.
MVVS) The broken line at the scheme means shield wire.
4 When the Outdoor unit connected with system controller, power-supply to TB7 of the
OU OU outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the
Connector outdoor units will enable the outdoor unit to supply power to TB7, or an extra power
CN41 CN40 Note4 supplying unit PAC-SC51KUA should be used. The transmission cable (above 1.25mm2,
Note4 shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is called
centralized control transmission cable. The shield wire of the centralized control
To other OU transmission cable must be grounded at the Outdoor unit whose CN41 is changed to
CN40. When the power supplying unit PAC-SC51KUA is used, connect the shielded
cable to the ground terminal on the PAC-SC51KUA.
LW TB1 TB3 TB7 LW TB1 TB3 TB7 5 MA R/C transmission cable (0.3-1.25mm2) must be less than 200m in length, while ME
GFI WB (L1,L2,L3,N) (M1,M2) (M1,M2) GFI WB (L1,L2,L3,N) (M1,M2) (M1,M2) R/C transmission cable (0.3-1.25mm2) must be less than 10m in length. But transmission
cable to the ME R/C can be extend using a M-NET cable (>=1.25mm2) when the length
TB7 TB7 is counted in the M-Net length.
Power supply (S) Power supply (S) 6 MA remote controller and ME remote controller should not be grouped together.
3-phase 4-wire 3-phase 4-wire When a PAR-CT01MA or PAR-3X MA-Series (X indicates 1, 2…) is connected to a
380-400-415V 50/60Hz 380-400-415V 50/60Hz group, no other MA remote controllers can be connected to the same group.
Note10,12 Note10,12 7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
transmission cable to connect all the TB15 terminals of the Indoor units. It is called
Note3 "Grouping".
Note3 If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set
address to Indoor unit and ME remote controller. For the method, refer to 11-4. "Address
Setting".
8 Indoor board consumes power from TB3. The power balance should be considered
To *1 or *2 according to System Design 11-3 "System configuration restrictions".
9 If Transmission booster is needed, be sure to connect the shield wires to the both sides
*1 to the booster.
10 The critical current for choosing power source equipment is approximate
(Using MA remote controller) 1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).
Connecting TB5 terminal. 11 When System controller (SC) is connected to the system, turn the SW5-1 on.
12 The phases of electricity power must be confirmed to be right used. Phase-reverse, or
phase-missing could break the controllers.
LW >=dia.1.6mm Pull box
GFI WB >=dia.1.6mm

Note7 LW
Power supply GFI WB
1-phase
220-240V 50/60Hz TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15
Note10 (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) Power supply TB1 (M1,M2) (L,N) (1,2)
S S S 1-phase (R,S) E S
* Power supply, GFI·LW·WB IU (Shield) (Shield) (Shield) 220-240V 50/60Hz
TB2 TB3 (Shield)
specifications vary with the MA R/C cable
model of connected indoor S S 0.3-1.25mm2
units (Shield) (Shield)
<=200m
Indoor-outdoor Transmission Note5
transmission cable booster
>=1.25mm2 Note6 Note8
Shield cable Note7 Note9
MA R/C MA R/C MA R/C

*2
(Using ME remote controller)
Connecting TB5 terminal.

LW >=dia.1.6mm Pull box


GFI WB >=dia.1.6mm

Note7 LW
Power supply GFI WB
1-phase
220-240V 50/60Hz TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15
Note10 (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) Power supply
TB1 (M1,M2) (L,N) (1,2)
S S S 1-phase S
220-240V 50/60Hz (R,S) E
* Power supply, GFI·LW·WB IU (Shield) (Shield) (Shield) TB2 TB3 (Shield)
specifications vary with the
model of connected indoor S S ME R/C cable
units (Shield) (Shield) 0.3~1.25mm2
<=10m
Indoor-outdoor Transmission Note5
transmission cable booster
>=1.25mm2 Note8
Shield cable Note6 Note9
Note7
ME R/C ME R/C ME R/C

Symbol Model Ground-fault interrupter Local switch Wiring breaker*4 Minimum Wire thickness
*1, *2, *4 BKC OCP*3, *4 (NFB) Power wire Earth wire
<A> <A> <A> <mm2> <mm2>

GFI Ground-fault interrupter PUCY-P200YKD 20A 100mA 0.1sec. or less 20 20 20 4 4


LW Local switch PUCY-P250YKD 30A 100mA 0.1sec. or less 25 25 30 4 4
BKC Breaker capacity PUCY-P300YKD 30A 100mA 0.1sec. or less 32 32 30 4 4
OCP Over-current protector PUCY-P350YKD 30A 100mA 0.1sec. or less 32 32 30 4 4
WB Wiring breaker PUCY-P400YKD 40A 100mA 0.1sec. or less 40 40 40 6 6
NFB Non-fuse breaker PUCY-P450YKD 40A 100mA 0.1sec. or less 40 40 40 6 6
OU Outdoor unit PUCY-P500YKD 40A 100mA 0.1sec. or less 40 40 40 6 6
IU Indoor unit
SC System controller *1 The Ground-fault interrupter should support Inverter circuit. (e.g. Mitsubishi Electric's NV-S-Series or equivalent).
*2 Ground-fault interrupter should combine using of local switch or wiring breaker.
MA R/C MA remote controller
*3 It shows data for B-type fuse of the breaker for current leakage.
ME R/C ME remote controller *4 If a large electric current flows due to malfunction or faulty wiring, earth-leakage breakers on the unit side and on the centralized controller side
may both operate.
Depending on the importance of the system, separate the power supply system or take protective coordination of breakers.

MEES18K047 160
0000005024.BOOK 161 ページ 2018年11月12日 月曜日 午後6時54分

10. ELECTRICAL WORK Y-Series (Cooling-only)

The local standards and/or regulations is applicable at a higher priority.


10-4-3. PUCY-P1050-1500YSKD, PUCY-EP750-1100YSKD
<In the case a system controller is connected.>
Centralized control Note:
Note11 transmission cable 1 The transmission cable is not-polarity double-wire.
SC >=1.25mm2 2 Symbol means a screw terminal for wiring.
Shield cable 3 The shield wire of transmission cable should be connected to the grounding terminal at

PUCY-P-Y(S)KD, EP-YSKD
(CVVS, CPEVS Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be
MVVS) connected to the S terminal at Indoor unit or all shield wire should be connected together.
The broken line at the scheme means shield wire.
4 When the Outdoor unit connected with system controller, power-supply to TB7 of the
Connector outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the
CN41 CN40 Note4 outdoor units will enable the outdoor unit to supply power to TB7, or an extra power
OU OU OU
Note4 supplying unit PAC-SC51KUA should be used. The transmission cable (above 1.25mm2,
To other OU shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is called
centralized control transmission cable. The shield wire of the centralized control
LW TB1 TB3 TB7 LW TB1 TB3 TB7 LW TB1 TB3 TB7 transmission cable must be grounded at the Outdoor unit whose CN41 is changed to
GFI WB (L1,L2,L3,N) (M1,M2) (M1,M2) GFI WB (L1,L2,L3,N) (M1,M2) (M1,M2) GFI WB (L1,L2,L3,N) (M1,M2) (M1,M2)
CN40. When the power supplying unit PAC-SC51KUA is used, connect the shielded
TB7 TB7 TB7 cable to the ground terminal on the PAC-SC51KUA.
Power supply (S) Power supply (S) Power supply (S)
3-phase 4-wire 3-phase 4-wire 3-phase 4-wire 5 MA R/C transmission cable (0.3-1.25mm2) must be less than 200m in length, while ME
380-400-415V 50/60Hz 380-400-415V 50/60Hz 380-400-415V 50/60Hz R/C transmission cable (0.3-1.25mm2) must be less than 10m in length. But transmission
Note10,12 Note10,12 Note10,12
cable to the ME R/C can be extend using a M-NET cable (>=1.25mm2) when the length
is counted in the M-Net length.
Note3 Note3
Note3 6 MA remote controller and ME remote controller should not be grouped together.
When a PAR-CT01MA or PAR-3X MA-Series (X indicates 1, 2…) is connected to a
group, no other MA remote controllers can be connected to the same group.
7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
transmission cable to connect all the TB15 terminals of the Indoor units. It is called
"Grouping".
If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set
address to Indoor unit and ME remote controller. For the method, refer to 11-4. "Address
Setting".
To *1 or *2 8 Indoor board consumes power from TB3. The power balance should be considered
according to System Design 11-3 "System configuration restrictions".
*1 9 If Transmission booster is needed, be sure to connect the shield wires to the both sides
to the booster.
(Using MA remote controller) 10 The critical current for choosing power source equipment is approximate
Connecting TB5 terminal. 1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).
11 When System controller (SC) is connected to the system, turn the SW5-1 on.
12 The phases of electricity power must be confirmed to be right used. Phase-reverse, or
LW phase-missing could break the controllers.
>=dia.1.6mm Pull box
GFI WB >=dia.1.6mm

Note7 LW
Power supply GFI WB
1-phase
220-240V 50/60Hz TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15
Note10 (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) Power supply TB1 (M1,M2) (L,N) (1,2)
S S S 1-phase (R,S) E S
* Power supply, GFI·LW·WB IU (Shield) (Shield) (Shield) 220-240V 50/60Hz
TB2 TB3 (Shield)
specifications vary with the MA R/C cable
model of connected indoor S S 0.3-1.25mm2
units (Shield) (Shield)
<=200m
Indoor-outdoor Transmission Note5
transmission cable booster
>=1.25mm2 Note6 Note8
Shield cable Note7 Note9
MA R/C MA R/C MA R/C

*2
(Using ME remote controller)
Connecting TB5 terminal.

LW >=dia.1.6mm Pull box


GFI WB >=dia.1.6mm

Note7 LW
Power supply GFI WB
1-phase
220-240V 50/60Hz TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15 TB5 TB2 TB15
Note10 (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) (M1,M2) (L,N) (1,2) Power supply
TB1 (M1,M2) (L,N) (1,2)
S S S 1-phase S
220-240V 50/60Hz (R,S) E
* Power supply, GFI·LW·WB IU (Shield) (Shield) (Shield) TB2 TB3 (Shield)
specifications vary with the
model of connected indoor S S ME R/C cable
units (Shield) (Shield) 0.3~1.25mm2
<=10m
Indoor-outdoor Transmission Note5
transmission cable booster
>=1.25mm2 Note8
Shield cable Note6 Note9
Note7
ME R/C ME R/C ME R/C

Symbol Model Ground-fault interrupter Local switch Wiring breaker*4 Minimum Wire thickness
*1, *2, *4 BKC OCP*3, *4 (NFB) Power wire Earth wire
<A> <A> <A> <mm2> <mm2>

GFI Ground-fault interrupter PUCY-P200YKD 20A 100mA 0.1sec. or less 20 20 20 4 4


LW Local switch PUCY-P250YKD 30A 100mA 0.1sec. or less 25 25 30 4 4
BKC Breaker capacity PUCY-P300YKD 30A 100mA 0.1sec. or less 32 32 30 4 4
OCP Over-current protector PUCY-P350YKD 30A 100mA 0.1sec. or less 32 32 30 4 4
WB Wiring breaker PUCY-P400YKD 40A 100mA 0.1sec. or less 40 40 40 6 6
NFB Non-fuse breaker PUCY-P450YKD 40A 100mA 0.1sec. or less 40 40 40 6 6
OU Outdoor unit PUCY-P500YKD 40A 100mA 0.1sec. or less 40 40 40 6 6
IU Indoor unit
SC System controller *1 The Ground-fault interrupter should support Inverter circuit. (e.g. Mitsubishi Electric's NV-S-Series or equivalent).
*2 Ground-fault interrupter should combine using of local switch or wiring breaker.
MA R/C MA remote controller
*3 It shows data for B-type fuse of the breaker for current leakage.
ME R/C ME remote controller *4 If a large electric current flows due to malfunction or faulty wiring, earth-leakage breakers on the unit side and on the centralized controller side
may both operate.
Depending on the importance of the system, separate the power supply system or take protective coordination of breakers.

MEES18K047 161
0000005024.BOOK 162 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

11-1. Transmission cable length limitation


11. M-NET CONTROL

11-1-1. Using MA Remote controller


Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable) L1+L2+L3, L1+L2+L4+L5, L3+L4+L5, L6+L2+L3, L6+L2+L4+L5 <=500m(1000m*1)[1640ft.(3280ft.*1)] 1.25mm2 [AWG16] or thicker
Max. length to Outdoor (M-NET cable) L1+L6, L3, L2+L4+L6, L5 <=200m[656ft.] 1.25mm2 [AWG16] or thicker
PUCY-P-Y(S)KD, EP-YSKD

Max. length from MA to Indoor for each group a1+a2, a1+a2+a3+a4 <=200m[656ft.] 0.3-1.25 mm2 [AWG22-16]
24VDC to AG-150A n <=50m[164ft.] 0.75-2.0 mm2 [AWG18-14]
*1 When the wiring length exceeds 500 m (1640 ft), consult the sales office.

L6 L1

Group1 Group3 Group5


OS OC IC IC IC IC

(52) (51) (01) (04) (05) (06)


TB3 TB3 TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15
M1M2 M1M2 M1M2 S 1 2 M1M2 S 1 2 M1M2 S 1 2 M1M2 S 1 2

a2
TB7 TB7
M1M2 S M1M2 S

a1
a1

a4

A B A B A B
a2

a2

a3
Shielded wire
MA MA MA
L2

OC L3
(54 ) IC IC IC

TB7
(02) (03) (07)
M1 M2 S
TB3 TB5 TB15 TB5 TB 15 TB5 TB15
M1M2 M1M2 S 1 2 M1M2 S 1 2 M1M2 S 1 2
L4

Power Supply Unit


a1

PAC-SC51KUA
L4

A B S
V+V-FG

A B
L5

AE-200E AG-150A
MA

A B S A B S V+V-FG

OC, OS: Outdoor unit controller; IC: Indoor unit controller; MA: MA remote controller

11-1-2. Using ME Remote controller


Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7, L1+L2+L3+L5, L3+L4+L6+L7, <=500m(1000m*1)[1640ft.(3280ft.*1)] 1.25mm2 [AWG16] or thicker
L8+L2+L3+L4, L8+L2+L3+L5, L8+L2+L6+L7, L3+L5+L6+L7
Max. length to Outdoor (M-NET cable) L1+L8, L3+L4, L2+L6+L8, L7, L3+L5 <=200m[656ft.] 1.25mm2 [AWG16] or thicker
Max. length from ME to Indoor e1, e2, e3, e4 <=10m[32ft.]*2 0.3-1.25 mm2 [AWG22-16] *2
24VDC to AG-150A n <=50m[164ft.] 0.75-2.0 mm2 [AWG18-14]
*1 When the wiring length exceeds 500 m (1640 ft), consult the sales office.
*2. If the length from ME to Indoor exceed 10m, use 1.25 mm2 [AWG16] shielded cable, but the total length should be counted into Max. length via Outdoor.

L8 L1

Group1 Group3 Group5


OS OC IC IC IC IC

(52) (51) (01) (04) (05) (06)


TB3 TB3 TB5 TB5 TB5 TB5
M1M2 M1M2 M1M2 S M1M2 S M1M2 S M1M2 S

TB7 TB7
M1M2 S M1M2 S
e1

e3
e2

A B A B A B
Shielded wire (101) (105) (155)
ME ME ME
L2

OC L3 L4
(54 ) IC IC IC

TB7
(02) (03) (07)
M1 M2 S
TB3 TB5 TB5 TB5
M1M2 M1M2 S M1M2 S M1M2 S
L5
L6

Power Supply Unit


PAC-SC51KUA
e4
L6

A B S
V+V-FG

A B
(103)
L7

AE-200E AG-150A
ME

A B S A B S V+V-FG

OC, OS: Outdoor unit controller; IC: Indoor unit controller; ME: ME remote controller

MEES18K047 162
0000005024.BOOK 163 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

11-2. Transmission cable specifications


Transmission cables (Li) M-NET remote controller cables (ei) MA Remote controller cables (ai)
Shielding wire (2-core)
Type of cable Sheathed 2-core cable (unshielded) CVV
CVVS, CPEVS or MVVS

PUCY-P-Y(S)KD, EP-YSKD
Cable size More than 1.25 mm2 [AWG16] 0.3 1.25 mm2 [AWG22 16] 0.3 1.25 mm2 [AWG22 16]*1

When 10 m [32ft] is exceeded, use cables with


Remarks Max length: within 200 m Max length: 200 m [656ft]
the same specification as transmission cables.

*1 To wire PAR-CT01MA, PAR-3X MA-Series (X indicates 1, 2…), and Simple CVVS, MVVS: PVC insulated PVC sheathed shielded control cable
MA remote controller, use a wire with a diameter of 0.3 mm2 [AWG22] CPEVS: PE insulated PVC sheathed shielded communication cable
CVV: PVC insulated PVC sheathed control cable

MEES18K047 163
0000005024.BOOK 164 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

11-3. System configuration restrictions


11-3-1. Common restrictions for the CITY MULTI system
For each Outdoor/Heat source unit, the maximum connectable quantity of Indoor unit is specified at its Specifications table.
A) 1 Group of Indoor units can have 1-16 Indoor units;
*OA processing unit GUF-RD(H) is considered as Indoor unit.
PUCY-P-Y(S)KD, EP-YSKD

B) Maximum 2 remote controllers for 1 group;


*MA/ME remote controllers cannot be present together in 1group.
*When a PAR-CT01MA, PAR-40MA, or PAR-3X MA-Series (X indicates 1, 2…) is connected to a group, no other MA
remote controllers can be connected to the same group.
C) 1 Lossnay unit can interlock maximum 16 Indoor units; 1 Indoor unit can interlock only 1 Lossnay unit.
D) Maximum 3 System controllers are connectable when connecting to TB3 of the Outdoor/Heat source unit.
E) A maximum of 6 system controller are connectable to TB3 and TB7 of Outdoor/Heat source unit.
F) 4 System controllers or more are connectable when connecting to TB7 of the Outdoor/Heat source unit, if the
transmission power is supplied by the power supply unit PAC-SC51KUA.
*System controller connected as described in D) would have a risk that the failure of connected
Outdoor/Heat source unit would stop power supply to the System controller.

11-3-2. Ensuring proper communication power and the number of connected units for M-NET
In order to ensure proper communication among Outdoor/Heat source unit, Indoor unit, Lossnay, OA processing unit
GUF-RD(H), and Controllers, the transmission power situation for the M-NET should be observed. In some cases,
Transmission booster should be used. Taking the power consumption of Indoor unit as 1, the equivalent power consumption
or supply of others are listed at Table 1 and Table 2.
Both the transmission line for centralized controller and indoor-outdoor transmission line must meet the conditions listed
below. (Both conditions a) and b) must be met.)
a) [Total equivalent power consumption] ≤ [The equivalent power supply]
b) [Total equivalent number of units (Table 1)] ≤ [40]
Table 1 The equivalent power consumption and the equivalent number of units
Category Model The equivalent power consumption The equivalent number of units
Except for the models indicated by *2
CITY MULTI indoor unit
PEFY-AF2500, 3000, 4000, 5000, 6000MH
OA unit
GUF-50, 100 1 1
CITY MULTI connection kit
PAC-LV11M-J
Air handling unit controller
PAC-AH125, 140, 250, 500M-J
CITY MULTI indoor unit *2 PDFY-P100VM-E-RE 2 2
BC controller CMB 2 1
P100VM-E-BU 6 1
P200VM-E1-AU
5 1
P200VM-E2-AU
PWFY *1 (E)P100VM-E1-AU
(E)P100VM-E2-AU
1 1
P140VM-E1-AU
P140VM-E2-AU
P250, 300, 500, 600VM-E(-F) 1 1
PFAV
P750, 900VM-E(-F) 2 2
PFV, PEV P200, 250, 400, 500YM-A 1 1
PAR-CT01MA
PAR-21MA
PAR-31MA
PAR-32MA
PAR-33MA
PAR-40MA
MA remote controller/Lossnay 0 0
PAC-YT52CRA
PAR-FA32MA
LGH
PZ-60DR-E
PZ-61DR-E
PZ-43SMF-E
PAR-U02MEDA 0.5 1
ME remote controller
PZ-52SF 0.25 1
AE-200E
AE-50E
0 0
EW-50E
LM-AP
AG-150A
System controller EB-50GU-J 0.5 1
PAC-IF01AHC-J
AT-50B 1.5 5
PAC-YG60MCA
PAC-YG66DCA 0.25 1
PAC-YG63MCA
ON/OFF controller PAC-YT40ANRA 1 1
MN converter CMS-MNG-E 2 1
Outdoor/Heat source unit TB7 power consumption 0 0
System control interface MAC-333IF-E
0 0
A-M converter PAC-SF83MA-E
*1 PWFY cannot be connected to PUMY model.

MEES18K047 164
0000005024.BOOK 165 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

Table 2 The equivalent power supply


Category Model The equivalent power supply

Transmission Booster PAC-SF46EPA 25 *1

Power supply unit PAC-SC51KUA 5

PUCY-P-Y(S)KD, EP-YSKD
Expansion controller PAC-YG50ECA 6

BM ADAPTER BAC-HD150 6

AE-200E/AE-50E 0.75

System controller EW-50E 1.5

LM-AP 0
TB3 and TB7 total TB7 only TB3 only
32 *1-equivalent power
Outdoor unit except S-Series and TKA *2 32 *1 6 supplied to TB7
Outdoor/Heat source unit
S-Series outdoor unit 12 *1 0 12 *1

TKA outdoor unit 32 *1 - *3 32 *1

*1 When one or more indoor units listed below is connected, subtract 3 from the equivalent power supply.

Table 3
Category Model
Sized P200/P250
Indoor unit
PEFY-AF4000/5000/6000MH, PFFY-P400/500YM-E, PDFY-P100VM-E-RE
Air handling unit controller PAC-AH250/500M-J
PFAV PFAV-P500/600/750/900VM-E(-F)
PFV PFV-P400/500YM-A
PEV PEV-P400/500YM-A
*2 If PAC-SC51KUA is used to supply power at TB7 side, no power supply need from Outdoor/Heat source unit at TB7, Connector TB3 itself will therefore
have 32.
*3 Do not supply power to TB7 from TKA outdoor units.
Use PAC-SC51KUA or PAC-SF46EPA when connecting an M-NET device to TB7.

With the equivalent power consumption values and the equivalent number of units in Table 1 and Table 2, PAC-SF46EPA can
be designed into the air-conditioner system to ensure proper system communication according to (A), (B), (C).
(A) Firstly, count from TB3 at TB3 side the total equivalent number of units of Indoor units, OA processing units, ME remote
controller, and System controllers. If the total equivalent number of units reaches 40, a PAC-SF46EPA should be set.
(B) Secondly, count from TB7 side to TB3 side the total transmission power consumption. If the total equivalent power
supply reaches 32, a PAC-SF46EPA should be set. Yet, if a PAC-SC51KUA or another controller with a built-in power
supply, such as PAC-YG50ECA, is used to supply power at TB7 side, count from TB3 side only.
(C) Thirdly, count from TB7 at TB7 side the total transmission power consumption, If the total equivalent power supply for
only TB7 reaches 6, a PAC-SF46EPA should be set. Also, count from TB7 at TB7 side the total equivalent number of
units of System controllers, and so on. If the total equivalent number of units reaches 40, a PAC-SF46EPA should be set.
* The equivalent power supply of S-Series outdoor unit is 12.
* When one or more indoor units listed in Table 3 is connected, subtract 3 from the equivalent power supply.

System example

TB7 TB3 UP

TRANSMISSION BOOSTER
MODEL
PAC-SF46EPA

POWER RATING 220-240V:0.7A ~/N

50

WEIGHT 3.4kg

MADE IN JAPAN

01 02 Transmission
booster
(No.1)

ME remote ME remote
controller controller
TB7 TB3
N1 N2
Transmission booster (No.1) should be used, if the total equivalent number of Within N2, conditions 1,2 should be followed.
Outdoor/Heat source unit
units of Indoor units, OA processing units and ME remote controllers reaches 40, 1.The total equivalent number of units of Indoor units,
or if the total equivalent transmission power consumption reaches 32. OA processing units and ME remote controller should
not exceed 40.
UP
2.The total equivalent transmission power consumption
should not exceed 25.
TRANSMISSION BOOSTER
MODEL
PAC-SF46EPA

220-240V:0.7A ~/N
POWER RATING
50

WEIGHT 3.4kg

MADE IN JAPAN

Transmission
Lossnay booster Lossnay
unit PAC-SF46EPA unit
Centralized controller (No.2)
(AE-200E)

N3 N4
Transmission booster (No.2) should be used, Within N4, the total equivalent transmission
if the total equivalent transmission power consumption reaches 5. power consumption should not exceed 25.

MEES18K047 165
0000005024.BOOK 166 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

11-3-3. Ensuring proper power supply to System controller

The power to System controller (excluding AE-200E, AE-50E, EW-50E, BAC-HD150, LM-AP) is supplied via M-NET transmission line. M-NET
transmission line at TB7 side is called Centralized control transmission line while one at TB3 side is called Indoor-Outdoor/Heat source transmission
line. There are 3 ways to supply power to the System controller .
A) Connecting to TB3 of the Outdoor/Heat source unit and receiving power from the Outdoor/Heat source unit.
PUCY-P-Y(S)KD, EP-YSKD

B) Connecting to TB7 of the Outdoor/Heat source unit and receiving power from the Outdoor/Heat source unit.
(Not applicable to the PUMY model)
C) Connecting to TB7 of the Outdoor/Heat source unit but receiving power from power supply unit PAC-SC51KUA.
* System controllers (AE-200E, AE-50E, EW-50E, BAC-HD150, LM-AP) have a built-in function to supply power to the M-NET transmission
lines, so no power needs to be supplied to the M-NET transmission lines from the Outdoor/Heat source units or from PAC-SC51KUA.

11-3-3-A. When connecting to TB3 of the Outdoor/Heat source unit and receiving power from the
Outdoor/Heat source unit. Fig. 11-3-3-A M-NET transmission lines System
(Indoor-Outdoor/Heat source transmission lines) controller
Maximum 3 System controllers can be connected to TB3. Outdoor
/Heat source
unit Group Group
If there is more than 1 Outdoor/Heat source unit, it is TB7
TB3

necessary to replace power supply switch connector CN41 Replacement of


CN41 with CN40 Indoor unit

with CN40 on one Outdoor/Heat source unit. M-NET transmission lines


(transmission lines
for central controller) MA remote controller

Outdoor
/Heat source
unit Group Group
TB3
TB7
Use CN41
as it is. Indoor unit

ME remote controller

System
controller

11-3-3-B. When connecting to TB7 of the Outdoor/Heat source unit and receiving power from the Outdoor/Heat source unit.
(Not applicable to the PUMY model)
A maximum of 6 system controller are connectable to TB3 and TB7 of
Outdoor/Heat source unit. (Not applicable to the PUMY model) Fig. 11-3-3-B M-NET transmission lines
(Indoor-Outdoor/Heat source transmission lines)
It is necessary to replace power supply switch connector CN41 with Outdoor
/Heat source
unit Group Group
CN40 on one Outdoor/Heat source unit. TB7
TB3

Replacement of
CN41 with CN40 Indoor unit

M-NET transmission lines


(transmission lines
for central controller) MA remote controller

Outdoor
/Heat source
unit Group Group
TB3
TB7
Use CN41
as it is. Indoor unit

ME remote controller

System
controller

11-3-3-C. When connecting to TB7 of the Outdoor/Heat source unit but receiving power from PAC-SC51KUA.
When using PAC-SC51KUA to supply transmission power, the Fig. 11-3-3-C M-NET transmission lines
(Indoor-Outdoor/Heat source transmission lines)
power supply connector CN41 on the Outdoor/Heat source units Outdoor
/Heat source
unit Group Group
should be kept as it is. It is also a factory setting. TB3
TB7
1 PAC-SC51KUA supports maximum 1 AG-150A or Use CN41
as it is. Indoor unit
1 EB-50GU-J unit due to the limited power 24VDC at its TB3. M-NET transmission lines
However, 1 PAC-SC51KUA supplies transmission power at its (transmission lines
for central controller) MA remote controller

TB2 equal to 5 Indoor units, which is referable at Table 2. Outdoor


/Heat source
If System controller, ON/OFF controller connected to TB7 consume unit Group Group
TB3
transmission power more than 5 (Indoor units), Transmission TB7
Use CN41
booster PAC-SF46EPA is needed. PAC-SF46EPA supplies as it is. Indoor unit

transmission power equal to 25 Indoor units. PAC-SC51KUA


ME remote controller

CAUTION System
controller
■AG-150A/EB-50GU-J*1 are recommended to connect to TB7 because it performs back-up to a
number of data. Fig. 11-3-3-D
In an air conditioner system has more than 1 Outdoor/Heat source units, AG-150A/EB-50GU-J M-NET transmission lines
receiving transmission power at TB3 or TB7 on one of the Outdoor/Heat source units would have a Outdoor
(Indoor-Outdoor/Heat source transmission lines)
/Heat source
risk that the connected Outdoor/Heat source unit failure would stop power supply to unit Group Group
AG-150A/EB-50GU-J, and disrupt the whole system. TB7
TB3

When applying apportioned electric power function, AG-150A/EB-50GU-J are necessary to Use CN41
as it is. Indoor unit
connected to TB7 and has its own power supply unit PAC-SC51KUA.
Note: Power supply unit PAC-SC51KUA is for AG-150A/EB-50GU-J. M-NET transmission lines
(transmission lines
MA remote controller
*1: AG-150A is an example model of system controllers. for centralized controller)

Outdoor
/Heat source
■How to connect system controllers (AE-200E, AE-50E, EW-50E, BAC-HD150, LM-AP) to a given system unit Group Group

System controllers (AE-200E, AE-50E, EW-50E, BAC-HD150, LM-AP) have a built-in function to supply TB7
TB3

power to the M-NET transmission lines, so no power needs to be supplied to the M-NET transmission Use CN41
as it is. Indoor unit
lines from the Outdoor/Heat source units or from PAC-SC51KUA.
Leave the power supply connector on the Outdoor/Heat source unit connected to CN41 as it is.
ME remote controller
Refer to 11-3-2 for information about the power-supply capacity of each system controller System
controller
(EW-50E, BAC-HD150, LM-AP) to the low-level system controllers.

MEES18K047 166
0000005024.BOOK 167 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

11-3-4. Power supply to LM-AP


1-phase 220-240VAC power supply is needed.
The power supply unit PAC-SC51KUA is not necessary when connecting only the LM-AP. Yet, make sure to change
the power supply changeover connector CN41 to CN40 on the LM-AP.

11-3-5. Power supply to expansion controller

PUCY-P-Y(S)KD, EP-YSKD
1-phase 100-240VAC power supply is needed.
The power supply unit PAC-SC51KUA is not necessary.
The expansion controller supplies power through TB3, which equals 6 indoor units. (refer to Table 2)

11-3-6. Power supply to BM ADAPTER


1-phase 100-240VAC power supply is needed.
The power supply unit PAC-SC51KUA is not necessary when only BM ADAPTER is connected.
Yet, make sure to move the power jumper from CN41 to CN40 on the BM ADAPTER.

11-3-7. Power supply to AE-200E/AE-50E/EW-50E


1-phase 100-240VAC power supply is needed.
The power supply unit PAC-SC51KUA is not necessary when connecting only the AE-200E/AE-50E/EW-50E.

MEES18K047 167
0000005024.BOOK 168 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

11-4. Address setting


11-4-1. Switch operation

In order to constitute CITY MULTI in a complete system, switch Rotary switch


PUCY-P-Y(S)KD, EP-YSKD

operation for setting the unit address No. and connection No. is Branch
required. No. setting Unit address No. setting

Address No. of outdoor unit, indoor unit and remote controller. F 0 12 9


01
9
01

BC E

3456

2 3

2 3
D

7 8

7 8
The address No. is set at the address setting board.
789A 45 6 45 6
Caution for switch operations

Be sure to shut off power source before switch setting. If operated with power source on, switch can
not operate properly.
No units with identical unit address shall exist in one whole air conditioner system. If set erroneously,
the system can not operate.

MA remote controller

¥ When connecting only one remote controller to one group, it is always the main remote controller.
When connecting two remote controllers to one group, set one remote controller as the main remote controller
and the other as the sub remote controller.
¥ The factory setting is Main .

PAR-3X MA-Series (X indicates 1, 2…), PAR-CT01MA


The MA remote controller does not have the switches listed above.
Refer to the installation manual for the function setting.

PAC-YT52CRA
Setting the dip switches
There are switches on the back of the top case. Remote controller Main/Sub and other function settings are
performed using these switches. Ordinarily, only change the Main/Sub setting of SW1.
(The factory settings are ON for SW1, 2, and 3 and OFF for SW4.)

SW No. SW contents Main ON OFF Comment


Remote controller Set one of the two remote controllers at one
1 Main Sub
Main/Sub setting group to “ON”.
Temperature display When the temperature is displayed in
2 Celsius Fahrenheit
units setting [Fahrenheit], set to “OFF”.
Indoor temperature When you want to display the indoor
3 Yes No
display temperature, set to “ON”.

MEES18K047 168
0000005024.BOOK 169 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

11-4-2. Rule of setting address

Unit Address setting Example Note


Indoor unit

PUCY-P-Y(S)KD, EP-YSKD
System control interface
(MAC-333IF-E)
A-M converter 9 0 1 9 0 1
Use the most recent address within the same group of

7 8

7 8
2 3

2 3
(PAC-SF83MA-E) 01 ~ 50 4 5 6 4 5 6 indoor units.
Air handling unit controller
(PAC-AH125, 140, 250, 500M-J) 10 1
CITY MULTI connection Kit
(PAC-LV11M-J)
The smallest address of indoor unit in same refrigerant
system + 50
Assign sequential address numbers to the outdoor
9 0 1 9 0 1 units in one refrigerant circuit system. OC, OS1 and
51 ~ 99, 100

7 8

7 8
2 3

2 3
Outdoor unit 4 5 6 4 5 6 OS2 are automatically detected. (Note 2)
(Note1) Please reset one of them to an address between 51
10 1 and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
Local remote controller

01 01
9 9
The smallest address of indoor unit in the group + 100
ME remote controller 1
2 3

2 3
7 8

7 8

101 ~ 150 45 6 45 6
(Main) The place of "100" is fixed to "1"
Fixed
10 1

01 01 The address of main remote controller + 50


9 9
ME remote controller
1
2 3

2 3
7 8

7 8

(Sub) 151 ~ 199, 200 45 6 45 6


The address automatically becomes "200" if it is set
Fixed as "00"
10 1

01 01 01
9 9 9
The smallest group No. to be managed + 200
2 3

2 3

2 3

ON/OFF remote
7 8

7 8

7 8

201 ~ 250 45 6 45 6 45 6
controller The smallest group No. to be managed is changeable.
100 10 1

AE-200E/AE-50E
EW-50E
AG-150A 000, 201 ~ 250 0,2 0~5 0~9 AT-50B cannot be set to "000".
System controller

EB-50GU-J
100 10 1
AT-50B

PAC-YG50ECA 000, 201 ~ 250 0,2 0~5 0~9 Settings are made on the initial screen of AG-150A.
100 10 1

BAC-HD150 000, 201 ~ 250 0,2 0~5 0~9 Settings are made with setting tool of BM ADAPTER.

100 10 1

9 0 1 9 0 1
7 8

7 8
2 3

2 3

LMAP04-E 201 ~ 250 2 4 5 6 4 5 6

Fixed
10 1

9 01 9 01
78

78
23

23

PAC-YG60MCA 01 ~ 50 456 456

10 1
PI, AI, DIDO

9 01 9 01
78

78
23

23

PAC-YG63MCA 01 ~ 50 456 456

10 1

9 01 9 01
78

78
23

23

PAC-YG66DCA 01 ~ 50 456 456

10 1

9 01 9 01
Lossnay, OA After setting the addresses of all the indoor units,
78

78
23

23

01 ~ 50
processing unit assign an arbitrary address.
456 456

10 1

9 01 9 01

2
78

78
23

23

PAC-IF01AHC 201 ~ 250 456 456


Fixed
10 1

Note1: To set the address to "100", set it to "50"


Note2: Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending
order of their address.

MEES18K047 169
0000005024.BOOK 170 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

11-4-3. System examples

Factory setting
Original switch setting of the outdoors, indoors, controllers, LM-AP and BM ADAPTER at shipment is as follows.
PUCY-P-Y(S)KD, EP-YSKD

Outdoor unit : Address: 00, CN41: ON (Jumper), DipSW5-1: OFF


Indoor unit : Address: 00
ME remote controller : Address: 101
LM-AP : Address: 247, CN41: ON (Jumper), DipSW1-2: OFF
BM ADAPTER : Address: 000, CN41: ON (Jumper)
AE-200E/AE-50E/EW-50E : Address: 000, CN21: ON (Jumper)

Setting at the site


DipSW5-1(Outdoor) : When the System Controller is used, all the Dip SW5-1 at the outdoor units should be
set to "ON". * Dip SW5-1 remains OFF when only LM-AP is used.
DipSW1-2(LM-AP) : When the LM-AP is used together with System Controller, DipSW1-2 at the LM-AP should be
set to "ON".
CN40/CN41 : Change jumper from CN41 to CN 40 at outdoor control board will activate central transmission
power supply to TB7;
(Change jumper at only one outdoor unit when activating the transmission power supply
without using a power supply unit.)
Change jumper from CN41 to CN 40 at LM-AP/BM ADAPTER will activate transmission power
supply to LM-AP/BM ADAPTER itself;
Power supply unit is recommended to use for a system having more than 1 outdoor unit,
because the central transmission power supply from TB7 of one of outdoor units is risking that
the outdoor unit failure may let down the whole system controller system.
CN21(AE-200E/AE-50E/EW-50E) : Activates the power supply to M-NET transmission line from AE-200E/AE-50E/EW-50E
(CN21: ON (power supplied), OFF (power not supplied)

11-4-3-1. MA remote controller, Single-refrigerant-system, No System Controller


<Three outdoor units> <Two outdoor units> <One outdoor unit>

OC OS1 OS2 OC OS1 OC


00 00 00 00 00 00
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1


OFF OFF OFF OFF OFF OFF
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 3 Group 4

Indoor unit
00 00 00 00 00
TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15

SRU 1*
MA R/C MA R/C MA R/C MA R/C
(Main) (Sub)

1*
Wireless R/C

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. No address setting is needed.
3. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at 11-3. "System configuration restrictions".
4. When a PAR-CT01MA or PAR-3X MA-Series (X indicates 1, 2…) is connected to a group, no other MA remote controllers can be
connected to the same group.

MEES18K047 170
0000005024.BOOK 171 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

11-4-3-2. MA remote controller, Single-refrigerant-system, System Controller


<Three outdoor units> <Two outdoor units> <One outdoor unit>

OC OS1 OS2 OC OS1 OC

PUCY-P-Y(S)KD, EP-YSKD
51 52 53 51 52 51
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1


ON ON ON ON ON ON
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 3 Group 4

Indoor unit
01 02 03 04 05
TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15 TB5 TB15

201
SRU 1*
SC MA R/C MA R/C MA R/C MA R/C
(Main) (Sub)

1*
Wireless R/C

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*SC can be connected to TB3 side or TB7 side;
Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.
NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. Address should be set to Indoor units and centralized controller.
3. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at 11-3. "System configuration restrictions".
4. When a PAR-CT01MA or PAR-3X MA-Series (X indicates 1, 2…) is connected to a group, no other MA remote controllers can be
connected to the same group.

MEES18K047 171
0000005024.BOOK 172 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

11-4-3-3. MA remote controller, Multi-refrigerant-system, System Controller at TB7/TB3 side, Booster for long M-NET wiring

OC OS1 OS2 OC OS1 OC


PUCY-P-Y(S)KD, EP-YSKD

TB7 TB7 TB7 TB7 TB7 TB7


51 52 53 91 92 98
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1


ON ON ON ON ON ON
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 21

Indoor unit
01 02 03 30
TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15

TB2 Transmission Booster


PAC-SF46EPA
202 SRU *1
Power supply unit SC*3 MA R/C MA R/C MA R/C
(PAC-SC51KUA) *2 *4 (Main) (Sub)

000 or 201 *1
SC*3 Wireless R/C

Group 31 Group 32 Lossnay Group 33 Group 34 Group 35


Interlocked with
Indoor unit M-NET address 42 Lossnay
41 42 43 44 45 46
TB5 TB15 TB5 TB5 TB5 TB15 TB5 TB15 TB5 TM4

203 SRU *1 142


SC *3 ME R/C MA R/C MA R/C MA R/C Lossnay
(Main) (Sub) remote
controller
*1
Wireless R/C

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
For AG-150A, 24V DC should be used with the PAC-SC51KUA.
For AE-200E, AE-50E, and EW-50E the power supply unit PAC-SC51KUA is unused.
*3 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main"
controller and others as "sub".
AE-200E, AE-50E, EW-50E, BAC-HD150, and LM-AP are for exclusive use as a "main" system controller and cannot be used as a “sub”
system controller.
Make the setting to only one of the system controllers for "prohibition of operation from local remote controller".
*4 The power supply unit is not necessary for AE-200E, AE-50E, EW-50E, BAC-HD150, and LM-AP.
NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. Address should be set to Indoor units, Lossnay, and system controller.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for
transmission use. The power balance is needed to consider for long M-NET wiring.
Details refer to 11-3. "System configuration restrictions".
4. When a PAR-CT01MA or PAR-3X MA-Series (X indicates 1, 2…) is connected to a group, no other MA remote controllers can be connected
to the same group.

MEES18K047 172
0000005024.BOOK 173 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

11-4-3-4. ME remote controller, Single-refrigerant-system, No system controller


<Three outdoor units> <Two outdoor units> <One outdoor unit>

OC OS1 OS2 OC OS1 OC

PUCY-P-Y(S)KD, EP-YSKD
51 52 53 51 52 51
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1


OFF OFF OFF OFF OFF OFF
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 3 Group 4

Indoor unit
01 02 03 04 05
TB5 TB5 TB5 TB5 TB5

101 102 104 105 155


ME R/C ME R/C ME R/C ME R/C ME R/C

NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. Address should be set to Indoor units and ME remote controllers.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME RC consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to 11-3. "System configuration restrictions".

11-4-3-5. ME remote controller, Single-refrigerant-system, System controller, Lossnay


<Three outdoor units> <Two outdoor units> <One outdoor unit>

OC OS1 OS2 OC OS1 OC


51 52 53 51 52 51
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1


ON ON ON ON ON ON
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Lossnay


Group 3 Group 4 Group 5
Interlocked with
Indoor unit M-NET address 02 Lossnay
01 02 03 04 05 06
TB5 TB5 TB5 TB5 TB5 TB5 TM4

201 101 102 104 105 155


SC ME R/C ME R/C ME R/C ME R/C ME R/C Lossnay
remote
controller

*SC can be connected to TB3 side or TB7 side;


Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.
NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. Address should be set to Indoor units, Lossnay, centralized controller, and ME remote controllers.
3. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at 11-3. "System configuration restrictions".

MEES18K047 173
0000005024.BOOK 174 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

11-4-3-6. ME remote controller, Multi-refrigerant-system, System Controller at TB 7side, Lossnay, Booster for long M-NET wiring

OC OS1 OS2 OC OS1 OC


PUCY-P-Y(S)KD, EP-YSKD

TB7 TB7 TB7 TB7 TB7 TB7


51 52 53 91 92 97
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1


ON ON ON ON ON ON
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 21

Indoor unit
01 02 03 30
TB5 TB5 TB5 TB2 TB3 TB5

TB2 Transmission Booster


PAC-SF46EPA
202 101 102 130 180
Power supply unit SC *2 ME R/C ME R/C ME R/C ME R/C
(PAC-SC51KUA) *1 *3

000 or 201

SC*2

Group 31 Group 32 Group 33 Group 34 Group 35


Lossnay
Interlocked with
Indoor unit M-NET address 42 Lossnay
41 42 43 44 45 46
TB5 TB5 TB5 TB5 TB5 TB5 TM4

203 141 142 144 145 195


SC *2 ME R/C ME R/C ME R/C ME R/C ME R/C Lossnay
remote
controller

*1 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
For AG-150A, 24V DC should be used with the PAC-SC51KUA.
For AE-200E, AE-50E, and EW-50E the power supply unit PAC-SC51KUA is unused.
*2 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main"
controller and others as "sub".
AE-200E, AE-50E, EW-50E, BAC-HD150, and LM-AP are for exclusive use as a "main" system controller and cannot be used as a “sub”
system controller.
*3 The power supply unit is not necessary for AE-200E, AE-50E, EW-50E, BAC-HD150, and LM-AP.

NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to 11-3. "System configuration restrictions".

MEES18K047 174
0000005024.BOOK 175 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

11-4-3-7. ME remote controller, Multi-refrigerant-system, No Power supply unit

OC OS OC
TB7 TB7 TB7

PUCY-P-Y(S)KD, EP-YSKD
51 52 56
CN40 CN41 CN40 CN41 CN40 CN41

DipSW5-1 DipSW5-1 DipSW5-1


OFF OFF OFF
TB3 TB3 TB3

Group 1 Group 2

01 02 03 04 05

101 105
ME R/C ME R/C

Group 4 Group 3

10 09 08 07 06

110 107
ME R/C ME R/C
NOTE
It is necessary to change the connecter to CN40 on the outdoor unit control board (only one outdoor unit) when the group is set between other refrigerant systems.
It is necessary to set on the remote controller by manual when group sets on the different refrigerant system. Please refer to remote controller installation manual.

11-4-3-8. ME remote controller, Multi-refrigerant-system, System Controller at TB7 side, No Power sypply unit

OC OS OC
TB7 TB7 TB7
51 52 56
CN40 CN41 CN40 CN41 CN40 CN41

DipSW5-1 DipSW5-1 DipSW5-1


ON ON ON
TB3 TB3 TB3

Group 1 Group 2

01 02 03 04 05

201 101 105


SC ME R/C ME R/C

Group 4 Group 3

10 09 08 07 06

110 107
ME R/C ME R/C
NOTE
It is necessary to change the connecter to CN40 on the outdoor unit control board (only one outdoor unit) when the group is set between other refrigerant systems.
It is necessary to set on the remote controller by manual when group sets on the different refrigerant system. Please refer to remote controller installation manual.

MEES18K047 175
0000005024.BOOK 176 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

11-4-3-9. TG-2000A(*1)+AE-200E/AE-50E/EW-50E
AE-200E can control max. 50 indoor units;
TG-2000A can control max. 40 of AE-200E/AE-50E/EW-50E;*2
TG-2000A can control max. 2000 indoor units.
PUCY-P-Y(S)KD, EP-YSKD

AE-200E
000 OC
CN21 TB7
51
CN40 CN41

DipSW5-1
ON
TB3

Group 1 Group 2 Group 40

Indoor unit
01 02 03 42
HUB
TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15

Transmission Booster
SRU *3 PAC-SF46EPA

MA R/C MA R/C MA R/C


(Main) (Sub)
PC with
*3
TG-2000A
Wireless R/C
AE-50E/
LAN EW-50E

000 OC OS OC
TB7 TB7 TB7
51 52 91
CN40 CN41 CN40 CN41 CN40 CN41

DipSW5-1 DipSW5-1 DipSW5-1


ON ON ON
TB3 TB3 TB3

Group 1 Group 2 Group 21


Indoor unit
01 02 03 30
TB5 TB5 TB5 TB2 TB3 TB5

Transmission Booster
101 102 PAC-SF46EPA 130 180
ME R/C ME R/C ME R/C ME R/C

Group 31 Group 32 Group 33 Group 34 Group 35


Lossnay
Interlocked with
Indoor unit M-NET address 42 Lossnay
41 42 43 44 45 46
TB5 TB5 TB5 TB5 TB5 TB5 TM4

141 142 144 145 195 Lossnay


ME R/C ME R/C ME R/C ME R/C remote
ME R/C controller

*1 TG-2000A (Ver.6.5 or later) supports AE-200E/AE-50E (Ver.7.10 or later).


TG-2000A (Ver.6.60 or later) supports EW-50E.
*2 When AE-200E connected with AE-50E/EW-50E is connected, the number of AE-50E/EW-50E will be the maximum controllable number.
TG-2000A can control up to 40 AE-200E/AE-50E/EW-50E or AE-200E without AE-50E/EW-50E connection.
*3 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*4 When a PAR-CT01MA or PAR-3X MA-Series (X indicates 1, 2…) is connected to a group, no other MA remote controllers can be
connected to the same group.

MEES18K047 176
0000005024.BOOK 177 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

11-4-3-10. AE-200E + AE-50E/EW-50E


AE-200E can control max. 200 indoor units/via AE-50E/EW-50E.

PUCY-P-Y(S)KD, EP-YSKD
<Three outdoor units> <Two outdoor units> <One outdoor unit>
AE-200E
000
CN21
OC OS1 OS2 OC OS1 OC
TB7 TB7 TB7 TB7 TB7 TB7
51 52 53 51 52 51
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1


ON ON ON ON ON ON
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 40

Indoor unit
01 02 03 42
TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15

Transmission Booster
SRU *1 PAC-SF46EPA

MA R/C MA R/C MA R/C


(Main) (Sub)
*1
Wireless R/C
HUB
AE-50E/
EW-50E
000
CN21 OC OS1 OS2 OC OS1 OC
TB7 TB7 TB7 TB7 TB7 TB7
PC with 51 52 53 91 92 96
Browser CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1


ON ON ON ON ON ON
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 21


Indoor unit
AE-50E/
EW-50E 01 02 03 30
000 TB5 TB5 TB5 TB2 TB3 TB5
CN21
Transmission Booster
101 102 PAC-SF46EPA 130 180
ME R/C ME R/C ME R/C ME R/C
AE-50E/ Group 31 Group 32 Lossnay Group 33 Group 34
EW-50E Interlocked with
000 Indoor unit M-NET address 42
CN21 41 42 44 45
43
TB5 TB5 TB5 TB5 TB5

141 142 144 145 195


ME R/C ME R/C ME R/C ME R/C ME R/C

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*2 When a PAR-CT01MA or PAR-3X MA-Series (X indicates 1, 2…) is connected to a group, no other MA remote controllers can be
connected to the same group.

MEES18K047 177
0000005024.BOOK 178 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

11-4-3-11. LM-AP
LM-AP can transmit for max. 50 indoor units;
If system controller (SC) is used, DipSW1-2 at LM-AP and DipSW5-1 at Outdoor unit should set to "ON".
Change Jumper from CN41 to CN40 to activate power supply to LM-AP itself for those LM-AP connected without system
PUCY-P-Y(S)KD, EP-YSKD

controller (SC).
LM-AP can transmit for max.
LM-AP(01) 50 indoor units in single-refrigerant-system or multi-refrigerant-system.
identified by Neuron ID
<Three outdoor units> <Two outdoor units> <One outdoor unit>
247
CN40 CN41
OC OS1 OS2 OC OS1 OC
TB7 TB7 TB7 TB7 TB7 TB7
DipSW1-2
OFF 51 52 53 51 52 51
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1


OFF OFF OFF OFF OFF OFF
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 40


Indoor unit
01 02 03 42
TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15
AE-200E
Transmission Booster
000 PAC-SF46EPA
CN21 SRU *1
MA R/C MA R/C MA R/C
(Main) (Sub)

*1
Wireless R/C
LM-AP(02)
LONWORKS®

identified by Neuron ID

247
CN40 CN41 OC OS1 OS2 OC OS1 OC
TB7 TB7 TB7 TB7 TB7 TB7
DipSW1-2 51 52 53 91 92 97
ON CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1


ON ON ON ON ON ON
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 21


Indoor unit
01 02 03 30
TB5 TB5 TB5 TB2 TB3 TB5

Transmission Booster
101 102 PAC-SF46EPA 130 180
ME R/C ME R/C ME R/C ME R/C
Lossnay
Group 31 Group 32 Group 33 Group 34 Group 35
Interlocked with
Indoor unit M-NET address 42 Lossnay
41 42 43 44 45 46
PC TB5 TB5 TB5 TB5 TB5 TB5 TM4

LONWORKS® card
141 142 144 145 195
LONWORKS card®
ME R/C ME R/C ME R/C ME R/C ME R/C Lossnay
remote
controller
LONWORKS® card For other equipments (Lighting, security, elevator etc.)
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*2 When a PAR-CT01MA or PAR-3X MA-Series (X indicates 1, 2…) is connected to a group, no other MA remote controllers
can be connected to the same group.

MEES18K047 178
0000005024.BOOK 179 ページ 2018年11月12日 月曜日 午後6時54分

11. M-NET CONTROL Y-Series (Cooling-only)

11-4-3-12. BACnet®
EW-50E (AE-200E) can control up to 50 units/groups (including Lossnay).
*To use the BACnet® function on EW-50E (AE-200E), BACnet® license registration is required.
Change Jumper from CN41 to CN40 to activate power supply to BM ADAPTER itself for those BM ADAPTER connected

PUCY-P-Y(S)KD, EP-YSKD
without the power supply unit.
EW-50E(01)
<Three outdoor units> <Two outdoor units> <One outdoor unit>
000
HUB CN40 CN41
OC OS1 OS2 OC OS1 OC
LAN2 TB7 TB7 TB7 TB7 TB7 TB7
51 52 53 51 52 51
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1


ON ON ON ON ON ON
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 40


Indoor unit
01 02 03 42
TB5 TB15 TB5 TB15 TB5 TB15 TB2 TB3 TB5 TB15

Transmission Booster
SRU *1 PAC-SF46EPA

MA R/C MA R/C MA R/C


(Main) (Sub)

*1
Wireless R/C

EW-50E(02)
BACnet ®

000
CN40 CN41 OC OS1 OS2 OC OS1 OC
LAN2 TB7 TB7 TB7 TB7 TB7 TB7
51 52 53 91 92 96
CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41

DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1 DipSW5-1


ON ON ON ON ON ON
TB3 TB3 TB3 TB3 TB3 TB3

Group 1 Group 2 Group 21


Indoor unit
01 02 03 30
TB5 TB5 TB5 TB2 TB3 TB5

Transmission Booster
101 102 PAC-SF46EPA 130 180
ME R/C ME R/C ME R/C ME R/C

Group 31 Group 32 Lossnay Group 33 Group 34


Interlocked with
Indoor unit M-NET address 42
41 42 43 44 45
TB5 TB5 TB5 TB5 TB5

141 142 144 145 195


ME R/C ME R/C ME R/C ME R/C ME R/C
HUB
For other equipments (Lighting, security, elevator etc.)
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*2 When a PAR-CT01MA or PAR-3X MA-Series (X indicates 1, 2…) is connected to a group, no other MA remote controllers can be
connected to the same group.

MEES18K047 179
0000005024.BOOK 180 ページ 2018年11月12日 月曜日 午後6時54分

12. PIPING DESIGN Y-Series (Cooling-only)

12-1. R410A Piping material


12. PIPING DESIGN

Refrigerant pipe for CITY MULTI shall be made of phosphorus deoxidized copper, and has two types.
A. Type-O: Soft copper pipe (annealed copper pipe), can be easily bent with human's hand.
B. Type-1/2H pipe: Hard copper pipe (Straight pipe), being stronger than Type-O pipe of the same radical thickness.

The maximum operation pressure of R410A air conditioner is 4.30 MPa [623psi]. The refrigerant piping should ensure the safety
PUCY-P-Y(S)KD, EP-YSKD

under the maximum operation pressure. MITSUBISHI ELECTRIC recommends pipe size as Table1, or You shall follow the local
industrial standard. Pipes of radical thickness 0.7mm or less shall not be used.

Table 1. Copper pipe size and radial thickness for R410A CITY MULTI.
Size (mm) Size (inch) Radial thickness (mm) Radial thickness (mil) Pipe type
ø6.35 ø1/4" 0.8 [32] Type-O
ø9.52 ø3/8" 0.8 [32] Type-O
ø12.7 ø1/2" 0.8 [32] Type-O
ø15.88 ø5/8" 1.0 [40] Type-O
ø19.05 ø3/4" 1.2 [48] Type-O
ø19.05 ø3/4" 1.0 [40] Type-1/2H or H
ø22.2 ø7/8" 1.0 [40] Type-1/2H or H
ø25.4 ø1" 1.0 [40] Type-1/2H or H
ø28.58 ø1-1/8" 1.0 [40] Type-1/2H or H
ø31.75 ø1-1/4" 1.1 [44] Type-1/2H or H
ø34.93 ø1-3/8" 1.2 [48] Type-1/2H or H
ø41.28 ø1-5/8" 1.4 [56] Type-1/2H or H
* For pipe sized ø19.05 (3/4") for R410A air conditioner, choice of pipe type is up to you.
* The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes that meet the
local standards.

Flare

Due to the relative higher operation pressure of R410A compared to R22, the flare connection should follow dimensions
mentioned below so as to achieve enough the air-tightness.

Flare pipe Pipe size A (For R410A) (mm[in.]) Flare nut Pipe size B (For R410A) (mm[in.])
ø6.35 [1/4"] 9.1 ø6.35 [1/4"] 17.0
ø9.52 [3/8"] 13.2 ø9.52 [3/8"] 22.0
ø12.70 [1/2"] 16.6 ø12.70 [1/2"] 26.0
A

ø15.88 [5/8"] 19.7 ø15.88 [5/8"] 29.0


ø19.05 [3/4"] 24.0 B ø19.05 [3/4"] 36.0

MEES18K047 180
0000005024.BOOK 181 ページ 2018年11月12日 月曜日 午後6時54分

12. PIPING DESIGN Y-Series (Cooling-only)

Procedures for installing the branched pipes


Refer to the instructions that came with the branched pipe kit (separately sold) for details.
[1] Branches on the indoor-unit side

■Joint

PUCY-P-Y(S)KD, EP-YSKD
To outdoor/heat source unit To branch pipe or indoor unit

Vertical installation
Horizontal installation (The branched pipes must face up.)
Indoor-unit side (branched pipe)

±15° or less

±15° or less

Outdoor/heat source-unit side (main pipe)


Restrictions for installing the joint described here only apply to CMY-Y202S-G2 and CMY-Y302S-G2 in the gas line.
CMY-Y202S-G2 and CMY-Y302S-G2 in the gas line must be installed horizontally (see figure above) or with the
branched pipes facing up.
If the size of the refrigerant pipe that is selected by following the instructions under “Piping Design” section does not
match the size of the joint, use a reducer to connect them. A reducer is included in the kit.

■Header
Pipe cutter

or

To indoor unit
To outdoor/heat source unit Reducer
No restrictions apply to the installation of the header.
If the size of the refrigerant pipe that is selected by following the instructions under “Piping Design” section does not
match the size of the header, cut the pipe to an appropriate size using a pipe cutter, or use a reducer to connect them.
If the number of header branches exceeds the number of pipes to be connected, cap the unused header branches.
Caps are included in the kit.

[2] Branches on the outdoor/heat source-unit side

Note. Refer to the figure below for the installation position of the twinning pipe.
Twinning pipe
±15°

Slope of the twinning pipes are at an angle within ±15° to the horizontal plane.
Inclination of the branched pipes
The inclination of the branched pipes must be ±15° or less against the horizontal plane.
Excessive inclination of the branched pipes may damage the unit.

Minimum length of the straight section of the pipe before the branched pipes
Always use the pipes supplied in the branched pipe kit, and make sure the straight section of the pipe immediately
before it connects to the branched pipe is at least 500 mm (19-11/16 in.). Failure to do so may damage the unit.

MEES18K047 181
0000005024.BOOK 182 ページ 2018年11月12日 月曜日 午後6時54分

12. PIPING DESIGN Y-Series (Cooling-only)

12-2. Piping Design

Rule for piping size selection


OU
PUCY-P-Y(S)KD, EP-YSKD

Header
B
1st Joint
Capped
H' (OU under IU)
H (OU above IU)

D E a b c

Joint IU IU IU

d e f g

h1
IU IU IU IU

IU: Indoor unit , OU: Outdoor unit


1. Selecting joints
Select joints from Table 4-1 [Selection criteria for joints] based on the total capacity of indoor units on the downstream side.
When selecting the first joint for the system to which the outdoor unit listed in Table 4-2 [See the table below for the first joint of the
outdoor unit described below.] is connected, select the first joint from Table 4-2.

2. Selecting headers
Select headers from Table 5 [Header selection rule] based on the number of indoor units to be connected.
Refer to Table 5, which shows the total capacity limits, for the indoor units to be connected on the downstream side.
When connecting a header directly to the outdoor unit, select the header by referring to the notes in Table 5.
*The piping cannot be branched on the downstream of the header.

3. Selecting refrigerant pipe sizes


(1) Between outdoor unit and the 1st joint [A]
Select the appropriate size pipes for the selected outdoor unit from Table 1 [Piping "A" size selection rule].
(2) Between joints [B, C, D, and E]
Select the appropriate size pipes from Table 2 [Piping "B", "C", "D", … size selection rule] based on the total capacity of indoor units on
the downstream side.
(3) Between joints and indoor units [a, b, c, d, e, f, and g]
Select the appropriate size pipes from Table 3 [Piping "a", "b", "c", "d", … size selection rule] based on the capacity of indoor units.
(4) After selecting the pipe sizes in accordance with steps (1) through (3) above, if the size of the pipes on the downstream is larger than that
on the upstream, it is not necessary to be bigger than the upstream one.
(5) If any of the following applies to the selection made in Item 3-(1)-(4) above, reselect the pipe size.
(Not applicable to some models)
(a) If the length of the pipe to any indoor unit from the first joint exceeds 40 m [131 ft.], use one size larger liquid pipe after the joint that is
located before the point where the pipe length exceeds 40 m [131 ft.].
(b) Set indoor unit(s) which is vertically closer to the outdoor unit as “base unit(s)”.
Only the indoor units that have a height difference of more than 15 m [49 ft.] from base unit will be termed “Target units”.
Use one size larger liquid pipe from the target units to the joint prior to which 15 m [49 ft.] height difference has exceeded.
(Not applicable to the liquid pipes whose sizes were increased under item (5)-(a)).

(6) Calculate the amount of refrigerant to be added based on the pipe sizes selected in Items 1 through 3-(5) above, and make sure that the
total amount of the initial charge and the additional charge combined will not exceed the maximum allowable refrigerant charge amount.
If this amount exceeds the maximum allowable amount, redesign the system (i.e., piping length) so that the total refrigerant charge will not
exceed the maximum allowable amount.

MEES18K047 182
0000005024.BOOK 183 ページ 2018年11月12日 月曜日 午後6時54分

12. PIPING DESIGN Y-Series (Cooling-only)

12-2-1. PUCY-P200-500YKD Piping

OU

Note1. No joint after Header; Piping direct to Indoor Unit from Header;

PUCY-P-Y(S)KD, EP-YSKD
Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.

Header
B
1st joint
Capped
H' (OU under IU)
H (OU above IU)

L1

C
L2

D E a b c

Joint IU IU IU

d e f g

h1
IU IU IU IU

Fig. 12-2-1A Piping scheme IU: Indoor unit , OU: Outdoor unit

Piping length (m [ft.]) Bent equivalent length "M"


Item Piping in the figure Max. length Max. equivalent length Outdoor Model M (m/bent [ft./bent])
Total piping length A+B+C+D+E+a+b+c+d+e+f+g 1000 [3280'] - PUCY-P200YKD 0.42 [1.38]
Farthest IU from OU (L1) A+C+D+E+g / A+B+c 165 [541'] 190 [623'] PUCY-P250YKD 0.42 [1.38]
Farthest IU from first joint (L2) C+D+E+g / B+c 40 [131'] *2 40 [131'] PUCY-P300YKD 0.42 [1.38]
Height between OU and IU (OU above IU) H 50 [164'] *1 - PUCY-P350YKD 0.47 [1.54]
Height between OU and IU (OU under IU) H' 40 [131'] - PUCY-P400YKD 0.50 [1.64]
Height between IU and IU h1 15 [49'] *3 - PUCY-P450YKD 0.50 [1.64]
OU: Outdoor Unit, IU: Indoor Unit PUCY-P500YKD 0.50 [1.64]
*1 90m is available depending on the model and installation conditions. For more detailed information, contact your local distributor.
*2 90 m is available. When the piping length exceeds 40m, use one size larger liquid pipe starting with the section of piping where 40m is exceeded and all piping after that point.
In the figure above, if the piping labeled “E” exceeds 40 meters (but does not exceed 90 meters), increase the size of the liquid piping labeled E, f, and g by one size.
*3 30 m is available. If the height difference between indoor units exceeds 15 meters (but does not exceed 30 meters), use one-size larger pipes for indoor unit liquid pipes.
In the figure above, if “h1” exceeds 15 meters, increase the size of the liquid piping labeled C, D, E, d, e, f, and g by one size.

Table 1 Piping "A" size selection rule (mm [in.]) Table 4-1 Selection criteria for joints
Outdoor unit Pipe(Liquid) Pipe(Gas) Total down-stream Indoor capacity Joint
PUCY-P200YKD ø9.52 [3/8"] ø22.20 [7/8"] ~ P200 CMY-Y102SS-G2
PUCY-P250YKD ø9.52 [3/8"] *1 ø22.20 [7/8"] P201 ~ P400 CMY-Y102LS-G2
PUCY-P300YKD ø9.52 [3/8"] *2 ø22.20 [7/8"] P401 ~ P650 CMY-Y202S-G2
PUCY-P350YKD ø12.70 [1/2"] ø28.58 [1-1/8"] P651 ~ CMY-Y302S-G2
PUCY-P400YKD ø12.70 [1/2"] ø28.58 [1-1/8"] *Concerning detailed usage of joint parts, refer to its Installation Manual.
PUCY-P450YKD ø15.88 [5/8"] ø28.58 [1-1/8"] Table 4-2
PUCY-P500YKD ø15.88 [5/8"] ø28.58 [1-1/8"] See the table below for the first joint of
the outdoor unit described below.
*1. Farthest IU from OU (L1)>=90m [295ft.]; ø12.70 [1/2"]
Outdoor unit model Joint model
*2. Farthest IU from OU (L1)>=40m [131ft.]; ø12.70 [1/2"]
P450, P500 CMY-Y202S-G2

Table 2 Piping"B","C","D","E"size selection rule (mm [in.]) Table 5 Header selection rule
Total down-stream Indoor capacity Pipe(Liquid) Pipe(Gas) 4-branch Header 8-branch Header 10-branch Header
~ P140 ø9.52 [3/8"] ø15.88 [5/8"] CMY-Y104-G CMY-Y108-G CMY-Y1010-G
P141 ~ P200 ø9.52 [3/8"] ø19.05 [3/4"] Total down-stream Indoor capacity <=P200 <=P400 <=P650
P201 ~ P300 ø9.52 [3/8"] ø22.20 [7/8"] * CMY-Y104-G can directly connect PUCY-P200YKD, but can NOT directly connect PUCY-P250YKD, or above;
* CMY-Y108-G can directly connect PUCY-P200-(E)P450Y(S)KD, but can NOT directly connect
P301 ~ P400 ø12.70 [1/2"] ø28.58 [1-1/8"] PUCY-(E)P500Y(S)KD or above;
P401 ~ P650 ø15.88 [5/8"] ø28.58 [1-1/8"] * CMY-Y1010-G can directly connect PUCY-P200-(E)P650Y(S)KD;
P651 ~ P800 ø19.05 [3/4"] ø34.93 [1-3/8"] * CMY-Y104-G can NOT connect P200 indoor unit or above, but CMY-Y108, Y1010-G can do;
* Concerning detailed usage of Header parts, refer to its Installation Manual.
P801 ~ ø19.05 [3/4"] ø41.28 [1-5/8"]
Note3. Indoor capacity is described as its model size;
For example, PEFY-P32VMA-E, its capacity is P32;
Table 3 Piping "a","b","c","d","e","f","g" size selection rule (mm [in.]) Note4. Total down-stream Indoor capacity is the summary of the model size of Indoors downstream.
Indoor Unit size Pipe(Liquid) Pipe(Gas) For example, PEFY-P25VMA-E+PEFY-P32VMA-E: Total Indoor capacity=P25+P32=P57
P15,P20,P25,P32,P40,P50,GUF-50RD(H) ø6.35 [1/4"] ø12.70 [1/2"] Note5. Piping sized determined by the Total down-stream indoor capacity is NOT necessary
to be bigger than the up-stream one.
P63,P71,P80,P100,P125,P140,GUF-100RD(H) ø9.52 [3/8"] ø15.88 [5/8"] i.e. A>=B; A>=C>=D
P200 ø9.52 [3/8"] ø19.05 [3/4"]
P250 ø9.52 [3/8"] ø22.20 [7/8"]
P400 ø12.70 [1/2"] ø28.58 [1-1/8"]
P500 ø15.88 [5/8"] ø28.58 [1-1/8"]

MEES18K047 183
0000005024.BOOK 184 ページ 2018年11月12日 月曜日 午後6時54分

12. PIPING DESIGN Y-Series (Cooling-only)

12-2-2. PUCY-P550-1000YSKD, PUCY-EP400-700YSKD Piping


OU Note1. No joint after Header; Piping direct to Indoor Unit from Header;
OU Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.
PUCY-P-Y(S)KD, EP-YSKD

Trap (gas pipe only)

OK NG
h2
Downward To indoor unit Upward To indoor unit 2m To indoor unit 2 m max To indoor unit
T incline incline
S
Install the pipes from the outdoor unit to the branch If the length of pipe between the branch joint and outdoor
joint with a downward incline. unit exceeds 2 m, provide at rap at a distance 2 m or less
from the branch joint.
Header
A B Capped
H' (OU under IU)
H (OU above IU)

1st joint a b c
Outdoor Twinning Kit
CMY-Y100VBK3, 200VBK2 IU IU IU
C L1
L2

D E

h1
d e f g
Joint
IU IU IU

IU

Fig. 12-2-1B Piping scheme IU : Indoor unit , OU : Outdoor unit


Piping length (m [ft.]) Bent equivalent length "M"
Item Piping in the figure Max. length Max. equivalent length Outdoor Model M (m/bent [ft./bent])
Total piping length S+T+A+B+C+D+E+a+b+c+d+e+f+g 1000 [3280'] - PUCY-EP400YSKD 0.50 [1.64]
Distance between OU and OU S+T 10[32'] - PUCY-EP450YSKD 0.50 [1.64]
Height between OU and OU h2 0.1[0.3'] - PUCY-EP500YSKD 0.50 [1.64]
Farthest IU from OU (L1) S(T)+A+C+D+E+g / S(T)+A+B+c 165 [541'] 190 [623'] PUCY-P550YSKD 0.50 [1.64]
Farthest IU from the first joint (L2) C+D+E+g / B+c 40 [131'] *2 40 [131'] PUCY-P600YSKD 0.50 [1.64]
Height between OU and IU (OU above IU) H 50 [164'] *1 - PUCY-(E)P650YSKD 0.50 [1.64]
Height between OU and IU (OU under IU) H' 40 [131'] - PUCY-(E)P700YSKD 0.70 [2.29]
Height between IU and IU h1 15 [49'] *3 - PUCY-P750YSKD 0.70 [2.29]
OU: Outdoor Unit, IU: Indoor Unit PUCY-P800YSKD 0.70 [2.29]
*1 90m is available depending on the model and installation conditions. For more detailed information, contact your local distributor.
*2 90 m is available. When the piping length exceeds 40m, use one size larger liquid pipe starting with the section of piping PUCY-P850YSKD 0.80 [2.62]
where 40m is exceeded and all piping after that point. PUCY-P900YSKD 0.80 [2.62]
In the figure above, if the piping labeled “E” exceeds 40 meters (but does not exceed 90 meters), increase the size of the liquid
piping labeled E, f, and g by one size. PUCY-P950YSKD 0.80 [2.62]
*3 30 m is available. If the height difference between indoor units exceeds 15 meters (but does not exceed 30 meters), use one-size PUCY-P1000YSKD 0.80 [2.62]
larger pipes for indoor unit liquid pipes. In the figure above, if “h1” exceeds 15 meters, increase the size of the liquid piping labeled
C, D, E, and g by one size.

Table 1 Piping "A" size selection rule (mm [in.])


Outdoor unit Twinning kit Pipe(Liquid) Pipe(Gas) Table 4-1 Selection criteria for joints
PUCY-P550-650YSKD ø12.70 [1/2"] ø28.58 [1-1/8"] *1 Total down-stream Indoor capacity Joint
CMY-Y100VBK3 ø15.88 [5/8"] ø28.58 [1-1/8"] *2
PUCY-EP400-650YSKD ~ P200 CMY-Y102SS-G2
PUCY-P700-1000YSKD ø19.05 [3/4"] ø34.93 [1-3/8"] *3 P201 ~ P400 CMY-Y102LS-G2
CMY-Y200VBK2
PUCY-EP700YSKD ø19.05 [3/4"] ø41.28 [1-5/8"] *4 P401 ~ P650 CMY-Y202S-G2
CMY-Y100VBK3; *1 PUCY-EP400YSKD, *2 PUCY-EP450-(E)P650YSKD P651 ~ CMY-Y302S-G2
CMY-Y200VBK2; *3 PUCY-(E)P700-P800YSKD, *4 PUCY-P850-1000YSKD *Concerning detailed usage of joint parts, refer to its Installation Manual.
For Piping size "S","T", please refer to specification of the Twinning kit CMY-Y100VBK3, 200VBK2 at *The total capacity of the units in the downstream of the branch joint on at least one of the piping lines that
the Outdoor unit's external drawing. are connected to the branch joint should be 650 or below.
If the total capacity of the units in the downstream of the branch joints on both lines is 650 or above use
two branch joints (CMY-Y302S-G2).
Table 4-2
See the table below for the first joint of the outdoor
Table 2 Piping"B","C","D","E" size selection rule (mm [in.]) unit described below.
Total down-stream Indoor capacity Pipe(Liquid) Pipe(Gas) Outdoor unit model Joint model
~ P140 ø9.52 [3/8"] ø15.88 [5/8"] P550 to P650, EP450 to EP650 CMY-Y202S-G2
P141 ~ P200 ø9.52 [3/8"] ø19.05 [3/4"] P700 to P1000, EP700 CMY-Y302S-G2
P201 ~ P300 ø9.52 [3/8"] ø22.20 [7/8"]
P301 ~ P400 ø12.70 [1/2"] ø28.58 [1-1/8"] Table 5 Header selection rule
P401 ~ P650 ø15.88 [5/8"] ø28.58 [1-1/8"] 4-branch Header 8-branch Header 10-branch Header
P651 ~ P800 ø19.05 [3/4"] ø34.93 [1-3/8"] CMY-Y104-G CMY-Y108-G CMY-Y1010-G
P801 ~ ø19.05 [3/4"] ø41.28 [1-5/8"] Total down-stream Indoor capacity <=P200 <=P400 <=P650
* CMY-Y104-G can directly connect PUCY-P200YKD, but can NOT directly connect PUCY-P250YKD or above;
* CMY-Y108-G can directly connect PUCY-P200-(E)P450Y(S)KD, but can NOT directly connect
Table 3 Piping "a","b","c","d","e","f","g" size selection rule (mm [in.]) PUCY-(E)P500Y(S)KD or above;
Indoor Unit size Pipe(Liquid) Pipe(Gas) * CMY-Y1010-G can directly connect PUCY-P200-(E)P650Y(S)KD;
* CMY-Y104-G can NOT connect P200 indoor unit or above, but CMY-Y108, Y1010-G can do;
P15,P20,P25,P32,P40,P50,GUF-50RD(H) ø6.35 [1/4"] ø12.70 [1/2"] * Concerning detailed usage of Header parts, refer to its Installation Manual.
P63,P71,P80,P100,P125,P140,GUF-100RD(H) ø9.52 [3/8"] ø15.88 [5/8"] Note3. Indoor capacity is described as its model size;
P200 ø9.52 [3/8"] ø19.05 [3/4"] For example, PEFY-P32VMA-E, its capacity is P32;
Note4. Total down-stream Indoor capacity is the summary of the model size of Indoors downstream.
P250 ø9.52 [3/8"] ø22.20 [7/8"] For example, PEFY-P25VMA-E+PEFY-P32VMA-E: Total Indoor capacity=P25+P32=P57
P400 ø12.70 [1/2"] ø28.58 [1-1/8"] Note5. Piping sized determined by the Total down-stream indoor capacity is NOT necessary
to be bigger than the up-stream one.
P500 ø15.88 [5/8"] ø28.58 [1-1/8"] i.e. A>=B; A>=C>=D

MEES18K047 184
0000005024.BOOK 185 ページ 2018年11月12日 月曜日 午後6時54分

12. PIPING DESIGN Y-Series (Cooling-only)

12-2-3. PUCY-P1050-1500YSKD, PUCY-EP750-1100YSKD Piping


OU OU Note1. No joint after Header; Piping direct to Indoor Unit from Header;
OU Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.

PUCY-P-Y(S)KD, EP-YSKD
Trap (gas pipe only)

OK NG
h2 M N
Downward To indoor unit Upward To indoor unit 2m To indoor unit 2 m max To indoor unit
incline incline
T
S Install the pipes from the outdoor unit to the branch If the length of pipe between the branch joint and outdoor
joint with a downward incline. unit exceeds 2 m, provide at rap at a distance 2 m or less
from the branch joint.
Header
1st Outdoor Capped
A B
H' (OU under IU)
H (OU above IU)

CMY-Y300VBK3

2nd Outdoor 1st joint a b c


CMY-Y300VBK3
IU IU IU
C L1
L2

D E

h1
d e f g
Joint
IU IU IU

IU
Fig. 12-2-1C Piping scheme IU : Indoor unit , OU : Outdoor unit
Piping length (m [ft.]) Bent equivalent length "M"
Item Piping in the figure Max. length Max. equivalent length Outdoor Model M (m/bent [ft./bent])
Total piping length S+T+M+N+A+B+C+D+E+a+b+c+d+e+f+g 1000[3280'] (800[2624] *4) - PUCY-EP750YSKD 0.70 [2.29]
PUCY-EP800YSKD 0.70 [2.29]
Distance between OU and OU M+N+S+T 10[32'] -
PUCY-EP850YSKD 0.80 [2.62]
Height between OU and OU h2 0.1[0.3'] - PUCY-EP900YSKD 0.80 [2.62]
Farthest IU from OU (L1) M(N)+S+A+C+D+E+g / M(N)+S+A+B+c 165[541'] 190[623'] PUCY-EP950YSKD 0.80 [2.62]
Farthest IU from the first joint (L2) C+D+E+g / B+c 40[131'] *2 40[131'] PUCY-EP1000YSKD 0.80 [2.62]
Height between OU and IU (OU above IU) H 50[164'] *1 - PUCY-(E)P1050YSKD 0.80 [2.62]
Height between OU and IU (OU under IU) H' 40[131'] - PUCY-(E)P1100YSKD 0.80 [2.62]
PUCY-P1150YSKD 0.80 [2.62]
Height between IU and IU h1 15[49'] *3 -
PUCY-P1200YSKD 0.80 [2.62]
OU: Outdoor Unit, IU: Indoor Unit
PUCY-P1250YSKD 0.80 [2.62]
Note: The pipe length restrictions apply to the piping “A” as follows.
P1400: 110 m max. PUCY-P1300YSKD 0.80 [2.62]
P1450: 90 m max. PUCY-P1350YSKD 0.80 [2.62]
P1500: 60 m max. PUCY-P1400YSKD 0.80 [2.62]
*1 90m is available depending on the model and installation conditions. For more detailed information, contact your local distributor.
*2 90 m is available. When the piping length exceeds 40m, use one size larger liquid pipe starting with the section of piping where 40m is
PUCY-P1450YSKD 0.80 [2.62]
exceeded and all piping after that point. PUCY-P1500YSKD 0.80 [2.62]
In the figure above, if the piping labeled “E” exceeds 40 meters (but does not exceed 90 meters), increase the size of the liquid piping
labeled E, f, and g by one size.
*3 30 m is available. If the height difference between indoor units exceeds 15 meters (but does not exceed 30 meters), use one-size
larger pipes for indoor unit liquid pipes. In the figure above, if “h1” exceeds 15 meters, increase the
size of the liquid piping labeled C, D, E, and g by one size.
*4 The maximum total piping length in the system with the P1400 through P1500 model units is
800 meters.
Table 1 Piping "A" size selection rule (mm [in.]) Table 4-1 Selection criteria for joints
Outdoor unit Twinning kit Pipe(Liquid) Pipe(Gas) Total down-stream Indoor capacity Joint
PUCY-P1050-1500YSKD ø19.05 [3/4"] ø34.93 [1-3/8"] *1 ~ P200 CMY-Y102SS-G2
CMY-Y300VBK3 ø19.05 [3/4"] ø41.28 [1-5/8"] *2
PUCY-EP750-1100YSKD P201 ~ P400 CMY-Y102LS-G2
CMY-Y300VBK3; *1 PUCY-EP750-EP800YSKD, *2 PUCY-(E)P850-P1500YSKD P401 ~ P650 CMY-Y202S-G2
For Piping size "M", "N", "S", "T", please refer to specification of the Twinning kit CMY-Y300VBK3 at P651 ~ CMY-Y302S-G2
the Outdoor unit's external drawing.
*The total capacity of the units in the downstream of the branch joint on at least one of the piping lines that
are connected to the branch joint should be 650 or below.
If the total capacity of the units in the downstream of the branch joints on both lines is 650 or above use two
branch joints (CMY-Y302S-G2).
*Concerning detailed usage of joint parts, refer to its Installation Manual.
Table 2 Piping"B","C","D","E" size selection rule (mm [in.]) Table 4-2
Total down-stream Indoor capacity Pipe(Liquid) Pipe(Gas) See the table below for the first joint of the outdoor
unit described below.
~ P140 ø9.52 [3/8"] ø15.88 [5/8"]
Outdoor unit model Joint model
P141 ~ P200 ø9.52 [3/8"] ø19.05 [3/4"]
P201 ~ P300 ø9.52 [3/8"] ø22.20 [7/8"] P1050 to P1500, EP750 to EP1100 CMY-Y302S-G2
P301 ~ P400 ø12.70 [1/2"] ø28.58 [1-1/8"] Table 5 Header selection rule
P401 ~ P650 ø15.88 [5/8"] ø28.58 [1-1/8"] 4-branch Header 8-branch Header 10-branch Header
P651 ~ P800 ø19.05 [3/4"] ø34.93 [1-3/8"] CMY-Y104-G CMY-Y108-G CMY-Y1010-G
P801 ~ ø19.05 [3/4"] ø41.28 [1-5/8"] Total down-stream Indoor capacity <=P200 <=P400 <=P650
* CMY-Y104-G can directly connect PUCY-P200YKD, but can NOT directly connect PUCY-P250YKD or above;
Table 3 Piping "a","b","c","d","e","f","g" size selection rule (mm [in.]) * CMY-Y108-G can directly connect PUCY-P200-(E)P450Y(S)KD, but can NOT directly connect
PUCY-(E)P500Y(S)KD or above;
Indoor Unit size Pipe(Liquid) Pipe(Gas) * CMY-Y1010-G can directly connect PUCY-P200-(E)P650Y(S)KD;
P15,P20,P25,P32,P40,P50,GUF-50RD(H) ø6.35 [1/4"] ø12.70 [1/2"] * CMY-Y104-G can NOT connect P200 indoor unit or above, but CMY-Y108, Y1010-G can do;
* Concerning detailed usage of Header parts, refer to its Installation Manual.
P63,P71,P80,P100,P125,P140,GUF-100RD(H) ø9.52 [3/8"] ø15.88 [5/8"] Note3. Indoor capacity is described as its model size;
P200 ø9.52 [3/8"] ø19.05 [3/4"] For example, PEFY-P32VMA-E, its capacity is P32;
Note4. Total down-stream Indoor capacity is the summary of the model size of Indoors downstream.
P250 ø9.52 [3/8"] ø22.20 [7/8"] For example, PEFY-P25VMA-E+PEFY-P32VMA-E: Total Indoor capacity=P25+P32=P57
P400 ø12.70 [1/2"] ø28.58 [1-1/8"] Note5. Piping sized determined by the Total down-stream indoor capacity is NOT necessary
P500 ø15.88 [5/8"] ø28.58 [1-1/8"] to be bigger than the up-stream one.
i.e. A>=B; A>=C>=D

MEES18K047 185
0000005024.BOOK 186 ページ 2018年11月12日 月曜日 午後6時54分

12. PIPING DESIGN Y-Series (Cooling-only)

12-3. Refrigerant charging calculation


Sample connection(with 8 indoor units) (PUCY-P1050YSKD)
OU OU
OU Note1. No joint after Header; Piping direct to Indoor Unit from Header;
Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;
PUCY-P-Y(S)KD, EP-YSKD

Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.

Trap (gas
pipe only)
OK NG
A B 2m To indoor unit 2 m max To indoor unit
D Downward To indoor unit Upward To indoor unit
incline incline

C Install the pipes from the outdoor unit to the branch If the length of pipe between the branch joint and outdoor
joint with a downward incline. unit exceeds 2 m, provide at rap at a distance 2 m or less
from the branch joint.

Outdoor Twinning Kit


E F G I

a b c d
1st joint

IU IU IU IU
1 : P250 2 : P200 3 : P80 4 : P71

J K M

e f g i

IU IU IU IU
5 : P140 6 : P125 7 : P63 8 : P25

Amount of refrigerant to be charged


Refrigerant for extended pipes (field piping) is not factory-charged to the outdoor unit. Add an appropriate amount of refrigerant
for each pipe on site.
Record the size of each liquid pipe and the amount of refrigerant that was charged on the outdoor unit for future reference.

Calculating the amount of refrigerant to be charged


The amount of refrigerant to be charged is calculated with the size of the on-site-installed liquid pipes and their length.
Calculate the amount of refrigerant to be charged according to the formula below.
Round up the calculation result to the nearest 0.1 kg. (i.e., 16.03 kg = 16.1 kg)
* When connecting one or more PEFY-P20VMA3-E units, add 0.54 kg of refrigerant each of these units.
* When connecting LEV kit (PAC-LV11M-J), additional refrigerant charge may be required. Contact your local distributor for details.
* When connecting one or more PEFY-P25/32/40VMA3-E units, add 0.74 kg of refrigerant for each of these units.
* When connecting one or more PEFY-P50/63/71/80/100/125VMA3-E units, add 1.16 kg of refrigerant for each of these units.
* When connecting one or more PEFY-P50/63/71/80/100VMHS2-E units, add 2.70 kg of refrigerant for each of these units.

<Amount of refrigerant to be charged>


Calculating the amount of refrigerant to be charged
Total length of ø19.05 Total length of ø15.88 Total length of ø12.7 Total length of ø9.52 Total length of ø6.35 Additional charge Total capacity of Charged amount
liquid pipe x 0.29 liquid pipe x 0.2 liquid pipe x 0.12 liquid pipe x 0.06 liquid pipe x 0.024 connected indoor units
Outdoor unit model Charged amount
+ + + + + + ~80 2.0kg
P200 - 81~160 2.5kg
(m)x0.29(kg/m) (m)x0.2(kg/m) (m)x0.12(kg/m) (m)x0.06(kg/m) (m)x0.024(kg/m)
P250 - 161~330 3.0kg
P300 - 331~390 3.5kg
391~480 4.5kg
P350 -
Amount of factory- Sample calculation P400 -
481~630
631~710
5.0kg
6.0kg
charged refrigerant PUCY-P1050YSKD P450
P500
-
6.0kg
711~800 8.0kg
801~890 9.0kg
Indoor
Outdoor unit model Charged amount a : ø9.52 15m 891~1070 10.0kg
A : ø15.88 3m 1:P250
P200 model 1071~1250 12.0kg
5.5kg B : ø12.70 2m 2:P200 b : ø9.52 15m
P250 model C : ø19.05 2m 3:P80 c : ø9.52 5m 1251~ 14.0kg
P300 model 6.5kg D : ø12.70 1m 4:P71 d : ø9.52 5m
P350 model E : ø19.05 40m 5:P140 e : ø9.52 5m
F : ø15.88 10m 6:P125 f : ø9.52 5m
P400 model
11.5kg G : ø12.70 5m 7:P63 g : ø9.52 5m
P450 model I : ø9.52 5m 8:P25 i : ø6.35 5m
P500 model J : ø12.70 20m
11.8kg
K : ø9.52 5m
M : ø9.52 5m

Total length for ø19.05 C+E=42


each pipe size : ø15.88 A+F=3+10=13m
ø12.70 B+D+G+J=2+1+5+20=28m
ø9.52 I+K+M+a+b+c+d+e+f+g=5+5+5+15+15+5+5+5+5+5=70m
ø6.35 i=5m
This yields the following result : =42x0.29+13x0.2+28x0.12+70x0.06+5x0.024+0+10
=32.46kg
=32.5kg

MEES18K047 186
0000005024.BOOK 187 ページ 2018年11月12日 月曜日 午後6時54分

12. PIPING DESIGN Y-Series (Cooling-only)

■Maximum refrigerant charge


There is a limit to the amount of refrigerant that can be charged into a unit. Regardless of the amount yielded by the
formula above, observe the maximum refrigerant charge in the table below.

P200 P250 P300 P350 P400 P450 P500 P550 P600 P650 P700 P750 P800 P850
Total index of the outdoor units
YKD YKD YKD YKD YKD YKD YKD YSKD YSKD YSKD YSKD YSKD YSKD YSKD

PUCY-P-Y(S)KD, EP-YSKD
Factory charged kg 5.5 6.5 6.5 11.5 11.5 11.5 11.8 13.0 18.0 18.0 18.0 18.0 23.0 23.0
Maximum refrigerant charge Charged on site kg 17.9 25.5 29.4 33.8 36.5 47.8 56.3 51.2 56.5 59.6 72.0 75.1 78.6 82.7
Total for system kg 23.4 32.0 35.9 45.3 48.0 59.3 68.1 64.2 74.5 77.6 90.0 93.1 101.6 105.7

P900 P950 P1000 P1050 P1100 P1150 P1200 P1250 P1300 P1350 P1400 P1450 P1500
Total index of the outdoor units
YSKD YSKD YSKD YSKD YSKD YSKD YSKD YSKD YSKD YSKD YSKD YSKD YSKD
Factory charged kg 23.0 23.3 23.6 24.5 29.5 34.5 34.5 34.5 34.5 34.5 34.8 35.1 35.4
Maximum refrigerant charge Charged on site kg 84.9 92.5 101.9 91.4 93.2 94.5 94.5 94.5 94.5 94.5 94.2 93.9 93.6
Total for system kg 107.9 115.8 125.5 115.9 122.7 129.0 129.0 129.0 129.0 129.0 129.0 129.0 129.0

EP400 EP450 EP500 EP650 EP700 EP750 EP800 EP850 EP900 EP950 EP1000 EP1050 EP1100
Total index of the outdoor units
YSKD YSKD YSKD YSKD YSKD YSKD YSKD YSKD YSKD YSKD YSKD YSKD YSKD
Factory charged kg 11.0 12.0 13.0 18.0 23.0 22.5 23.5 24.5 24.5 24.5 29.5 34.5 34.5
Maximum refrigerant charge Charged on site kg 34.8 46.8 50.7 60.5 74.2 76.5 78.6 80.7 82.9 85.2 88.7 92.2 94.5
Total for system kg 45.8 58.8 63.7 78.5 97.2 99.0 102.1 105.2 107.4 109.7 118.2 126.7 129.0

MEES18K047 187
0000005024.BOOK 188 ページ 2018年11月12日 月曜日 午後6時54分

13. OUTDOOR INSTALLATION Y-Series (Cooling-only)

13-1. Requirement on installation site


13. OUTDOOR INSTALLATION

1. No direct thermal radiation to the unit.


2. No possibility of annoying the neighbors by the sound of the unit.
Valves and refrigerant flow on the outdoor unit may generate noise.
3. Avoid the sites where strong winds blow.
PUCY-P-Y(S)KD, EP-YSKD

4. With strength to bear the weight of the unit.


5. Drain flow from the unit is cared at heating mode.
6. Enough space for installation and service as shown at 13-2.
7. Avoid the sites where acidic solutions or chemical sprays (sulfuric compounds) are used frequently.
8. The unit should be secure from combustible gas, oil, steam, chemical gas like acidic solution, sulfur gas and so on.

MEES18K047 188
0000005024.BOOK 189 ページ 2018年11月12日 月曜日 午後6時54分

13. OUTDOOR INSTALLATION Y-Series (Cooling-only)

13-2. Spacing
In case of single installation
• Secure enough space around the unit as shown in the figure.
• If the wall height exceeds the height limit, widen the space labeled "L" and "W" by the amount that exceeds the limit (labeled <h> in the figure).
• Clearance shown in this section are proper airflow, installation, and service. Additional spacing maybe required depending on load code.

PUCY-P-Y(S)KD, EP-YSKD
(1) Walls are lower than the height limit.

Should be shorter than

500 [19-11/16]
the unit height

W
Should be shorter than
the unit height

W L

450 [17-23/32]
Condition L W
Minimum space behind the unit 100 [3-15/16] 50 [1-31/32]
Minimum space on both sides of the unit 300 [11-13/16] 15 [19/32]

(2) If the wall height (H) of the front, rear or side exceeds the wall height restriction

h h
h
h
Should be shorter than

Should be shorter than

h 500 [19-11/16] h Should be shorter than


500 500 [19-11/16]
the unit height

W
the unit height

W
the unit height
[19-11/16] W
Should be shorter than

Should be shorter than

Should be shorter than

L
the unit height

the unit height

the unit height

W L W W L

450 [17-23/32] + h 450 [17-23/32] + h 450 [17-23/32] + h

Condition L W
Minimum space behind the unit 100 [3-15/16] + h 50 [1-31/32] + h
Minimum space on both sides of the unit 300 [11-13/16] + h 15 [19/32] + h

(3) If there are obstacles at the upper part of the unit

240 [9-15/32] 1000 [39-3/8]


45°
Air deflector grills
(field supplied)

50 [1-31/32]

(Unit : mm [in.])

MEES18K047 189
0000005024.BOOK 190 ページ 2018年11月12日 月曜日 午後6時54分

13. OUTDOOR INSTALLATION Y-Series (Cooling-only)

In case of collective installation and continuous installation

• When multiple units are installed adjacent to each other, secure enough space to allow for air circulation and
passageways between groups of units as shown in the figures.
* Leave both sides of each group of units open.
PUCY-P-Y(S)KD, EP-YSKD

• As with single installation, if the wall height exceeds the height limit, widen the space in the front and
the back of a given group of units by the amount that exceeds the limit (labeled <h> in the figure).
• If there is a wall at both the front and the rear of the unit, install up to six units (three units: P500) consecutively
in the side direction and provide a space of 1000mm or more as inlet space/passage space for each six units (three units: P500).

(1) Side-by-side installation


<The space on both sides of a given group of units is minimum.> <The space on both sides of a given group of units is minimum.>

* *

30 [1-3/16] h 100
[3-15/16] h
500 [19-11/16]
500 [19-11/16]
h h
300 [11-13/16] + h
Unit height 100 [3-15/16] + h
* Unit height *
450 [17-23/32] + h 450 [17-23/32] + h

(2) Face-to-face installation


<There are walls in the front and the back of a given group of units.> <There is a wall on one side.>

* h
500 [19-11/16]
h
100 [3-15/16] + h
Unit height 450 [17-23/32]
h 450 [17-23/32]
*
450 [17-23/32]
Unit height 450 [17-23/32]
15 [19/32] + h
450 [17-23/32] + h

(3) Combination of face-to-face and side-by-side installations


<There are walls in the front and the back of a given group of units.> <There is a wall on one side and either the front or the back of a given group of unit.>

h
Unit height

h h
500 500
[19-11/16] [19-11/16]
1000
300 [39-3/8] + h 300
[11-13/16] + h [11-13/16] + h
*
900 [35-7/16]
900 [35-7/16]
h * *
500 300 [11-13/16] + h
[19-11/16]

(Unit : mm [in.])

MEES18K047 190
0000005024.BOOK 191 ページ 2018年11月12日 月曜日 午後6時54分

13. OUTDOOR INSTALLATION Y-Series (Cooling-only)

13-3. Piping direction

13-3-1. Lifting method


· When lifting the unit with ropes, run the ropes under the unit and use the lifting hole.

PUCY-P-Y(S)KD, EP-YSKD
· Support the unit at four points with two ropes, and avoid giving mechanical shock.
· Suspension rope angle must be 40° or less, so as to avoid compressing fan guard.
· Use two ropes, each at least 8m [26 ft.] in length
· Use ropes strong enough to support the weight of the unit.
· Always suspend the unit from four corners. (It is dangerous to suspend a unit from two corners and must not be attempt-
ed.)
· Use protective pads to keep the ropes from scratching the panels on the unit.
· Use a 50mm [1-31/32 in.] or thicker cardboard or cloth as a protective pad on the top of the unit to prevent contact
between the fan guard and slings.
1 P200-P300 2 P350-P450
40°
Slings Slings 40°
(Min. 8m [26 ft.] x 2) (Min. 8m [26 ft.] x 2)
Fan guard Fan guard
50mm [1-31/32 in.] or
50mm [1-31/32 in.] or thicker protective pads
thicker protective pads
(two each in the front (two each in the front
and back) and back)

Protective pads
Protective pads
(two each in the
(two each in the front and back)
front and back)

Sling holes
(two each in the front and back) Sling holes
(two each in the front and back)

3 P500 40°
Slings
(Min. 8m [26 ft.] x 2)
Fan guard

50mm [1-31/32 in.] or


thicker protective pads
(two each in the front
and back)

Protective pads
(two each in the
front and back)

Sling holes
(two each in the front and back)
CAUTION
Exercise caution when transporting products.

· Products weighing more than 20 kg [45 LBS] should not be carried alone.
· Do not carry the product by the PP bands.
· To avoid the risk of injury, do not touch the heat exchanger fins.
· Plastic bags may pose a risk of choking hazard to children. Tear plastic bags into pieces before disposing of them.
· When lifting and transporting outdoor units with ropes, run the ropes through lifting hole at the unit base. Securely
fix the unit so that the ropes will not slide off, and always lift the unit at four points to prevent the unit from falling.

MEES18K047 191
0000005024.BOOK 192 ページ 2018年11月12日 月曜日 午後6時54分

13. OUTDOOR INSTALLATION Y-Series (Cooling-only)

13-3-2. Installation
· Secure the unit with anchor bolts as shown in the figure below so that the unit will not topple over with strong wind or
during an earthquake.
· Install the unit on a durable base made of such materials as concrete or angle steel.
· Take appropriate anti-vibration measures (e.g., vibration damper pad, vibration isolation base) to keep vibrations and
PUCY-P-Y(S)KD, EP-YSKD

noise from being transmitted from the unit through walls and floors.
When installing a unit on a base, place an anti-vibration pad between the base and the unit.
· When using a rubber cushion, install it so that the cushion covers the entire width of the unit leg.
· Install the unit in such a way that the corner of the angle bracket at the base of the unit shown in the figure below is
securely supported.
· Install the anchor bolt in such a way that the top end of the anchor bolt do not stick out more than 30 mm [1-3/16 in.].
· This unit is not designed to be anchored with post-installation-type anchor bolts, although by adding fixing brackets
anchoring with such type of anchor bolts becomes possible.
A : M10 anchor bolt procured at the site.

B : Corner is not seated.


C : Fixing bracket for hole-in anchor bolt
(3 locations to fix with screws).
D : Anti-vibration rubber
Install it so that the rubber covers the entire width of the unit leg.

WARNING
Properly install the unit on a surface that can withstand the weight of
the unit. Unit installed on an unstable surface may fall and cause injury.

WARNING
Take appropriate safety measures against strong winds and earth-
quakes to prevent the unit from falling.
30mm max.

Install the unit in such a


way that the corner of
D the angle bracket at the B
base of the unit shown
in the figure is securely
A supported. The brackets
may bend if they are not
securely supported. C

Take into consideration the durability of the base, water drainage route (Drain water is discharged from outdoor units
during operation.), piping route, and wiring route when performing foundation work.
13-3-3. Anchor bolt positions
<P200-P450>
• Individual installation • Collective installation (Unit : mm [in.])
681±3 [(26-23/32~26-15/16)]

681±3 [(26-23/32~26-15/16)]

PUCY P200-P300
A 760±2 [29-15/16(29-27/32~30)]

PUCY P350-P450
A 1060±2 [41-3/4(41-21/32~41-13/16)]

30 [1-3/16] 30 [1-3/16]
A A 190 [7-1/2] A 190 [7-1/2] A
(For maintenance)
Leave a minimum of 30 mm [1-3/16 in.] between units.

<P500>
681±3 [(26-23/32~26-15/16)]

681±3 [(26-23/32~26-15/16)]

PUCY P500
A 795±2 [31-5/16(31-1/4~31-13/32)]
30 [1-3/16] 30 [1-3/16]
A A A A 190 [7-1/2] A A 190 [7-1/2] A A
(For maintenance) (For maintenance)
Leave a minimum of 30 mm [1-3/16 in.] between units.

MEES18K047 192
0000005024.BOOK 193 ページ 2018年11月12日 月曜日 午後6時54分

13. OUTDOOR INSTALLATION Y-Series (Cooling-only)

13-3-4. Installation
When the pipes and/or cables are routed at the bottom of the unit, make sure that the through hole at the base of
the unit does not get blocked with the installation base.
When the pipes are routed at the bottom of the unit, the base should be at least 100 mm in height.

PUCY-P-Y(S)KD, EP-YSKD
· P200-P300 · P350-P450
(Unit : mm) (Unit : mm)
2X2-14X20 Oval hole
222 150 272 150 2X2-14X20 Oval hole
251 83

29.5
301 83
137
84

29.5
177

145
227

84
121
147
196

121
144
196
(Mounting pitch)

(Mounting pitch)
94

94
(740)
681

(740)
681
Refrigerant service
Refrigerant service Refrigerant service valve <gas>
valve <gas> Refrigerant service
valve <liquid>
valve <liquid>
80 1060 80

29.5
80 760 80
29.5

(Mounting pitch) (Mounting pitch)

Bottom view Bottom view

· P500 (Unit : mm)


2X3-14X20 Oval hole
561 150
590 83
29.5
145

516
84
121
144
196

(Mounting pitch)
94

(740)
681

Refrigerant service Refrigerant service


valve <liquid> valve <gas>

80 795 795 80
29.5

(Mounting pitch) (Mounting pitch)


Bottom view

Installation base parallel to the unit’s front panel

13-3-5. Refrigerant pipe routing


The gaps around the edges of through holes for pipes and wires on the
unit allow water or mice to enter the unit and damage its parts. Close
these gaps with filler plates.

This unit allows two types of pipe routing:


• Bottom piping
• Front piping

CAUTION
To prevent small animals, water, and snow from
entering the unit and damage its parts, close the
gap around the edges of through holes for pipes
and wires with filler plates.
Filler plate Fill the gap at the site
(not supplied)

MEES18K047 193
0000005024.BOOK 194 ページ 2018年11月12日 月曜日 午後6時54分

13. OUTDOOR INSTALLATION Y-Series (Cooling-only)

13-3-6. Twinning on the outdoor unit side


The tilt angle of the twinning pipe
The tilt angle of the twinning pipe must be within ±15° with the horizontal plane.
Tilting the twinning pipe more than specified will cause damage to the unit.
PUCY-P-Y(S)KD, EP-YSKD

The length of the straight part of the pipe before the branching
For the twinning kit, always use the accessory piping parts. Note: See the following drawing for the fitting
The length of the straight part of pipe connected in front of the position of the twinning pipe.
Twinning pipe
twinning pipe must be 500 mm [19-11/16 in.] or longer.
(Connect the field piping so that the length of the straight part

±15°
of pipe connected in front of the twinning pipe can be 500 mm
[19-11/16 in.] or longer.)
The tilt angle of the twinning pipe should
If the length is less than 500 mm [19-11/16 in.], it will cause damage
be within ±15°with the horizontal plane.
to the unit.

Precautions for outdoor unit combinations


<A> Install the piping so that oil will not accumulate in the stopped outdoor unit.

unit 1 unit 2 unit 3 unit 1 unit 2 unit 3

1.

To Indoor unit
To Indoor unit Downward slope
Twinning pipe Upward slope
Twinning pipe Twinning pipe Twinning pipe

The NG example shows that oil accumulates because the units are installed on a reverse gradient while unit 1 is in operation, and unit 3 is stopped.

unit 1 unit 2 unit 3

2. unit 1 unit 2 unit 3 unit 1 unit 2 unit 3

h1
h1

h1 = 0.2 m (7-7/8 in) max h1 > 0.2 m (7-7/8 in)


The NG example shows that oil accumulates into units 1 and 2 while unit 3 is in operation, and units 1 and 2 are stopped.
Vertical pipe height (h) should be 0.2 m (7-7/8 in) or below.

unit 2 unit 3 unit 2 unit 3

3. unit 1 unit 1

h2 h2
h2 = 0.1 m (3-15/16 in) max h2 > 0.1 m (3-15/16 in)

The NG example shows that oil accumulates into unit 1 while unit 3 is in operation, and unit 1 is stopped. Vertical pipe height (h) should be 0.2 m (7-7/8 in) or below.

unit 1 unit 2 unit 1 unit 2

unit 3 unit 3
4.
h2
h2
h2 = 0.1 m (3-15/16 in) max h2 > 0.1 m (3-15/16 in)

The NG example shows that oil accumulates into unit 3 while unit 1 is in operation, and unit 3 is stopped. Vertical pipe height (h) should be 0.2 m (7-7/8 in) or below.

<B> When the piping on the outdoor unit side (from the twinning pipe) exceeds 2 m [6 ft], ensure a trap (gas pipe only) within 2 m [6 ft].
Make sure the height of the trap is 200 mm [7-7/8 in] or more.
If there is no trap, oil can accumulate inside the pipe, causing a shortage of oil and may damage the compressor.

<2 m [6 ft.] or less> <More than 2 m [6 ft.]>


Trap
(gas pipe only)

200 mm [7-7/8 in.]


To Indoor unit or over To Indoor unit
2m [6 ft.]
Less than 2 m [6 ft.]

Caution:
• Do not install traps other than the ones between outdoor units described on a separate sheet to prevent oil backflow and compressor start-up failure.
• Do not install solenoid valves to prevent oil backflow and compressor start-up failure.
• Do not install a sight glass because it may show improper refrigerant flow.
If a sight glass is installed, inexperienced technicians that use the glass may overcharge the refrigerant.

MEES18K047 194
0000005024.BOOK 195 ページ 2018年11月12日 月曜日 午後6時54分

13. OUTDOOR INSTALLATION Y-Series (Cooling-only)

<PUCY-P550YSKD>

Outdoor unit1 Outdoor unit 2

PUCY-P-Y(S)KD, EP-YSKD
Twinning pipe 1
To indoor unit
200mm [7-7/8 in.]
or less

<PUCY-P1050YSKD>

Outdoor unit 1 Outdoor unit 2 Outdoor unit 3

Twinning pipe 1 Twinning pipe 2


To Indoor unit
200mm [7-7/8 in.]
or less

MEES18K047 195
0000005024.BOOK 196 ページ 2018年11月12日 月曜日 午後6時54分

13. OUTDOOR INSTALLATION Y-Series (Cooling-only)

13-3-7. Twinning on the outdoor unit side


See the following drawing for connecting the pipes between the outdoor units.
<In case of 2units combination>
PUCY-P-Y(S)KD, EP-YSKD

Field piping

Twinning kit

Field piping

The le
n
must gth of the
be 50 s
0 mm traight pip
[19-1 e
1/16
in.] o
r long
er

<In case of 3units combination>

Field piping

Twinning kit

Field piping
Twinning kit

Field piping
The le
ngth
must of the
be 50 s
0 mm traight pip
[19-1 e
1/16 in
.] or lo
nger The le
ngth
must of the
be 50 s
0 mm traight pip
[19-1 e
1/16 in
.] or lo
nger

CAUTION
The length of the straight pipe must be 500mm[19-11/16 in.] or longer.
If not, it may cause improper operation.

MEES18K047 196
0000004605.BOOK 1 ページ 2018年1月18日 木曜日 午前8時42分

INSTALLATION INFORMATION

I.INSTALLATION INFORMATION

1. Installation information ..................................................................................................................................... 2


1-1. General precautions................................................................................................................................ 2
1-2. Precautions for Indoor unit and BC controller ......................................................................................... 3
1-3. Precautions for Fresh air intake type indoor unit .................................................................................... 4
1-4. Precautions for Outdoor unit/Heat source unit........................................................................................ 4
1-5. Precautions for Control-related items ..................................................................................................... 5

MEES17K141 a-4 1
0000004605.BOOK 2 ページ 2018年1月18日 木曜日 午前8時42分

1. Installation information
I.INSTALLATION
1. Installation information
INFORMATION

* Refer to the enclosed Installation Manual for details on installation. Arrange to have an expert install the system correctly.

1-1. General precautions


1-1-1. Usage
The air-conditioning system described in this Data Book is designed for human comfort.
INSTALLATION INFORMATION

This product is not designed for preservation of food, animals, plants, precision equipment, or art objects. To prevent
quality loss, do not use the product for purposes other than what it is designed for.
To reduce the risk of water leakage and electric shock, do not use the product for air-conditioning vehicles or vessels.

1-1-2. Installation environment


Do not install any unit other than the dedicated unit in a place where the voltage changes a lot, large amounts of mineral
oil (e.g., cutting oil) are present, cooking oil may splash, or a large quantity of steam can be generated such as a kitchen.
Do not install the unit in acidic or alkaline environment.
Installation should not be performed in the locations exposed to chlorine or other corrosive gases. Avoid near a sewer.
To reduce the risk of fire, do not install the unit in a place where flammable gas may be leaked or inflammable material
is present.
This air conditioning unit has a built-in microcomputer. Take the noise effects into consideration when deciding the
installation position. Especially in a place where antenna or electronic device are installed, it is recommended that the
air conditioning unit be installed away from them.
Install the unit on a solid foundation according to the local safety measures against typhoons, wind gusts, and earth-
quakes to prevent the unit from being damaged, toppling over, and falling.

1-1-3. Backup system


In a place where air conditioner's malfunctions may exert crucial influence, it is recommended to have two or more
systems of single outdoor/heat source units with multiple indoor units.

1-1-4. Unit characteristics


Heat pump efficiency of outdoor unit depends on outdoor temperature. In the heating mode, performance drops as the
outside air temperature drops. In cold climates, performance can be poor. Warm air would continue to be trapped near
the ceiling and the floor level would continue to stay cold. In this case, heat pumps require a supplemental heating
system or air circulator. Before purchasing them, consult your local distributor for selecting the unit and system.
When the outdoor temperature is low and the humidity is high, the heat exchanger on the outdoor unit side tends to
collect frost, which reduces its heating performance. To remove the frost, Auto-defrost function will be activated and the
heating mode will temporarily stop for 3-10 minutes. Heating mode will automatically resume upon completion of defrost
process.
Air conditioner with a heat pump requires time to warm up the whole room after the heating operation begins, because
the system circulates warm air in order to warm up the whole room.
The sound levels were obtained in an anechoic room. The sound levels during actual operation are usually higher than
the simulated values due to ambient noise and echoes. Refer to the section on "SOUND LEVELS" for the measurement
location.
Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes even when operating normally. Please consider to avoid location where quietness is required.
For BC/HBC controller, it is recommended to unit to be installed in places such as ceilings of corridor, restrooms and
plant rooms.
The total capacity of the connected indoor units can be greater than the capacity of the outdoor/heat source unit.
However, when the connected indoor units operate simultaneously, each unit's capacity may become smaller than the
rated capacity.
When the unit is started up for the first time within 12 hours after power on or after power failure, it performs initial startup
operation (capacity control operation) to prevent damage to the compressor. The initial startup operation requires 90
minutes maximum to complete, depending on the operation load.

1-1-5. Relevant equipment


Use an earth leakage breaker (ELB) with medium sensitivity, and an activation speed of 0.1 second or less.
Consult your local distributor or a qualified technician when installing an earth leakage breaker.
If the unit is inverter type, select an earth leakage breaker for handling high harmonic waves and surges.
Leakage current is generated not only through the air conditioning unit but also through the power wires. Therefore, the
leakage current of the main power supply is greater than the total leakage current of each unit. Take into consideration
the capacity of the earth leakage breaker or leakage alarm when installing one at the main power supply. To measure
the leakage current simply on site, use a measurement tool equipped with a filter, and clamp all the four power wires
together. The leakage current measured on the ground wire may not accurate because the leakage current from other
systems may be included to the measurement value.
Do not install a phase advancing capacitor on the unit connected to the same power system with an inverter type unit
and its equipment.
If a large current flows due to the product malfunctions or faulty wiring, both the earth leakage breaker on the product
side and the upstream overcurrent breaker may trip almost at the same time. Separate the power system or coordinate
all the breakers depending on the system's priority level.
MEES17K141 a-4 2
0000004605.BOOK 3 ページ 2018年1月18日 木曜日 午前8時42分

1. Installation information

1-1-6. Unit installation


Your local distributor or a qualified technician must read the Installation Manual that is provided with each unit carefully
before performing installation work.
Consult your local distributor or a qualified technician when installing the unit. Improper installation by an unqualified
person may result in water leakage, electric shock, or fire.

INSTALLATION INFORMATION
Ensure there is enough space around each unit.

1-1-7. Optional accessories


Only use accessories recommended by Mitsubishi Electric. Consult your local distributor or a qualified technician when
installing them. Improper installation by an unqualified person may result in water leakage, electric leakage, system
breakdown, or fire.
Some optional accessories may not be compatible with the air conditioning unit to be used or may not suitable for the
installation conditions. Check the compatibility when considering any accessories.
Note that some optional accessories may affect the air conditioner's external form, appearance, weight, operating
sound, and other characteristics.

1-1-8. Operation/Maintenance
Read the Instruction Book that is provided with each unit carefully prior to use.
Maintenance or cleaning of each unit may be risky and require expertise. Read the Instruction Book to ensure safety.
Consult your local distributor or a qualified technician when special expertise is required such as when the indoor unit
needs to be cleaned.

1-2. Precautions for Indoor unit and BC controller


1-2-1. Operating environment
The refrigerant (R410A) used for air conditioner is non-toxic and nonflammable. However, if the refrigerant leaks, the
oxygen level may drop to harmful levels. If the air conditioner is installed in a small room, measures must be taken to
prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak.
If the units operate in the cooling mode at the humidity above 80%, condensation may collect and drip from the indoor
units.

1-2-2. Unit characteristics


The return air temperature display on the remote controller may differ from the ones on the other thermometers.
The clock on the remote controller may be displayed with a time lag of approximately one minute every month.
The temperature using a built-in temperature sensor on the remote controller may differ from the actual room tempera-
ture due to the effect of the wall temperature.
Use a built-in thermostat on the remote controller or a separately-sold thermostat when indoor units installed on or in
the ceiling operate the automatic cooling/heating switchover.
The room temperature may rise drastically due to Thermo OFF in the places where the air conditioning load is large
such as computer rooms.
Be sure to use a regular filter. If an irregular filter is installed, the unit may not operate properly, and the operation noise
may increase.
The room temperature may rise over the preset temperature in the environment where the heating air conditioning load
is small.

1-2-3. Unit installation


The insulation for low pressure pipe between the BC controller and outdoor/heat source unit shall be at least 20 mm
thick. If the unit is installed on the top floor or in a high-temperature, high-humidity environment, thicker insulation may
be necessary.
Do not have any branching points on the downstream of the refrigerant pipe header.
When a field-supplied external thermistor is installed or when a device for the demand control is used, abnormal stop of
the unit or damage of the electromagnetic contactor may occur. Consult your local distributor for details.
When indoor units operate a fresh air intake, install a filter in the duct (field-supplied) to remove the dust from the air.
The 4-way or 2-way Airflow Ceiling Cassette Type units that have an outside air inlet can be connected to the duct, but
need a booster fan to be installed at site. Refer to the chapter "Indoor Unit" for the available range for fresh air intake
volume.
Operating fresh air intake on the indoor unit may increase the sound pressure level.

MEES17K141 a-4 3
0000004605.BOOK 4 ページ 2018年1月18日 木曜日 午前8時42分

1. Installation information
1-3. Precautions for Fresh air intake type indoor unit
1-3-1. Usage
This unit mainly handles the outside air load, and is not designed to maintain the room temperature. Install other air con-
ditioners for handling the air conditioning load in the room.
INSTALLATION INFORMATION

1-3-2. Unit characteristics


This unit cannot perform the drying operation. The unit will continue the fan operation and blow fresh air (air that is not
air-conditioned) when the Heating Thermo-OFF or Cooling Thermo-OFF mode is selected.
The fan may stop tentatively when the unit is connected to the simultaneous cooling/heating operation type outdoor/heat
source unit (R2/WR2-Series) or during the defrost cycle.
This unit switches the Thermo ON or OFF depending on the room temperature. The outside air is directly supplied into
the room during Thermo OFF. Take caution of the cold supply air due to low outside air temperature and of condensation
in the room due to high humidity of the outside air.
Outside air temperature ranges for the operation must be as follows:
Cooling: 21ºCD.B./15.5ºCW.B. ~ 43ºCD.B./35ºCW.B.
Heating: -10ºCD.B.~ 20ºCD.B
The unit is forced to operate Thermo OFF (fan operation) when the outside air temperature is as follows.
Cooling: 21ºCD.B or below; Heating: 20ºCD.B or above
Either a remote controller (sold separately) or a remote sensor (sold separately) must be installed to monitor the room
temperature.
If only this unit is used as an indoor unit, condensation may form at the supply air grill while the unit is operated in the
cooling mode. This unit cannot operate dehumidifying.
Use the unit in the way that the airflow rate will not exceed the 110% of the rated airflow.

1-4. Precautions for Outdoor unit/Heat source unit


1-4-1. Installation environment
Outdoor unit with salt-resistant specification is recommended to use in a place where it is subject to salt air.
Even when the unit with salt-resistant specification is used, it is not completely protected against corrosion. Be sure to
follow the directions or precautions described in Instructions Book and Installation Manual for installation and
maintenance. The salt-resistant specification is referred to the guidelines published by JRAIA (JRA9002).
Install the unit in a place where the flow of discharge air is not obstructed. If not, the short-cycling of discharge air may
occur.
Provide proper drainage around the unit base, because the condensation may collect and drip from the outdoor units.
Provide water-proof protection to the floor when installing the units on the rooftop.
In a region where snowfall is expected, install the unit so that the outlet faces away from the direction of the wind, and
install a snow guard to protect the unit from snow. Install the unit on a base approximately 50 cm higher than the
expected snowfall. Close the openings for pipes and wiring, because the ingress of water and small animals may cause
equipment damage. If SUS snow guard is used, refer to the Installation Manual that comes with the snow guard and take
caution for the installation to avoid the risk of corrosion.
When the unit is expected to operate continuously for a long period of time at outside air temperatures of below 0ºC,
take appropriate measures, such as the use of a unit base heater, to prevent icing on the unit base. (Not applicable to
the PUMY-Series)
Install the snow guard so that the outlet/inlet faces away from the direction of the wind.
When the snow accumulates approximately 50 cm or more on the snow guard, remove the snow from the guard. Install
a roof that is strong enough to withstand snow loads in a place where snow accumulates.
Provide proper protection around the outdoor units in places such as schools to avoid the risk of injury.
A cooling tower and heat source water circuit should be a closed circuit that water is not exposed to the atmosphere.
When a tank is installed to ensure that the circuit has enough water, minimize the contact with outside air so that the
oxygen from being dissolved in the water should be 1 mg/L or less.
Install a strainer (50 mesh or more recommended) on the water pipe inlet on the heat source unit.
Interlock the heat source unit and water circuit pump.
Note the followings to prevent the freeze bursting of pipe when the heat source unit is installed in a place where the
ambient temperature can be 0ºC or below.
Keep the water circulating to prevent it from freezing when the ambient temperature is 0ºC or below.
Before a long period of non use, be sure to purge the water out of the unit.
Salt-resistant unit is resistant to salt corrosion, but not salt-proof.
Please note the following when installing and maintaining outdoor units in marine atmosphere.
1. Install the salt-resistant unit out of direct exposure to sea breeze, and minimize the exposure to salt water mist.
2. Avoid installing a sun shade over the outdoor unit, so that rain will wash away salt deposits off the unit.
3. Install the unit horizontally to ensure proper water drainage from the base of the unit. Accumulation of water in the base
of the outdoor unit will significantly accelerate corrosion.
4. Periodically wash salt deposits off the unit, especially when the unit is installed in a coastal area.
5. Repair all noticeable scratches after installation and during maintenance.
6. Periodically check the unit, and apply anti-rust agent and replace corroded parts as necessary.

MEES17K141 a-4 4
0000004605.BOOK 5 ページ 2018年1月18日 木曜日 午前8時42分

1. Installation information

1-4-2. Circulating water


Follow the guidelines published by JRAIA (JRA-GL02-1994) to check the water quality of the water in the heat source
unit regularly.
A cooling tower and heat source water circuit should be a closed circuit that water is not exposed to the atmosphere.
When a tank is installed to ensure that the circuit has enough water, minimize the contact with outside air so that the

INSTALLATION INFORMATION
oxygen from being dissolved in the water should be 1 mg/L or less.

1-4-3. Unit characteristics


When the Thermo ON and OFF is frequently repeated on the indoor unit, the operation status of outdoor/heat source
units may become unstable.

1-4-4. Relevant equipment


Provide grounding in accordance with the local regulations.

1-5. Precautions for Control-related items


1-5-1. Product specification
To introduce the MELANS system, a consultation with us is required in advance. Especially to introduce the electricity
charge apportioning function or energy-save function, further detailed consultation is required. Consult your local
distributor for details.
Billing calculation for AE-200E/AE-50E/EW-50E/AG-150A/EB-50GU-J/TG-2000A, or the billing calculation unit is
unique and based on our original method. (Backup operation is included.) It is not based on the metering method, and
do not use it for official business purposes. It is not the method that the amount of electric power consumption (input) by
air conditioner is calculated. Note that the electric power consumption by air conditioner is apportioned by using the ratio
corresponding to the operation status (output) for each air conditioner (indoor unit) in this method.
In the apportioned billing function for AE-200E/AE-50E/EW-50E/AG-150A and EB-50GU-J, use separate watthour me-
ters for A-control units, K-control units, and packaged air conditioner for City Multi air conditioners. It is recommended
to use an individual watthour meter for the large-capacity indoor unit (with two or more addresses).
When using the peak cut function on the AE-200E/AE-50E/EW-50E/AG-150A or EB-50GU-J, note that the control is
performed once every minute and it takes time to obtain the effect of the control. Take appropriate measures such as
lowering the criterion value. Power consumption may exceed the limits if AE-200E/AE-50E/EW-50E/AG-150A or EB-
50GU-J malfunctions or stops. Provide a back-up remedy as necessary.
The controllers cannot operate while the indoor unit is OFF. (No error)
Turn ON the power to the indoor unit when operating the controllers.
When using the interlocked control function on the AE-200E/AE-50E/EW-50E/AG-150A/EB-50GU-J/PAC-YG66DCA or
PAC-YG63MCA, do not use it for the control for the fire prevention or security. (This function should never be used in
the way that would put people's lives at risk.) Provide any methods or circuit that allow ON/OFF operation using an
external switch in case of failure.

1-5-2. Installation environment


The surge protection for the transmission line may be required in areas where lightning strikes frequently occur.
A receiver for a wireless remote controller may not work properly due to the effect of general lighting. Leave a space of
at least 1 m between the general lighting and receiver.
When the Auto-elevating panel is used and the operation is made by using a wired remote controller, install the wired
remote controller to the place where all air conditioners controlled (at least the bottom part of them) can be seen from
the wired remote controller. If not, the descending panel may cause damage or injury, and be sure to use a wireless
remote controller designed for use with elevating panel (sold separately).
Install the wired remote controller (switch box) to the place where the following conditions are met.
Where installation surface is flat
Where the remote controller can detect an accurate room temperature
The temperature sensors that detect a room temperature are installed both on the remote controller and indoor unit.
When a room temperature is detected using the sensor on the remote controller, the main remote controller is used
to detect a room temperature. In this case, follow the instructions below.
 Install the controller in a place where it is not subject to the heat source.
(If the remote controller faces direct sunlight or supply air flow direction, the remote controller cannot detect an ac-
curate room temperature.)
 Install the controller in a place where an average room temperature can be detected.
 Install the controller in a place where no other wires are present around the temperature sensor.
(If other wires are present, the remote controller cannot detect an accurate room temperature.)
To prevent unauthorized access, always use a security device such as a VPN router when connecting
AE-200E/AE-50E/EW-50E/AG-150A/EB-50GU-J or TG-2000A to the Internet.

MEES17K141 a-4 5
0000004605.BOOK 6 ページ 2018年1月18日 木曜日 午前8時42分

MEES17K141 a-4 6
CAUTION FOR REFRIGERANT LEAKAGE

I.CAUTION FOR REFRIGERANT LEAKAGE

1. Caution for refrigerant leakage ........................................................................................................................ b-3-2


1-1. Refrigerant property ................................................................................................................................. b-3-2
1-2. Confirm the Critical concentration and take countermeasure .................................................................. b-3-2

MEES16K041 b-3- 1
1. Caution for refrigerant leakage
I.CAUTION
1.
The installer and/or air conditioning system specialist shall secure safety against refrigerant leakage according to local regulations or standards.
Caution for
FORrefrigerant
REFRIGERANT
leakageLEAKAGE

The following standard may be applicable if no local regulation or standard is available.

1-1. Refrigerant property


R410A refrigerant is harmless and incombustible. The R410A is heavier than the indoor air in density. Leakage of the refrigerant in a room
has possibility to lead to a hypoxia situation. Therefore, the critical concentration specified below shall not be exceeded even if the leakage
happens.
Critical concentration
Critical concentration hereby is the refrigerant concentration in which no human body would be hurt if immediate measures can be taken
when refrigerant leakage happens.
Critical concentration of R410A: 0.44kg/m3
CAUTION FOR REFRIGERANT LEAKAGE

(The weight of refrigeration gas per 1 m3 air conditioning space.);


The Critical concentration is subject to ISO5149, EN378-1.
For the CITY MULTI system, the concentration of refrigerant leaked should not have a chance to exceed the critical concentration in
any situation.

1-2. Confirm the Critical concentration and take countermeasure


The maximum refrigerant leakage concentration (Rmax) is defined as the result of the possible maximum refrigerant weight (Wmax) leaked
into a room divided by its room capacity (V). It is referable to Fig.1-1. The refrigerant of Outdoor/Heat source unit here includes its original
charge and additional charge at the site.
The additional charge is calculated according to the refrigerant charging calculation of each kind of Outdoor/Heat source unit, and shall not
be over charged at the site. Procedure 1-2-1~3 tells how to confirm maximum refrigerant leakage concentration (Rmax) and how to take
countermeasures against a possible leakage.
Outdoor/Heat source unit (No.1) Outdoor/Heat source unit (No.1) Outdoor/Heat source unit (No.2)

Flow of refrigerant Flow of refrigerant Flow of refrigerant

Indoor unit Indoor unit

Maximum refrigerant leakage concentration (Rmax) Maximum refrigerant leakage concentration (Rmax)
Rmax=Wmax / V (kg/m3) Rmax=Wmax / V (kg/m3) W1: Refrigerant weight of Outdoor/Heat source unit No.1
where, Wmax=W1+W2 W2: Refrigerant weight of Outdoor/Heat source unit No.2

Fig. 1-1 The maximum refrigerant leakage concentration


1-2-1.Find the room capacity (V),
If a room having total opening area more than 0.15% of the floor area at a low position with another room/space, the two rooms/space
are considered as one.The total space shall be added up.
1-2-2.Find the possible maximum leakage (Wmax) in the room.If a room has Indoor unit(s) from more than 1 Outdoor/Heat source unit, add
up the refrigerant of the Outdoor/Heat source units.
1-2-3.Divide (Wmax) by (V) to get the maximum refrigerant leakage concentration (Rmax).
1-2-4.Find if there is any room in which the maximum refrigerant leakage concentration (Rmax) is over 0.44kg/m3.
If no, then the CITY MULTI is safe against refrigerant leakage.
If yes, following countermeasure is recommended to do at site.
Countermeasure 1: Let-out (making V bigger)
Design an opening of more than 0.15% of the floor area at a low position of the wall to let out the refrigerant whenever leaked.
e.g.make the upper and lower seams of door big enough.
Countermeasure 2: Smaller total charge (making Wmax smaller)
e.g.Avoid connecting more than 1 Outdoor/Heat source unit to one room.
e.g.Using smaller model size but more Outdoor/Heat source units.
e.g.Shorten the refrigerant piping as much as possible.
Countermeasure 3: Fresh air in from the ceiling (Ventilation)
As the density of the refrigerant is bigger than that of the air. Fresh air supply from the ceiling is better than air exhausting from the ceiling.
Fresh air supply solution refers to Fig.1-2~4.
Refrigerant pipe (high pressure pipe)
Fresh air supply fan (always ON) Fresh air supply fan Fresh air supply fan
Refrigerant pipe Refrigerant pipe Refrigerant stop valve

to Outdoor/Heat source unit to Outdoor/Heat source unit to Outdoor/Heat source unit

Indoor unit Indoor unit Indoor unit


Indoor space
Indoor space Indoor space

(Floor) (Floor) (Floor)


Opening Opening Opening

Sensor for refrigerant leakage (Oxygen sensor or refrigerant sensor). Sensor for refrigerant leakage (Oxygen sensor or refrigerant sensor).
[At 0.3m height from the floor] [At 0.3m height from the floor]

Fig.1-2.Fresh air supply always ON Fig.1-3.Fresh air supply upon sensor action Fig.1-4.Fresh air supply and refrigerant
shut-off upon sensor action
Note 1. Countermeasure 3 should be done in a proper way in which the fresh air supply shall be on whenever the leakage happens.
Note 2. In principle, MITSUBISHI ELECTRIC requires proper piping design, installation and air-tight testing after installation to avoid leakage happening.
In the area should earthquake happen, anti-vibration measures should be fully considered.
The piping should consider the extension due to the temperature variation.

MEES16K041 b-3- 2
Warning
■ Do not use refrigerant other than the type indicated in the manuals provided with the unit and on the nameplate.
- Doing so may cause the unit or pipes to burst, or result in explosion or fire during use, repair, or at the time of disposal of the unit.
- It may also be in violation of applicable laws.
- MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong
type of refrigerant.
■ Our air conditioning equipment and heat pumps contain a fluorinated greenhouse gas, R410A.

New publication effective Nov. 2018


MEES18K047 Specifications subject to change without notice