Professional Documents
Culture Documents
Damping in Structures: 18.1 Concepts
Damping in Structures: 18.1 Concepts
18
18.1 CONCEPTS
•• The larger the damping ratio, ξ, the larger the ratio of successive peak displacements in free
vibration (un /un + 1), and the quicker the decay of oscillations.
•• The damping ratio can be determined from measurements using the vibration theory of a
single-degree-of-freedom system.
•• The damping ratio is a measure of the amount of damping in a structure which can effectively
reduce structural vibration at resonance.
•• The higher the amplitude of free vibration of a structure, the larger will be the critical damp-
ing ratio and the smaller will be the natural frequency.
u ( 0 ) + u ( 0 ) ξω
u (t ) = sin ω D t + u ( 0 ) cos ω D t e − ξ ωt (16.15)
ωD
where ω and ωD are the angular frequencies of the undamped and damped systems, respectively.
EXAMPLE 18.1
10
5
un
un+1
un+m
u(t) (mm)
2 4 6 8 10
–5 t (s)
2π / ωD
–10
FIGURE 18.1
Damped free vibration.
Consider free vibrations of an undercritically damped system that has the following
properties:
ω
f= = 1.0 Hz, ξ = 0.05, u (0 ) = 10 mm and u (0 ) = 0
2π
SOLUTION
Substituting the data into Equation 16.15, the displacements of the system can be
represented in graphical form, as shown in Figure 18.1.
It can be seen that
•• The damped system oscillates about its neutral position with a constant angular
frequency ωD.
•• The oscillation decays exponentially due to the damping.
Consider any two successive positive peaks such as un and un + 1 which occur at time n(2π/ωD)
and (n + 1)(2π/ωD), respectively. Equation 16.15 can be used to obtain the ratio of the two successive
peak values as
un 2πξω
= exp (18.2)
un + 1 ω D
Taking the natural logarithm of both sides of the equation and substituting ω D = ω 1 − ξ 2 into
Equation 18.2, the logarithmic decrement of damping, δ, is obtained since ξ is normally small for
structural systems:
un 2πξ δ 1 u
δ = ln = 2πξ or ξ = = ln n (18.3)
un + 1 1− ξ 2 2 π 2 π un +1
The larger the damping ratio ξ, the larger the ratio of un /un + 1 and thus the quicker the decay
of the oscillation.
Considering two positive peaks from Figure 18.1 which are not adjacent, say un and un + m,
Equation 18.3 becomes
un 2πmξ δ
δ = ln = = 2πmξ or ξ = (18.4)
un + m 1− ξ 2 2 m π
Thus, the damping ratio can be evaluated from Equation 18.3 or Equation 18.4 by measuring
any two positive peak displacements and the number of cycles between them.
If the damping is perfectly viscous, Equations 18.3 and 18.4 will give the same result. However,
this may not be true in all practical situations as will be shown in Section 18.4.
The advantages of using free vibration test responses to obtain values of damping ratio are
•• The requirements for equipment and instrumentation are minimal in comparison with forced
vibration test methods.
•• Only relative displacement amplitudes need to be measured.
•• The initial vibration can be generated by any convenient method, such as an initial displace-
ment, an impulse or a sudden change of motion.
A 1
MD = = (17.12)
∆ st (1 − f / f ) + (2ξf p / f )2
2
p
2
where:
fp is the frequency of the load
f is the natural frequency of the system
At resonance of a structure with a low damping ratio, the frequency of oscillation is approx-
imately equal to the natural frequency of the structure, that is, f p = f and Equation 18.12 becomes
A 1
MD = = (18.5)
∆ st 2ξ
Thus, if both the static displacement and the maximum dynamic displacement of a single-degree-
of-freedom system (or a particular mode of a structure) at resonance can be determined experimen-
tally, the critical damping ratio can be calculated from Equation 18.5. More accurate methods for
determining the damping ratio from forced vibration tests can be found in [1–3].
(a) (b)
FIGURE 18.2
(a,b) Effect of the damping provided by oil.
Figure 18.2a shows two identical steel strips acting as cantilevers. The only difference between
the two cantilevers is that connected to the free end of the cantilever on the left is a vertical metal
bar which in turn is attached to a disc immersed in oil. Figure 18.2b shows the disc by lifting up the
free end of the strip. Thus, the effect of the oil and the device can be examined.
Press the free ends of the two cantilevers down by the same amount and then release them sud-
denly. It will be observed that the cantilever on the left only vibrates for a small number of cycles
before stopping while the cantilever on the right oscillates through many cycles demonstrating the
effect of viscous damping provided by the oil.
•• Suspend the bare bar and give it a knock at its lower end using the other metal bar, as shown
in Figure 18.3a. A sound will be generated from the bar for several seconds as it reverberates.
•• Suspend the wrapped bar and give it a similar knock on the exposed metal part (Figure 18.3b).
This time only a brief dull sound is heard as the rubber wrapping dissipates much of the
energy of the vibration.
(a) (b)
FIGURE 18.3
(a,b) Effect of damping on sound transmission.
0.02
0.611 Hz
2.87% crit
0.01
Acceleration (m s–2)
0.0
1.08 9.22 (s)
–0.01
Time (s)
–0.02
FIGURE 18.4
Extraction of natural frequency and damping ratio from free vibration records. (From Ellis, B. R. and
Ji, T. The Structural Engineer, 74, 186–192, 1996.)
TABLE 18.1 N
atural Frequency and Damping Ratio
Determined from Various Sections of Decay
extracted from the five samples are given in Table 18.1 and related to the amplitude of vibration at
the start of each sample [4].
From Table 18.1 it can be observed that
•• The higher the amplitude of vibration, the smaller the natural frequency and the larger the
damping ratio.
•• The natural frequency for the relative amplitude of 1.00 is 6.86% lower than that for the rel-
ative amplitude of 0.062, while the damping ratio at the relative amplitude of 1.00 is 238%
higher than that at the relative amplitude of 0.062.
When the building vibrated with small amplitudes, the relative movements between joints and
other connections in the structure were small, involving frictional forces doing less work, and lead-
ing to lower damping ratios than were found when amplitudes were larger with associated larger
relative joint movements and friction-related work. These variations have been observed in many
different types of structure.
TABLE 18.2 M
easured Characteristics of the Principal Mode of Vibration of a Single Panel for a
Range of Floors
Natural
Floor type Frequency (Hz) Damping (% crit)
Steel beams with composite floor 6.39 0.61
Slimfloor 12.03 0.67
In situ concrete 11.89 0.86
Steel beams with composite floor 5.31 0.87
Steel beams with composite floor 5.43 1.34
Steel girders with prestressed concrete planks 4.95 1.35
Deep profiled concrete slab 7.43 1.56
Steel beams with composite floor 8.50 1.65
Steel beams with composite floor 6.70 1.75
Composite steel/concrete beams with precast hollow floor units 7.91 1.81
Steel beams with precast concrete planks and false floor 6.96 1.90
Steel beams with composite floor 5.26 2.72
Steel beams with composite floor plus furnishings 9.26 4.45
Sprung wooden dance floor 7.62 4.54
Beam and pot floor 11.93 5.08
Source: Ellis, B. R., Ji, T., El-Dardiry, E. and Zheng, T. The Structural Engineer, 88, 18–26, 2010.
The previous paragraphs, and indeed most literature, suggest that damping is a constant factor,
but measurements show that damping does vary with amplitude of vibration, the damping generally
increasing with increasing amplitude of vibration. So, damping values should be measured at ampli-
tudes of vibration of a similar level to those under consideration.
A number of measurements have been made on various types of floor (at vibration amplitudes
similar to those induced by people walking) and these are given in Table 18.2, which lists the
floors in order of increasing damping so the range of damping values can be appreciated. It can be
observed from the table that there is quite a wide range of damping values.
The floors with the lower damping values have one thing in common: they have a continuous
floor system. The floors built up with precast concrete panels tend to have higher damping values
due to the joints which provide an extra damping mechanism. The furnished floors also tend to have
higher damping values, but it is questionable whether damping from furnishings can be relied on
and it is often the least furnished areas of multipanel floors that encounter problems. The two highly
damped floors are both quite old and of a type of construction with many joints.
(a) (b)
FIGURE 18.5
(a,b) Damping devices installed on the London Millennium Footbridge.
Stiff material
Rubber
FIGURE 18.6
Deformation of bonded layers.
FIGURE 18.7
The test floor.
0.015
Acceleration (g)
0.005
–0.005
–0.015
–0.025
1 2 3 4 5 6 7 8
Time (s)
0.00
–0.01
1 2 3 4 5 6 7 8
Time (s)
FIGURE 18.8
Floor vibration induced by walking loads, with and without the damping layer.
A floor panel, 6 × 9 m, in the steel-frame test building at the BRE Cardington Laboratory,
was selected for testing with and without damping layers (Figure 18.7). A variety of comparative
tests were conducted including heel-drop tests, forced vibration tests and walking tests at different
speeds.
Figure 18.8 shows the comparison of acceleration–time histories induced by the same individ-
ual walking on the floor panel without and with the damping layer. The benefit of the constrained
damping layer in reducing the vibration of the floor is obvious.
PROBLEMS
1. The damping ratio in a structure is likely to be affected by the methods for pro-
cessing the measurements. Carry out the following exercises:
a. Digitise the acceleration and time curve shown in Figure 18.4.
b. Use Equation 18.3 to determine the damping ratio using the first two peak
values and the third and fourth peak values respectively.
c. Abstract the natural frequency and damping ratio from the digitised data.
2. A chimney has a fundamental natural frequency of 1.3 Hz and a damping ratio of
0.4% and a building has a fundamental natural frequency of 1.0 Hz and a damping
ratio of 0.5%. If the same initial disturbance is applied to each of the two struc-
tures to induce free vibration in their fundamental modes, does the vibration of
the building decay more quickly than that of the chimney? Give reasons to justify
your answer.
REFERENCES
1. Beards, C. F. Structural Vibration: Analysis and Damping, London: Arnold, 1996.
2. Clough, R. W. and Penzien, J. Dynamics of Structures, New York: McGraw-Hill,
1993.
3. Chopra, A. K. Dynamics of Structures, Upper Saddle River, NJ: Prentice Hall, 1995.
4. Ellis, B. R. and Ji, T. Dynamic testing and numerical modelling of the Cardington
steel framed building from construction to completion, The Structural Engineer,
74, 186–192, 1996.
5. Ellis, B. R., Ji, T., El-Dardiry, E. and Zheng, T. Determining the dynamic character-
istics of multi-panel floors, The Structural Engineer, 88, 18–26, 2010.
6. Ellis, B. R. Full-scale measurements of the dynamic characteristics of tall buildings
in the UK, Journal for Wind Engineering and Industrial Aerodynamics, 59, 365–382,
1996.
7. Dallard, P., Fitzpatrick, A. J., Flint, A., Le Bourva, S., Low, A., Ridsdill-Smith, R. M.
and Willford, M. The London Millennium Footbridge, The Structural Engineer, 79,
17–33, 2001.
268