ABB Utilities GmbH RTU560
Remote Terminal Unit
Connections and Settings
Binary Output 23BA30
Application, characteristics and technical data have Relay contact output
to be taken from the hardware data sheet:
Each interposing relay has two NO-contacts which
are wired to a screw terminal block.
23BA30 1 KGT 150 405
A yellow LED indicates the ON position of an interpos-
Operation ing relay.
The module 23BA30 has 16 interposing relays with
two normally open contacts each. The 23BA30 mod-
ule can be used for interposing the 16 output chan-
nels of a 23BA20 board.
Processing function
If used for interposing output in a 1:1 form, the 16 re-
lays are direct connected to the 23BA20 output chan-
nels.
j Open all switches of DIP-switch register S1
(OFF position)
j Use system cable 23SK31 or 23SK41
(see figure 5)
j Plug connector b of 23SK31/41 between:
position X1-10 and X2-8
j Plug the negative pole of the 24 V DC to
X1-1/2 and/or to X2-15/16
j Plug the positive pole of of tghe 24 V DC to
the common returns W01/W02 of 23BA20
board.
Doc.No.: 1KGT 150 438 V001 1 33
ABB Utilities GmbH
Connections and Settings 23BA30 RTU560
Settings
S1-1 to S1-8 Meaning
OFF Direct interposing
ON
OFF
Table 1: S1 DIP-switch positions
Fig. 1: Board layout and settings
34 Doc.No.: 1KGT 150 438 V001 1
ABB Utilities GmbH
RTU560 Connections and Settings 23BA30
X2 / 17
16
15
X3 / 64
14 32
k16 63
13 31
12 62
30
11 k15 61
29
10
60
9 28
k14 59
8 27
k16
7 58
26
6 k15 k13 57
25
5
k14 56
4 24
k12 55
3 k13 23
2 54
k12 22
1 k11 53
21
k11
52
20
k10 k10 51
19
k9 50
18
k9 49
1 2 3 4 5 6 7 8 17
S1
k8 48
16
k8 47
k7 15
46
k6 14
X1 / 18 k7 45
k5 13
17
44
16 12
k4 k6 43
15 11
k3 42
14
10
13 k5 41
k2 9
12
40
k1 8
11
k4 39
10 7
9 38
6
8 k3 37
5
7
36
6 4
k2
35
5 3
4 34
2
3 k1 33
1
2
1
relays k1 - k15 like k16
Fig. 2: Logic block diagram
Doc.No.: 1KGT 150 438 V001 1 35
ABB Utilities GmbH
Connections and Settings 23BA30 RTU560
subrack
23BA20
W01/W02 A01 - A16 23SK35 R002x = 23TP21
or
+ 23SK45 R002x = 23ET23
Process voltage a
UP = 24 V DC
-
b
Assignment:
23BA20 23BA30
2 3 10 18 1 8 15 16
A01 k1
X1 X2 A02 k2
.... ....
23BA30 A15 k15
A16 k16
Fig. 3: System cable direct connection
36 Doc.No.: 1KGT 150 438 V001 1
ABB Utilities GmbH
RTU560 Connections and Settings 23BA30
shield
x = cable length
l (m)
1.75
2.5
Connections
1
Rubric
2
3
4
x
Rubrik R002x = direct connection systemcable
Connector a = 23BA20 output
Connector b = 23BA30 X1 / 10-18 and X2 / 1-8
Fig. 4: System cable 23SK35
Doc.No.: 1KGT 150 438 V001 1 37
ABB Utilities GmbH
Connections and Settings 23BA30 RTU560
shield
x = cable length
l (m)
1.75
2.5
Connections
1
Rubric
2
3
4
x
Common return
23BA20 output
W 01/02
6.3 Faston connector
on 23TP22/23 pin A
cable shield
l = 0.5 m
A
Rubrik R002x = direct connection systemcable
Connector a = 23BA20 output
Connector b = 23BA30 X1 / 10-18 and X2 / 1-8
Connector c = common return 23BA20
Fig. 5: System cable 23SK45
ABB Utilities GmbH
68309 Mannheim (Germany)
Telephone +49 (0) 621 381-7592
Telefax +49 (0) 621 381-7622 06/2002 Subject to alteration
38 Doc.No.: 1KGT 150 438 V001 1