You are on page 1of 77

ABB AG, PGGA-P, January 2017

RTU500 series
Module overview
RTU500 series
Contents

Introduction to RTU500 series

RTU560 product line

RTU540 product line

RTU520 product line

RTU500 series modules

© ABB Group
January 19, 2020 | Slide 2
Suitable for all applications
RTU500 series overview

© ABB Group
January 19, 2020 | Slide 3
RTU500 series
RTU560 product line

RTU560 product line


 RTU560 CMUs
 RTU560 Power supply units
 RTU560 I/O modules
 RTU560 Racks
 RTU560 Serial communication
 RTU560 Ethernet communication
 RTU560 Real time clocks

© ABB Group
January 19, 2020 | Slide 4
RTU500 series
RTU560 communication units

560HMR01 560CMR01 560CMR02

Serial
- 2x RS-232 or RS-485 6 x RS232/485
interfaces
Ethernet interfaces 2x 10/100 Base T 2x 10/100 Base T 2x 10/100 Base T

USB ports 4 1 -

Number of Up to 10,000 data points Up to 10,000 data points


data points (depending on configuration) (depending in configuration)

Support of
Yes Yes
Multi-CMU

© ABB Group
January 19, 2020 | Slide 5
RTU500 series
RTU560 communication units

 Human machine interface (HMI)


560HMR01 for RTU560
 Windows 7 Professional (32 bit)
 2x Ethernet interfaces (10/100 Base T)
 4x USB ports for mouse and keyboard
 1x VGA port for monitor
 1x Stereo audio-output
 SSD hard drive
 Occupies two slots of the rack
 Runs Windows based operating system
for RTU560 integrated HMI or SDM600
 Communicates via Ethernet LAN
interfaces
 No external PC necessary thanks to
integrated solution
 Fan free, no rotating parts

© ABB Group
January 19, 2020 | Slide 6
RTU500 series
RTU560 communication units

 Communication unit (CMU) 560CMR01


for RTU560
 Interfaces
 1 x Micro-USB interface for
webserver access
 2 serial communication interfaces
(RS-232 or RS-485)
 2x Ethernet 10/100 BaseT
 IO bus (SPB) on the backside
 CPU
 ARM based platform
 SD card (2GB) for firmware
 128 MB RAM
 Only one slot width
 Usable in multiple CMU
configurations

© ABB Group
January 19, 2020 | Slide 7
RTU500 series
RTU560 communication units

 Remote communication unit 560CMR02


for RTU560
 Interfaces
 1 x Micro-USB interface for
webserver access
 6 serial communication interfaces
(RS-232 or RS-485)
 2x Ethernet 10/100 BaseT
 IO bus (SPB) on the backside
 CPU
 ARM based platform
 SD card (2GB) for firmware
 128 MB RAM
 Two slots width
 Usable in multiple CMU
configurations

© ABB Group
January 19, 2020 | Slide 8
RTU500 series
RTU560 power supply units

560PSR00 560PSU01 560PSU02

Input 24…60 V DC 110…220 V DC 48…220 V DC

Output power 44.3 W 44.3 W 85 W

© ABB Group
January 19, 2020 | Slide 9
RTU500 series
RTU560 power supply units

 Power supply unit 560PSR00


 Input: 24…60 V DC
 Output total 44.3 W,
 5 V DC: 0.2 A ...5.5 A and
24 V DC: 0...0.7 A
 1 LED for 5V, 1 LED for 24 V
signalization
 Potential isolation between the input
and the outputs, cooling by natural
convection
 Electronic power limitation, short-
circuit proof, controlled load
balancing
 Parallel operation with monitoring of
redundant power supply
configuration
 Alarm indication in case of failure
 Reverse voltage protection
© ABB Group
January 19, 2020 | Slide 10
RTU500 series
RTU560 power supply units

 Power supply unit 560PSU01


 Input: 110...220 V DC (R0002)
 Output total 44.3 W,
5 VDC: 0.2 A ...5.5 A and
24 VDC: 0...0.7 A
 1 LED for 5V, 1 LED for 24 V
signalization
 Electronic power limitation, short
circuit proof, controlled load
balancing
 Alarm indication in case of failure
 Redundant operation up to 3 CMUs

© ABB Group
January 19, 2020 | Slide 11
RTU500 series
RTU560 power supply units

 Power supply unit 560PSU02


 Input: 48...220 V DC
 Output total 85 W,
 5 VDC: 0…15 A and
24 VDC: 0...0.7 A

 1 LED for 5V, 1 LED for 24 V


signalization
 Electronic power limitation, short
circuit proof, controlled load
balancing
 Alarm indication in case of failure
 Redundant operation up to 8 CMUs

© ABB Group
January 19, 2020 | Slide 12
RTU500 series
RTU560 input/output modules

560BIR01 23BA20/23 23AE23 23AA21

Binary input Binary output Analog input Analog output


16 inputs 16 outputs 8 inputs 2 outputs
24…60 VDC 24…60 VDC / 2A 0...20 VDC / ±2 / ±5 / ±2.5 / ±5 / ±10 /
110…125 VDC ±10 / ±20 / ±40mA ±20mA or 4...20mA

© ABB Group
January 19, 2020 | Slide 13
RTU500 series
RTU560 input/output modules

23BE50 23BA40 23BE40

Binary input Binary output Binary input


16 inputs
64 inputs 16 outputs
110…125 VDC and
24…60 VDC 24…220 VDC/ 250 VDC
220…250 VDC

© ABB Group
January 19, 2020 | Slide 14
RTU500 series
RTU560 input/output modules

 Binary input module 560BIR01


 16 binary input channels
 One module for all types of binary
input signals ( single indications,
double point indications, digital
measured values, counters)
 Galvanic insulation by optocouplers
 Input voltage 24/60 VDC
 Input voltage 110/125 VDC
 LED signal for each input
 Temporary storage of 50 time-
stamped event messages

© ABB Group
January 19, 2020 | Slide 15
RTU500 series
RTU560 input/output modules

 Binary output board 23BA20


 16 binary relay output channels
 Can be used for following types of signal
(object commands with 1 or 2 pole output
without check, 1.5 or 2 pole output with
check, set-point messages, general
output messages)
 Galvanic insulation by relays
 Operating voltage 24...60 V DC
 Switching capacity:
40 VA (L/R=30ms) @ 60 V DC
 Continuous current of a relay group (8
with common return): max 2A

© ABB Group
January 19, 2020 | Slide 16
RTU500 series
RTU560 input/output modules

 Command Output monitoring board


23BA23
 Usage in combination with 23BA20
 (1 out of n) check
 2 test and switching circuits
 Auxiliary test voltage 24…60 V DC
 Galvanic isolation of the check
circuit
 Suppression of line frequency during
measuring
 Monitoring of output duration and
reset in case of fault
 Monitoring of switching voltage
before and during the command
output
© ABB Group
January 19, 2020 | Slide 17
RTU500 series
RTU560 input/output modules

 Analog input board 23AE23


 8 differential inputs
 Input current ± 2 mA, ± 5 mA,
±10 mA, ± 20 mA, ± 40mA
 Input voltage ± 2 V DC,
0...20 V DC
 12 bit + sign = 4096 steps
 Occupies one slot in RTU560 subrack
 Low-pass filter for suppression of non
line frequency AC disturbance
 Over voltage protection
 Zero point monitoring, switch-over
recognition, smoothing, threshold value
monitoring on absolute value

© ABB Group
January 19, 2020 | Slide 18
RTU500 series
RTU560 input/output modules

 Analog output board


23AA21
 2 channels
 Output current ± 2.5 mA,
± 5 mA, ± 10 mA, ± 20 mA
or 4...20mA
 11 bit + sign resolution
 Occupies one slot in
RTU560 subrack
 Outputs are isolated
between the channels and
from the power supply

© ABB Group
January 19, 2020 | Slide 19
RTU500 series
RTU560 input/output modules

 64 binary input board 23BE50


 64 binary inputs
 Process voltage: 24…60 V DC
 Input functions as 23BE23
 Groups with common return per 16
inputs
 One module for different types of
binary signals (single indications,
double indications, position
information, digital measured values,
string information, pulse counters)
 Galvanic insulation by optical
couplers
 LED signal for each output
 Power supply: 24 V DC
 Usable without additional terminals
© ABB Group
January 19, 2020 | Slide 20
RTU500 series
RTU560 input/output modules

 Binary input board 23BE40


 16 binary input channels
 Process voltage
 110…125 V DC: R0011
 220…250 V DC: R0012
 Inputs without common return
 One module for different types of binary
signals (single indications, double
indications, position information, digital
measured values, string information,
pulse counters)
 Galvanic insulation by optocouplers
 Input current 1,5 mA (chopped)
 Oxide film break function for 8 inputs
 LEDs for signalization of all input
channels
 Power supply: 24 V DC
© ABB Group
January 19, 2020 | Slide 21
RTU500 series
RTU560 input/output modules

 Binary output board 23BA40


 16 binary relay output channels
 Isolated relay output contacts NO, 2-
pole connection
 Switching voltage
24…220 V DC / 250 V AC
 Max. switching current: 300 mA at
110 VDC, 200 mA at 220 VDC
(L/R=40ms)
 Max. switching capacity: 120 W (DC)
 Continuous current: 8A

© ABB Group
January 19, 2020 | Slide 22
RTU500 series
RTU560 racks

Swing frame Mounting plate


560SFR02 560MPR03 560MPR01

Slots for power


2 2 -
supplies units

Support of
Up to 8 Up to 8 Max. 2
communication units

Mixed configurations With CMU and I/O With CMU and I/O With CMU and I/O

© ABB Group
January 19, 2020 | Slide 23
RTU500 series
RTU560 racks

 560MPR01
 1 or 2 Slots for 560CMU02
 Up to 8 slots for I/O modules
 24 V DC external power supply
 Extension connector for I/O bus
(extension rack, DIN rail I/O modules
110/220 V DC)
 Alarm and warning contact output
 Separate input for process voltage
(24…60 V DC)
 Power distribution for monitoring and
command voltage
 23BA23 configurable for 1,5 pole
command outputs and (1 out of n) check
 Screw connectors, access from front

© ABB Group
January 19, 2020 | Slide 24
RTU500 series
RTU560 racks

 560BCU02 R001
 Bus connection unit for 560MPR01
 Alarm and warning contacts
 Minute pulse in- and output
 Connection of up to 2 CMU modules

© ABB Group
January 19, 2020 | Slide 25
RTU500 series
RTU560 racks

 560MPR03 & 560SFR02


 Available for wall mounting (560MPR03)
and swing frame (560SFR02)
 Supports 1 or 2 power supply units
(560PSR00, 560PSU01/02)
 Up to 8 units 560CMU02 are supported
 Mixed configurations with CMU and I/O
 Mixed configurations 560CMU02

Redundant power supply, 17 slots

Single power supply, 18 slots

© ABB Group
January 19, 2020 | Slide 26
RTU500 series
RTU560 racks

 560BCU04 R0001
 Bus Connection Unit for 560MPR03
 Basic board for support of 2 units
560CMU0x
 Alarm and warning contacts
 Minute pulse in- and output

 560BCU04 R0002
 Bus Connection Unit for 560MPR03
 Extension kit for 10 additional 560CMU0x
 Alarm and warning contacts
 Minute pulse in- and output

© ABB Group
January 19, 2020 | Slide 27
RTU500 series
RTU560 racks

 560BCU05 R0001
 Bus Connection Unit for 560SFR02
 Basic board for support of 2 units
560CMU0x
 Alarm and warning contacts
 Minute pulse in- and output

 560BCU05 R0002
 Bus Connection Unit for 560SFR02
 Extension kit for 10 additional 560CMU0x
 Alarm and warning contacts
 Minute pulse in- and output

© ABB Group
January 19, 2020 | Slide 28
RTU500 series
RTU560 serial communication

Serial optical interfaces Analog line modems


23OK24 23WT23/24/25

© ABB Group
January 19, 2020 | Slide 29
RTU500 series
RTU560 serial communication

 Fiber optic coupler 23OK24


 Fiber optic connection with bayonet
socket BFOC/2.5 (IEC-SC86B)
 Optical connection of protection devices
according to IEC 60870-5-103
 With point to point connection
 In a multi-drop link connection
 In a bus link
 Connection to any other unit with optical
interface
 Optical booster to extend a fiber optic
link
 Glass fiber optic wave length 820 nm
 ST connector (BFOC 2,5)
 Suitable as star coupler for RS485 bus
 Cable length up to 2.600 m

© ABB Group
January 19, 2020 | Slide 30
RTU500 series
RTU560 serial communication

 Modem 23WT23
 FSK modem for voice band range (300-
2400 Hz) according to CCITT V.23
 2- or 4-wire lines, duplex or half duplex
 Baud rate 1.200 bit/s
 Adjustable by jumpers
 Point to point or multidrop configurations,
in multidrop configurations up to 10
remote station in one line
 Disconnect test sockets on front side
 Only one slot necessary
 Power supply:
R0001: 5 V DC / 350 mA, R0002: 24 V
DC / 70 mA

© ABB Group
January 19, 2020 | Slide 31
RTU500 series
RTU560 serial communication

 Modem 23WT24
 FSK modem for wide band range (300-
18000 Hz)
 2- or 4-wire lines, duplex or half duplex
 Baud rate: 9.600 Baud
 Distances up to 20 km, Point to point
 Distances up to 10 km, multi-drop
configuration for up to 10 remote stations
 Disconnect test sockets on front side
 Only one slot necessary
 Power supply: 5 V DC

© ABB Group
January 19, 2020 | Slide 32
RTU500 series
RTU560 serial communication

 Modem 23WT25
 FSK modem in voice band range (300-
3400Hz) according to CCITT
 Variants:
R0001: power supply 5 V DC
R0002: power supply 24 V DC
 2- or 4-wire lines, duplex or half duplex
 Baud rate 50 bit/s if 24-channel-CCITT-
raster is used, up to 2.400 bit/s if one
channel is used
 Digital signal processor (DSP) for
conversion of binary information to voice
band and vice versa
 Point to point or multi-drop
configurations, in multi-drop
configurations carrier can be switched off
 Disconnect test sockets on front side
© ABB Group
January 19, 2020 | Slide 33
RTU500 series
RTU560 Ethernet communication

Ethernet and optical switches


560NUS04/12 560NMS24/34
unmanaged managed/ SDSL

- For linear networks - Point-to-point


- Ring configuration

© ABB Group
January 19, 2020 | Slide 34
RTU500 series
RTU560 Ethernet communication

 4 port integrated unmanaged local


switch – 560NUS04
 4 fast Ethernet 10/100 BaseT ports for
LAN port multiplication
 Additional interfaces for diagnosis and
LAN/WAN communication
 Unmanaged
 Auto negotiation 10/100Mbps
 Automatic Cross over detection and
correction (MDI/X)
 Only for linear networks (no ring
configuration)
 No STP/ RSTP supported
 Plug and play – no configuration required

© ABB Group
January 19, 2020 | Slide 35
RTU500 series
RTU560 Ethernet communication

 4 port integrated unmanaged switch with 2 x


FX – 560NUS12
 2 fast Ethernet 10/100 BaseT ports
 2 SFP cages for fiber optical interfaces
 Unmanaged
 Auto negotiation 10/100Mbps
 Automatic cross over detection and correction
(MDI/X)
 Different SFP modules
 560NFO13: mono-mode fiber, up to 15 km
 560NFO15: mono-mode fiber, up to 40 km
 560NFO85: multi-mode fiber, up to 2 km
 Only for linear networks
 No STP/RSTP supported
 Media converter to optical Ethernet
 Plug and play – no configuration required
 Alarm relays with configurable jumper FX link
detection

© ABB Group
January 19, 2020 | Slide 36
RTU500 series
RTU560 Ethernet communication

 4 port integrated managed switch


560NMS24 with 2 x SDSL
 4 port integrated managed switch
560NMS34 with 1 x SDSL
 SDSL interface (Symmetric Digital
Subscriber Line)
 4 x fast Ethernet RJ45 ports
 1 or 2 DSL WAN ports for copper
 Bandwidth from 192kbit/s up to 11Mbit/s
 Automatic through-connection in case of
power cut
 Managed switch
 Ring configuration possible
 Alarm relays configured by software
 Line transformer (560LTD03) isolation:
10 kV

© ABB Group
January 19, 2020 | Slide 37
RTU500 series
RTU560 real time clocks

560RTC01 560RTC02 560RTC03

Input signal GPS DCF77 IRIG-B

© ABB Group
January 19, 2020 | Slide 38
RTU500 series
RTU560 real time clocks

 Real time clock 560RTC01/02/03


 560RTC01: designed for GPS receiving
 560RTC02: designed for long-wave
DCF 77 transmitter receiving
 560RTC03: IRIG-B time codes
 IRIG-B123
 IRIG-B122
 AFNOR NFS 87-500
 IRIG-B003
 IRIG-B002
 AFNOR NFS 87-500 (DC)

© ABB Group
January 19, 2020 | Slide 39
RTU500 series
RTU540 product line

RTU540 product line


 RTU540 CMUs
 540CMD01
 540CIG01

© ABB Group
January 19, 2020 | Slide 40
RTU500 series
RTU540 communication units

540CID01 540CMD01

Serial
4 4
interfaces

Ethernet
2 2
10/100 BaseT

16 BI,
Integrated
8 BO, None
I/Os
8 AI (mA Signals))

Binary inputs/outputs
Extension I/O Analogue inputs/outputs
modules Direct analog inputs
Optional: fault current detection

Dimensions
204 x 105 x 90 mm 204 x 105 x 70 mm
WxHxD

© ABB Group
January 19, 2020 | Slide 41
RTU500 series
RTU540 communication units

 Communication unit 540CMD01


 DIN rail mounted base module
 Metal housing
 4 serial ports (RS-232, RS-485)
 2 Ethernet ports
 Power supply: 24…125 VDC
 With connection interface to RTU500
series I/O-extension modules

© ABB Group
January 19, 2020 | Slide 42
RTU500 series
RTU540 communication units

 Communication unit 540CID01


 DIN rail mounted base module
 Metal housing
 4 serial ports (RS-232, RS-485)
 2 Ethernet port (10/100 BaseT)
 Integrated I/Os (16 BI, 8 BO, 8 AI (mA
Signals)), (1 out of n) check
 Power supply: 24…125 VDC
 Process voltage:
R0001 24…60 VDC
R0002 110 …125 VDC
 With connection interface to RTU500
series I/O-extension modules

© ABB Group
January 19, 2020 | Slide 43
RTU500 series
RTU520 product line

RTU520 product line


 RTU520 communication units
 RTU520 power supply units
 RTU520 input/output modules
 RTU520 input/output adapters

© ABB Group
January 19, 2020 | Slide 44
RTU500 series
RTU520 communication units

 Communication unit 520CMD01


 1x Ethernet 10/100 BaseT
 3x Serial (2x RS485, 1x RS232)
 1x USB configuration interface
 Direct connection up to 8 IO devices
 Additionally extendable with up to 8
I/O modules with 520ADD01
 SD card slot
 Battery buffered real time clock
optionally available

© ABB Group
January 19, 2020 | Slide 45
RTU500 series
RTU520 communication units

 Command output monitoring 520CSD01


 Function for low end RTU‘s required
in several markets
 1 out n check for RTU520
 4 additional relay command outputs
60VDC, 5A continuous load

© ABB Group
January 19, 2020 | Slide 46
RTU500 series
RTU520 power supply units

 Power supply unit 520PSD01


 Input voltage: 24 VDC, 20 W
 Cooling by natural convection
 Reverse voltage protection
 LEDs for supervision of the internal
voltages
 Supply up to 16 RTU520 IO modules
possible
 Efficiency: 85%

© ABB Group
January 19, 2020 | Slide 47
RTU500 series
RTU520 input/output modules

 Analog input module 520AID01


 6 analog inputs,
 R0001: for mA signals (2,5 mA, 5
mA, 10 mA, 20 mA, unipolar, bipolar)
 R0002: for V signal (1 VDC, 10
VDC, unipolar, bipolar)
 AD converter resolution 13 bit
 Automatic zero calibration
 Accuracy for mA signals: 0,25%

© ABB Group
January 19, 2020 | Slide 48
RTU500 series
RTU520 input/output modules

 Binary input module 520BID01


 16 binary inputs with 2 groups and
common return for 8 Inputs
 Galvanic isolated via opto coupler
 1 LED per input
 R0001: 24-60 VDC
 R0002: 110/125 VDC
 Time stamping: 1 ms resolution
 Single or double indication
 Counter inputs (max 25 Hz)
 Bit string indication (8 bit, 16 bit)

© ABB Group
January 19, 2020 | Slide 49
RTU500 series
RTU520 input/output modules

 Binary output module 520BOD01


 8 command outputs, with relay
outputs
 1 LED per output
 Switching voltage: 150 VDC, 240W
resistive load
 Max. current: 8 A @ 30 VDC
 Single or double commands
 Regulation commands
 Digital set points (8 bit)

© ABB Group
January 19, 2020 | Slide 50
RTU500 series
RTU520 input/output modules

 Analog output module 520AOD01


 2 analog outputs:
 mA signals (2,5 mA, 5 mA, 10 mA,
20 mA, 4…20 mA, unipolar, bipolar)
 V signals (1,25 VDC, 2,5 VDC, 5
VDC, 10 VDC, unipolar, bipolar)
 Configuration with DIP switches
 Unipolar, bipolar, live zero setting by
software configuration
 Accuracy: 0,25 %

© ABB Group
January 19, 2020 | Slide 51
RTU500 series
RTU520 input/output modules

 Module to measure temperator (PT100


elements) 520PTD01
 For direct connection of PT100
elements for 2/4 wire connection
 6 inputs available
 Temperature range:± 200°C
 Resolution:12 bit
 Automatic zero calibration
 Accuracy: ± 1°C (-25°C…125°C)
 Conversion time (50 Hz): 80 ms

© ABB Group
January 19, 2020 | Slide 52
RTU500 series
RTU520 input/output adapters

 Adapter module 520ADD01


 To extend Wired Or Bus (WRB)
with additional RTU520 I/O
modules
 Number of modules selectable via
jumper at front side (4 or 8)
 Input: WRB, ribbon cable
 Output: WRB, ribbon cable

© ABB Group
January 19, 2020 | Slide 53
RTU500 series
RTU520 input/output adapters

 Adapter module 520ADD02


 To extend WRB to decentralized
locations
 Number of modules selectable
via jumper at front side (4 or 8)
 Input: WRB
 Output 1: fiber optical interface
(multimode)
 Output 2: RS485

© ABB Group
January 19, 2020 | Slide 54
RTU500 series
RTU520 input/output adapters

 Adapter module 520ADD03


 To convert RS485 or fiber
optical connections to WRB at
decentralized locations
 Requires 520PSD01
 Up to 16 I/O modules supported

© ABB Group
January 19, 2020 | Slide 55
RTU500 series
1 out of n check for RTU520

 Command output monitoring (1 out n check)


520CSD01:
 New function for low end RTU‘s required
in several markets
 Project requirements can be solved now
with RTU520 instead of RTU540
 1 out n check for RTU520
 4 additional relay command outputs
60VDC, 5A continuous load
RTU500 series
RTU500 series modules

RTU500 series modules


 RTU500 series power supply units
 RTU500 series I/Os
 RTU500 series I/O adapters
 RTU500 series multimeters
 RTU500 series serial communication
 RTU500 series Ethernet communication

© ABB Group
January 19, 2020 | Slide 57
RTU500 series
RTU500 series power supply units

CP-E24/2,5 560PSU40 560PSU41 23VG23/24

90…375 V DC 110…220 V DC 24…60 V DC 115…230 V AC


Input
85…264 V AC 85…264 V AC

Output 24 V DC / 2,5 A 24 V DC / 2,5A 24 V DC / 2,5A 24VDC / 2A / 10 A

© ABB Group
January 19, 2020 | Slide 58
RTU500 series
RTU500 series power supply units

 DIN rail power supply unit CP-E 24/2,5


 Input voltage
 90…375 V DC
 85…264 V AC
 Max. output power 60 W, 24 V DC: 2,5 A
 LEDs for status indication
 Open circuit, overload and short circuit
protection
 Signaling output "DC OK" (Transistor) for
output voltage OK

© ABB Group
January 19, 2020 | Slide 59
RTU500 series
RTU500 series power supply units

 DIN rail power supply unit


560PSU40/41
 Input voltage
 560PSU40: 85…375 V DC /85…264 V
AC
 560PSU41: 24…60 V DC
 Max. output power 60 W, 24 V DC: 2,5 A
 1 LED for voltage supervision 24 V DC
 Overload and short-circuit protection
 Power good signal available
(only 560PSU40)
 Parallel operation possible
(only 560PSU40)

© ABB Group
January 19, 2020 | Slide 60
RTU500 series
RTU500 series power supply units

 Main adapter 23VG23 with integrated


battery charger
 Input Voltage 115 / 230 V AC without
switch over
 24 V DC output voltage
 Power output 48 W
 Output current min. 0.2 A and max. 2 A
 Integrated components:
 Battery charging device
 Switch over device
 Exhaustive discharge protection

© ABB Group
January 19, 2020 | Slide 61
RTU500 series
RTU500 series power supply units

 Main adapter 23VG24


 Input Voltage 115 / 230 V AC
 Output voltage 24 V DC
 Power output approx. 240 W
 Output current max. 10 A

© ABB Group
January 19, 2020 | Slide 62
RTU500 series
RTU500 series multimeters

560CVD03 500CVD11 500CVD21

Metering with fault current Metering with fault


Current voltage
Metering detection and directional current detection and
transformers
information directional information

© ABB Group
January 19, 2020 | Slide 63
RTU500 series
RTU500 series multimeters

 Multimeter 560CVD03
 CT/VT interface with 3 voltage and 3 current
inputs for direct monitoring of 3 wire 85…400 V
AC
 Power values (W, VA, VAR)
 Power factor, frequency
 Energy Wh, Varh
 Current inputs: 1A, 5A
 Power supply:
 LO: 24…48 V DC
 HI: 80…260 V DC
80…330 V AC
 2 versions are available:
 Without display
 With display and push buttons to select the
shown value

© ABB Group
January 19, 2020 | Slide 64
RTU500 series
RTU500 series multimeters

 Multimeter 560CVD11
 Fault current detection, fault passage
indication
 CT/VT interface with 4 voltage and
4 current inputs for direct monitoring of
3/4 wire 10…300 V AC
 Power values (W, VA, VAR)
 Power factor, frequency
 Energy Wh, Varh
 Current inputs: 1A, 5A
 Power supply:
 LO: 24…48 V DC
 HI: 80…260 V DC
80…330 V AC

© ABB Group
January 19, 2020 | Slide 65
RTU500 series
RTU500 series multimeters

 Multimeter 500CVD21
 Cost optimized solution for multi feeder
applications
 Fault current detection, fault passage indication
 CT/VT interface with inputs for direct monitoring
of 3/4 wire 10…500 V AC
 24 currents
 8 feeders (3 pole) or
 6 feeders (4 pole)
 Power values (W, VA, VAR)
 Power factor, frequency
 Energy Wh, Varh
 Current inputs: 1A, 5A
 Power supply:
 LO: 24…48 V DC
 HI: 80…260 V DC
80…330 V AC

© ABB Group
January 19, 2020 | Slide 66
RTU500 series
RTU500 series serial communication

Modems Line transformers


560FSM10 560FSM11 500LTD01 500LTD02 (FSK)

Auxiliary voltage 24…60 V DC 24…60 V DC - -


Isolation test
- - 10 kV 7.5 kV
voltage
Communication
300…2,400 3,000…18,000 - -
baud
Baud rate (Baud) 1,200 9,600 - -

© ABB Group
January 19, 2020 | Slide 67
RTU500 series
RTU500 series serial communication

 Modem
 560FSM10
 V.23 modem
 Functionality compatible with
23WT23
 Voice band range: 300…2,400 Hz
 Power supply: 24…60 V DC ±20%
 560FSM11
 9600 baud modem
 Functionality compatible with
23WT24
 Wide band range: 300…18,000 Hz
 Power supply: 24..60 V DC ±20%

© ABB Group
January 19, 2020 | Slide 68
RTU500 series
RTU500 series serial communication

 Line transformer 500LTD01


 Isolated line transformer for galvanic
isolation of transmission line
 Frequency range: 0,3 kHz to 3.4 kHz
 Ratio 1:1
 Isolation test voltage 10 kV
 Optimized for line impedances of 600 Ω
 Insulation resistance: 10000 MΩ at 500 V

© ABB Group
January 19, 2020 | Slide 69
RTU500 series
RTU500 series serial communication

 Line transformer 500LTD02 (FSK)


 Isolated line transformer for galvanic
isolation of transmission line
 Frequency range: 2 kHz to 50 kHz
 Ratio 1:1
 Isolation test voltage 7.5 kV
 Optimized for line impedances of 150 Ω
 Insulation resistance: 10000 MΩ at 500 V

© ABB Group
January 19, 2020 | Slide 70
RTU500 series
RTU500 series Ethernet communication

560NMD01 560NMD02 560NMD11 500NMD20 500LTD03 (DSL)

Ethernet 4x 10/ 4x 10/ 4x 10/


interfaces 100 Base T 100 Base T 100 Base T

SDSL
1 2 1
interfaces

Optical
- - 1
interfaces

Serial
1 2 1
interfaces

Isolation test
- - - 10 kV
voltage

© ABB Group
January 19, 2020 | Slide 71
RTU500 series
RTU500 series Ethernet communication

 DIN rail integrated managed switch


560NMD01
 4x fast Ethernet 10/100 baseT port
(RJ45, electrical, autonegotiating)
 1x SDSL-port up to 11,4 Mbps
 RS232 interface for configuration or
tunneling of serial data
 EXT connector for external storage of
configuration data
 STP and RSTP support
 Alarm relay configured by software
 Functionally compatible with 560NMS34
 35 mm DIN-rail mountable
 24-60 V DC supply voltage

© ABB Group
January 19, 2020 | Slide 72
RTU500 series
RTU500 series Ethernet communication

 DIN rail integrated managed switch


560NMD02
 4x fast Ethernet 10/100 baseT port
(RJ45, electrical, autonegotiating)
 2x SDSL-port up to 11.4 Mbps
 2x RS232 interface for configuration or
tunneling of serial data
 EXT connector for external storage of
configuration data
 STP and RSTP support
 Alarm relay configured by software
 Functionally compatible with 560NMS24
 35 mm DIN-rail mountable
 24-60 V DC supply voltage

© ABB Group
January 19, 2020 | Slide 73
RTU500 series
RTU500 series Ethernet communication

 DIN rail integrated managed switch


560NMD11
 4x fast Ethernet 10/100 baseT port
(RJ45, electrical, autonegotiating)
 1x SFP slot, without optical transmitter/
receiver
 1x SDSL-port up to 11.4 Mbps
 2x RS232 interface for configuration or
tunneling of serial data
 EXT connector for external storage of
configuration data
 STP and RSTP support
 Alarm relay configured by software
 Functionally compatible with 560NMS34
 35 mm DIN-rail mountable
 24-60 V DC supply voltage

© ABB Group
January 19, 2020 | Slide 74
RTU500 series
RTU500 series Ethernet communication

 DIN rail integrated managed switch


500NMD20
 4x fast Ethernet 10/100 baseT port
(RJ45, electrical, autonegotiating)
 2x SFP slot, without optical transmitter/
receiver
 2x RS232 interface for configuration or
tunneling of serial data
 EXT connector for external storage of
configuration data
 STP and RSTP support
 Alarm relay configured by software
 Functionally compatible with 560NMS34
 35 mm DIN-rail mountable
 24-60 V DC supply voltage

© ABB Group
January 19, 2020 | Slide 75
RTU500 series
RTU500 series Ethernet communication

 Line transformer 500LTD03 (DSL)


 Isolated line transformer for galvanic
isolation of transmission line with DSL
 Frequency range: 1 kHz to 1 MHz
 Ratio 1:1
 Isolation test voltage 10 kV
 Optimized for line impedances of 100 Ω
 Insulation resistance: 10000 MΩ at 500 V

© ABB Group
January 19, 2020 | Slide 76