You are on page 1of 8

ABB Utility Automation RTU560

Remote Terminal Unit


Connections and Settings
Binary Output 23BA20

Application, characteristics and technical data have Settings


to be taken from the hardware data sheet:
There are no settings required and possible on the
23BA20 board.
23BA20 1 KGT 150 403
Signalling
Operation
The board monitors and checks its functionality as
The 23BA20 board has sixteen output relays. Two well as the dialog via the peripheral bus. Detected er-
groups of eight contacts have the same common re- rors are indicated and/or transmitted by the board:
turn. This allows to split the output channels only to
--- by the red LED ”ST” on the front plate
two different process voltage sources.
--- by the red LED ”PST” on the front plate
--- by diagnostic messages
Processing function
The I/O micro controller (EAP Ein- Ausgabe-Prozes- LED ”ST”
sor / Input- output processor) activates any output The ”ST” LED indicates board errors or peripheral
forced by the VAP of CMU (CMU = communication bus errors.
unit) by a command output request. The EAP con-
trols the time duration of a pulse output by the loaded The ”ST”-LED indicates:
pulse length time value. --- board runs initialization procedure
--- board is doing a cold- or warm start
Output monitoring and supervision --- board has detected a memory error (RAM or
EPROM)
Any output is checked and monitored by the EAP by --- micro controller faulty
different tests and supervision functions:
--- no dialog via the peripheral bus for at least 2
--- the output pattern is read back before the output minutes. The board is not polled by the PBP of
is activated CMU.
--- the 24 V DC from backplane bus to switch the
output relays is supervised during an active out- LED ”PST”
put The LED indicates an error at command output:
--- the pulse duration is controlled by the EAP --- 24 V DC for the output relays failed during com-
--- any detected error is indicated by LEDs. mand output
--- Time out PBP during active output. Any active
One or two pole outputs output is stopped (switched off).
Fig. 2: to Fig. 4: show the different principle wir-
LED ”CO”
ings for one or two pole output channels.
At least one output relay is switched on. The ”CO”
See the 23BA21 ”Connections and Settings” for the LED is direct connected to the 24 V DC. ”CO” is ON for
wiring if (1 out of n) check is requested. the time an output is active (pulse or persistent).

Doc.No.: 1KGT 150 436 V000 1 1


ABB Utility Automation

Connections and Settings 23BA20 RTU560

ST output W 01
relay: K01 b22
k01 A 01
z32
k02 A 02
b32
k03 A 03
d32
k04 A 04
z30
k05 A 05
Micro b30
controller k06 A 06
RTU Peripheral Bus

d30
k07 A 07
K08
z28
k08 A 08
RAM b28
W 02
K09 d22
k09 A 09
EPROM d28
k10 A 10
z26
k11 A 11
b26
EAP k12 A 12
d26
CO k13 A 13
z24
k14 A 14
K1 b24
k15 A 15
K16 d24
k16 A 16
z22
PST
+ 24 V DC k1

Fig. 1: Logic block diagram and front plate

2 Doc.No.: 1KGT 150 436 V000 1


ABB Utility Automation
RTU560 Connections and Settings 23BA20

23TP21 23ET23 Signal identification Re-


Re
R0031 R0011 Sub-connector Identification Meaning mark
1 1 z32 A 01 binary output 01
2 2 b32 A 02 binary output 02
3 3 d32 A 03 binary output 03
4 4 z30 A 04 binary output 04
5 5 b30 A 05 binary output 05
6 6 d30 A 06 binary output 06
7 7 z28 A 07 binary output 07
8 8 b28 A 08 binary output 08
9 9 d28 A 09 binary output 09
10 10 z26 A 10 binary output 10
11 11 b26 A 11 binary output 11
12 12 d26 A 12 binary output 12
13 13 z24 A 13 binary output 13
14 14 b24 A 14 binary output 14
15 15 d24 A 15 binary output 15
16 16 z22 A 16 binary output 16
17 19 A (Faston 6,3) A cable shield
18 17 b22 W 01 common return output 1 to 8
19 18 d22 W 02 common return output 9 to 16
The pin configuration of 23ET23 subrack corresponds to the direct pin configuration of the board connector

Subrack terminal connection:

TP21 ET23

Placement of signal terminal connectors on subracks

Doc.No.: 1KGT 150 436 V000 1 3


ABB Utility Automation

Connections and Settings 23BA20 RTU560

23BA20 23TP21 Signal- Process


R 0031 identific.
k 01 A 01
1
k 02 A 02
2
k 03 A 03
3
k 04 A 04
4
k 05 A 05
5
k 06 A 06
6
k 07 A 07
7
k 08
A 08
8
k 09 A 09
9
k 10 A 10
10
k 11 A 11
11
k 12
A 12
12
k 13 A 13
13
k 14 A 14
14
k15 A 15
15
k16
A 16
16
*
A
17

b22 * W 01
18

d22 * W 02
19

+ UP ---UP
UP = process voltage ( 24 / 48 / 60 V DC)

Fig. 2: Binary output 1 pole same process voltage circuit on both halfs.
* Pin assignment 23TP21
23TP21 23TP21
Board
R0031 R0011
A 17 19
b22 18 17
d22 19 18

Connection diagram 23TP21 subrack

4 Doc.No.: 1KGT 150 436 V000 1


ABB Utility Automation
RTU560 Connections and Settings 23BA20

23BA20 23TP21 Signal- Process


R 0031 identific.
k 01 A 01
1
k 02 A 02
2
k 03 A 03
3
k 04 A 04
4
k 05 A 05
5
k 06 A 06
6
k 07 A 07
7
k 08
A 08
8
k 09 A 09
9
k 10 A 10
10
k 11 A 11
11
k 12
A 12
12
k 13 A 13
13
k 14 A 14
14
k15 A 15
15
k16
A 16
16
*
A
17

b22 * W 01
18

d22 * W 02
19

+ UP ---UP + Pn --- Pn
UP = process voltage ( 24 / 48 / 60 V DC) e.g. 23BA21 test circuit

Fig. 3: Binary output 1 pole. Different process voltage sources on k 01-k 08 and k 09-k 16
* Pin assignment 23TP21
23TP21 23TP21
Board
R0031 R0011
A 17 19
b22 18 17
d22 19 18

Connection diagram 23TP21 subrack

Doc.No.: 1KGT 150 436 V000 1 5


ABB Utility Automation

Connections and Settings 23BA20 RTU560

23BA20 23TP21 Signal- Process


R 0031 identific.
k 01 A 01
1
k 02 A 02
2
k 03 A 03
3
k 04 A 04
4
k 05 A 05
5
k 06 A 06
6
k 07 A 07
7
k 08
A 08
8
k 09 A 09
9
k 10 A 10
10
k 11 A 11
11
k 12
A 12
12
k 13 A 13
13
k 14 A 14
14
k15 A 15
15
k16
A 16
16
*
A
17

b22 * W 01
18

d22 * W 02
19

(--- Pn) --- UP + UP (+ Pn)


UP = process voltage ( 24 / 48 / 60 V DC) or 23BA21 test circuit

Fig. 4: Binary output 2 pole. Either direct or by 1 out of n check


* Pin assignment 23TP21
23TP21 23TP21
Board
R0031 R0011
A 17 19
b22 18 17
d22 19 18

Connection diagram 23TP21 subrack

6 Doc.No.: 1KGT 150 436 V000 1


ABB Utility Automation
RTU560 Connections and Settings 23BA20

Doc.No.: 1KGT 150 436 V000 1 7


ABB Utility Automation

Connections and Settings 23BA20 RTU560

ABB Utility Automation GmbH


Postfach 1140, 68520 Ladenburg
Telephon (06203) 71---2932
Telefax (06203) 71---2812 11/2000 Technische Änderungen vorbehalten

8 Doc.No.: 1KGT 150 436 V000 1